MAXA I-290 Series Inverter Air Water Heat Pumps with Axial Fans User Manual
- June 16, 2024
- MAXA
Table of Contents
- I-290 Series Inverter Air Water Heat Pumps with Axial Fans
- HOW TO KEEP THE MANUAL
- PERMITTED USED
- GENERAL SAFETY GUIDELINES
- PURPOSE AND CONTENTS OF THE MANUAL
- I-CR INSTALLATION
- I-CR CONNECTIONS
- EDITING DYNAMIC SET-POINT
- CIRCULATOR
- COMPRESSOR OR ACTIVATION LOGIC
- FAN CONTROL OF THE FINNED EXCHANGER
- CONTROLLER FUNCTIONS
- FUNCTIONS THAT CAN BE ACTIVATED WITH HI-T2 ACCESSORY (OPTIONAL)
- FUNCTIONS THAT CAN BE ACTIVATED WITH GI3 MODULE (OPTIONAL)
- TABLES OF PERMITTED SETUPS FOR USER AND INSTALLER
- ALARMS
- MODBUS VARIABLES
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Chiller and Inverter Air/Water heat pumps with axial fans
Controller Manual
Models
i-290 0106
i-290 0109
i-290 0112
i-290 0115
i-290 0118
I-290 Series Inverter Air Water Heat Pumps with Axial Fans
This manual has been created for informative purpose. The company declines any responsibility for the results of any projecting or any installation based on the explanations and/or on the technical specifications provided in this manual. It is besides forbidden the reproduction under any form of the texts and of the figures contained in this manual. This manual is a translation from the official italian language version. For reasons of environmental respect the Company will not provide the hard copy in the original language which could be directly requested or downloaded from the Company website at any time. In case of any dispute, the original language manual will be the trusted one. Even partial reproduction PROHIBITED © Copyright – Advantix SpA
00 | 30-01-2023 | M.S. | A.B. | Issued |
---|---|---|---|---|
Rev | Date | Edited | Approved | |
Catalogo | Serie | |||
MCO02050120000_00 | **CONTROL FOR INVERTER AIR/WATER CHILLERS AND HEAT |
PUMPS WITH AXIAL FANS**
The electrical and electronic products and any waste should not be disposed of with normal household waste, but disposed of according to WEEE law in accordance with the directive 2012/19/EU, inquiring thereof at the place of residence or with the retailer in the case where the product is replaced with a similar one.
HOW TO KEEP THE MANUAL
The company reserves the right to modify its products and related manuals without necessarily updating previous versions of the reference material. We also decline any responsibility for possible inaccuracies in the manual if due to printing or transcription errors. The customer shall store any updated copy of the manual or parts of it delivered by the manufacturer as an attachment to this manual. The company is available to give any detailed information about this manual and to give information regarding the use and the maintenance of its own units.
1.1 GRAPHIC SYMBOLS USED IN THE MANUAL
| Indicates prohibited operations.
---|---
| Indicates potentially hazardous situation for people and/or the proper
functioning of the unit.
| Hazardous electrical voltage – Electrocution hazard.
| Indicates important information that the operator has to follow in order to
guarantee the correct operation of the unit in complete safety. Also indicates
some general information.
PERMITTED USED
- The company excludes any contractual and extra contractual liability for damage caused to persons, animals or objects, by incorrect installation, setting and maintenance, improper use of the equipment, and the partial or superficial reading of the information contained in this manual.
- These units are built for the heating and/or cooling of water. Any other use not expressly authorised by the manufacturer is considered improper and therefore not allowed.
- All the work must be executed by skilled and qualified personnel, competent on the existing regulations in country of installation.
- This appliance is intended to be used by expert or trained operators in shops, light industry and in factories, or for commercial use by non-expert personnel.
- The appliance may be used by children at least 8 years old and by persons with reduced physical, sensory or mental capabilities or without experience or the necessary knowledge as long as they are supervised or after they themselves have received instructions on the safe use of the appliance and understand the relevant dangers. Children must not play with the appliance. The cleaning and maintenance which the user is expected to carry out on the unit cannot be done by children without supervision.
GENERAL SAFETY GUIDELINES
Before starting any type of operation on the unit, every user and operator
must have perfect knowledge of operation of the machine and of its controls
and have read and understood all of the information in this manual and in the
user-installer manual.
3.1 PERSONAL PROTECTIVE EQUIPMENT
Refer to the user-installer manual which accompanies the unit.
3.2 WORKERS’ HEALTH AND SAFETY
Refer to the user-installer manual which accompanies the unit.
| IT IS PROHIBITED:
---|---
To remove and/or to tamper with any safety device.
For unauthorised personnel to access the electric panel.
To work on live systems.
To touch the systems if not authorised to do so.
To allow children or unassisted disabled persons to use the appliance.
To touch the appliance when barefoot or parts of the body are wet or
damp.
To perform any cleaning operation when the master switch is ‘ON’.
To pull, detach or twist the appliance’s electric cables.
To step on, sit down on and/or place any type of object on the appliance.
To spray or pour water directly on the unit.
To dispose of, abandon or leave within reach of children packaging
materials (cardboard, staples, plastic bags, etc.) as they may represent a
hazard for the environment and one’s life.
To tamper with or replace parts of the unit without the specific consent of
the manufacturer. The manufacturer shall have no responsibility whatsoever in
case of unauthorised operations.
| CAUTION:
Refer to the user-installer manual which accompanies the unit before
proceeding.
All the operation described below must be done by QUALIFIED PERSONNEL
ONLY.
The electrical wiring to the terminal blocks has to be done only by
qualified personnel.
Any routine and/or extraordinary maintenance operation must be carried out
with the machine stopped and disconnected.
Do not place your hands or introduce screwdrivers, spanners or any other
tools on moving parts.
The machine operator and maintenance personnel must receive suitable
training for the performance of their tasks in safety.
Only authorised personnel are allowed to have access to the electric
panel.
Operators must know how to use personal protective equipment and the
accident-prevention rules of national and interna- tional laws and
regulations.
The operator’s workplace has to be kept clean, tidy and clear of objects
that may hinder free movement. Appropriate lighting of the work place shall be
provided so as to allow the operator to carry out the required operations
safely. Poor or excessive lighting can cause risks.
Ensure that work places are always adequately ventilated and that the
extraction systems are working, in good condition and in compliance with the
requirements of the laws in force.
Not all of the configurations described can be activated and/or modified at
the same time.
Values other than the default values can jeopardise proper operation of the
unit. For further information regarding the value to set, you can refer
directly to ADVANTIX S.p.a.
The company excludes any contractual and extra contractual liability for
damage caused to persons, animals or objects, by incorrect installation,
setting and maintenance, improper use of the equipment, and the partial or
superficial reading of the information contained in this manual.
| The power supply has to respect the limits shown on the unit’s technical
label: failing this, the warranty shall expire immedi- ately. Before beginning
any type of operation, make sure that power is disconnected.
---|---
Connect the conductors in order: phase, neutral and earth.
Dimensioning of the power cables must take into consideration the TECHNICAL
DATA provided in the user-installer manual accompanying the unit. Also
consider any auxiliary heating devices.
Effective earthing is mandatory; the manufacturer is not responsible for
damage caused in its absence.
When undergoing maintenance, the unit must be disconnected from the power
supply, and it must be unplugged in such a way that the operator can verify
from wherever he accesses that the plug remains disconnected.
Use cables that meet the regulations in force in the different countries.
After the unit has been running for 10 minutes, make sure that the screws
on the power terminal block remain secured.
| Install upstream of each unit a suitable QF protective device and power
disconnector, with delayed characteristic curve, with at least 3 mm contact
opening and adequate breaking capacity and residual current protection. The
size of the circuit breaker must comply with absorption of the unit. See the
TECHNICAL DATA in the user-installer manual which accompanies the unit. Also
consider any auxiliary heating devices.
---|---
Before performing any operations on the electric panel, IT IS MANDATORY:
To switch off the unit from the control panel (“OFF” displayed).
To place the general residual current device QF at “OFF”.
To wait 15 seconds before accessing the electric panel.
To check the grounding before performing any operation.
To remain well isolated from the ground, with dry hands and feet, or using
insulated platforms and gloves.
To keep foreign materials away from the system.
PURPOSE AND CONTENTS OF THE MANUAL
The manual is intended to provide the essential information to configure the
controller of the units.
It is addressed to the installer and operators of the appliance and it enables
them to use the equipment efficiently, even if they do not have any previous
specific knowledge of it.
Not all of the functions described can be activated and/or selected at the
same time. Contact our headquarters for further information.
The manual describes the machine at the moment it was sold. It must therefore
be considered adequate with respect to the state-of-the-art in terms of
potentiality, ergonomics, safety and functionality.
The company also performs technological upgrades and does not consider itself
obliged to update the manuals of previous machine versions which could even be
incompatible. Therefore make sure to use the supplied manual for the installed
. Contact our headquarters in case of updates or doubts.
The user is recommended to follow the instructions contained in this booklet,
especially those concerning safety and routine maintenance.
KEY | DESCRIPTION |
---|---|
ON/OF BACKLIGHT |
Function that works at the thermostat level, switches LEDs and backlight
off/on. When the keypad is in OFF mode, does not accept commands.
This function has no effect on machine control, but enables/disables
thermostat interaction. Allows you to exit the menu.
If pressed for 3 seconds, activates standby mode and locks the keyboard (lock
icon appears).
This functionality has no effect on the machine control, but enables/disables
user interaction with the thermostat keyboard.
| UP
It allows you to move to a higher menu or to increase the value of a
parameter.
KEY| DESCRIPTION
---|---
| DOWN
It allows you to move to a lower menu or to decrease the value of a parameter.
| CHRONOTHERMOSTAT
Allows to set the operating bands for thermostation on the room temperature
detected by the probe present in the i-CR.
| CHANGE SEASON KEY
To change the season press for 3 seconds or switch the heat pump or chiller
OFF.
| ENTER KEY
It allows you to enter menu or to confirm a parameter.
LED backlighting is switched off if the keyboard has not been used for more than 1 minute. In this case, the first press on a key reactivates the keyboard by making the LEDs light up, but the function associated with the key is not executed.
I-CR INSTALLATION
The control is designed for wall mounting according to DIN 503. Indoor use.
On the back of the control, there are pre-drilled slots to be removed by
applying pressure with a screwdriver, so that the holes for fastening can be
drilled.
Before doing so, open the control itself, applying light pressure to the
bottom and top of the control, so as to separate the back panel from the front
panel.
Use the back panel and drill the holes in the two slots.
Do not use the panel directly as a template to drill holes in the wall, the
electronics could be damaged during this operation.
In detail follow the following steps to open the i-CR:
I-CR CONNECTIONS
Two connection cables are required between chiller unit or heat pump and i-CR remote control:
- 3X1.5mmq shielded twisted pair cable for Modbus R+/R-/GND communication.
- 2×1.5mmq cable for 12Vac power supply.
| DESCRIPTIONS| i-CR TERMINALS| CHILLER OR HEAT PUMP TERMINALS|
NOTE
---|---|---|---|---
CABLE 1| POWER SUPPLY| PIN 12| 12Vac|
PIN 13| 12Vac
CABLE 2
|
COMMUNICATION
| PIN 9| GND RS485|
SHIELDED AND TWISTED CABLE
PIN 7| RS485 +
PIN 8| RS485 –
| DESCRIPTIONS| i-CR TERMINALS| CHILLER OR HEAT PUMP TERMINALS|
NOTE
---|---|---|---|---
CABLE 3| DIGITAL INPUT| PIN 1| | VOLTAGE-FREE CONTACT
PIN2
7.1 MENU
Press Enter to enter the first-level menu. The following items appear here:
With the arrow keys you navigate through the possible entries, with the Enter
key you select the chosen menu, with the ON/OFF KEY you exit again.
MENU | LABEL | PASSWORD LEVEL | OTHER CONDITIONS |
---|---|---|---|
Water Setpoint (in cool and heat, eco and normal) | Set | User | — |
Ambient setpoint (in cold and heat, eco and normal) | SetA | User | — |
i-CR Remote Keypad Mode of Op- eration | ModE | User | — |
Alarms | Err | User | Only if active alarms |
Setting date and hours | Date | User | — |
Password | PSS | User | — |
Machine parameters and thermostat rooms | Par | Installer | — |
Operating hours | oHr | Installer | — |
USB | USb | Installer | Only with pen drive with relevant update files |
Firmware version of the control inside the electrical panel | Fir | Installer |
Version, Revision and Sub
Alarm history| Hist| Installer| Only if data are present in the history
Menu with manual forcing| For| Installer| —
System Status Menu| SYS| Installer| —
The PSS menu is accessed to enter the service password and to enable access
with a higher user permission. Once you exit the menu completely, you lose the
password privilege and must enter it again.
7.1.1 Set
Setting WATER setpoint cooling and heating.
Water setpoint | Default |
---|---|
Coo | 7.0°C |
HEA | 45.0°C |
Water setpoint | Default |
--- | --- |
SAN | 48.0°C |
SAN2 | 45.0°C |
COO2 | 18.0°C |
HEA2 | 35.0°C |
7.1.2 SetA
Setting of AMBIENT setpoints (i-CR on-board probe measurements). Disabled in
diS mode.
Setp | Default |
---|---|
Coo | 25.0°C |
HEA | 20.0°C |
CooE | 30.0°C |
HEAE | 15.0°C |
7.1.3 ModE
Selecting the ModE menu sets the type of operation (default operation mode is
‘diS’).
| diS: Ambient thermostat function disabled.
This mode can be recognised by the fact that neither the manual icon nor the
chronothermostat icon appears.
The icon with the drop symbol is present. The temperature displayed is that of
the control probe of the heat pump or chiller. The
symbol is only displayed when the machine is ON. In this mode, air sets are
not be settable (menu SetA does not appear).
---|---
| ComF: Ambient thermostat function active.
The thermoregulation request will be evaluated based on the temperature read
by the thermostat and the normal seasonal room set.
The temperature displayed is the air temperature read by the probe on board
the i-CR thermostat.
This mode can be recognised by only the presence of the manual symbol.
| Eco: ECO function manual.
The thermoregulation request will be evalueted based on the temperature read
by the thermost and the ECO seasonal room set.
This mode can be recognised by the presence of the manual and leaf icon.
| Cron: Active chronothermostat.
The thermoregulation request follows the programming of the weekly
chronothermostat which in turn can be in one of the following bands: OFF Eco
ComF
This mode can be recognised by the presence of the clock indicating the active
chronothermostat, the active time zone can be identified by the presence or
absence of the moon and leaf symbols.
This menu is always accessible. To set the chronothermostat see chapter 8.14.
7.1.4 Err
In this menu you can see the abbreviations of the current alarms active on the
chiller or heat pump.
Use the UP and DOWN buttons to scroll through the various alarms present.
If there are no alarms, the message ‘noAL’ appears.
The presence of an error on the chiller or heat pump can be recognised by the
presence of the icon. Manual reset of machine alarms: This is done
automatically by switching the machine to OFF with the MODE button (if there
is an alarm signal on the screen).
7.1.5 Date
Setting date and hour:
- YEAr: from 2018 to 2099
- Mon: from 1 (January) to 12 (December)
- DAy: from 1 to 31 (with dynamic limitation for some months/years)
- Hour: from 00:00 to 23:59
The day of the week is calculated automatically.
Daylight saving time handled automatically with EU rule.
On the display, by default, day 1 is Monday and day 7 is Sunday. By setting
parameter K50 = 1, day 1 will be Sunday.
Note: When at start-up the board detects that the date and time have been
reset, this menu is automatically presented to ask for the date and time to be
entered.
