legrand 7862 Pass And Seymour 2Pole Manual Control Switch User Manual
- June 16, 2024
- Legrand
Table of Contents
legrand 7862 Pass And Seymour 2Pole Manual Control Switch
Catalog Number(s): 7860, 7862, 7862-R, 7863, 7863-R,
CAUTION: RISK OF ELECTRIC SHOCK. DISCONNECT POWER BEFORE INSTALLING.
NEVER WIRE ENERGIZED COMPONENTS.
NOTICE: For installation by a qualified electrician by national and local
electric codes and the following instructions.
WIRING INSTRUCTIONS
WIRING INSTRUCTIONS FOR HORSEPOWER RATED AC SWITCH IN NEMA JR ENCLOSURE, without overload protection.
- Pass & Seymour I Legrand catalog no·s:
- 7860: NEMA 3R enclosure suitable for use with P&S 7862 and 7863 switches.
- 7862-R: 60 AMP 2 POLE switch with NEMA 3R enclosure. Side wire box lug termination. Device accepts #14 to #4 AWG wire.
- 7863-R: 60 AMP 3 POLE switch with NEMA 3R enclosure. Side wire box lug termination. Device accepts #14 to #4 AWG wire.
CAUTION: RISK OF ELECTRIC SHOCK. DISCONNECT POWER BEFORE INSTALLING.
NEVER WIRE ENERGIZED COMPONENTS.
NOTICE: For installation by a qualified electrician by national and local
electric codes and the following instructions.
Select proper wire size and type for load and application. Refer to National Electrical Code”, article 310, for conductor information.
Wiring method
-
Mount box using (2) assembly holes provided on back of box and install conduit.
-
The equipment grounding conductor must be pigtailed and connected to the green box lug on BOTH the cover and the box. Tighten to same torque as terminal screws (See chart No. 1 for torque values).
-
Place the front cover lever in the “OFF” position. Place the toggle of the swrtch in the “OFF” position and orient switch so the toggle is pointed towards the bottom of the enclosure.
-
Strip wires to 5/8″. Do not tin conductors. Insert conductor fully into appropriately marked terminals (see diagram).
See chart No. 1 for torque values. -
Assemble switch on top of box mounting bracket. Fasten with screws and washers provided. Tighten to 12 #/in.
-
To install cover, position the switch toggle in the cover toggle-actuator, slide top of cover under overlap on top of box and swing down to close. Install screw to secure.
WIRING INSTRUCTIONS FOR HORSEPOWER RATED AC SWITCH, without overload protection.
- Pass & Seymour I Legrand catalog nos:
- 7862: 60 AMP 2 POLE switch Side wire box lug termination. Device accepts #14 to #4AWG wire.
- 7863: 60AMP 3 POLE switch. Side wire box lug termination. Device accepts #14 to #4AWG wire.
CAUTION: RISK OF ELECTRIC SHOCK. DISCONNECT POWER BEFORE INSTALLING.
NEVER WIRE ENERGIZED COMPONENTS.
NOTICE: For installation by a qualified electrician by national and local
electric codes and the following instructions.
Select proper wire size and type for load and application. Refer to National Electrical Code”, article 310, for conductor information.
Wiring method
- Strip wires to 5/8′. Do not tin conductors. Insert conductor fully into appropriately marked terminals (see diagram). See Chart No. 1 for torque values.
Applies to Pass & Seymour/ Legrand Enclosure Cat. No. 7860
Horsepower Rated AC Switch in NEMA 3R Enclosure, Without Overload Protection.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>