Danfoss ip54 kit VACON NXP Air Cooled Instruction Manual

June 16, 2024
Danfoss

Danfoss ip54 kit VACON NXP Air Cooled Instruction

Product Information

Specifications

  • Enclosure Protection Class: IP54
  • Provides protection against dust and water sprayed from all directions
  • Does not protect against strong jets of water or immersion

VACON IP54 Kit Contents
FR4 (Type designation code: NXIP54FR4)

  1. IP54 enclosure for FR4
  2. IP54 cable cover with fan
  3. Cable entry flange with rubber grommets
  4. Cable extension for fa
  5. Plastic sealing
  6. Screws (4×10)
  7. Warning sticker

FR5 (Type designation code: NXIP54FR5)

  1. IP54 enclosure for FR5
  2. IP54 cable cover with fan
  3. Cable entry flange with rubber grommets
  4. Cable extension for fan
  5. Plastic sealing
  6. Screws (4×10)
  7. Warning sticker

FR6 (Type designation code: NXIP54FR6)

  1. IP54 enclosure for FR6
  2. IP54 lid with fan
  3. Cable entry flange with rubber grommets
  4. Cable extension for fan
  5. Rubber sealings
  6. Screws (4×10)
  7. Warning sticker

Product Usage Instructions

Installation Instructions #1
FR4

  1. Detach the fan.
  2. Insert the plastic sealing (#4).
  3. Carefully re-install the fan ensuring that the connector clip fits accurately. DO NOT SLAM, DO NOT FORCE!!
  4. Remove the plastic cover of the frequency converter and open the small lid on the power unit cover. Leave the opening uncovered.
  5. Seal the air inlets with the rubber sealings (#4). Leave the opening uncovered.
  6. Fix the IP54 lid with fan (#2) on the power unit cover.
  7. Open the control cable cover and remove the cable entry flange.
  8. Remove the power cable cover and detach the grounding rack.
  9. Take the IP54 cable cover and connect the fan power cable to the connector marked with ‘FAN’.
  10. Use the attached screws to fix the IP54 cable cover with fan and the grounding rack.

FR5
The installation instructions are the same as for FR4, except for step 2b. Instead of inserting the plastic sealing, insert the rubber sealing.

FR6
The installation instructions are the same as for FR5, except for step 4a. Instead of leaving the opening uncovered, remove the plastic cover of the frequency converter and open the small lid on the power unit cover.

FAQ

  • Q: What is the purpose of the IP54 kit?
    The IP54 kit enhances the enclosure protection class of the frequency converter, protecting against dust and water sprayed from all directions.

  • Q: Does the IP54 enclosure protect against strong jets of water or immersion?
    No, the IP54 enclosure does not protect against strong jets of water or the effects of immersion.

  • Q: When should I consider using the IP54 kit?
    The IP54 kit should be considered when the frequency converter is used in ambient conditions that might pose a risk to its proper functioning, such as moist or dusty environments.

GENERAL

Using these instructions, you can enhance the enclosure protection class of your IP21 class frequency converter to IP54. Such a higher protection level may be necessary when the frequency converter is used in such ambient conditions that might constitute a risk for the proper functioning of the converter (moist, dust).
According to standard IEC 60529 (EN 60 529), the IP54 frequency converter enclosure provides protection against dust and water sprayed from all directions. Limited ingress of both is permitted.

VACON IP54 KIT CONTENTS

NOTE : An IP54 enclosure does not protect the frequency converter against strong jets of water or the effects of immersion.
The contents of the IP54 kits for different frames are shown in the following pictures.

FR4 (Type designation code: NXIP54FR4)

  1. IP54 enclosure for FR4
  2. IP54 cable cover with fan
  3. Cable entry flange with rubber grommets
  4. Cable extension for fan
  5. Plastic sealing
  6. Screws (4×10)
  7. Warning sticker

FR5 (Type designation code: NXIP54FR5)

  1. IP54 enclosure for FR5
  2. IP54 cable cover with fan
  3. Cable entry flange with rubber grommets
  4. Cable extension for fan
  5. Rubber sealings
  6. Screws (4×10)
  7. Warning sticker

FR6 (Type designation code: NXIP54FR6)

  1. IP54 enclosure for FR5
  2. IP54 lid with fan
  3. Cable entry flange with rubber grommets
  4. Cable extension for fan
  5. Rubber sealings
  6. Screws (4×10)
  7. Warning sticker

INSTALLATION

These instructions guide you through the installation of the IP54 kit that you have purchased for your FR4, FR5 or FR6 size frequency converter enclosure class IP21. NOTE: If you have purchased your converter before March 2004, follow the installation instructions under Error! Reference source not found..
Please note the white triangles in the lower left corners of the installation pictures. They designate the frame(s) the picture applies to. If no triangles exist, the step is applicable to all frames.

Installation Instructions #1

Information sticker
Each IP54 upgrade kit delivered by the factory includes a sticker (shown below).
Please check IP54/Collar (1) and mark the installation date (2) on the sticker. Finally, attach the sticker on your drive.

www.danfoss.com

Document ID: Vacon Ltd
Member of the Danfoss Group
Runsorintie 7
65380 Vaasa
Finland

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals