PowerWalker VFI 1000 CG PF1 Emergency Power Supply UPS Instruction Manual

June 16, 2024
PowerWalker

VFI 1000 CG PF1 Emergency Power Supply UPS

Product Information

Specifications

  • Model: PowerWalker VFI 1000 CG PF1
  • Model: PowerWalker VFI 1500 CG PF1
  • Model: PowerWalker VFI 2000 CG PF1
  • Model: PowerWalker VFI 3000 CG PF1
  • Model: PowerWalker VFI 1000 RMG/S PF1
  • Model: PowerWalker VFI 1500 RMG PF1
  • Model: PowerWalker VFI 2000 RMG/S PF1
  • Model: PowerWalker VFI 3000 RMG PF1
  • Type: Manual Uninterruptible Power Supply System
  • Version: 1.4.1

Important Safety Warning

Please comply with all warnings and operating instructions in
this manual strictly. Save this manual properly and read carefully
the following instructions before installing the unit. Do not
operate this unit before reading through all safety information and
operating instructions carefully.

Transportation

Please transport the UPS system only in the original package to
protect against shock and impact.

Preparation

Condensation may occur if the UPS system is moved directly from
a cold to a warm environment. The UPS system must be absolutely dry
before being installed. Please allow at least two hours for the UPS
system to acclimate to the environment. Do not install the UPS
system near water or in moist environments. Do not install the UPS
system where it would be exposed to direct sunlight or near a
heater. Do not block ventilation holes in the UPS housing.

Battery Safety

Batteries may cause electric shock and have a high short-circuit
current. Please take the precautionary measures specified below and
any other necessary measures when working with batteries:

  1. Remove watches, rings, or other metal objects.

  2. Use tools with insulated handles.

  3. Wear rubber gloves and boots.

  4. Do not lay tools or metal parts on top of batteries.

  5. Disconnect charging source and load prior to installing or
    maintaining the battery.

  6. Remove battery grounds during installation and maintenance to
    reduce the likelihood of shock. Remove the connection from ground
    if any part of the battery is determined to be grounded.

When changing batteries, install the same number and same type
of batteries or battery packs.

  • For UPS with internally mounted battery:

    1. Instructions shall carry sufficient information to enable the
      replacement of the battery with a suitable manufacturer and catalog
      number.

    2. Safety instructions to allow access by Service Personnel shall
      be stated in the installation/service handbook.

    3. If batteries are to be installed by Service Personnel,
      instructions for interconnections, including terminal torque, shall
      be provided.

Do not attempt to dispose of batteries by burning them. This
could cause a battery explosion. Do not open or destroy batteries.
Escaping electrolyte can cause injury to the skin and eyes. It may
be toxic.

Fuse and Dismantling

Please replace the fuse only with the same type and amperage in
order to avoid fire hazards. Do not dismantle the UPS system.

WARNING: This is a category C2 UPS product. In
a residential environment, this…

Product Usage Instructions

Troubleshooting

Refer to page 20 of the user manual for troubleshooting
steps.

Storage and Maintenance

Refer to page 21 of the user manual for storage and maintenance
guidelines.

Specifications

Refer to page 22 of the user manual for detailed specifications
of the product.

FAQ

Q: Can I transport the UPS system without the original

package?

A: It is recommended to transport the UPS system only in the
original package to protect against shock and impact.

Q: Can I install the UPS system near water or in moist

environments?

A: No, it is not recommended to install the UPS system near
water or in moist environments.

Q: Can I dispose of batteries by burning them?

A: No, you should not attempt to dispose of batteries by burning
them as it could cause a battery explosion.

PowerWalker VFI 1000 CG PF1

PowerWalker VFI 1500 CG PF1

EN

PowerWalker VFI 2000 CG PF1

PowerWalker VFI 3000 CG PF1

PowerWalker VFI 1000 RMG/S PF1 PowerWalker VFI 1500 RMG PF1 PowerWalker VFI 2000 RMG/S PF1 PowerWalker VFI 3000 RMG PF1