7.1.6 PSS
Setting password to enter in the installer menu.
7.1.7 Par
This menu gives access to all machine parameters. The parameters are collected
in groups, each group is identified by a three-digit code, while the index of
each parameter is preceded by a letter.
DESCRIPTION| GROUP IDENTIFICATION CODE| PARAMETER INDEX|
VISIBILITY
---|---|---|---
Configuration i-CR| KBT| K01-| User/Installer
Configuration| CnF| H01-| Installer
Compressor| CP| C01-| Installer
Alarms| ALL| A01-| Installer
Regulation| rE| b01-| Installer
Pump| PUP| P01-| Installer
Heating elements| Fro| r01-| Installer
Defrosting| dFr| d01-| Installer
Hz min / max| LbH| L0-| Installer
*Solar*| SUn| S01-| Installer
Mixer valve**| rAD| i01-| Installer
(*) To be configured if Gi module present.
To access the installer parameters: PRG -> PSS -> PRG -> (insert installer
password) ->PRG ->PAr -> PRG.
In the KBT “display configuration” group are the configurations for remote
control i-CR:
Code| Description| Default value| Minimum limit|
Maximum limit| Unit| PSW
---|---|---|---|---|---|---
K01
| Baudrate serial Modbus
0 = 4800 baud
1 = 9600 baud
2 = 19200 baud
3 = 38400 baud|
1
|
0
|
3
|
Num.
|
U
K02
| Modbus serial parity
0 = No parity with 2 stop bits 1 = ODD parity with 1 stop bit 2 = EVEN parity
with 1 stop bit
3 = No parity with 1 stop bit|
2
|
0
|
3
|
Num.
|
U
K03| Modbus communication timeout| 60| 0| 120| s| U
K30| Backlight power| 100%| 10| 100| %| I
K31
| Automatic menu exit timeout 0: No timeout managed
N > 0: After N seconds without pressing any buttons you return to the main
page|
0
|
0
|
120
|
s
|
U
K32| Timeout for switching to standby 0 = Standby not managed| 60| 0| 120| s| U
K33
| Standby brightness K33 = 0: off
K33 > 0: Percentage brightness compa-
red to normal operation|
100%
|
0
|
100
|
%
|
U
K50
| Weekday offset
0 = Monday is day 1
1 = Sunday is day 1|
0
|
0
|
1
|
Num.
|
I
K100| Temperature probe calibration| 0| -10.0| 10.0| °C| I
7.1.8 OPERATING [oHr]
This displays the operating hours of the compressor (oH1) and of the
circulator (oHP1), and the number of compressor starts (cC1).
Pressing ESC for 3 seconds resets the currently displayed count.
Please note that the menu is password-protected.
7.1.9 USB MENU [USB]
Only visible with pen drive with related files (formatted in FAT32).
The following are the functions available by using the USB pen drive connected
the board.
Please note that the menu is password-protected.
CAUTION
All the operations with INSTALLER visibility must be carried out by QUALIFIED
PERSONNEL.
The company excludes any contractual and extra contractual liability for
damage caused to persons, animals or objects, by incorrect installation,
setting and maintenance, improper use of the equipment, and the partial or
superficial reading of the information contained in this manual.
7.1.9.1 FIRMWARE UPDATE [UPdF]
In case of firmware update, it is possible to make the upgrade by means of a
USB pen drive, using the USB port in the controller.
For the upgrade:
- Copy the upgrade files in the root directory of a USB pen-drive;
- Set the unit in Standby and shut it down by placing the master switch at OFF;
- Insert the pen-drive into the USB port of the controller;
- Power on the unit, placing the master switch at ON;
- Access the parameters PRG -> PSS -> PRG -> (enter Service password) -> PRG -> USB -> UPdF -> PRG. Selecting this item starts the automatic firmware upgrade procedure. The display shows a count indicating the transferred Kbytes. When the counts ends the firmware is correctly loaded;
- When the installation is complete, the board returns to normal operation and the machine is ready to be activated;
- Switch off the unit, placing the master switch at OFF;
- Wait 5 minutes for complete discharge of the compressors;
- Remove the pen drive from the USB port;
- Power on the unit, placing the master switch at ON.
7.1.9.2 PARAMETERS UPDATE [UPPA]
In case of parameters update, it is possible to make the upgrade by means of a
USB pen drive, using the USB port in the controller.
For the upgrade:
- Copy the upgrade parameter files in the root directory of a USB pen-drive;
- Set the unit in Standby and shut it down by placing the master switch at OFF;
- Insert the pen-drive into the USB port of the controller;
- Power on the unit, placing the master switch at ON;
- Access the parameters PRG -> PSS -> PRG -> (enter service password) -> PRG -> USB -> UPPA -> PRG. Selecting this item starts the automatic parameters upgrade procedure. The display shows a count indicating the transferred Kbytes;
- When the count is over, switch off the unit, placing the master switch at OFF;
- Remove the pen drive from the USB port;
- Power on the unit, placing the master switch at ON.
7.1.10 MENU VERSIONE FIRMWARE [Fir]
Firmware Version (uEr), Firmware revision (rEu) and sub (SUb) can be
dispalyed.
Please note that the menu is password-protected.
7.1.11 HIST
This menu is used to display the alarm history saved in the machine. The
alarms are displayed in reverse chronological order, the most most recent
alarm is displayed first. Use the Up and Down buttons to scroll through the
various records present. In the transitions where the thermostat reads the new
alarm, dashes briefly appear dashes appear briefly, indicating that the value
is not yet available.The acronym of the saved alarm (Exxx) is displayed by
default. Repeatedly pressing the Enter key scrolls the other date in the
record which are:
- Alarm time in hh:mm format (24 hours)
- Day of month ‘d0xx’ (where xx = 1 – 31)
- Month ‘M0xx’ (where xx = 1 – 12)
- Year “y0xx” (where xx = 0 – 99)
In the event that the board at the time of the alarm did not have a valid date
and time available, the conventional time shown is in days and hours since the
last power-on of the board. In this case, the month and year fields do not
appear and the day field can also be 0.
Note:
In the alarm history also ends the event of successful disinfection, in this
case ‘ALOK’ appears instead of the alarm acronym.
7.1.12 For
This menu, which is accessible with at least the installer password, allows
certain forcings to be activated on the machine:
- dEFr: Used to activate a manual defrost cycle. Pressing the Enter key sends the command to the machine and exits the menu.
- PumP: This is used to manually activate the system pump to carry out a system bleed. Pressing the Enter key sends the command to the machine and exits the menu. Note that the command is only accepted by the machine if it is set to OFF.
- ALEG: It is possible to force an anti-legionella disinfection cycle in manual mode (see For menu). Once the forcing has been sent to the machine via the menu, it is kept active for 60 minutes. In the event of a power failure during these 60 minutes, the request is lost. To be able to perform the anti-legionella function, the following resources must be enabled on the heat pump: The DHW must be enabled: H10 > 0. The DHW integration resistors must be enabled: r15 > 0 and there must be a digital output configured for this purpose (value 26). The DHW temperature probe must be configured and present (value 6).
- CIrC: This item is used to manually activate the system pump for recirculation with the pump at 100% for 1 hour. Pressing Enter sends the command to the machine and exits the menu. Pressing Enter again on the item with an active function the forcing is terminated. Note that the command is only accepted by the machine if it is set to OFF. The machine exits this mode if you leave the OFF condition, even if the entire forcing time has not yet elapsed.
- SoIP: This item is used to manually activate the solar pump. Pressing the Enter key sends the command to the machine and exits the menu. By pressing Enter again on the entry with active function, the forcing is terminated. Note that the command is only accepted by the machine only if it is set to OFF. The machine exits this mode if you leave the OFF condition.
7.1.13 SYS
System status menu, in this menu you can see some system parameters:
With the UP and DOWN KEYS you select which status to see.
Pressing the ENTER KEY toggles between the name of the status and its value.
Status | Meaning |
---|---|
S001 | Unit inlet water probe temperarure |
S002 | Unit flow water probe temperature |
S003 | Sanitary probe temperature |
S004 | System remote probe temperature |
S005 | Outside air probe temperature |
S006 | Thermostat firmware version |
S007 | Suction pressure |
S008 | Discharge pressure |
S009 | Compressor suction probe temperature |
S010 | Compressor delivery probe temperature |
S011 | Solar collector probe temperature |
S012 | Solar storage tank probe temperature |
S013 | Temperature of DHW preparer flow sensor |
S014 | Flow [L/min] |
S015 | Mixer valve flow temperature probe |
Note: Show ‘—-‘ if value not available.
7.2 DISPLAY
In standard operation, the display shows the water outlet temperature in
tenths of Celsius degrees or the alarm code if at least one is active. If
several alarms are triggered, the first one is displayed while the second one
will be displayed as soon as the first one is reset. In menu mode, the display
depends on the current position. Below is a list of the main icons with their
meanings:
ICON | DESCRIPTION | NOTE |
---|---|---|
Cooling | ON Fixed: operation mode Cooling | |
Heating | ON Fixed: operation mode Heating | |
Sanitary | ON fixed: Sanitary enabled Flashing: Sanitary in progress | |
Water drop | On when the main page displays machine water temperature instead |
of room temperature.
| Manual| When the chronothermostat is not active but the “mode” setting is.
| Maximum Hz| ON when maximum Hz function is active.
| Chronothermostat| Visible when the ambient chronothermostat is operative.
ICON| DESCRIPTION| NOTE
---|---|---
| Economy| Eco mode active (from manual or chrono-programme band).
| Off mode| Off mode (from manual or chrono-programme band).
| Password active| Indicates that you have access to menus under a password.
The dots next to it indicate the password level entered.
| Padlock| Indicates active keypad lock.
| Alarm| Indicates that an alarm is present.
| Error link| Indicates lack of communication with the unit.
| Pump| On fixed when the pump of the unit is active.
| Compressor| Flashing: Unit on call.
Steadily lit: at least 1 compressor running.
| Antilegionella| On fixed: Disinfection cycle. Flashing: last cicle not
executed.
| Antifreeze| On fixed when antifreeze resistences are activated, if present.
| Solar| On fixed when solar pump is activated, if present.
| Resistors| Fixed on when system integration or DHW heating elements are
active, if present.
| Boiler| On fixed when boiler enable is active, if present.
| Defrost| On fixed when defrosting in progress.
7.3 KEYPAD LOCK
- AUTOMATIC: An automatic (standby) keypad lock is managed: after K32 (default 60 seconds) seconds of inactivity, the keypad LEDs are switched off and the LCD brightness is reduced as defined by K33 (default 100%), then, when one of the keys is the LEDs are activated to indicate the activation of the keyboard. There is no other effect on this event from the key pressed. With the leds active, the keyboard responds as required. For settings see par. 8.5.2.
- MANUAL: In addition to the automatic keypad lock as described in the machine interface section, there is the possibility of implementing a manual keyboard lock: Pressing the ON/OFF button for 3 seconds locks the keyboard. This is indicated by the padlock. At Each time a key is pressed in this lock situation, the padlock flashes together with the word “Lock”. To unlock the keypad press the ON/OFF key again for 3 seconds. pressed for the first time,
7.4 TERMINAL BLOCK
See relevant chapter in the i-290 User-Installer Manual.
TERMINAL BLOCK | CONNECTION | TYPE |
---|---|---|
PE | Connect the earthing cable |
Input for 1-Ph/N/PE power supply, 230 V, 50 Hz.
(only for sizes 0106/0109/0112)
N| Connect the neutral cable from mains
L| Connect phase L1 cable from mains
L2| Connect phase L2 cable from mains|
Input for 3-Ph/N/PE power supply, 400 Vac, 50 Hz. (only for sizes 0115 / 0118)
L3| Connect phase L3 cable from mains
1A| Signal connection channel 1 Modbus RTU + remote keyboard|
Modbus communication for remote keyboard i-CR For signal use shielded twisted pair cable 3 x 0.75 mm2 (1A = pin 7, 1B = pin 8, 1C = pin9) For power supply use 2 x 1 mm2 cable (connect to pins 12 and 13)
1B| Signal connection channel 1 Modbus RTU – remote keyboard
1C| Signal connection channel 1 Modbus GND remote keyboard
12 Vac| Remote keyboard power supply (12 Vac, 50 Hz, 500 mA)
12 Vac| Remote keyboard power supply (12 Vac, 50 Hz, 500 mA)
2A| Signal connection channel 2 Modbus RTU +, GI3 module or remote
supervision| Connection of GI3 module, if fitted as an accessory.
Alternatively connection of Modbus RTU RS 485 communication for remote
supervision, if CM accessory present. The GI3 module and CM supervision cannot
be connected at the same time.
2B| Signal connection channel 2 Modbus RTU -, GI3 module or remote supervision
2C| Signal connection channel 2 Modbus GND, GI3 module or remote supervision
ID2| Remote summer/winter mode change input (to activate the function see
relevant section in the MCO manual)| Voltage-free digital input
ID3| Remote on/off input (closed = machine on / open = machine off)| Voltage-
free digital input
A16
| DHW probe (to activate the function see the relevant section in the MCO man-
ual)| Analogue input
A17| System remote probe (to activate the function see relevant section in the
MCO manual)| Analogue input
A18
| Double set point (to activate the function see the relevant section in the
MCO man- ual)| Digital input
DO3 ()| System integration resistance| Single-phase voltage output 230 Vac,
50 Hz, maximum current 300 mA (AC1)
DO6 ()| Valve outlet sanitary hot water| Single-phase voltage output 230 Vac,
50 Hz, maximum current 300 mA (AC1)
DO7 (*)| Valve outlet second set point| Single-phase voltage output 230 Vac,
50 Hz, maximum current 300 mA (AC1)
(*) if used, it is recommended to drive a relay coil or contactor with the voltage output to manage the resource.
EDITING DYNAMIC SET-POINT
The regulator allows you to modify the set-point by adding up the value according to the temperature of the outdoor air probe. To use this function, edit the values from parameter b08 to b14 following the information below (edited by the installer). Parameters of regulator PAr -> rE
- b08 enable = 1/disable=0 dynamic set-point.
- b09 = maximum cooling offset.
- b10 = maximum heating offset.
- b11 = Cooling outdoor temperature setting.
- b12 = Heating outdoor temperature setting.
- b13 = Cooling temperature delta.
- b14 = Heating temperature delta.
Edit the setpoint depending on the outdoor temperature:
8.1 SETTINGS FOR STANDARD CLIMATIC CURVES
CURVE| Setpoint Heat| Setpoint Cool| b08| B09|
b10| B11| b12| B13| b14
---|---|---|---|---|---|---|---|---|---
A| 20°C| —| 1| —| 13°C| —| 20°C| —| -25°C
B| 20°C| —| 1| —| 18°C| —| 20°C| —| -27°C
C| 20°C| —| 1| —| 25°C| —| 20°C| —| -29°C
D| 40°C| —| 1| —| 10°C| —| 20°C| —| -28°C
E| 40°C| —| 1| —| 15°C| —| 20°C| —| -25°C
F| —| 5°C| 1| 5°C| —| 37°C| | -17°C| —
G| —| 10°C| 1| 8°C| —| 40°C| | -20°C| —
CIRCULATOR
The circulator of the heat pump can be set in the following operating modes:
- operation on call by temperature controller
- operating on call by temperature controller with periodic activation;
- continuous operation (default); The circulator is switched off immediately if:
- There is a manual reset pump block alarm, including the flow switch alarm;
- With remote input in standby or off, the pump (if running) is always switched off with a delay equal to P02 in tenths of a minute (default P02=2) T
The circulator can be configured with P03 to operate independently from the compressor or on call. 0=continuous operation in heating/cooling mode(default P03=0) 1=operating on call by temperature controller Note: with active no-flow alarm in automatic reset, the circulator is on even if the compressor is off. The circulator is always on when the antifreeze heaters are running and if operation of the hydraulic pump in antifreeze is enabled. Antifreeze operation is enabled if the regulation temperature drops below P04 °C (default 5°C), and disables if the regulation temperature rises above P04+P05 °C (Default value P05=2,0°C). Note: It is possible to change the maximum and minimum speed of the circulator by adjusting parameters P07 and P08 respectively.
