VIESMANN WB2 Gas Train Replacement Installation Guide

June 16, 2024
VIESMANN

Installation instructions
for contractors
Gas train replacement

Safety instructions

Please follow these safety instructions closely to prevent accidents and material losses.

Safety instructions explained

Danger
This symbol warns against the risk of injury.
Note
Details identified by the word “Note” contain additional information.
Installation, initial start-up, inspection, aintenance and repairs must only be carried out by a competent person (heating engineer/installation contractor).
Before working on the equipment/heating system, isolate the power supply (e.g. by removing a separate mains  fuse or by means of a mainsisolator) and safeguard against unauthorised reconnection.
When using gas as fuel, also close the main gas shut-off valve and safeguard against unauthorised reopening.
Repairing components which fulfil a safety function can compromise the safe operation of your heating system. For replacements, use only original spare parts supplied or approved by Viessmann.

Application

Gas train with 20 V operating voltage:

  • Vitodens 200, type WB2
  • Vitodens 222, type WS2

Gas train with 230 V operating voltage:

  • Vitodens 300, type WB3A
  •  Vitodens 333, type WS3A

Replacing the gas train

Note
The new gas train is not provided with a gas restrictor. Remove the gas restrictor from the gas train being replaced or from the conversion kit and install it in the new gas train.

  1. Remove front panel and cover.

  2. Disconnect power cables\leads from gas train A and differential pressure sensor B.

  3. Remove differential pressure sensor B and (if installed) differential pressure sensor adaptor C from gas train A by pulling them upwards..

  4. Undo the two screws from inletside flange D.
    Replacing the gas train (cont.)

  5. Undo the three screws from gas train A.

  6.  Remove gas train A by pulling it forwards.

  7. Undo gas restrictor retainer E from old gas train A, remove gas restrictor F and insert in gas restrictor retainer E on new gas train A.

  8.  Only for Vitodens 300 to 35 kW and Vitodens 333: Undo connection adaptor G from new gas train A and fit new differential pressure sensor adaptor H to new gas train A.

  9. Check whether the O-rings have been inserted into the openings of connection adaptor G or differential pressure sensor adaptor H.

  10.  Connect differential pressure sensor B to new gas train A (click into place).

  11. Check whether the outlet-side gasket is fitted to new gas train A.

  12. Secure gas train A to burner (torque 5 Nm).

  13. Fit flange D (torque 5 Nm).

  14.  Connect the power cables to gas train A and differential pressure sensor B.

  15. Start the boiler and check it is working correctly.
    Danger
    Escaping gas leads to a risk of explosion.
    Check all gas connections for tightness.

  16. Fit front panel and cover.

Viessmann Werke GmbH & Co. KG
D-35107 Allendorf
Telephone: +49 6452 70-0
Fax: +49 6452 70-2780
www.viessmann.com

https://support.viessmann.com/technical- documents?documentNumber=5492918&version=1&country=GB&language=en&documentType=VMA

Viessmann Limited
Hortonwood 30, Telford
Shropshire, TF1 7YP, GB
Telephone: +44 1952 675000
Fax: +44 1952 675040
E-mail: [email protected]
5492918Subject to technical modifications.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

VIESMANN User Manuals

Related Manuals