Manual Uninterruptible Power Supply System

Version: 1.4.1

Table of Contents
1. Important Safety Warning ……………………………………………………………………….. 1 1-1. Transportation …………………………………………………………………………………………………………… 1 1-2. Preparation……………………………………………………………………………………………………………….. 1 1-3. Installation ……………………………………………………………………………………………………………….. 1 1-4. Operation …………………………………………………………………………………………………………………. 1 1-5. Maintenance, service and faults…………………………………………………………………………………… 2
2. Installation and setup ……………………………………………………………………………… 3 2-1. Rear panel view ………………………………………………………………………………………………………… 3 2-2. Operating principle ……………………………………………………………………………………………………. 4 2-3. Install the UPS (Only for RT Models) ………………………………………………………………………….. 4 2-4. Setup the UPS …………………………………………………………………………………………………………… 5 2-5. Battery Replacement (Only for RT Models) …………………………………………………………………. 8 2-6. Battery Kit Assembly (option for RT Models) ………………………………………………………………. 9
3. Operations ……………………………………………………………………………………………. 11 3-1. Button operation ……………………………………………………………………………………………………….11 3-2. LCD Panel ……………………………………………………………………………………………………………….11 3-3. Audible Alarm…………………………………………………………………………………………………………. 13 3-4. LCD display wordings index …………………………………………………………………………………….. 13 3-5. UPS Setting…………………………………………………………………………………………………………….. 14 3-6. Operating Mode Description …………………………………………………………………………………….. 18 3-7. Faults Reference Code……………………………………………………………………………………………… 19 3-8. Warning indicator ……………………………………………………………………………………………………. 19
4. Troubleshooting…………………………………………………………………………………….. 20 5. Storage and Maintenance……………………………………………………………………….. 21 6. Specifications ……………………………………………………………………………………….. 22

1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
1-1. Transportation Please transport the UPS system only in the original package to protect against shock and impact.
1-2. Preparation Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment. Do not install the UPS system near water or in moist environments. Do not install the UPS system where it would be exposed to direct sunlight or near heater. Do not block ventilation holes in the UPS housing.
1-3. Installation Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets. Place cables in such a way that no one can step on or trip over them. Do not connect domestic appliances such as hair dryers to UPS output sockets. The UPS can be operated by any individuals with no previous experience. Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system. Please use only VDE-tested, CE-marked (or UL- marked for 100/110/115/120/127 VAC models) mains cable (e.g., the mains cable of your computer) to connect the UPS system to the building wiring outlet (shockproof outlet). Please use only VDE-tested, CE-marked (or UL-marked for 100/110/115/120/127 VAC models) power cables to connect the loads to the UPS system. When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA. Temperature Rating – Units are considered acceptable for use in a maximum ambient of 40°C (104°F). For Pluggable Equipment – The socket-outlet shall be installed near the equipment and shall be easily accessible.
1-4. Operation Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads. The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet. In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains. Prevent no fluids or other foreign objects from inside of the UPS system.
1

1-5. Maintenance, service and faults The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel. Caution – risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous. Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors. Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries. Caution – risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present! Caution – Do not dispose of batteries in a fire. The batteries may explode. Caution – Do not open or mutilate batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic. Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary when working with batteries: a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
e) Disconnect charging source and load prior to installing or maintaining the
battery.
f) Remove battery grounds during installation and maintenance to reduce
likelihood of shock. Remove the connection from ground if any part of the
battery is determined to be grounded. When changing batteries, install the same number and same type of batteries or
battery packs. For UPS with internally mounted battery
a) Instructions shall carry sufficient information to enable the replacement of the
battery with a suitable manufacturer and catalogue number.
b) Safety instructions to allow access by Service Personnel shall be stated in the
installation/service handbook.
c) If batteries are to be installed by Service Personnel, instructions for
interconnections, including terminal torque, shall be provided. Do not attempt to dispose of batteries by burning them. This could cause battery
explosion. Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin
and eyes. It may be toxic. Please replace the fuse only with the same type and amperage in order to avoid fire
2

hazards. Do not dismantle the UPS system. WARNING: This is a category C2 UPS product. In a residential environment, this
product may cause radio interference, in which case the user many be required to take additional measures. (only for 220/230/240 VAC system)
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.
2-1. Rear panel view Tower Models IEC Type

1K/1.5K
Rack/Tower Models IEC Type 1K/1.5K

2K

3K

2K

3K

3

1. Programmable outlets: connect to non-critical loads. 2. Output receptacles: connect to mission-critical loads. 3. AC input 4. Network/Fax/Modem surge protection 5. USB communication port 6. RS-232 communication port 7. SNMP intelligent slot 8. Emergency power off function connector (EPO) 9. External battery connection

2-2. Operating principle The operating principle of the UPS is shown as below
Input

Output

EMI/RFI Filters

Rectifier /PFC

Dynamic Bypass

Inverter

DC-to-DC Converter

Battery Charger

Battery

The UPS is composed of mains input, EMI/RFI filters, rectifier/PFC, inverter, battery charger, DC-to-DC converter, battery, dynamic bypass and UPS output.