9.1 CONTINUOUS OPERATION [P03=0] – Default
The circulator is only off with the unit OFF, in all other cases it is always
on.
9.2 OPERATION ON CALL FROM TEMPERATURE CONTROLLER [P03=1]
In this operating mode, the circulator is active on demand by the temperature
controller, after a delay time of P01 seconds (default P01=30) from when the
pump switched on, the compressor switches on as well.
Whereas when switching off, the pump is deactivated after a delay time of P02
minutes (default P02=2) from when the compressor switches off.
With automatic reset flow switch alarm triggered, the circulator is on even if
the compressor is off.
9.3 OPERATING ON CALL FROM TEMPERATURE CONTROLLER WITH PERIODIC
ACTIVATION
The function is disabled if P17=0 (default).
If P03=1, the circulator turns on periodically for a time defined by the
parameter P17 (in seconds) after a count, lasting a time set by parameter P16
(in minutes), activated when the pump switches off because temperature control
fulfilled.
With automatic reset flow switch alarm triggered, the pump is on even if the
compressor is off.
The periodical function is a suspended if the antifreeze protection trips.
9.4 PROPORTIONAL REGULATION OF THE CIRCULATOR
The speed of the circulator changes depending on the temperature difference
between the inlet water and outlet water of the heat exchanger, according to
the diagram below, where:
- P07: Maximum speed = 100%
- P08: Minimum speed = 75%
- P09: modulating pump inlet/outlet water Delta T setting (°C) (according to model)
- P10: Modulating pump Delta = 3°C (default)
The circulator is at maximum speed in DHW production.
Note: If the parameter r33 > 0, then the circulator can be running on
call even to activate the system and/or sanitary heater, see par.10.8.
9.5 SYSTEM VENTING
Function used to vent the system, with the circulator at maximum speed.
To enable the function:
- Controller OFF
- Access the parameters PRG ->PSS ->PRG -> (enter Service password)
- Press the UP and DOWN keys simultaneously for 3 seconds
The circulator switches on at maximum speed, and then switches off after 5
minutes.
The system venting cycle can be exited manually by pressing the MODE/ESC key,
or by pressing the UP and DOWN keys simultaneously for 3 seconds.
During this function, the flow switch alarm is disabled, the maintenance
technician must guarantee that there is water inside the system.
COMPRESSOR OR ACTIVATION LOGIC
The restart of compressors is in operation of a set point refered to the inlet
water temperature. It is based on calculation of ∆T,set which is the
difference between outlet water temperatures and inlet water temperatures,
detected while the compressor for thermoregulation is turning off.
10.1 REGULATION IN COOLING MODE
- Tw,out,set = adjusted setpoint in cooling;
- Tw, in, set = value of the water inlet probe recorded at the instant the compressor switches off when setpoint is reached;
- ∆T,set = Tw,out,set – Tw,in,set;
- b05 = compressor delta cut-off set= 0°C (default);
- b24 = cut-on hysteresis limitation;
- b25 = delta cut-on compressor set= 3°C.
- The compressor shutdown is set by the parameter b05: the compressor shutdown when Tw,out < Tw,out,set – b05
- The compressor restart starts when Tw,out > (Tw,out,set + ∆T,set + b25)
EXCEPTION: The value of ∆T,set is limited by b24.
If ∆T,set >b24 (default value 7°), the compressors restart when: Tw,out >
(Tw,out,set + b24 + b25).
10.2 REGULATION IN HEAT MODE
- Tw,out,set = setting setpoint in heat mode
- Tw, in, set = value of the water inlet probe recorded at the instant the compressor switches off when setpoint is reached.
- ∆T,set = Tw,out,set – Tw,in,set
- b24 = cut-on hysteresis limitation;
- b05 = compressor regulation delta cut-off = 0°C (default)
- b25 = compressor regulation delta cut-on = 3°C
- The compressor shutdown is regulated by parameter b05: the compressor shutdown when is regulated by parameter b05 Tw,out > Tw,out,set + b05
- The compressor restart when: Tw,out < (Tw,out,set – ∆Tset – b25)
EXCEPTION: The value of ∆T,set is limited by b24.
If ∆T,set >b24 (default value 7°), the compressors restart when: Tw,out < (Tw,out,set – b24 – b25).
FAN CONTROL OF THE FINNED EXCHANGER
Ventilation control is a function of condensing pressure in chiller mode, and
a function of evaporating pressure in heat pump mode.
The regulation of ventilation is dependent on the operating conditions of the
machine.
A pre-ventilation occurs every time the compressor switches on and off.
CONTROLLER FUNCTIONS
The following is a list of the functions which can be activated in the machine
controller; not all of them can be selected simultaneously.
Values other than the default values can jeopardise proper operation of the
unit. If in doubt on which value to set, contact our headquarters.
12.1 ANTIFREEZE PROTECTION HEATERS (IF KA ACCESSORY IS AVAILABLE)
If the optional KA kit is present, the function is active by default.
The water antifreeze heaters on the faces of the evaporator plates even
activate with the machine off (but powered) when the delivery water
temperature drops below r02 °C (default 4°C) in “heating” mode or below r03 °C
(default 4°C) in “cooling” mode or when witched “OFF”. The heaters are
switched off when the temperature measured by the outlet water probe exceeds
r02+r06 in “heating” or r03+r06 in “cooling” or when “OFF” (default value
r06=2.0 °C).
The heating cable at the base of the machine activates when the outdoor air
temperature drops below 3°C. It deactivates when the outdoor temperature rises
above 5°C.
12.2 ENABLING DOMESTIC HOT WATER PRODUCTION
To activate the domestic hot water functions, connect a probe to be placed
inside the tank to terminals X17.1-X17.2 (enabled as analogue input).
The sanitary function must be enabled after positioning and connecting the
temperature probe.
I/O resource – Parameter | VALUE | Function |
---|
H10
| 0 (default)| Function disabled
1| Function active in heating and cooling mode.
The remote on-off function does not disable DHW production.
2| Function active in heating and cooling mode.
The remote on-off function disables DHW production.
3| Function active in heating mode.
The remote on-off function does not disable DHW production.
4| Function active in heating mode.
The remote on-off function disables DHW production.
5| Function active in cooling mode.
The remote on-off function does not disable DHW production.
6| Function active in cooling mode.
The remote on-off function disables DHW production.
ST6 can be activated via H17| 6| DHW temperature probe enabling
DO6 can be activated via H84| 6| DHW valve control
If the domestic hot water temperature is lower than its setting (set by
default at 48°C, edited by accessing the menu PRG->Set->SAN) the machine
activates the DHW valve and the compressor is set at maximum frequency,
starting modulation one degree before the setting and switching off one degree
after. When the set point is reached, the valve goes back to the rest
condition and the compressor starts to regulate normally. Switching from
utility water to domestic hot water, the working probe changes from “water
outlet probe” to “DHW tank probe”. Switching from winter mode to sanitary
mode, the compressor does not switch off and is brought to the maximum
frequency established by the controller, whereas switching from summer mode to
domestic hot water, the compressor is switched off and waits a safety time.
Defrosting is always carried out in winter mode on the utility side, and never
on the domestic hot water tank.
NOTE: -If H10 = 1/3/5. Switching off the unit by remote control (remote
on-off, see paragraph 10.4.1) does not affect domestic hot water operation.
The unit goes to priority sanitary mode just powered on. The display on the
machine shows the temperature detected by the probe inside the DHW tank. When
the sanitary cycle has finished, the display goes back to showing the water
outlet probe temperature. If the remote ON-OFF digital input (terminals 15.1 /
15.2) is open, with sanitary function enabled (H10=1 and H20=6), the wording
“SAN” will appear on the machine display. When the sanitary cycle has
finished, the display goes back to showing “E00” indicating that the remote
ON-OFF contact is open. -If H10 = 2/4/6, the remote on-off function disables
domestic hot water production and operation of the heat pump in heatin and
cooling mode, system side.
12.2.1 MEMORISING THE PROBE IN HEATING MODE
Switching from utility water to domestic hot water, the working probe changes
from “water outlet probe” to “DHW tank probe”. For this reason, in heating
mode, before entering sanitary mode, the last value read by the heat pump
delivery probe is stored.
When sanitary temperature control is fulfilled, the system side temperature of
reference goes back to that previously stored. The memory function interrupts:
- when the temperature read by the probe becomes lower than the stored value;
- or when a time equal to b06 seconds (default b06 = 45) has elasped.
12.2.2 HEATING MODE ON DHW STORAGE TANK
If the parameter H130=1, the machine exploits the DHW storage tank even for
central heating. In these conditions, the outlet of the DHW valve is also
enabled during operation in heating mode and not only in sanitary mode. The
valve is deactivated during defrosting and in cooling mode. When H130=1, the
DHW integration heater can be enabled also to act as system integration
heater: to do this, set r10=1 e r15=2 (for other r15 settings see Paragraph
10.6.3); furthermore no digital output must be set as system integration
heater.
12.2.3 INSUFFICIENT HEAT EXCHANGE IN A DHW SYSTEM
During DHW production, if the heat pump flow probe detects a temperature
higher than 60°C, the DHW valve output is de-energised (D06), and the value of
the DHW probe at this time is recorded (Tsan,set).
-if the operation is San or Cool+San the compressor is stopped.
-If the operation is Heat+San, the system evaluates for b06 seconds whether there is a demand for heating from the system. If the system requires it, the compressor continues to work on the system, otherwise it is switched off.
-If the DHW resistor is present (e.g. DO3, H81=26), r15 = 0 or 1 and r24=2 or 3 it is activated until the DHW setpoint detected by the DHW probe is met (and any offset).
The compressor restarts when the flow temperature of the heat pump falls below
60°C again and the temperature measured by the DHW probe is lower than
Tsan,set – 4°C.
I/O Resource- Parameter | Function |
---|---|
ID3 can be activated via H47 | Enables remote On /Off function |
If the unit is switched off by remote control during defrosting, the heat pump
finishes defrosting and then places itself in off mode via remote control.
12.3.2 SUMMER/WINTER MODE CHANGE
The function can be set on digital input ID 2 (terminals X16.1/X16.2).
Heating or cooling mode of the heat pump can be managed by remote control.
I/O resource – Parameter | Value | Function |
---|---|---|
ID2 can be activated via H46 | 3 | Open contact -> heat pump in cooling mode. |
Closed contact -> heat pump in heating mode.
The poles of the digital input can be swapped by setting H75 = 2.
12.4 SYSTEM WATER REMOTE PROBE
In some system solutions (e.g. heat pump in parallel to boiler on same
hydronic circuit and shut off diverter valve) it could be necessary to enable
a system remote temperature probe so that the controller can correctly process
the management.
I/O resource- Parameter | Value | Description |
---|---|---|
ST7 can be activated via H18 | 41 | Enables system remote probe |
In the presence of the system remote probe, if the storage tank temperature is
satisfied, it is avoided to activate the compressors even if the regulation
probe requires it.
The conditions for the application of thermoregulation lockout are as follows:
– the heat pump is not performing DHW
– the heat pump is not defrosting
– all compressors are switched-off
The blocking conditions are as follows:
Operating mode| Conditions inhibiting the restart of
thermoregulation
---|---
| heating| System remote probe > setpoint – b22
| cooling| System remote probe < setpoint + b22
Nota: b22=5°C. See paragraph 13.
12.5 FUNCTIONS DIGITAL OUTPUTS CAN BE ACTIVATED
If the machine block signal function is not active, one of the following
signals can be configured at the DO7/N terminals and the user terminal block.
12.5.1 MACHINE BLOCK
Configured by default, a voltage output signalling the presence of an alarm.
Resource I/O (Parameter) | Value | Function |
---|---|---|
DO7 attivabile via H85 | 47 | Alarm signalling |
12.5.2 AUXILIARY RESISTANCES
In some system solutions, it may be necessary to use an integration resistor
for the system and/ or for the DHW. To define the mode of intervention of the
integration resistors, the parameter r24 must be set:
- r24=0 integration resistors not used;
- r24=1 use of system integration resistor only;
- r24=2 use of DHW integration resistor only;
- r24=3 use of both system integration resistor and domestic hot water integration resistor.
12.5.2.1 SYSTEM HEATER
If the regulation temperature remains below water setpoint in heating (Hea) –
0.5°C for a time equal to r12 the integration heater is activated according to
operation of the machine in joint time slots or in substitution, as indicated
in Paragraph 10.11.
The heater switches off when the setpoint is reached (also taking into account
an offset set with parameters r29 or r30).
If the regulation temperature remains below the water setpoint minus r11 (°C)
and the machine is blocked due to triggering of an alarm, the heater switches
on. It switches off when the machine exits the alarm block.
I/O resource – Parameter | Value | Function |
---|---|---|
r10 | 1 | Function enabling |
r11 | 0.5°C (default) | Heaters in heating integration delta |
r12 | 8 minutes (default) | Heaters in heating integration delta |
r24 | 1/3 | Type of use of heaters |
D03 can be activated via H81 | 22 | System integration heater |
12.5.2.2 PLANT HEATER IN DEFROST
During the defrost cycle (see Paragraph 10.12.2), setting r21=1 (in addition
to r10=1 and r24=1 or 3) activates the plant side electric heater, if
requested (regulation temperature lower than water setpoint -r11(°C), without
waiting the time defined by r12.
12.5.2.3 DHW HEATER
Function which can be activated instead of managing the plant heater
This is an additional resource for heating the domestic hot water storage tank
if the compressor alone is not capable of fulfilling the request in a
reasonable time. If domestic hot water production lasts longer than r16
(minutes) or if the machine blocks due to triggering of an alarm, the heater
switches on. It switches off when the unit finishes domestic hot water
production (also taking into account an offset on the setpoint with parameter
r31, as explained in Paragraph 10.11.1).
I/O resource – Parameter | Value | Function |
---|---|---|
r15 | 1 | Function enabling |
r16 | 8 minutes (default) | DHW integration activation delay |
r24 2/3 Type of
use of heaters
D03 can be activated via H81| 26| System integration heater
Note: The domestic hot water function must be enabled (see paragraph
10.2)
12.5.2.4 SINGLE SYSTEM/DHW INTEGRATION HEATER
By configuring the DHW integration heater, it is possible to use this heater
declared also as plant integration heater, setting the parameter r15=2 and
r24=3.
In case of plant integration demand, the heater declared as DHW integration is
activated, thus allowing to have a single integration heater for plant,
domestic hot water and plant under defrost.
12.5.2.5 INTEGRATION HEATER SELECTION MODE
The priority can be set in the order to activate the plant side and sanitary
side integration heaters; specifically the configurations are:
1. r14=0 (default), the heaters can be activated simultaneously, if present;
2. r14=1, the heaters can be activated, excluding one another:
2.1. r20=0, priority to the plant (the DHW heater only switches on if the
temperature control for the plant side heater is fulfilled);
2.2.r20=1, priority to DHW (the plant side heater only switches on if the
temperature control for the sanitary side heater is fulfilled).
12.5.2.6 CIRCULATOR MANAGEMENT WITH HEATER ON
The circulator of the heat pump can be activated when the plant and/or DHW
integration heaters are active with the compressors not running (by
substitution, by alarm or by integration in bracket II or III).
