Asurity BG-110 Metal Drain Pan Latching Switch Instruction Manual
- June 16, 2024
- Asurity
Table of Contents
Asurity BG-110 Metal Drain Pan Latching Switch
Product Information
Specifications
- Product Name: Metal Drain Pan Latching Switch BG-110
- Warranty: 3 years
- Max Rating: 30 VAC, 8A, and 100 VAC
- Fits pans up to 3 inches deep
Product Usage Instructions
Installation Instructions
WARNING: WORK SAFE, READ THIS! FAILURE TO READ AND COMPLY WITH ALL WARNINGS, CAUTIONS, INSTRUCTIONS PRIOR TO STARTING INSTALLATION MAY CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE AND VOID WARRANTY.
This device must be installed in accordance with manufacturer’s instructions. This installation must follow all applicable local plumbing, drainage, and electrical codes.
Remove electric shock hazard — DISCONNECT THE POWER BEFORE INSTALLING SWITCH to avoid electrical shock and/or equipment damage. Do not use on circuits exceeding 24 volts to avoid damage to switch, shock, or fire hazard. Switch must be connected to an isolated transformer with a max rating of 30 VAC, 8A, and 100 VAC.
In any installation where property damage might result from inoperative switch due to a power outage, back-up system(s) and/or alarm should be installed. The switch must only be installed by a licensed contractor or under the direct supervision of same. The condensation pan must be properly maintained after installation and remain free from foreign objects, rust, or other obstructions that might interfere with the proper operation of the float switch.
Installing the Float Switch on Drain Pan
- Disconnect power to unit at main panel.
- Disconnect power to the low voltage thermostat circuit.
- Slide the float switch onto the side of the pan.
- Lightly secure the float switch by tightening the thumb screws. DO NOT OVER TIGHTEN. (Refer to Fig. 1)
- Push down until unit is seated properly. Fits pans up to 3b inches deep. (Refer to Fig. 2)
- Finish tightening thumb screws.
Wiring the BG-110 in a Conventional HVAC System
- Ensure the power is disconnected to the unit at the main panel prior to moving to the next step. Refer to the appliance manufacturer’s installation and operating instructions and also review wire layout in their instructions.
- Locate the red wire coming from the 24 volt thermostat R terminal. (NOTE: If not present, it is recommended that an inline fuse to protect 24 volt circuit be installed.)
- Disconnect or cut red wire. Connect one of the long wires of the BG-110, using a wire nut, to the thermostat side of the circuit. Connect the other long wire of the BG-110, using a wire nut, to the air handler side of the circuit or to the terminal in the unit. Incorporating both switch wires in the red circuit will shut the unit off. (Refer to Fig. 3)
Testing the Float Switch
- Check viewing window. If red float is in the tripped position, press reset button. (Refer to Fig. 4)
- At start up, check initial average load.
- With unit on, test switch by raising float. Unit should stop running if switch is correctly wired.
- To test switch responsiveness, fill pan with water to ensure that the switch stops the unit before the pan overflows; once confirmed, remove the water.
FAQ
- Q: Can I use the switch on circuits exceeding 24 volts?
- No, using the switch on circuits exceeding 24 volts can cause damage to the switch and pose a shock or fire hazard.
- Q: Who should install the switch?
- The switch must only be installed by a licensed contractor or under the direct supervision of the same.
- Q: How should I maintain the condensation pan after installation?
- The condensation pan must be properly maintained and kept free from foreign objects, rust, or other obstructions that might interfere with the proper operation of the float switch.
WARNING: WORK SAFE, READ THIS!
FAILURE TO READ AND COMPLY WITH ALL WARNINGS, CAUTIONS, AND INSTRUCTIONS PRIOR TO STARTING INSTALLATION MAY CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE AND VOID WARRANTY.
INSTALLATION INSTRUCTIONS
This device must be installed in accordance with manufacturer’s instructions. This installation must follow all applicable local plumbing, drainage, and electrical codes.
Remove electric shock hazard — DISCONNECT THE POWER BEFORE INSTALLING SWITCH to avoid electrical shock and/or equipment damage. Do not use on circuits exceeding 24 volts to avoid damage to switch, shock, or fire hazard. Switch must be connected to an isolated transformer with a max rating of 30 VAC, 8A, and 100 VAC.
In any installation where property damage might result from an inoperative switch due to a power outage, back-up system(s) and/or alarm should be installed. The switch must only be installed by a licensed contractor or under the direct supervision of same. The condensation pan must be properly maintained after installation and remain free from foreign objects, rust, or other obstructions that might interfere with the proper operation of the float switch.
INSTALL FLOAT SWITCH ON DRAIN PAN
(To ensure proper performance of product, instructions must be followed.)
- Disconnect power to unit at main panel.
- Disconnect power to the low voltage thermostat circuit.
- Slide the float switch onto the side of the pan.
- Lightly secure the float switch by tightening the thumb screws (Fig.1). DO NOT OVER TIGHTEN.
- Push down until unit is seated properly (Fig. 2). Fits pans up to 3″ deep.
- Finish tightening thumb screws.
WIRING
WIRING THE BG-110 IN A CONVENTIONAL HVAC SYSTEM
(To ensure proper performance of product, instructions must be followed.)
- Ensure the power is disconnected to the unit at the main panel prior to moving to the next step. Refer to the appliance manufacturer’s installation and operating instructions and also review wire layout in their instructions.
- Locate the red wire coming from the 24 volt thermostat “R” terminal.
- NOTE: If not present, it is recommended that an inline fuse to protect 24 volt circuit be installed.
- Disconnect or cut red wire. Connect one of the long wires of the BG-110, using a wire nut, to the thermostat side of the circuit. Connect the other long wire of the BG-110, using a wire nut, to the air handler side of the circuit or to the terminal in the unit. Incorporating both switch wires in the red circuit will shut the unit off (Fig. 3).
- TEST THE FLOAT SWITCH
- Check viewing window (Fig 4). If red float is in the tripped position. Press reset button (Fig. 5).
- At start up, check initial average load.
- With unit on, test switch by raising float. Unit should stop running if switch is correctly wired.
- To test switch responsiveness, fill pan with water to ensure that the switch stops the unit before the pan overflows; once confirmed, remove the water.
WARRANTY AND CONTACT
WARRANTY
Visit asurityhvacr.com for warranty information.
- diversitech.com
- 800.995.2222
Asurity® is a registered trademark of DiversiTech Corporation.
©2023 DiversiTech Corporation