2-3. Install the UPS (Only for RT Models) For safety consideration, the UPS is shipped out from factory without connecting battery wires. Before install the UPS, please follow below steps to re-connect battery wires first.

Step 1

Step 2

Step 3

Remove front panel.

Connect the AC input and re-connect battery wires.

Put the front panel back to the unit.

This UPS can be either displayed on the desk or mounted in the 19″ rack chassis. Please choose proper installation to position this UPS.

4

Rack-mount Installation Step 1

Step 2

Tower Installation Step 1

Step 2

2-4. Setup the UPS Before installing the UPS, please read below to select proper location to install UPS. 1. UPS should be placed on the flat and clean surface. Place it in an area away from vibration,
dust, humidity, high temperature, flammable liquids, gases, corrosive and conductive contaminants. Install the UPS indoors in a clean environment, where it is away from window and door. Maintain minimum clearance of 100mm in the bottom of the UPS to avoid dust and high temperature.
2. Maintain an ambient temperature range of 0ºC to 45ºC for UPS optimal operation. For every 5ºC above 45ºC, the UPS will derate 12% of nominal capacity at full load. The highest working temperature requirement for UPS operation is 50ºC.
3. It’s required to maintain maximum altitude of 1000m to keep UPS normal operation at full load UPS. If it’s used in high altitude area, please reduce connected load. Altitude derating power with connected loads for UPS normal operation is listed as below:
4. Place UPS: It’s equipped with fan for cooling. Therefore, place the UPS in a well-ventilated area. It’s required to maintain minimum clearance of 100mm in the front of the UPS and
5

300mm in the back and two sides of the UPS for heat dissipation and easy maintenance. 5. Connect to External Battery Pack
When connecting external battery packs, please be sure to connect polarity correctly. Connect positive pole of battery pack to positive pole of external battery connector in UPS and negative pole of battery pack to negative pole of external battery connector in UPS. Polarity misconnection will cause UPS internal fault. It’s recommended to add one breaker between positive pole of battery pack and positive pole of external battery connector in UPS to prevent damage to battery packs from internal fault. The required specification of breaker: voltage 1.25 x battery voltage/set; current 50A Please choose battery size and connected numbers according to backup time requirement and UPS specifications. To extend battery lifecycle, it’s recommended to use them in the temperature range of 15ºC to 25ºC.
Step 1: External battery connection Follow the right chart to make external battery connection.
Step 2: UPS input connection Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. For 200/208/220/230/240VAC models: The power cord is supplied in the UPS package. Note: Check if the site wiring fault indicator lights up in LCD panel. It will be illuminated when the UPS is plugged into an improperly wired utility power outlet (Refer to Troubleshooting section). Please also check if there is a circuit breaker against overcurrent and short circuit between the mains and AC input of the UPS for safety operation. The recommended protection value as following: For 200/208/220/230/240VAC models: 10A for the 1K and 1.5K models, 16A for the 2K
and 3K models.
Step 3: UPS output connection There two kinds of outputs: programmable outlets and general outlets. Please connect noncritical devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to critical devices by setting shorter backup time for non-critical devices.
6

Step 4: Communication connection

Communication port:

USB port

RS-232 port

Intelligent slot

To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring options.
Step 5: Network connection Network/ Fax/ Phone surge port
Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone line cable.
Step 6: Disable and enable EPO function This UPS is equipped with EPO function. By default, the UPS is delivered from factory with Pin 1 and pin 2 closed (a metal plate is connected to Pin 1 and Pin2) for UPS normal operation. To activate EPO function, remove two screws on EPO port and metal plate will be removed. Note: The EPO function logic can be set up via LCD setting. Please refer to program 16 in UPS setting for the details.
It’s in closed status for UPS normal operation as default.

To activate EPO function, remove these two screws.
Step 7: Turn on the UPS Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period.
Step 8: Install software For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. Use supplied RS-232 or USB communication cable to connect RS-232/USB port of UPS and RS-232/USB port of PC. Then, follow below steps to install monitoring software.
7

1. Insert the included installation CD into CD-ROM drive and then follow the on-screen instructions to proceed software installation. If there no screen shows 1 minute after inserting the CD, please execute setup.exe file for initiating software installation.
2. Follow the on-screen instructions to install the software. 3. When your computer restarts, the monitoring software will appear as an orange plug icon
located in the system tray, near the clock.

2-5. Battery Replacement (Only for RT Models) NOTICE: This UPS is equipped with internal batteries and user can replace the batteries without shutting down the UPS or connected loads.(hot-swappable battery design) Replacement is a safe procedure, isolated from electrical hazards. CAUTION!! Consider all warnings, cautions, and notes before replacing batteries. Note: Upon battery disconnection, equipment is not protected from power outages.