-r33 = 0: The circulator of the heat pump is activated on demand of the compressors or boiler,
-r33 = 1: The circulator of the heat pump is activated if the plant heater is active.
-r33 = 2: 2: The circulator of the heat pump is activated if the DHW heater is active.
-r33 = 3: The circulator of the heat pump is activated if the plant or DHW heater is active.
The circulator switches off after post-pumping (P02).
12.5.3 BOILER ENABLING
Function which can be activated instead of managing the double setpoint.
This is an additional resource to enable the boiler in integration or
substitution of the heat pump.
Define the use mode by setting the parameter r23:
-
r23=0 (default) boiler not used (operating priority of heaters);
-
r23=1 only boiler on plant used (operating priority of heaters);
-
r23=2 only DHW boiler used (operating priority of heaters);
-
r23=3 DHW and plant boiler used (operating priority of heaters); In the case of r31>0, when the DHW set point is reached, the DHW 3-way valve switches to the system;
-
r23=4 only boiler on plant with priority used (no heater operating priority);
-
r23=5 only boiler in sanitary with priority used (no heater operating priority);
-
r23=6 boiler on plant and in sanitary with priority used (no heater operating priority); In the case of r31>0, when the DHW set point is reached, the DHW 3-way valve switches to the system.
-
r23=7 boiler use both in DHW and system (priority of resistor intervention). In the case of r31>0, when the DHW set point is reached, the DHW 3-way valve remains switched to DHW.
-
r23=8 boiler use in DHW and on system with priority (no priority to resistor intervention). In the case of r31>0, when the DHW set point is reached, the DHW 3-way valve remains switched to DHW.
Define the supply of the boiler, setting parameter r32: -
r32 = 0: boiler without circulator with temperature control by heat pump,
-
r32 = 1: boiler with autonomous circulator with temperature control by heat pump;
-
r32 = 2: boiler without circulator with autonomous temperature control;
-
r32 = 3: boiler with circulator with autonomous temperature control.
I/O resource- Parameter | Value | Function |
---|---|---|
r10 | 1 | Plant integration enabling |
r12 | 8 minutes (default) | Plant integration activation delay |
r15 | 1 | DHW integration enabling |
r16 | 8 minutes (default) | DHW integration activation delay |
r23 | 1÷6 | Type of use of boiler |
r32 | 1÷3 | Boiler supply |
DO3 can be activated via H81 | 29 | Boiler enabling |
12.5.4 ACTIVATION OF INTEGRATION HEATERS AND BOILER IN JOINT OPERATION AND IN
SUBSTITUTION OF HEAT PUMP COMPRESSOR
The auxiliary parts that can be used for joint operation or for operation in
substitution are:
- boiler
- plant integration heater
- DHW integration heater
Considering the operating modes in heating and/or DHW, there are 4 operating areas:
If you need to change the values of the parameters r22, r28, r08, follow r22 ≥
r28 ≥ r08.
Setting r22=r28 allows you to eliminate the zone relative to joint operation
bracket I; setting r28=r08 allows you to eliminate the zone relative to joint
operation bracket II; setting r22=r28=r08 allows you to eliminate both
brackets relative to joint operation.
Do not modify value r08, as it could jeopardise operation of the unit
12.5.4.1 OPERATION IN HEAT PUMP MODE
Normal operation of the heat pump in which the integration resistors and/or
the boiler only intervene when a heat pump alarm is triggered.
12.5.4.2 JOINT OPERATION (I BRACKET)
If the outdoor temperature is between r22 and r28, the compressor operates in
synergy with the auxiliary heaters in winter or DHW mode.
In this operating bracket, first the heat pump is activated and after r12
minutes the plant side auxiliary heaters, or after r16 minutes the sanitary
side auxiliary heaters.
The intervention priorities are defined by the parameters r14, r20, r23, r24.
It goes back to normal operation if the outdoor temperature is greater than
r22+1.0 (°C).
NOTE: In the joint operating bracket, the boiler is temperature
controlled by the plant water remote probe (if enabled). In particular, if the
temperature detected by the remote probe is lower than the Hea setpoint, the
boiler is switched on and then will go off when the temperature detected by
the remote probe is higher than the Hea setpoint. The heat pump follows the
activation logic described in paragraph 10.5.
If the remote plant water probe is not enabled, the boiler will be managed by
the delivery probe of the heat pump.
12.5.4.3 JOINT OPERATION (II BRACKET)
If the outdoor temperature is between r28 and r08, the compressor operates in
synergy with the auxiliary heaters.
In this operating bracket, first the boiler is activated, then the heat pump
and auxiliary heaters intervene after a time defined by r12 (minutes) for the
plant side and r16 (minutes) for the sanitary side
The intervention priorities are defined by the parameters r14, r20, r23, r24.
It goes back to normal operation if the temperature rises above r28+1.0 (°C).
Note: In the joint operating bracket, the boiler is temperature controlled by
the plant water remote probe (if enabled). In particular, if the temperature
detected by the remote probe is lower than the Hea setpoint, the boiler is
switched on and then will go off when the temperature detected by the remote
probe is higher than the Hea setpoint. The heat pump follows the activation
logic described in paragraph 10.5.
If the remote plant water probe is not enabled, the boiler will be managed by
the delivery probe of the heat pump.
12.5.4.4 OPERATION IN SUBSTITUTION
If the outdoor temperature drops below r08 use of the heat pump compressor
will be inhibited.
– If the auxiliary system is composed of plant and/or DHW heaters, they are
active in substitution of the compressor with defined times, r12 (minutes) for
plant side and r16 (minutes) for sanitary side.
Whereas in the operation in substitution bracket, the integrations do not need
to be enabled with r10 or r15 as the heaters need to operate in substitution
(and not in integration) of the heat pump (therefore simply select the type of
use with the parameter r24).
– If the auxiliary system is a boiler with autonomous circulator (r32 = 1 or
3).
The circulator of the heat pump is off, after P01 (default 30 seconds) the
boiler is enabled.
NOTE: With water side antifreeze protection, the pump used is activated
(or remains active) anyhow.
– If the auxiliary system in substitution is a boiler with autonomous
temperature control (r32 = 0 or 2).
The boiler is enabled regardless of the temperature control of the heat pump.
– If the auxiliary system in substitution is a boiler without circulator (r32
= 0 or 2).
The circulator of the heat pump is on when the boiler is enabled.
The compressor switches back on if the temperature rises above r08+ r09 (°C)
(r09=1.0 °C by default).
12.5.4.5 OPERATING BRACKETS – ACTIVATION OF INTEGRATION HEATERS (plant
remote water probe not enabled)
The possible configurations of the integration parameters are listed in tables
1,2,3 and 4 shown below, divided by operating brackets (the operating modes
and possible values of the parameters are indicated in the “STATUS” boxes
and in the parameters “rxx” so that a given order of intervention of the
integrations occurs in a certain operating mode of the unit; other statuses
and values of the parameters can be selected instead and therefore they are
provided in the same cell separated by the symbol ”/”).
| TABLE 1. NORMAL OPERATION IN HEAT PUMP
---|---
N°
| INTEGRATIONS INTERVENTION ORDER
(with set-point not reached and
machine blocked by alarm)
|
STATUS
|
OPERATION
|
r10
|
r15
|
r12
|
r16
|
r23
|
r24
7
| 1) DHW integration heater
2) After r16 minutes, boiler
|
HEAT+SAN
|
DHW
|
0/1
|
1
|
/
| Set the min- utes|
2/3
|
2/3
8
| 1) Boiler
2) After r16 minutes, DHW integra-
tion heater
|
HEAT+SAN
|
DHW
|
0/1
|
1
|
/
| Set the min- utes|
5/6
|
2/3
9
|
- Plant/DHW integration heater
| HEAT / HEAT+SAN|
HEAT/DHW
|
1
|
1
|
/
|
/
|
0
|
3
10
|
- Boiler
| HEAT / HEAT+SAN|
HEAT/DHW
|
0/1
|
0/1/2
|
/
|
/
|
3/6
|
0
11
| 1) Plant/DHW integration heater
2) After r12 minutes, boiler
| HEAT / HEAT+SAN|
HEAT/DHW
|
1
|
1
| Set the min- utes| Set the min- utes|
3
| 3
12
| 1) Boiler
2) After r12 minutes, plant/DHW in-
tegration heater
| HEAT / HEAT+SAN|
HEAT/DHW
|
1
|
1
| Set the min- utes| Set the min- utes|
6
|
3
| TABLE 2. JOINT OPERATION, BRACKET 1
---|---
N°| INTERVENTION ORDER
(with setpoint not reached)
| STATUS| OPERATION| r10| r15| r12| r16| r23| r24
1
| 1) Heat pump
2) After r12 minutes, plant integration
heater
| HEAT / HEAT+SAN|
HEAT
|
1
|
0/1/2
| Set the min- utes|
/
|
0/2/5
|
1/3
2
| 1) Heat pump
2) After r12 minutes, boiler
| HEAT / HEAT+SAN|
HEAT
|
0/1
|
0/1/2
| Set the min- utes|
/
|
1/3/4/6
|
0/2
3
| 1) Heat pump
2) After r12 minutes, plant integration
heater
3) After further r12 minutes, boiler
|
HEAT / HEAT+SAN
|
HEAT
|
1
|
0/1/2
|
Set the min- utes
|
/
|
1/3
|
1/3
4
| 1) Heat pump
2) After r12 minutes, boiler
3) After further r12 minutes, plant inte-
gration heater
|
HEAT / HEAT+SAN
|
HEAT
|
1
|
0/1/2
|
Set the min- utes
|
/
|
4/6
|
1/3
5
| 1) Heat pump
2) After r16 minutes, plant integration
heater
|
HEAT+SAN
|
DHW
|
0/1
|
1
|
/
| Set the
minutes
|
0/1/4
|
2/3
6
| 1) Heat pump
2) After r16 minutes, boiler
|
HEAT+SAN/
|
DHW
|
0/1
|
0/1/2
|
/
| Set the
minutes
|
2/3/5/6
|
2/3
7
| 1) Heat pump
2) After r16 minutes, plant integration
heater
3) After further r16 minutes, boiler
|
HEAT+SAN
|
DHW
|
0/1
|
1
|
/
|
Set the
minutes
|
2/3
|
2/3
8
| 1) Heat pump
2) After r16 minutes, boiler
3) After further r16 minutes, DHW inte-
gration heater
|
HEAT+SAN
|
DHW
|
0/1
|
1
|
/
|
Set the
minutes
|
5/6
|
2/3
9
| 1) Heat pump
2) After r12 minutes, plant/DHW inte-
gration heater
| HEAT / HEAT+SAN|
HEAT/DHW
|
1
|
1
| Set the min- utes| Set the
minutesi
|
0
|
3
10
| 1) Heat pump
2) After r12 minutes, boiler
| HEAT / HEAT+SAN|
HEAT/DHW
|
0/1
|
0/1/2
| Set the min- utes| Set the
minutes
|
3/6
|
0
11
| 1) Heat pump
2) After r12 minutes, plant/DHW inte-
gration heater
3) After further r12 minutes, boiler
|
HEAT / HEAT+SAN
|
HEAT/DHW
|
1
|
1
|
Set the min- utes
|
Set the
minutes
|
3
|
3
12
| 1) Heat pump
2) After r12 minutes, boiler
3) After further r12 minutes, plant/
DHW integration heater
|
HEAT / HEAT+SAN
|
HEAT/DHW
|
1
|
1
|
Set the min- utes
|
Set the
minutes
|
6
|
3
| TABLE 3. JOINT OPERATION, BRACKET 2
---|---
N°| INTERVENTION ORDER
(with setpoint not reached)
| STATUS| OPERATION| r10| r15| r12| r16| r23| r24
1
| 1) Boiler
2) After r12 minutes, heat pump
| HEAT / HEAT+SAN|
HEAT
|
0/1
|
0/1/2
| Set the min- utes|
/
|
1/3/4/6
|
0/2
| TABLE 3. JOINT OPERATION, BRACKET 2
---|---
N°| INTERVENTION ORDER
(with setpoint not reached)
| STATUS| OPERATION| r10| r15| r12| r16| r23| r24
2
| 1) Boiler
2) After r12 minutes, plant integration
heater
3) After further r12 minutes, heat pump
|
HEAT / HEAT+SAN
|
HEAT
|
1
|
0/1/2
|
Set the min- utes
|
/
|
1/3
|
1/3
3
| 1) Boiler
2) After r12 minutes, heat pump
3) After further r12 minutes, plant inte-
gration heater
|
HEAT / HEAT+SAN
|
HEAT
|
1
|
0/1/2
|
Set the min- utes
|
/
|
4/6
|
1/3
4
| 1) Plant integration heater
2) After r12 minutes, heat pump
| HEAT / HEAT+SAN|
HEAT
|
1
|
0/1/2
| Set the min- utes|
/
|
0/2/5
|
1/3
5
| 1) Boiler
2) After r16 minutes, heat pump
|
HEAT+SAN
|
DHW
|
0/1
|
0/1/2
|
/
| Set the min- utes|
2/3/5/6
|
0/1
6
| 1) Boiler
2) After r16 minutes, DHW integration
heater
3) After further r16 minutes, heat pump
|
HEAT+SAN
|
DHW
|
0/1
|
1
|
/
|
Set the min- utes
|
2/3
|
2/3
7
| 1) Boiler
2) After r16 minutes, heat pump
3) After further r16 minutes, DHW inte-
gration heater
|
HEAT+SAN
|
DHW
|
0/1
|
1
|
/
|
Set the min- utes
|
5/6
|
2/3
8
| 1) DHW integration heater
2) After r16 minutes, heat pump
|
HEAT+SAN
|
DHW
|
0/1
|
1
|
/
| Set the min- utes|
0/1/4
|
2/3
9
| 1) Boiler
2) After r12 minutes, heat pump
| HEAT / HEAT+SAN|
HEAT/DHW
|
1
|
1
| Set the min- utes| Set the min- utes|
3/6
|
0
10
| 1) Boiler
2) After r12 minutes, plant/DHW inte- gration heater
3) After further r12 minutes, heat pump| HEAT / HEAT+SAN|
HEAT/DHW| 1| 1| Set the min- utes| Set the min- utes| 3| 3
11
| 1) Boiler
2) After r12 minutes, heat pump
3) After further r12 minutes, plant/ DHW integration heater|
HEAT / HEAT+SAN
|
HEAT / SANITARIO
|
1
|
1
|
Set the min- utes
|
Set the min- utes
|
6
|
3
12
| 1) Plant/DHW integration heater
2) After r12 minutes, heat pump| HEAT / HEAT+SAN|
HEAT/DHW
|
1
|
1
| Set the min- utes| Set the min- utes|
0
|
3
| TABLE 4. OPERATION IN SUBSTITUTION
---|---
N°| INTERVENTION ORDER
(with setpoint not reached)
| STATUS| OPERATION| r10| r15| r12| r16| r23| r24
1
| 1) Boiler
2) After r12 minutes, Plant integration
heater
| HEAT / HEAT+SAN|
HEAT
|
0/1
|
0/1/2
| Set the min- utes|
/
|
4/6
|
1/3
2
| 1) Plant integration heater
2) After r12 minutes, boiler
| HEAT / HEAT+SAN|
HEAT
|
0/1
|
0/1/2
| Set the min- utes|
/
|
1/3
|
1/3
3
| 1) Boiler
2) After r12 minutes, DHW integration
heater
|
HEAT+SAN
|
DHW
|
0/1
|
0/1/2
|
/
| Set the min- utes|
5/6
|
2/3
4
| 1) DHW integration heater
2) After r12 minutes, boiler
|
HEAT+SAN
|
DHW
|
0/1
|
0/1/2
|
/
| Set the min- utes|
2/3
|
2/3
5
| 1) Boiler
2) After r12 minutes, Plant/DHW inte-
gration heater
| HEAT / HEAT+SAN|
HEAT/DHW
|
0/1
|
0/1/2
| Set the min- utes| Set the min- utes|
6
|
3
6
| 1) Plant/DHW integration heater
2) After r12 minutes, boiler
| HEAT / HEAT+SAN|
HEAT/DHW
|
0/1
|
0/1/2
| Set the min- utes| Set the min- utes|
3
|
3
7
|
- Boiler
| HEAT / HEAT+SAN|
HEAT
|
0/1
|
0/1/2
| Set the min- utes|
/
|
1/3/4/6
|
0/2
8
|
- Plant integration heater
| HEAT / HEAT+SAN|
HEAT
|
0/1
|
0/1/2
| Set the min- utes|
/
|
0/2/5
|
1/3
9
|
- Boiler
|
HEAT+SAN
|
DHW
|
0/1
|
0/1/2
|
/
| Set the min- utes|
2/3/5/6
|
0/1
10
|
- DHW integration heater
|
HEAT+SAN
|
DHW
|
0/1
|
0/1/2
|
/
| Set the min- utes|
0/1/4
|
2/3
11
|
- Boiler
| HEAT / HEAT+SAN|
HEAT/DHW
|
0/1
|
0/1/2
| Set the min- utes| Set the min- utes|
3/6
|
0
| TABLE 4. OPERATION IN SUBSTITUTION
---|---
N°| INTERVENTION ORDER
(with setpoint not reached)
| STATUS| OPERATION| r10| r15| r12| r16| r23| r24
12
|
- Plant/DHW integration heater
| HEAT / HEAT+SAN|
HEAT/DHW
|
0/1
|
0/1/2
| Set the min- utes| Set the min- utes|
0
|
3
Table 5 shows the settings to be configured to enable the integrations in “summer and sanitary” mode (in this case the only activation that can be activated is the DHW integration heater and the division into operating brackets does not apply).