Step 1

Step 2

Step 3

Remove front panel. Step 4

Disconnect battery wires. Step 5

Pull out the battery box by removing two screws on the front panel. Step 6

Remove the top cover of battery box and replace the inside batteries.
Step 7

After replacing the batteries, put the battery box back to original location and screw it tightly.

Re-connect the battery wires.

Put the front panel back to the unit.

8

2-6. Battery Kit Assembly (option for RT Models) NOTICE: Please assemble battery kit first before installing it inside of UPS. Please select correct battery kit procedure below to assemble it.

2-battery kit Step 1: Remove adhesive tapes.
Tapes

Step 2: Connect all battery terminals by following below chart.

Step 3: Put assembled battery packs on one side of plastic shells.

Step 4: Cover the other side of plastic shell as below chart. Then, battery kit is assembly well.

3-battery kit Step 1: Remove adhesive tapes.
Tapes
Tapes

Step 2: Connect all battery terminals by following below chart.

Step 3: Put assembled battery packs on one side of plastic shells as below chart.

Step 4: Cover the other side of plastic shell as below chart. Then, battery kit is assembly well.

9

4-battery kit Step 1: Remove adhesive tapes.
Tapes

Step 2: Connect all battery terminals by following below chart.

Tapes

Step 3: Put assembled battery packs on one side of plastic shells.

Step 4: Cover the other side of plastic shell as below chart. Then, battery kit is assembly well.

6-battery kit Step 1: Remove adhesive tapes.
Tapes

Step 2: Connect all battery terminals by following below chart.
Tapes

Step 3: Put assembled battery packs on one side of plastic shells.

Step 4: Cover the other side of plastic shell as below chart. Then, battery kit is assembly well.

10

3. Operations

3-1. Button operation

Button Function

ON/Mute Button
OFF/Enter Button
Select Button
ON/Mute + Select Button

Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.
Mute the alarm: After the UPS is turned on in battery mode, press and hold this button for at least 3 seconds to disable or enable the alarm system. But it’s not applied to the situations when warnings or errors occur.
Up key: Press this button to display previous selection in UPS setting mode.
Switch to UPS self-test mode: Press ON/Mute buttons for 3 seconds to enter UPS self-testing while in AC mode, ECO mode, or converter mode.
Turn off the UPS: Press and hold this button at least 2 seconds to turn off the UPS. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button.
Confirm selection key: Press this button to confirm selection in UPS setting mode.
Switch LCD message: Press this button to change the LCD message for input voltage, input frequency, input current, battery voltage, battery current, battery capacity, ambient temperature, output voltage, output frequency, load current and load percent.
Setting mode: Press and hold this button for 3 seconds to enter UPS setting mode when Standby and Bypass mode.
Down key: Press this button to display next selection in UPS setting mode.
Switch to bypass mode: When the main power is normal, press ON/Mute and Select buttons simultaneously for 3 seconds. Then UPS will enter to bypass mode. This action will be ineffective when the input voltage is out of acceptable range.
Exit setting mode or return to the upper menu: When working in setting mode, press ON/Mute and Select buttons simultaneously for 0.2 seconds to return to the upper menu. If it’s already in top menu, press these two buttons at the same time to exit the setting mode.

3-2. LCD Panel

11

Display

Function

Backup time information

Indicates the estimated backup time.
H: hours, M: minute, S: second.

Configuration and fault information

Indicates the configuration items, and the configuration items are listed

in details in section 3-5.

Indicates the warning and fault codes, and the codes are listed in details

in section 3-7 and 3-8.

Mute operation

Indicates that the UPS alarm is disabled.

Input, Battery, Temperature, Output & Load information IIndicate the input voltage, input frequency, input current, battery voltage, battery current, battery capacity, ambient temperature, output voltage, output frequency, load current and load percent.
k: kilo, W: watt, V: voltage, A: ampere, %: percent, : centigrade degree, Hz: frequency
Load information Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.

Indicates overload.
Programmable outlets information Indicates that programmable management outlets are working.
Mode operation information Indicates the UPS connects to the mains. Indicates the battery is working. Indicates charging status Indicates the bypass circuit is working. Indicates the ECO mode is enabled. Indicates the AC to DC circuit is working. Indicates the PFC circuit is working. Indicates the inverter circuit is working.
Indicates the UPS is working in converter mode.
Indicates the output is working. Battery information
Indicates the battery level by 0-24%, 25-49%, 50-74%, and 75-100%.

Indicates low battery.

12

3-3. Audible Alarm Battery Mode Low Battery Overload Fault Bypass Mode

Sounding every 5 seconds Sounding every 2 seconds
Sounding every second Continuously sounding Sounding every 10 seconds

3-4. LCD display wordings index Abbreviation Display content ENA DIS ESC HLS LLS AO AC EAT RAT SD OK ON BL OL OI NC OC SF EP TP CH BF BV FU BR EE

Meaning Enable Disable Escape High loss Low loss Active open Active close Estimated autonomy time Running autonomy time Shutdown OK ON Battery Low Over Load Over input current Battery No Connect Over Charge Site wiring fault EPO Temperature Charger Battery Fault Bypass Out Range Bypass frequency unstable Battery Replace EEPROM error

13

3-5. UPS Setting

Parameter 1

Parameter 2

There are three parameters to set up the UPS. Parameter 1: It’s for program alternatives.
Refer to below table. Parameter 2 is the setting options or values for each program

01: Output voltage setting

Interface

Setting

Parameter 2: Output voltage

For 200/208/220/230/240 VAC models, you may choose

the following output voltage:

200: presents output voltage is 200Vac

208: presents output voltage is 208Vac

220: presents output voltage is 220Vac

230: presents output voltage is 230Vac (Default)

240: presents output voltage is 240Vac

02: Frequency Converter enable/disable

Interface

Setting

Parameter 2: Enable or disable converter mode. You may

choose the following two options:

CF ENA: converter mode enable

CF DIS: converter mode disable (Default)

03: Output frequency setting

Interface

Setting

Parameter 2: Output frequency setting. You may set the initial frequency on battery mode: BAT 50: presents output frequency is 50Hz BAT 60: presents output frequency is 60Hz If converter mode is enabled, you may choose the following output frequency: CF 50: presents output frequency is 50Hz CF 60: presents output frequency is 60Hz

04: ECO enable/disable

Interface

Setting Parameter 2: Enable or disable ECO function. You may choose the following two options: ENA: ECO mode enable DIS: ECO mode disable (Default)

14

05: ECO voltage range setting

Interface

Setting Parameter 2: Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key. HLS: High loss voltage in ECO mode in parameter 2. For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from +7V to +24V of the nominal voltage. (Default: +12V) LLS: Low loss voltage in ECO mode in parameter 2. For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from -7V to -24V of the nominal voltage. (Default: -12V)

06: Bypass enable/disable when UPS is off

Interface

Setting

Parameter 2: Enable or disable Bypass function. You

may choose the following two options:

ENA: Bypass enable DIS: Bypass disable (Default)

07: Bypass voltage range setting

Interface

Setting

Parameter 2: Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key. HLS: Bypass high voltage point

For 200/208/220/230/240 VAC models:

230-264: setting the high voltage point in parameter 3 from 230Vac to 264Vac. (Default: 264Vac) LLS: Bypass low voltage point For 200/208/220/230/240 VAC models: 170-220: setting the low voltage point in parameter 3 from 170Vac to 220Vac. (Default: 170Vac)

08: Bypass frequency range setting

Interface

Setting Parameter 2: Set the acceptable high frequency point and acceptable low frequency point for Bypass mode by pressing the Down key or Up key. HLS: Bypass high frequency point For 50Hz output frequency models: 51-55Hz: setting the frequency high loss point from 51Hz to 55HZ(Default: 53.0Hz) For 60Hz output frequency models: 61-65Hz: setting the frequency high loss point from 61Hz to 65Hz(Default: 63.0Hz) LLS: Bypass low Frequency point

15

For 50Hz output frequency models:

45-49Hz: setting the frequency low loss point from 45Hz to 49HZ(Default: 47.0Hz) For 60Hz output frequency models: 55-59Hz: setting the frequency low loss point from 55Hz to 59Hz(Default: 57.0Hz)

09: Programmable outlets enable/disable

Interface

Setting

Parameter 2: Enable or disable programmable outlets. ENA: Programmable outlets enable DIS: Programmable outlets disable (Default)

10: Programmable outlets setting

Interface

Setting Parameter 2: Set up backup time limits for programmable outlets. 0-999: setting the backup time limits in minutes from 0999 for programmable outlets which connect to noncritical devices on battery mode. (Default: 999)

11: Autonomy limitation setting

Interface

Setting Parameter 2: Set up backup time on battery mode for general outlets. 0-999: setting the backup time in minutes from 0-999 for general outlets on battery mode. DIS: Disable the autonomy limitation and the backup time will depend on battery capacity. (Default) Note: When setting as “0”, the backup time will be only 10 seconds.