| TABLE 5. OPERATION IN COOL+SAN (DHW RUNNING)
---|---
N°
| INTEGRATIONS INTERVENTION ORDER -With setpoint not reached after r16 minutes from the start-up of the com- pressor or with setpoint not reached with machine blocked by alarm.|
STATUS
|
OPERATION
|
r10
|
r15
|
r12
|
r16
|
r23
|
r24
1| 1) DHW integration heater| COOL+SAN| DHW| 0/1| 1| /| Set theminutes| 0/1/2/3/4/5/6| 2/3
Table 6 shows the behaviour of the plant and DHW integration heaters in all the operating modes of the unit.
| TABLE 6. INTEGRATION HEATERS OPERATION
---|---
N°| STATUS| OPERATION| PLANT INTEGRATION HEATER| DHW
INTEGRATION HEATER
1
|
HEAT+SAN
|
HEAT
|
Works as indicated in TABLE 1,2,3 and 4.
| In “HEAT+SAN”, by default sanitary temperature con- trol has priority over that of the plant, therefore if re- quired by the temperature control, the unit goes to “SANITARY” mode and the DHW integration heater acts
as indicated in TABLES 1,2,3 and 4.
2
|
HEAT+SAN
|
DHW
| Only if all 3 of the following conditions are met: -the output is configured for Plant integration heater;
– r24=1/3 ; – plant water temperature remote probe pres- ent and configured ;
the plant integration heater is activated in the following situations:
– r12 minutes after the start of its count acti- vated in “HEAT” mode
previously running (see line 1);
– if its count is not already activated in the pre- vious “HEAT” mode,
r12 minutes after the tem- perature control demand.
– In SANITARY mode, with remote probe not configured, the plant integration
heater is de- activated or any of its counts are interrupted.
– With “remote on-off” contact open, the Plant integration heater is
deactivated.
|
Works as indicated in TABLES 1,2,3 and 4.
3| COOL+SAN| DHW| Cannot be activated| Works as indicated in TABLE 5.
4| COOL+SAN| COOL| Cannot be activated| Cannot be activated
12.5.4.6 AUXILIARY SYSTEMS OFFSET MANAGEMENT
Lastly you may establish that the boiler and/or integration heaters (according
to the resources and selected priorities) have a setpoint in heating mode and
in sanitary mode higher than that of the heat pump. This is achieved by
setting an offset on the following setpoints:
- r29 = First setpoint temperature offset for boiler and plant heaters (G02);
- r30 = Second setpoint temperature offset for boiler and plant heater (G05);
- r31 = Temperature offset for boiler and DHW heaters (G03);
This way the heat pump stops at the setpoint (G02,G03,G05) and the temperature
difference, according to the set outset, will be supplied by the boiler and/or
heaters.
12.5.5 SYSTEM SEASON
A digital output can be configured indicating the operating season of the
unit, plant side.
The output is active in summer mode, while it is deactivated in OFF or heating
mode.
During DHW production and defrosting, the output maintains the setting of the
source season.
I/O Resource (Parameter) | Value | Function |
---|---|---|
DO7 can be activated via H85 | 31 | Plant season warning |
12.5.6 ALARM
A voltage output can be configured to signal the presence of an alarm.
I/O Resource Parameter | Value | Function |
---|---|---|
DO7 can be activated via H85 | 24 | Alarm warning |
12.5.7 DEFROST
A digital output can be configured signalling defrosting in progress.
I/O Resource Parameter | Value | Function |
---|---|---|
DO7 can be activated via H85 | 21 | Defrost in progress warning |
12.6 DEFROST CYCLE
The defrost cycle is only active in heat pump mode and is used to prevent the
formation of ice on the surface of the air/air coil. The formation of ice on
the evaporator, which is quite frequent with very low outdoor temperatures, in
addition to considerably downgrading the thermodynamic performance of the
unit, also risks damaging the unit itself.
If the unit is switched off by remote control during defrosting, the heat pump
finishes defrosting and then places itself in off mode via remote control.
12.7 COMPRESSOR CRANKCASE HEATER
The crankcase heater is activated if the compressor has been off for at least
30 minutes and if the discharge temperature is below a certain threshold of 20
°C (with hysteresis of 2.0°C). The crankcase heater is disabled when the
compressor starts back up.
12.8 DOUBLE SET-POINT
This function introduces a second working set-point on the plant side, both in
cooling and heating mode.
The user terminal board allows a consent to be connected to switch from the
first to the second set-point and configured at digital input ID9 with
parameter H53 = 26. The valve, on the other hand, is connected in the terminal
board to digital output DO7 and is configured via parameter H85.
Parameter | VALUE | Function |
---|---|---|
H53 | 26 | Second set-point call |
H85 | 25 | 3-way valve for radiant panels |
H129
| 0| Function disabled (default)
1| Function configured but not active
2| Enabled only in cooling mode
3| Enabled only in heating mode
4| Enabled in cooling and heating mode
H138
| 0| DHW second setpoint function disabled (default)
1| Enabled the second DHW set point in cooling mode
2| Enabled the second DHW set point in heating mode
3| Enabled the second DHW set point in cooling and heating mode
12.9 MINIMUM HZ FUNCTIONALITY
Configuring parameter L02=1 and L03≠0 reduces the nominal operating Hz of the
compressor.
Parameter | VALUE | Function |
---|---|---|
L02 | 0 | Function not active |
1 | Enabling minimum Hz | |
L03 | 0 | Function not active |
1 | Function active only in cooling mode | |
2 | Function active only in heating mode | |
3 | Function active only in sanitary mode | |
4 | Function active in cooling and sanitary mode | |
5 | Function active in heating and sanitary mode | |
6 | Function active in cooling and heating mode | |
7 | Function always active |
With the function active, the output and power of the unit are limited, for
additional information see the installer user manual.
Configuring a digital input ID9 with parameter H53=21, the function can be
managed.
Parameter | VALUE | Function |
---|
H53
| 0 (default)| Function disabled
21| Open contact -> standard mode Closed contact -> mode Hz min/max
12.10 MAXIMUM HZ FUNCTIONALITY
Activating the function increases the power of the unit, please contact us for
information.
12.11 FLOWMETER
There is a flowmeter in each unit; it has the following characteristics:
Unit| Water measuring range [L/min]| Flow speed [m/s]| Flow rate [L/min]| Power supply
[Vdc]
| Current consumption without load| DN
---|---|---|---|---|---|---
0112 0115 0118| 5,0 – 85| 0,265 – 4,509| 0,5 – 150| 4.75 – 33| <5mA| 20
you can read the flow value in L/min from the remote display by pressing Enter -> SYS, and scrolling to S014.
FUNCTIONS THAT CAN BE ACTIVATED WITH HI-T2 ACCESSORY (OPTIONAL)
This is a touch screen remote control for centralised management of a
chiller/heat pump network. It includes humidity and temperature sensors for
the thermo hygrometric analysis of the environment and for the management of
the double set point for radiant floor heating systems that use a
dehumidification system.
The intuitive interface simplifies the use of the controller; all the
functions can be easily set through the use of an easy to understand synoptic.
The Hi-T remote control allows you to manage the following functions:
- Remote management;
- Management of a network, up to 7 heat pumps;
- Zone thermostat;
- Screed function;
- Antilegionella disinfection;
- Double set-point and humidity measurement;
- Dew point control;
- Climatic compensation;
- Booster circulator management;
- Management of single pump in a network;
- Alarm diagnostic system.
For further information, see the user-installer manual, or contact our headquarters.
FUNCTIONS THAT CAN BE ACTIVATED WITH GI3 MODULE (OPTIONAL)
The GI3 module is an optional kit which allows you to manage the following functions:
- Booster circulator management with the aid of two room thermostats (not supplied);
- Management of a plant side mixer valve both in heating and cooling mode;
- Solar – thermal integration management.
14.1 I/O RESOURCES OF THE CONTROLLER
The following is the list of I/O (inputs and outputs) that can be set to
activate the functions of the controller.
Resource| Parameter| Terminal block XGI| Factory
configuration| Description
---|---|---|---|---
Default value| Function
ST 5E| H27| 6.1 / 6.2| 0| Not set| Analogue input configurable with an
NTC-10kΏ probe at 25°C β 3435
ST 6E| H28| 7.1 / 7.2| 0| Not set| Analogue input configurable with an
NTC-10kΏ probe at 25°C β 3435
ST 7E (activated if ID 8E is not active|
H29
|
8.1 / 8.2
|
0
|
Not set
| Analogue input configurable with an NTC-10kΏ probe at 25°C β 3435
ID 8E (activated if ST 7E is not active)|
H62
|
0
|
Not set
| Voltage-free digital input
ID 9E| H63| 9.1 / 9.2| 0| Not set| Voltage-free digital input
DO 1E| H86| 1.1 (phase)
1.2(neutral)
| 0| Not set| 230Vac, 50Hz, 2A (AC1) single-phase live output.
DO 2E| H87| 2.2 (phase)
2.2(neutral)
| 0| Not set| 230Vac, 50Hz, 2A (AC1) single-phase live output.
DO 3E| H88| 3.1 (phase)
3.2(neutral)
| 0| Not set| 230Vac, 50Hz, 2A (AC1) single-phase live output.
DO 4E| H89| 4.1 (phase)
4.2(neutral)
| 0| Not set| 230Vac, 50Hz, 2A (AC1) single-phase live output.
DO 5E| H90| 5.1 (phase)
5.2(neutral)
| 0| Not set| 230Vac, 50Hz, 2A (AC1) single-phase live output.
GI terminal block
14.2 MANAGEMENT OF SECONDARY CIRCULATOR/RELAUNCH PUMP (WITH ROOM
THERMOSTAT)
Allows the management of two secondary or booster circulators serving the
system.
This allows up to 2 secondary circuits with independent calls, one of which
can be low temperature (mixed).
Two digital inputs and outputs are managed.
Resource I/O – Parameter | Value | Function | X terminals |
---|---|---|---|
ID9E can be activated via H63 | 19 | Room thermostat 1 | 9.1 / 9.2 |
ID8E can be activated via H62 | 32 | Room thermostat 2 | 8.1 / 8.2 |
DO5E can be activated via H90 | 43 | Secondary circulator circuit 1 | 5.1 (phase) |
5.2(neutral)
DO4E can be activated via H89| 33| Secondary circulator circuit 2| 4.1 (phase)
4.2(neutral)
The various scenarios with their configuration are shown below:
Configuration| T.A. 1| T.A. 2| Secondary circulator circuit 1|
Secondary circulator circuit 2| Mixing valve configuration (see chapter
14.3 mixing valve mangement)| Description
---|---|---|---|---|---|---
1| Single high temperature circuit| DI=19| –| DO=43| –| i06=0 (not enabled)|
A.T. contact 1 manages the one room call and consequently activates the
booster pump
2|
Two indipendent high temperature circuits
| DI=19| DI=32| DO=43| DO=33| i06=0 (not enabled)| The A.T. contact 1 works in the same way as for confi- guration 1, while the TA2 contact works in call for the output DO=33, which is managed as a booster pump for the secondary circuit 2, which in this configuration is also high temperature like the first.
3
|
Single mixed circuit
|
DI=19
or
DI=32
|
–
|
–
|
–
|
i06 > 0
DO=33 etc. (enabled)
| Contact T.A.1 works on the low-temperature circuit which is appropriately configured via the para- meters of the ‘rAd’ group. The output DO=33 acts as a booster pump for the
mixed circuit.
4| An independent high temperature and mixed circuit| DI=19| DI=32| DO=43| –|
i06 > 0 DO=33 etc. (enabled)| Contact T.A. 1 manages the call for the first
secondary circuit at high temperatu- re, activating the relative booster pump.
Contact T.A. 2 manages the call for the second secondary circuit at low
temperature (activation of DO=33 and relative adjustment of the mixing valve).
5| A high temperature circu- it and a mixed circuit| DI=19| –| DO=43| –| i06 >
0 DO=33 etc. (enabled)| The call is handled in parallel for both resources
DO=33 and DO=43
With the heat pump in OFF position, the booster circulator will be switched
off independently of the thermostat call.
If the machine is not equipped with either a remote plant sensor or a
secondary circulator, the room thermostat thermoregulation is as follows:
Room call | Compressor thermoregulation |
---|---|
b30=0 | b30=1 |
Active | Active |
Room call | Compressor thermoregulation |
--- | --- |
b30=0 | b30=1 |
Off ( ambient satisfied) | Compressor start is inhibited for room thermo- |
regulation (DHW and defrosting not affected by the lockout). If the compressor| Shutdown of active compressors for room ther- moregulation is forced (DHW and defrosting not affected)
The secondary circulator is switched off with a delay given by P02 (post-
pumping).
14.3 MIXER VALVE MANAGEMENT
The mixer valve is regulated by means of specific PID which strives to
maintain the delivery temperature of the radiant panel at the set value.
The setpoint setting can be found in the ‘Set’ Menu:
rCoo = Mixer flow temperature setpoint in cooling mode = 15°C (default)
rHea = Mixer flow temperature setpoint in heating mode = 30°C (default)
The resources and the parameters to be setting are the following:
I/O resource – Parameter| Description| Value| Function|
X terminals
---|---|---|---|---
ST 5E can be activated via H27| Analogue input| 44| Mixer probe| 1.1 / 1.2
ID9E can be activated via H63| Digital input| 19 or 32| Room thermostat 1 or
2| 4.1 / 4.2
DO1E can be activated via H86| Voltage output| 34| Valve open command| 5.1
(phase) / 6.2(neutral)
DO2E can be activated via H87| Voltage output| 35| Valve close command| 5.2
(phase)
DO3E can be activated vi H88| Voltage output| 33| Mixer pump| 7.1 / 7.2
i01| Valve opening time| Recover the value from the technical data supplied
installed| |
i02| Interval between two interruptions| 30 seconds1| |
i03| PID proportional band| 2°C2| |
i04| PID integral time| 300 seconds3| |
i05| PID derivative time| 0 4| |
i06| Mixer management only active in heating mode| 1| |
Mixer management only active in cooling mode| 2| |
Mixer management only active in heating and cooling mode| 3| |
i07| mixing valve in all recirculation inactive, in absence of call| 0| |
mixing valve in all recirculation active, in absence of call| 15
1Recommended value. Time interval between one corretion and the next.
2Recommended value. Intervention area defined by the difference between the
setpoint for the mixer flow and the temperature measured by mixing flow probe.
3Recommended value. Time taken by the mixing valve to switch from open to
closed and vice versa, when the difference between setpoint set for the flow
of the mixing valve and the value read by the mixing probe is greater than or
equal to proportional band. The more larger this value, the slower the change
in approach to the setpoint set for the mixing valve flow.
4 Derivate component of regulation; use only if you have a good knowledge of
regulator logic.
5 i07=1: in the following cases the mixing valve closes completely:
- with the room thermostat of the low-temperature circuit active, when I change the operating mode of the PDC from Heat (or Cool) to OFF, the DO “Valve close command” is activated for i01 seconds.
- If I open the room thermostat contact of the low-temperature circuit, the DO ‘Valve closing command’ is activated for i01 seconds.
14.3.1 Determination of setpoint
The setpoint on which to perform regulation is given by rCOO or rHEA
respectively in cooling and heating mode. If dynamic compensation of the
setpoint is enabled (b08=1), then the setpoint will be corrected the same way
as the heat pump/chiller.
The maximum and minimum value reached by the compensation are not controlled.
Therefore the parameters must be configured so that the setpoints are not
brought to unwanted values outside of the allowed work ranges.
14.3.2 Mixing pump
The mixing pump (DO3E) switches on when there is a call from the digital input
ambient thermostat (ID9E) and switches off with a delay of P02 from the
instant the thermostat call ceases.
14.4 SOLAR INTEGRATION MANAGEMENT
To enable te function, set S01=1.
Parameter | Description | Value | Function | X terminals |
---|---|---|---|---|
ST6E can be activated via H28 | Analogue input | 39 | Solar storage tank probe |
7.1 / 7.2
Parameter| Description| Value| Function| X terminals
---|---|---|---|---
ST7E can be activated via H29| Analogue input| 38| Solar collector probe| 8.1
/ 8.2
DO3E can be activated via H88| Live output| 30| Solar circulator| 3.1 (phase)
3.2(neutral)
DO4E can be activated via H89| Live output| 45| Solar exhaust valve| 4.1
(phase) 4.2(neutral)
14.4.1 Activation of solar circulator
Solar management is also active with the unit off.
The solar circulator is active in both of the following conditions are met:
• The temperature of the solar collector is higher than that defined by
parameter S13 (default 40°C), the solar circulator is activated;
• The temperature difference between the solar collector and that of the solar
storage tank is higher than the parameter S02 (default 6°C).
14.4.2 Collector protection
If the temperature of the collector exceeds parameter S04 (default 110°C), the
solar circulator is periodically on intermittently with the times set in:
• S05 = time ON (default 15 seconds);
• S06 = time OFF (default 15 seconds).
As hysteresis to exit the protection condition use S08 (default 2°C).
This protection is guaranteed even with the machine Off.
14.4.3 Collector overtemperature alarm
If the collector probe exceeds the value of parameter S12 (default 130°C),
there is an alarm condition E10 which blocks the solar circulator. The
hysteresis to return from the alarm condition is given by parameter S08
(default 2°C).
If an alarm is triggered, operation of the heat pump is guaranteed.
14.4.4 DHW overtemperature alarm
If the temperature of the DHW storage tank exceeds the parameter S10 (default
80°C), the alarm E50 is triggered.
The hysteresis to return from the alarm condition is given by parameter S11
(default 2°C).
If an alarm is triggered, operation of the heat pump is guaranteed.
14.4.5 Solar exhaust valve
If alarms E10 and E50 are triggered simultaneously, the solar exhaust valve
will be activated.
It is recommended to connect the output of terminals 8.1 (phase) – 8.2
(neutral) to a timed relay to manage the flow of the exhaust valve. If any
doubts arise, contact our headquarters.
14.4.6 Disposal of solar tank heat
The solar circulator runs to dissipate excess heat in the storage tank by
exploiting the solar collector if both of the following conditions are met:
-The temperature of the DHW storage tank is higher than parameter S15 (default 60°C);
-The temperature of the solar collector is lower than 35°C (parameter S13 – parameter S14).
The solar collector is off when at least one of the following conditions is
met:
-The temperature of the DHW storage tank is lower than parameter S15 (default 60°C).
-The temperature of the collector exceeds the parameter S13 (default 40°C), as conditions are no longer in place for proper dissipation of the heat.
14.4.7 Antifreeze
Function active if the parameter S01 = 1.
If the temperature of the solar collecor is lower than parameter S07 (default
5°C), the solar circulator is activated in antifreeze mode.
This protection is only enabled with the machine Off.
The function is inhibited if the temperature of the DHW storage tank is lower
than the value defined in parameter S16 (default 20°C).
This regulator also works with the unit Off.
Setting the parameter S01 = 2, the antifreeze function is never active (for
example because the solar plant is supplied with glycol).
Be careful as enabling this function could damage the entire system.
Note:
- Solar integration is NOT managed if the controller of the unit is OFF.
- The remote digital input OFF has no effect on solar management.
- During first ignition, check that the probe of the solar collector measures a temperature lower than 160°C and that this temperature corresponds to that read on the controller of the internal unit.
- Solar circulator live output 230V ac, 50Hz, 2A (AC1).
- For higher absorptions, connect the output to the contactor coil.
- Factory-set parameters for solar management, any other configurations are the responsibility of the user and/or installer. The company excludes any contractual and extra contractual liability for damage caused to persons, animals or objects, by incorrect installation, setting and maintenance, improper use of the equipment, and the partial or superficial reading of the information contained in this manual.
TABLES OF PERMITTED SETUPS FOR USER AND INSTALLER
| CAUTION
---|---
All the operations with INSTALLER visibility must be carried out by
QUALIFIED PERSONNEL.
Not all of the configurations can be activated and/or modified at the same
time.
Values other than the default values can jeopardise proper operation of the
unit. If in doubt on which value to set, contact our headquarters.
The company excludes any contractual and extra contractual liability for
damage caused to persons, animals or objects, by incorrect installation,
setting and maintenance, improper use of the equipment, and the partial or
superficial reading of the information contained in this manual.
We shall not be held liable for any breakage or malfunctioning caused by third
parties changing the default parameters if not expressly authorised to do so.
The following is the table of the allowed configurations; not all of them can
be selected simultaneously.
Values other than the default values can jeopardise proper operation of the
unit. If in doubt on which value to set, contact our headquarters.
Parame- ter| Description| Unit| Default| Range|
Visibility| Allowed configurations:|
---|---|---|---|---|---|---|---
Description| Notes
Coo| First cooling setpoint| °C| 7.0| 25÷Coo2| U| |
Hea| First heating setpoint| °C| 45.0| Hea2÷H01| U| |
San| Sanitary setpoint| °C| 48.0| 25÷H01| U| | If sanitary function
active. See par. 10.2
Coo2| Second cooling setpoint| °C| 18.0| Coo÷25| U| |
Hea2| Second heating setpoint| °C| 35.0| 25÷Hea| U| |
*rCOO| Mixing valve summer set-
point
| °C| 15.0| -50÷80| I| | Config if Gi accessory
present
*rHEA| Mixing valve winter setpoint| °C| 30.0| -50÷80| I| | Config if Gi accessory
present
San2| Second sanitary setpoint| °C| 45.0| 0÷80| l| |
H01| Maximum heating setpoint| °C| 75.0| -50÷80| l| |
H04| Mnimum cooling setpoint| °C| 5.0| -50÷80| l| |
H10| Sanitary function enabling| /| 0| 0÷6| I| See par. 10.2|
H17| Input configuration
Analogue ST6
| /| 0| 0÷49| I| 0 = Input disabled
6 = Domestic hot water probe
|
H18
| Input configuration Analogue ST7|
/
|
0
|
0÷49
|
I
| 0 = Input disabled
41 = Remote water temperature
probe
|
*H27| Input configuration
Analogue ST5E
| /| 0| 0÷49| I| 0 = Input disabled
44 = Mixer probe
| Only if Gi accessory
present
*H28| Input configuration
Analogue ST6E
| /| 0| 0÷49| I| 0 = Input disabled
39 = Solar storage tank probe
| Only if Gi accessory
present
*H29| Input configuration
Analogue ST7E
| /| 0| 0÷49| I| 0 = Input disabled
38 = Solar collector probe
| Only if Gi accessory
present
*H30| Input configuration
Analogue ST8E
| /| 0| 0÷49| l| | Only if Gi accessory
present
H46| Input configuration
Digital ID2
| /| 0| 0÷30| I| 0 = Input disabled
3 = Summer/winter mode change
|
H47| Input configuration
Digital ID3
| /| 2| 0÷30| I| 0 = Input disabled
2 = Remote On / Off
|
H53
|
Input configuration Digital ID9
|
/
|
0
|
0÷30
|
I
| 0 = Input disabled
21= Hz min/max remote 25= Silenced version
26 = Double set-point call
28 = DHW thermostat call
|
*H60| Input configuration Digital
ID6E
| /| 0| 0÷30| l| | Only if Gi accessory
present
*H61| Input configuration Digital
ID7E
| /| 0| 0÷30| l| | Only if Gi accessory
present
*H62| Input configuration Digital
ID8E
| /| 0| 0÷30| l| | Only if Gi accessory
present
*H63| Input configuration
Digital ID9E
| /| 0| 0÷30| I| 0 = Input disabled
19 = room thermostat
| Only if Gi accessory
present
H75
|
Digital inputs polarity
|
/
|
0
|
0÷255
|
I
| 0 = Digital inputs N.A.
1 = ID1 polarity inverted 2 = ID2 polarity inverted 4 = ID3 polarity inverted 8 = ID4 polarity inverted 16 = ID5 polarity inverted 32 = ID6 polarity inverted 64 = ID7 polarity inverted
128 = ID8 polarity inverted
|
H76
|
Digital inputs polarity
|
/
|
0
|
0÷255
|
I
| 0 = Digital inputs N.A.
1 = ID9 polarity inverted 2 = ID10 polarity inverted
4 = ID1E1 polarity inverted 8 = ID2E1 polarity inverted 16 = ID3E1 polarity inverted 32 = ID4E1 polarity inverted 64 = ID5E1 polarity inverted
128 = ID6E1 polarity inverted
|
H81
| Output configuration In DO3 power|
/
|
22
|
0÷48
|
I
| 0 = Output disabled
22 = Plant integration heater
26 = DHW integration heater
|
H82| Output configuration
In DO4 power
| /| 14| 0÷48| | 0 = Output disabled
= Resistenza scambiatore
|
H83| Output configuration
In DO5 power
| /| 28| 0÷48| | 0 = Output disabled
= Base resistance
|
H84| Output configuration
In DO6 power
| /| 6| 0÷48| I| 0 = Output disabled
6 = DHW valve
|
Parame- ter| Description| Unit| Default| Range|
Visibility| Allowed configurations:|
---|---|---|---|---|---|---|---
Description| Notes
H85
|
Output configuration In DO7 power
|
/
|
25
|
0÷48
|
l
| 0 = Output disabled
25 = Double set-point valve 29 = Boiler enabling
24 = Alarm warning
31 = Summer/winter operating mode warning
21 = Defrost warning
47 = Machine block warning
|
*H86| Output configuration
In voltage DO1E
| /| 0| 0÷48| I| 0= Output disabled
34= Valve opening command
| Only if Gi accessory
present
*H87| Output configuration
In voltage DO2E
| /| 0| 0÷48| I| 0= Output disabled
35= Valve closing command
| Only if Gi accessory
present
*H88| Output configuration
In voltage DO3E
| /| 0| 0÷48| l| 0 = Output disabled
30 = Solar circulator
| Only if Gi accessory
present
*H89| Output configuration
In voltage DO4E
| /| 0| 0÷48| l| 0 = Output disabled
45 = Solar exhaust valve
| Only if Gi accessory
present
*H90| Output configuration
In voltage DO5E
| /| 0| 0÷48| l| 0 = Output disabled
43 = Secondary circulator
| Only if Gi accessory
present
H100
|
Digital output polarity
|
/
| |
0÷255
|
l
| 0 = Digital inputs N.O.
1 = Inverted polarity of DO1 2 = Reversed polarity of DO2 4 = Reversed polarity of DO3 8 = Reversed polarity of DO4
16 = Reversed polarity of DO5 32 = Reversed polarity of DO6 64 = Reversed polarity of DO7
128 = Reversed polarity of DOE1
|
To reverse more than one polarity, do the sum of those you want to invert
H101
|
Digital output polarity
|
/
|
0
|
0÷255
|
l
| 0 = Digital inputs N.A.