12: Battery total AH setting

Interface

Setting Parameter 2: Set up the battery total AH of the UPS. 7-999: setting the battery total capacity from 7-999 in AH. Please set the correct battery total capacity if external battery bank is connected.

13: Maximum charger current setting

Interface

Setting

Parameter 2: Set up the charger maximum current. For low voltage model with 24/36/48VDC 1/2/4/6/8: setting the charger maximum current 1/2/4/6/8 in Ampere. (Default: 2A) For high voltage model with 24/36/48VDC 1/2/4/6/8/10/12: setting the charger maximum

current 1/2/4/6/8/10/12 in Ampere. (Default: 2A)

16

For low voltage and high voltage model with 72/96VDC 1/2/4/6/8: setting the charger maximum current 1/2/4/6/8 in Ampere. (Default: 2A) Note: Please set the appropriate charger current based on

battery capacity used. The recommended charging

current is 0.1C~0.3C of battery capacity as following table

for reference.

Battery capacity(AH) Total charging current (A)

7~20

2

20~40

4

40~60

6

60~80

8

80~100

10

100~150

12

14: Charger boost voltage setting

Interface

Setting

Parameter 2: Set up the charger boost voltage. 2.25-2.40: setting the charger boost voltage from 2.25 V/cell to 2.40V/cell. (Default: 2.36V/cell)

15: Charger float voltage setting

Interface

Setting

Parameter 2: Set up the charger float voltage.

2.20-2.33: setting the charger float voltage from 2.20

V/cell to 2.33V/cell. (Default: 2.28V/cell)

16: EPO logic setting

Interface

Setting

Parameter 2: Set up the EPO function control logic.

AO: Active Open (Default). When AO is selected as EPO

logic, it will activate EPO function with Pin 1 and Pin 2 in

open status.

AC: Active Close. When AC is selected as EPO logic, it will

activate EPO function with Pin 1 and Pin 2 in close status.

17: External output isolation transformer connection

Interface

Setting Parameter 2: Allow or disallow external output isolation transformer connection. ENA: If selected, it’s allowed to connect to an external output isolation transformer. DIS: If selected, it’s not allowed to connect to external output isolation transformer. (Default)

17

18: Display setting for autonomy time

Interface

Setting Parameter 2: Set up the display setting for autonomy time EAT: If EAT is selected, it will display the remaining autonomy time. (Default) RAT: If RAT is selected, it will show accumulated autonomy time so far.

19: Acceptable input voltage range setting

Interface

Setting

Parameter 2: Set the acceptable high voltage point and acceptable low voltage point for input voltage range by pressing the Down key or Up key. HLS: Input high voltage point For 200/208/220/230/240 VAC models: 280/290/300: setting the high voltage point in parameter 2. (Default: 300Vac) LLS: Bypass low voltage point For 200/208/220/230/240 VAC models: 110/120/130/140/150/160: setting the low voltage point in parameter 2. (Default: 110Vac)

00: Exit setting Interface

Setting Exit the setting mode.

3-6. Operating Mode Description

Operating mode Description

Online mode

When the input voltage is within acceptable

range, UPS will provide pure and stable AC

power to output. The UPS will also charge the

battery at online mode.

ECO mode

Energy saving mode:

When the input voltage is within voltage

regulation range, UPS will bypass voltage to

output for energy saving. The UPS will also

charge the battery at ECO mode.

Frequency Converter mode

When input frequency is within 40 Hz to 70 Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge battery under this mode.

LCD display

18

Battery mode Bypass mode Standby mode

When the input voltage is beyond the acceptable range or power failure, the UPS will backup power from battery and alarm is sounding every 5 seconds.
When input voltage is within acceptable range but UPS is overload, UPS will enter bypass mode or bypass mode can be set by front panel. Alarm is sounding every 10 seconds.
UPS is powered off and no output supply power, but still can charge batteries.

Fault mode

When a fault has occurred, the ERROR icon and the fault code will be displayed.

3-7. Faults Reference Code

Fault event

Fault code Icon Fault event

Fault code Icon

Bus start fail

01

x Battery voltage too

27

x

high

Bus over

02

x Battery voltage too low 28

x

Bus under

03

x Charger output short 2A

x

Inverter soft start fail 11

x Over temperature

41

x

Inverter voltage high 12

x Overload

43

Inverter voltage Low 13

x Charger failure

45

x

Inverter output short 14

x Over input current

49

x

3-8. Warning indicator Warning Low Battery Overload Over input current Battery is not connected
Over Charge

Icon (flashing)

Code

Alarm Sounding every 2 seconds Sounding every second Sounding 2 beep every 10 seconds Sounding every 2 seconds Sounding every 2 seconds

Site wiring fault
EPO enable Over temperature Charger failure
Battery fault

Sounding every 2 seconds
Sounding every 2 seconds Sounding every 2 seconds Sounding every 2 seconds Sounding every 2 seconds (At this time, UPS is off to remind
19

users something wrong with

battery)

Out of bypass voltage range

Sounding every 2 seconds

Bypass frequency unstable

Sounding every 2 seconds

Battery replacement

Sounding every 2 seconds

EEPROM error

Sounding every 2 seconds

NOTE: “Site Wiring Fault” function can be enabled/disabled via software. Please check

software manual for the details.