1 = Reversed polarity of DO2E 2 = Reversed polarity of DO3E 4 = Reversed polarity of DO4E 8 = Reversed polarity of DO5E 16 = Reversed polarity of DO6E
32 = Reversed polarity of DO7E
|
To reverse more than one polarity, do the sum of those you want to invert
H124
|
Serial baud rate
|
baud
|
1
|
0÷3
|
l
| 0=4800 baud
1=9600 baud
2=19200 baud
3=38400 baud
|
H125
|
Serial parity
|
/
|
2
|
0÷3
|
l
| 0=none parity, 2 stop bits 1=odd parity, 1 stop bit 2=even parity, 1 stop bit
3=none parity, 1stop bit
|
H126
|
Serial address
|
/
|
1
|
0÷200
|
l
| In the cascade configuration, assign a different address to each control-
ler.
|
H129| Enable second setpoint| /| 0| 0÷4| l| |
H130
| Heating with DHW storage tank|
/
|
0
|
0÷1
|
l
| 0 = Normal operation
1 = In Heating, machine always
turned towards DHW
|
H136
| OFF state deactivation with ID presence ON/OFF re-
mote
|
/
|
0
|
0÷1
|
l
| |
H138
|
Enabling second set point for DHW
|
/
|
0
|
0÷3
|
I
| 0 = DHW second set point function disabled (default)
1 = Enabled the second domestic set point in cooling mode
2 = Enabled the second DHW set point in heating mode
3 = Enabled the second domestic set
point in cooling and heating
|
H141| Priority communication
channels Modbus
| /| 1| 0÷1| I| 0 = Priority on channel 1 (CN14)
1 = Priority on channel 2 (CN12-N13)
|
H142
|
MODBUS 2 serial baud rate (CN12 – CN13)
|
/
|
1
|
0÷3
|
I
| 0 = 4’800 Baud
1 = 9’600 Baud
2 = 19’200 Baud
3 = 38’400 Baud
|
H143
|
Parity and Stop Bit serial MODBUS
|
/
|
2
|
0÷3
|
I
| 0 = No parity, 2 Stop bits 1 = ODD Parity, 1 Stop Bit 2 = EVEN parity, 1 Stop Bit
3 = No parity, 1 Stop Bit
|
H144| Serial address for MODBUS| /| 0| 0÷127| I| 0 = same address as
Serial Mocbus
1 (H126)
|
A08| Antifreeze alarm activation
setting
| °C| 3| -127÷127| l| Different values can jeopardise
proper operation of the unit
|
b01| Compressor regulation
band in cold
| °C| 2| 0,5÷5,0| l| |
b02| Compressor regulation
band in hot
| °C| 2| 0,5÷5,0| l| |
Parame- ter| Description| Unit| Default| Range|
Visibility| Allowed configurations:|
---|---|---|---|---|---|---|---
Description| Notes
b04| Radiant panels valve switch-
ing time
| sec| 30| 0÷600| l| Different values can jeopardise
proper operation of the unit
|
b05| Compressor cut-off hyster-
esis
| °C| 0| 0,5÷5| l| |
b06| Sanitary valve stroke time| sec| 45| 0÷255| I| |
b08| Enable dynamic setting| /| 0| 0÷1| I| |
b09| Maximum cooling offset| °C| 3.0| -50.0÷80.0| I| |
b10| Maximum heating offset| °C| -3.0| -50.0÷80.0| I| |
b11| Cooling outdoor tempera-
ture setting
| °C| 25| -127÷127| I| |
b12| Heating outdoor tempera-
ture setting
| °C| 15| -127÷127| I| |
b13| Cooling temperature delta| °C| -10.0| -50.0÷80.0| I| |
b14| Heating temperature delta| °C| 10.0| -50.0÷80.0| I| |
b15| 0-10V analogue input set-
ting decalibration band
| °C| 5.0| 0.0÷25.5| I| |
b21| System water reversing
valve switching time
| sec| 0| 0÷600| l| |
b22| Plant probe temperature
control cut-off hysteresis
| °C| 5.0| 0.0÷25.5| I| |
b24| Maximum ∆T,set for com-
pressors restart
| °C| 7.0| 0.0÷25.5| l| |
b25| Compressor cut-on hyster-
esis
| °C| 3.0| 0.0÷25.5| l| |
b30
| Enabling compressor switch-off with room call
satisfied
|
–
|
0
|
0÷1
|
l
| 0 = function disable 1 = function active|
P01| Pump ON compressor ON
delay
| sec| 30| 0÷255| I| |
P02| Pump OFF compressor OFF
delay
| min| 2.0| 0÷25.5| I| |
P03
|
Pump operating mode
|
/
|
0
|
0÷1
|
I
| | The pump is always on if the antifreeze
heaters are active.
P04| Pump setting in antifreeze| °C| 5| -15÷15| I| |
P05| Pump hysteresis in anti-
freeze
| °C| 2.0| 0.0÷15.0| I| |
P06| Set delta T water pump in
heating
| °C| 4°C| 0÷255| l| |
P07| Maximum pump speed| �| 100%| 65÷100| l| |
P08| Minimum pump speed| %| 75%| 50÷100| l| |
P09| Modulating pump inlet/out-
let water delta T setting
| °C| 2.0| 0÷15| I| |
P16| Interval between 2 periodi-
cal activations of the pump
| min| 0| 0÷600| I| |
P17| Operating time of the pump
in periodical mode
| sec| 0| 0÷255| I| |
r02
|
Antifreeze heaters setpoint in heating mode
|
°C
|
4
|
3÷6
|
I
| | Only change in the presence of glycol water. Contact our
headquarters.
r03
|
Antifreeze heaters setpoint in cooling mode
|
°C
|
4
|
3÷6
|
I
| | Only change in the presence of glycol water. Contact our
headquarters.
r06
|
Antifreeze heaters delta
|
°C
|
2.0
|
0.0÷25.5
|
I
| | Only change in the presence of glycol water. Contact our
headquarters.
r08
|
Operation in substitution
upper limit
|
°C
|
-20
|
-20÷50
|
I
|
Respect r22 ≥ r28 ≥ r08
| Do not modify this value, as it could jeopardise operation
of the unit
r09| Hysteresis for heat pump
blockage
| °C| 1,0| 0,0 ÷10,0| | |
r10| Plant integration enabling| /| 0| 0÷1| I| 0 = Function disabled
1 = Function enabled
|
r11| Plant integration heater
delta
| °C| 0.5| 0,0÷25.5| I| |
r12| Plant/heat pump integra-
tion heater activation delay
| min| 8| 0÷255| I| |
Parame- ter| Description| Unit| Default| Range|
Visibility| Allowed configurations:|
---|---|---|---|---|---|---|---
Description| Notes
r14
| Compressor bypass on system with sanitary heat- ing element active|
/
|
0
|
0÷1
|
I
| r14 = 1 during activation of the sani- tary heating elements is not permit- ted the use of plant-side compres-
sors is not permitted
|
r15| DHW integration enabling| /| 0| 0÷2| I| 0 = Function disabled
1 = Function enabled
|
r16| DHW/heat pump integra-
tion heater activation delay
| min| 8| 0÷255| I| |
r19
| Duration of tray heater ac- tivation
since last defrost
|
min
|
8
|
0÷255
|
I
| 0= resistance always active during defrost.|
r21
| Enables plant side mitiga- tion
with heaters in defrost
mode
|
/
|
0
|
0÷1
|
I
|
0= Function disabled
1= Function enabled
|
r22
|
Joint operation bracket I up- per limit
|
°C
|
7
|
-16÷50
|
I
|
Respect r22 ≥ r28 ≥ r08
| Do not modify this value, as it could jeopardise operation
of the unit
r23| Type of use of boiler| /| 0| 0÷8| I| |
r24| Type of use of integration
heaters
| /| 3| 0÷3| I| |
r25| Disinfection setpoint| °C| 80| 0÷100| l| |
r26| Disinfection duration| min| 12| 0÷255| l| |
r27| Heat pump setpoint in dis-
infection
| °C| 55.0| -500÷800| l| |
r28
|
Joint operation bracket II
upper limit
|
°C
|
-7
|
-16÷50
|
I
|
Respect r22 ≥ r28 ≥ r08
| Do not modify this value, as it could jeopardise operation
of the unit
r29
| First setpoint temperature offset for boiler and plant
heaters (HEA)
|
°C
|
0
|
0÷100
|
I
| |
r30
| Second setpoint tempera- ture offset for boiler and
plant heater (HEA2)
|
°C
|
0
|
0÷100
|
I
| |
r31| Temperature offset for boil-
er and DHW heaters (SAN)
| °C| 0| 0÷100| I| |
r32| Boiler supply| /| 0| 0÷3| I| |
r33| Pump management with
heaters active
| /| 3| 0÷3| I| |
r34
|
Disinfection day
|
/
|
0
|
0÷7
|
U
| 0 =Disabled
1 =Monday
2 =Tuesday
3 =Wednesday
4 =Thurday
5 =Friday
6 =Saturday
7 = Sunday
|
r35| Disinfection time (minute of
the day)
| /| 0| 0÷1439| U| |
r36
|
Anti-loop time on sanitary operation
|
min
|
0
|
0÷255
|
l
| | Control to prevent the machine remain in sanitary produc- tion indefinitely in- definitely because does not reach the set point.
Control active if pa- rameter R36 is dif- ferent from 0. In this case, the time of r36 is counted since the compressor started to work in the DHW mode. If the produc- tion of the DHW is not finished within r36 minutes, then you exit forced out of
sanitary production.
r37
|
Boiler operation in cooling + DHW mode
|
/
|
1
|
0÷2
|
l
| 0 = Boiler not used
1 = Boiler used in integration
2 = Boiler does DHW and PDC does
plant.
|
r38| Heat pump blockage thresh-
old for high T
| °C| 35| -127÷127| l| |
Parame- ter| Description| Unit| Default| Range|
Visibility| Allowed configurations:|
---|---|---|---|---|---|---|---
Description| Notes
r39| Heat pump blockage thresh-
old for high Text in heat
| °C| 46| -127÷127| l| |
d04| Defrost output pressure| bar| 18.0| -500÷800| l| |
d08| Minimum time between de-
frost and next
| min| 35| 0÷255| l| |
L02| User enablement for min.
Hz function
| /| 0| 0÷1| I| |
L03| Active min. Hz| /| 7| 0÷7| I| |
s01| Solar thermal enabling| /| 0| 0÷2| l| |
s02| Solar ∆T| °C| 0| 0÷25.5| l| |
s03| Solar hysteresis| °C| 0| 0÷25.5| l| |
s04| Maximum solar tempera-
ture
| °C| 0| 0÷255| l| |
s05| Pump on time in maximum
solar temperature
| sec| 0| 0÷255| l| |
s06| Pump off time in max. solar
temp
| sec| 0| 0÷255| l| |
s07| Solar antifreeze set| °C| 0| -127÷127| l| |
s08| Solar antifreeze hysteresis| °C| 0| 0÷25.5| l| |
s09| Constant for calculating so-
lar power output
| /| 0| 0÷999| l| |
s10| Maximum solar DHW stor-
age temperature thresold
| °C| 0| 0÷255| l| |
s11| Solar sanitary hysteresis| °C| 0| 0÷25.5| l| |
s12| Solar collector overfill alarm
threshold
| °C| 0| 0÷255| l| |
s13
| Minimum temperature
threshold collector for acti-
vation solar
|
°C
|
0
|
0÷255
|
l
| |
s14| Hysteresis for sanitary cool-
ing
| °C| 0| 0÷25.5| l| |
s15| Sanitary cooling threshold| °C| 0| 0÷255| l| |
s16
| Minimum temperature
thresold collector anti-
freeze storage
|
°C
|
0
|
0÷255
|
l
| |
*i01*| Valve opening time| sec| 0| 0÷600| l| |
i02**| Interval between two cor-
rections
| sec| 0| 0÷600| l| |
*i03*| PID proportional band| | 0| 0÷80.0| l| |
i04| PID integral time| sec| 0| 0÷2000| l| |
i05| PID derivative time| sec| 0| 0÷25.5| l| |
i06**| Radiant panel configuration| /| 0| 0÷3| l| |
*i07| mixing valve in all recircula-
tion, when no call is made
| /| 0| 0÷1| l| |
Ac09| Flow-meter minimum water
flow rate
| l/min| 0.0| 0÷100| l|
See par. “Flowmeter”
|
Ac10| Flowmeter outlet at the
minium flow rate
| Volt| 0.0| 0÷100| l|
Ac11
| Maximum flowmeter flow
rate (0106, 0109)
|
l/min
| 50.0| 0÷800|
l
|
Maximum flowmeter flow
rate (0112, 0115,0118)
| 85.0| 0÷800
Ac12| Flow meter outlet at the
maximum flow rate
| Volt| 0.0| 0÷100| l|
(*) If Gi module is present GI3
ALARMS
By placing the controller in OFF mode, the alarms reset and the counts of the
relative hour interventions are also reset. If the alarms are still triggered
when switching the unit back on, contact technical assistance. The values
indicated below could be subject to updates. If you have any doubts, contact
our headquarters.
16.1 [E006] FLOWMETER
The water side flowmeter is already installed inside the unit and MUST NOT be
tampered with or bypassed in any way. The flow switch is bypassed for 10
seconds after the unit is switched on. When the bypass time has elapsed, you
must evaluate the status of the digital input, if active, the flow is
considered present. If the flow is found to be missing for 5 seconds, the
alarm is triggered and the circulator switches on for 120 seconds If the alarm
triggers more than 3 times an hour, it must be reset manually.
The alarm does not trigger in the following conditions:
- During domestic hot water production;
- During the plant venting cycle function.
16.2 [E018] HIGH-TEMPERATURE
If the water delivery probe detects a value higher than 65°C for longer than
50 seconds, the alarm is active only in chiller mode. It deactivates when the
temperature returns below 62°C.
16.3 [E020] INCONGRUENT PRESSURES
For compressor enabled for more than 150 seconds, the suction pressure probe
detect a pressure higher than the condensation pressure probe, the alarm
displayed is E020. The alarm is not resettable (it is necessary to cut the
power supply to eliminate the alarm).
This alarm is not in defrosting mode.
16.4 [E005] ANTIFREEZE
If the outlet water probe has a value lower than A08 (3°C), the alarm is
active. It deactivates if the temperature recorded by the probe is higher than
+6°C. The alarm is bypassed for 120 seconds from switch on in heating mode.
16.5 [E611÷E681] PROBE ALARMS
The alarm is triggered if any connected or enabled probe is short-circuited or
interrupted.
The alarm also triggers if the upper limit (100°C) or the lower limit (-50°C)
of the probes is exceeded. A probe figured as sanitary probe will not trigger
any alarms if domestic hot water is not enabled.
NOTE:
If the pressure switch on the machine detects a pressure exceeding 30,5 bar
the driver and the compressor are powered off and probe error E641 is
displayed (Compressor discharge probe fault).
The alarm is cleared when the pressure drops below 23 bar.
16.6 [E801] TIMEOUT INVERTER
When the machine’s controller does not communicate with the driver board of
the compressor, a timeout alarm is triggered to avoid losing control of the
system.
16.7 [E801 ÷E981] INVERTER
Inverter alarms are indicated in the section ‘Alarm Table Utility Block’.
NB: alarm E981 “Inverter high pressure”:
- alarm intervention up to 3 times in one hour: resets automatically after pressure switch reset (after 140 seconds for sizes 106, 109 and 112, after 30 seconds for sizes 115 and 118).
- requires a manual reset if it trips more than 3 times in one hour.
16.8 [E00] REMOTE ON/OFF (WARNING)
If the unit is controlled by a remote digital input. See par. 10.4.1
16.9 [E001] HIGH-PRESSURE
If the pressure transducer on the unit detects a pressure higher than 30,3 bar
the alarm is triggered.
In this case the compressor is blocked immediately. The alarm is reset when
the pressure drops below 21,3 bar. If the alarm triggers more than 3 times an
hour, it must be reset manually.
16.10 [E002] LOW-PRESSURE
In chiller mode, if the pressure transducer on the unit detects a pressure
lower than 1,7 bar, the alarm is triggered.
In heat pump mode, if the pressure transducer on the unit detects a pressure
lower than 0,7 bar, the alarm is triggered.
The alarm is reset when the pressure rises 2.0 bar above the triggering
threshold.
A bypass time of 60 seconds is counted every time the compressor is activated.
When the alarm is triggered, it blocks the compressors of the circuit. The
alarm is reset manually if it triggers 3 times an hour.
16.11 [E008] DRIVER LIMITATION
If the compressor does not reach the speed at the intended ramp value within
30 minutes, the alarm is triggered and the compressor switches off for safety
purposes.
The alarm is reset manually if it triggers 3 times an hour.
16.12 [E041] 4-WAY VALVE
Manually reset alarm, it identifies malfunctioning of the 4-way reversing
valve.
The alarm does not trigger for a bypass time of approximately 180 seconds from
start-up of the compressor.
-
In heating and sanitary mode, the alarm is triggered when, the bypass time having elapsed, the water delivery temperature is lower than the
water return temperature of the heat pump – 1°C. -
In cooling mode, the alarm is triggered when, the bypass time having elapsed, the water delivery temperature is higher than the water
return temperature of the heat pump + 1°C.
16.13 POWER FAILURE
When restored:
- The instrument goes back to the condition it was in prior to the power failure
- if a defrost cycle is in progress, it is cancelled
- all of the timers in progress are cancelled and reinitialized
16.14 UTILITIES BLOCK ALARM TABLE
Code | DESCRIPTION | Block |
---|---|---|
E00 | Remote off | Machine |
E001 | High pressure alarm | Machine |
E002 | Low pressure alarm | Machine |
E005 | Antifreeze alarm | Machine |
E006 | Flow alarm | Machine |
E008 | Forced compressor shutdown for luck of lubrication | Machine |
E009 | Discharge high temperature alarm | Machine |
E010 | Solar collector high temperature alarm | Solar pump |
E018 | Cooling high temperature alarm | Machine |
E020 | Inverted trasductors pressure alarm | Machine/sanitary |
E041 | Incongruent temperature alarm | Machine |
E050 | DHW storage tank high temperature alarm | – |
E101 | Communication timeout with Slave 1 | Machine |
E611 | Water inlet probe failure | Machine |
E621 | Water outlet probe failure | Machine |
E631 | Compressor intake probe failure | Machine |
E641 | Compressor discharge probe fault / high pressure switch trip |
Machine
E651| Outdoor air probe failure| Machine
*E652| Mixer probe failure| Machine
E661*| DHW probe failure| Machine
E662| Solar storage tank probe failure| Machine
E671**| Plant remote probe failure| Machine
*E672| Solar collector probe failure| Machine
E691| Low pressure transducer failure| Machine
E701| High pressure probe failure| Machine
E711| Voltage input failure 0-10V DC| Machine
E801| Inverter timeout| Compressor
E821| IPM module overcurrent| Compressor
E831| PFC module overheating| Compressor
E841| Inverter abnormal voltage DC Bus side| Compressor
E851| Inverter Hardware problem| Compressor
E861| Inverter current too high| Compressor
E871| High temperature IPM module| Compressor
E881| Supply voltage out of limits| Compressor
E891| One or more compressor supply phases absent| Compressor
E901| Inverter model error| Compressor
E911| Inverter overload error| Compressor
E921| Inverter PFC module overcurrent| Compressor
E931| Internal communication error| Compressor
E941| PFC model fault| Compressor
E951| Inverter board probe error| Compressor
E961| Abnormal condition| Compressor
E971| EEPROM error| Compressor
E981| High pressure inverter| Compressor
(*) If Gi module present
MODBUS VARIABLES
The controller is configured as follows by default:
BAUD RATE | 9600 |
---|---|
PARITY | EVEN |
DATA BIT | 8 |
STOP BIT | 1 |
--- | --- |
DEVICE ID | 1 |
To configure the Modbus communication according to your requirements, you must modify the following logs:
H124 : BAUD RATE
0| 4800
1| 9600
2| 19200
3| 38400
H125 : PARITY, STOP BIT
0| NONE, 2 bit
1| ODD, 1 bit
2| EVEN, 1 bit
3| NONE, 1 bit
H126 : DEVICE ID| 1 ÷ 200
---|---
Modbus comands:
READING | HOLDING REGISTER |
---|---|
WRITING | 6-16 |
Register | Format |
Description | Note |
--- | --- |
1 | INT |
Firmaware informa- tion
| Firmaware versione|
2| INT| –| R| –| Firmware release|
3| BYTE (H)| –| R| –| Firmware sub-release|
BYTE (L)| –| R| –| Firmware creation day|
4| BYTE (H)| –| R| –| Firmaware creation month|
BYTE (L)| –| R| –| Firmware creation year|
80 ÷ 97| ASCII| –| R| –| Serial number| Registration number|
444| INT| –| R| 0 ÷ 800| Water flow rate| |
1089| INT| –| R/W| 1 ÷ 200| Serial address| Modbus serial ID|
200
|
INT
| –| R| –|
Machine settings
| (0) Stand by|
Reading values of
the machine status
–| R| –| (1) Cooling
–| R| –| (2) Heating
–| R| –| (4) Only sanitary mode¹
–| R| –| (5) Cooling + Sanitary¹
–| R| –| (6) Cooling + Sanitary¹
7201
|
BIT MASK
|
0
|
R/W
|
–
| Enablement of writing the machine status remotely| Necessary for the operation of the
reg. 7200.
7200
|
INT
| –| W| –| (0) Stand by| The writing values that are not allowed at this
address can lead to unexpected operations, so keep only those values that are
allowed in writing.
–| W| –| (1) Cooling
–| W| –| (2) Heating
–| W| –| (4) Only sanitary¹
–| W| –| (5) Cooling + Sanitary¹
–| W| –| (6) Heating + Sanitary¹
7201
|
BIT MASK
|
1
|
R/W
|
–
|
Setpoint
| Enablement of writing the machine status remotely| Necessary for the operation of the
reg. 7203/7208.
7203| °C/10| –| R/W| 5.0 ÷ 23.0| Cooling|
7204| °C/10| –| R/W| 25.0 ÷ 55.0-| Heating|
7205| °C/10| –| R/W| 25.0 ÷ 55.0| Santary|
7206| °C/10| –| R/W| 5.0 ÷ 23.0| Second cooling|
7207| °C/10| –| R/W| 25.0 ÷ 55.0| Second heating|
7208| °C/10| –| R/W| 0.0 ÷ 80.0| DHW preparer|
7201
|
BIT MASK
|
2
|
R/W
|
–
|
Second setpoint
| Enabling the switching to the second
setpoint
| Necessary for the operation of bit 0 of
reg. 7202.
7202| BIT MASK| 0| W| –| 0=primary setpoints, 1=secondary
setpoint
| Writing value
7217| BIT MASK| 0| R| –| 0=primary setpoints, 1=secondary
setpoint
| Reading value
7201
|
BIT MASK
|
3
|
R/W
|
–
|
Room temperature
call
|
Enablement of remote room call writing
| Necessary for the operation of bit 1 of
reg. 7202.
7202| BIT MASK| 1| R/W| –| Forced room temperature call remotely|
7201
|
BIT MASK
|
4
|
R/W
|
–
|
Sanitary call
| Enablement of remote sanitary call writing| Necessary for the operation of bit 1 of
reg. 7202.
7202| BIT MASK| 2| R/W| –| Forced remote sanitary mode call|
7201
|
BIT MASK
|
5
|
R/W
|
–
|
Anti-Legionella ²
| Enablement of anti-legionella cycle remotely| Necessary for the operation of bit 3 of
reg. 7202.
7202
|
BIT MASK
|
3
|
R/W
|
–
| Remote anti-legionella cycle request activation| The bit must be 1
for the entire cycle
period.
7216
|
BIT MASK
| 5|
R
|
–
| Anti-legionella cycle in progress|
6
|
Anti-legionella cycle failed or stopped
| It remains at 1 until the next cycle, or it resets itself when the board is turned
off.
7202| BIT MASK| 5| R/W| –| Plant air-vent| Forced plant air-vent| Only if the machine
is in Stand By (0).
Register| Format| Bit| R/W| Range| Name|
Description| Note
---|---|---|---|---|---|---|---
7202
|
BIT MASK
|
6
|
R/W
|
–
|
Santary disablig
|
Sanitary call prohibition (without exiting from the actual mode + SAN function)
| Active only if the setting of bit 3 is 7201 (when the room temp. call is also managed
remotely).
7202| BIT MASK| 7| R/W| –|
Defrosting
| Forced defrosting| Only if the machine
is in heating (2-6).
7214| BIT MASK| 13| R| –| Defrosting on call|
14| Defrosting in progress|
305| ora| –| R| –|
Operating hours
| Compressor 1|
307| ora| –| R| –| Compressor 2|
309| ora| –| R| –| Compressor 3|
313| ora| –| R| –| Compressor 1 circuit 2|
315| ora| –| R| –| Compressor 2 circuit 2|
317| ora| –| R| –| Compressor 3 circuit 2|
253| °C/10| –| R| –|
Temperature trans- ducer
| Evaporation|
254| °C/10| –| R| –| Condensation|
626| °C/10| –| R| –| Evporation circuit 2|
627| °C/10| –| R| –| Condensation circuit2|
400| °C/10| –| R| –|
Temperature ³
| Water inlet|
401| °C/10| –| R| –| Water outlet|
405| °C/10| –| R| –| DHW|
422| °C/10| –| R| –| Compressor inhlation|
428| °C/10| –| R| –| Outdoor|
433| °C/10| –| R| –| Compressor discharge 1|
434| °C/10| –| R| –| Compressor discharge 2|
435| °C/10| –| R| –| Compressor discharge 3|
437| °C/10| –| R| –| Solar collector|
438| °C/10| –| R| –| Solar accumulation|
440| °C/10| –| R| –| Plant remote|
443| °C/10| –| R| –| Radiant panels mixing delivery|
447| °C/10| –| R| –| DHW preparer recirculation|
20422| °C/10| –| R| –| Compressors inhalation (circuit 2)|
20433| °C/10| –| R| –| Compressor 1 discharge (circuit 2)|
20434| °C/10| –| R| –| Compressor 2 discharge (circuit 2)|
20435| °C/10| –| R| –| Compressor 3 discharge (circuit 2)|
406| bar/100| –| R| –|
Pressions ³
| High pressure|
414| bar/100| –| R| –| Low pressure|
20406| bar/100| –| R| –| Circuit 2 high pressure|
20414| bar/100| –| R| –| Circuit 2 low pressure|
7000| %/10| –| R| –|
Analogue output
| Condensation fan|
7001| %/10| –| R| –| Circulating pump|
628| %/10| –| R| –| Condensation fan circuit 2|
950
|
BIT MASK
| 0|
R
|
–
|
Alarms ⁴ ⁵
| High pressure| E001
1| Low pressure| E002
2| Compressor thermal protection| E003
3| Fan thermal protection| E004
4| Frost| E005
5| Lack of flow| E006
6| DHW preparer low temperature| E007
7| Lack of lubrication| E008
8| High discharge temperature of Cp1| E009
9| Solar collector at high temperature| E010
11| Generic blocking| E012
12| Compressor 2 thermal protection| E013
13| Fan 2 thermal protection| E014
15| Pump thermal protection| E016
Register| Format| Bit| R/W| Range| Name|
Description| Note
---|---|---|---|---|---|---|---
951
|
BIT MASK
| 0|
R
|
–
|
Alarms ⁴ ⁵
| Faulty boiler| E017
1| High temperature| E018
2| High discharge temperature of Cp2| E019
3| Inverted pressure transducers| E020
6| Compressor 3 thermal protection| E023
7| Fan 3 thermal protection| E024
8| Outside temperature out of limits| E025
9| Pump 2 thermal protection| E026
10| Generic warning| E040
11| Incongruent temperatures| E041
12| Poor heat exchange DHW| E042
13| DHW accumulation tank in high tem-
perature
| E050
14| I/O module 1 disconnected| E101
15| I/O module 2 disconnected| E102
952
|
BIT MASK
| 0|
R
|
–
|
Alarms ⁴ ⁵
| Probe 1 error| E611
1| Probe 2 error| E621
2| Probe 3 error| E631
3| Probe 4 error| E641
4| Probe 5 error| E651
5| Probe 6 error| E661
6| Probe 7 error| E671
7| Probe 8 error| E681
8| Probe 9 error| E691
9| Probe 10 error| E701
10| Probe 11 error| E711
11| Module 1 probe 1 error| E612
12| Module 1 probe 2 error| E622
13| Module 1 probe 3 error| E632
14| Module 1 probe 4 error| E642
15| Module 1 probe 5 error| E652
953
|
BIT MASK
| 0|
R
|
–
|
Alarms ⁴ ⁵
| Module 1 probe 6 error| E662
1| Module 1 probe 7 error| E672
2| Module 1 probe 8 error| E682
3| Module 1 probe 9 error| E692
4| Module 1 probe 10 error| E702
5| Module 1 probe 11 error| E712
6| Module 2 probe 1 error| E613
7| Module 2 probe 2 error| E623
8| Module 2 probe 3 error| E633
9| Module 2 probe 4 error| E643
10| Module 2 probe 5 error| E653
11| Module 2 probe 6 error| E663
12| Module 2 probe 7 error| E673
13| Module 2 probe 8 error| E683
14| Module 2 probe 9 error| E693
15| Module 2 probe 10 error| E703
Register| Format| Bit| R/W| Range| Name|
Description| Note
---|---|---|---|---|---|---|---
954
|
BIT MASK
| 0|
R
|
–
|
Alarms ⁴ ⁵
| Module 2 probe 11 error| E713
1| Link inverter 1| E801
2| Link inverter 2| E802
3| Link inverter 3| E803
4| Hardware fault inverter 1| E851
5| Hardware fault inverter 2| E852
6| Hardware fault inverter 3| E853
7| Overcurrent inverter 1| E861
8| Overcurrent inverter 2| E862
9| Overcurrent inverter 3| E863
10| High temperature inverter 1| E871
11| High temperature inverter 2| E872
12| High temperature inverter 3| E873
13| Bad voltage inverter 1| E881
14| Bad voltage inverter 2| E882
15| Bad voltage inverter 3| E883
955
|
BIT MASK
| 0|
R
|
–
|
Alarms ⁴ ⁵
| Phase sequence inverter 1| E891
1| Phase sequence inverter 2| E892
2| Phase sequence inverter 3| E893
3| Model error inverter 1| E901
4| Model error inverter 2| E902
5| Model error inverter 3| E903
6| Overload error inverter 1| E911
7| Overload error inverter 2| E912
8| Overload error inverter 3| E913
9| Overcurrent PFC inverter 1| E921
10| Overcurrent PFC inverter 2| E922
11| Overcurrent PFC inverter 3| E923
12| Internal communication error inverter 1| E931
13| Internal communication error inverter 2| E932
14| Internal communication error inverter 3| E933
15| Fault PFC inverter 1| E941
956
|
BIT MASK
| 0|
R
|
–
|
Alarms ⁴ ⁵
| Fault PFC inverter 2| E942
1| Fault PFC inverter 3| E943
2| Probe error inverter 1| E951
3| Probe error inverter 2| E952
4| Probe error inverter 3| E953
5| Abnormal condition inverter 1| E961
6| Abnormal condition inverter 2| E962
7| Abnormal condition inverter 3| E963
8| Inverter 1 EEPROM error| E971
9| Inverter 2 EEPROM error| E972
10| Inverter 3 EEPROM error| E973
11| High discharge temperature of Cp3| E029
12| Anti-legionella performed correctly| E060
13| Anti-legionella failed or stopped| E061
957
|
BIT MASK
| 7|
R
|
–
|
Alarms ⁴ ⁵
| High pressure inverter 1| E981
8| Alta pressione inverter 2| E982
9| Alta pressione inverter 3| E983
10| DC inverter fan motor error 1| E811
11| DC inverter fan motor error 2| E812
12| DC inverter fan motor error 3| E813
13| IPM inverter module overcurrent 1| E821
14| IPM inverter module overcurrent 2| E822
15| IPM inverter module overcurrent 3| E823
Register| Format| Bit| R/W| Range| Name|
Description| Note
---|---|---|---|---|---|---|---
958
|
BIT MASK
| 0|
R
|
–
|
Alarms ⁴ ⁵
| PFC inverter module overheating 1| E831
1| PFC inverter module overheating 2| E832
2| PFC inverter module overheating 3| E833
3| DC inverter bus voltage failure 1| E841
4| DC inverter bus voltage failure 2| E842
5| DC inverter bus voltage failure 3| E843
- if enabled
- the cycle is activated only if the DHW (4-5-6) status is terminated by the machine.
- if the read value is equal to 32766 the probe is not configured, if 32767 the probe is faulty.
- reset alarms, write the value 0 with the command 6 on any of the registers of the alarms area.
- the alarms of circuit 2 are mapped in the same way with an offset of 20000 (e.g. 20950).
Restart control, write with command 6 the value -3856 (without sign 61680) to register 200, only with compressor stopped.
ADVANTIX SpA
Via S. Giuseppe Lavoratore 24,
37040 Arcole (VR) Italy
Tel. (+39).045.76.36.585
E-mail: info@advantixspa.it
www.maxa.it
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>