4. Troubleshooting

If the UPS system does not operate correctly, please solve the problem by using the table

below.

Symptom

Possible cause

Remedy

No indication and alarm even The AC input power is not Check if input power cord

though the mains is normal.

connected well.

firmly connected to the

mains.

The AC input is connected Plug AC input power cord

to the UPS output.

to AC input correctly.

The icon and the warning
code flash on LCD display and alarm is sounding every 2 seconds.

The icons of and and

the warning code flash on LCD display. Alarm is sounding every 2 seconds.

The icons of

and

and

the warning code flash on LCD display. Alarm is sounding every 2 seconds. Fault code is shown as 27 on LCD display and alarm is continuously sounding. Fault code is shown as 28 on LCD display and alarm is continuously sounding.

The icons and and the

warning code flash on LCD display. Alarm is sounding every second.

EPO function is activated. Set the circuit in closed position to disable EPO function.

Line and neutral conductors of UPS input are reversed.

Rotate mains power socket by 180° and then connect to UPS system.

The external or internal battery is incorrectly connected.

Check if all batteries are connected well.

Battery voltage is too high Contact your dealer. or the charger is fault.

Battery voltage is too low Contact your dealer. or the charger is fault.

UPS is overload
UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass. After repetitive overloads, the UPS is locked in the Bypass mode. Connected

Remove excess loads from UPS output. Remove excess loads from UPS output.
Remove excess loads from UPS output first. Then shut down the UPS and

20

Symptom Fault code is shown as 49 on LCD display and alarm is continuously sounding. Fault code is shown as 43 and the icon is lighting on LCD display. Alarm is continuously sounding. Fault code is shown as 14 on LCD display and alarm is continuously sounding.
Fault code is shown as 01, 02, 03, 11, 12, 13 and 41 on LCD display and alarm is continuously sounding.
Battery backup time is shorter than nominal value.
Fault code is shown as 2A on LCD display and alarm is continuously sounding. Fault code is shown as 45 on LCD display. At the same time, alarm is continuously sounding.

devices are fed directly by the mains.
Possible cause UPS is over input current.

restart it.
Remedy Remove excess loads from UPS output.

The UPS shut down automatically because of overload at the UPS output. The UPS shut down automatically because short circuit occurs on the UPS output. A UPS internal fault has occurred. There are two possible results: 1. The load is still supplied, but directly from AC power via bypass. 2. The load is no longer supplied by power. Batteries are not fully charged
Batteries defect

Remove excess loads from UPS output and restart it.
Check output wiring and if connected devices are in short circuit status. Contact your dealer
Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer. Contact your dealer to replace the battery.

The short circuit occurs on the charger output.
The charger does not have output and battery voltage is less than 10V/PC.

Check if battery wiring of connected external pack is in short circuit status. Contact your dealer.

5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.

Storage

Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.
21

Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry

location. During storage, recharge the battery in accordance with the following table:

Storage Temperature

Recharge Frequency

Charging Duration

-25°C – 40°C

Every 3 months

1-2 hours

40°C – 45°C

Every 2 months

1-2 hours

6. Specifications

Tower Models (VFI CG PF1)

MODEL CAPACITY* INPUT

Low Line Transfer

Voltage Range

Low Line Comeback High Line Transfer

High Line

Comeback

Frequency Range

Phase

Power Factor

THDi

OUTPUT Output voltage

VFI 1000 CG PF1 VFI 1500 CG PF1 VFI 2000 CG PF1

1000VA/1000W

1500VA/1500W

2000VA/2000W

VFI 3000 CG PF1 3000VA / 3000W

160VAC/140VAC/120VAC/110VAC ± 5 % ( based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)
175VAC/155VAC/135VAC/125VAC ± 5 %
300 VAC ± 5 %
290 VAC ± 5 %
40Hz ~ 70 Hz Single phase with ground
0.99 @ full load 5% @ 205-245VAC THDU < 1.6% @ input and full linear load condition

200/208/220/230/240VAC

AC Voltage Regulation

Frequency Range (Synchronized Range) Frequency Range Current Crest Ratio

Harmonic Distortion

Transfer Time

AC Mode to Batt. Mode Inverter to Bypass

Waveform (Batt. Mode)

EFFICIENCY

AC Mode

ECO Mode

Battery Mode

BATTERY Battery Type Numbers Recharge Time

Charging Current

Charging Voltage

PHYSICAL

Dimension, D X W X H (mm)

Net Weight With battery

(kgs)

Without battery

ENVIRONMENT

Operation Humidity

Noise Level

MANAGEMENT

Smart RS-232 or USB

Optional SNMP

± 1% (Batt. Mode)
47 ~ 53 Hz or 57 ~ 63 Hz
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode) 3:1
2 % THD (Linear Load) ; 4 % THD (Non-linear Load)
Zero
< 4 ms Pure Sinewave

89% @ full charged battery

91% @ full charged battery

96% @ full charged battery

88%

90%

12V/7AH

12V/9AH

12V/7AH

12V/9AH

3

6

3 hours recover to 95% capacity for internal battery@ 2A charging current

200/208/220/230/240 VAC models: default 2A, max. 12A adjustable

Default: 2A, Max: 8A adjustable

41.0 VDC ± 1%

82.1 VDC ±1%

397 X 145 X 220

13.0

14.6

6.6

7

421 X 190 X 318

23.2

28.0

9.9

12.3

20-95 % RH @ 0- 40°C (non-condensing) Less than 50dBA @ 1 Meter (With fan speed control)

Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC Power management from SNMP manager and web browser

22

Rack Models (VFI RMG PF1):

MODEL

VFI 1000 RMG PF1 VFI 1500 RMG PF1 VFI 2000 RMG PF1 VFI 3000 RMG PF1

Long-Run Model

VFI 1000 RMGS

VFI 2000 RMGS

CAPACITY*

1000VA/1000W

1500VA/1500W

2000VA/2000W

3000VA / 3000W

INPUT

Low Line Transfer

160VAC/140VAC/120VAC/110VAC ± 5 % (based on load percentage 100% – 80 % / 80 % – 70 % / 70 – 60 % / 60 % – 0)

Voltage Range

Low Line Comeback High Line Transfer

175VAC/155VAC/135VAC/125VAC ± 5 % 300 VAC ± 5 % o

High Line Comeback

290 VAC ± 5 %

Frequency Range

40Hz ~ 70 Hz

Phase

Single phase with ground

Power Factor

0.99 @ full load

THDi

5% @ 205-245VAC THDU < 1.6% @ input and full linear load condition

OUTPUT

Output voltage

200/208/220/230/240VAC

AC Voltage Regulation

± 1% (Batt. Mode)

Frequency Range (Synchronized Range)

47 ~ 53 Hz or 57 ~ 63 Hz

Frequency Range

50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)

Current Crest Ratio

3:1

Harmonic Distortion

2 % THD (Linear Load) ; 4 % THD (Non-linear Load)

Transfer Time

AC Mode to Batt. Mode Inverter to Bypass

Zero < 4 ms

Waveform (Batt. Mode)

Pure Sinewave

EFFICIENCY

AC Mode

89% @ full charged battery

91% @ full charged battery

ECO Mode

96% @ full charged battery

Battery Mode

88%

90%

BATTERY

Battery Type

12V/7AH

12V/9AH

12V/7AH

12V/9AH

Numbers

2

3

4

6

Recharge Time

3 hours recover to 95% capacity for internal battery@ 2A charging current

Charging Current

200/208/220/230/240 VAC models: default 2A, max. 12A adjustable

Default: 2A, Max: 8A adjustable

Charging Voltage

27.4 VDC ± 1%

41.0 VDC ± 1%

54.8 VDC ± 1%

82.1 VDC ±1%

PHYSICAL

Dimension, D X W X H (mm)

410 x 438 x 88

510 x 438 x88

630 x 438 x 88

Net Weight With battery

14.1

15.5

23.3

27.5

(kgs)

Without battery

6.6

7.8

8.1

9.4

10.6

12.4

ENVIRONMENT

Operation Humidity

20-95 % RH @ 0- 40°C (non-condensing)

Noise Level

Less than 50dBA @ 1 Meter (With fan speed control)

MANAGEMENT

Smart RS-232 or USB

Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC

Optional SNMP

Power management from SNMP manager and web browser

  • Derate capacity to 80% of capacity when the output voltage is adjusted to 200VAC or 208VAC.

** Product specifications are subject to change without further notice.

23

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

PowerWalker User Manuals

Related Manuals