HID R10 iCLASS SE Express Reader Installation Guide

June 16, 2024
HID

HID R10 iCLASS SE Express Reader Installation Guide

Supplied parts

  • iCLASS SE Express R10 Reader (1)
  • Installation Guide (1)
  • 0.138-20 x 1.5″ self tapping screws (2) – for installing the reader directly to a wall
  • 0.138-32 x 0.375″ screws (3) – for mounting to an enclosure with Imperial (US) threads (2) and attaching the reader to the back plate (1)
  • M3.5 x 12mm screws (2) – for mounting to an enclosure with Metric (EU etc) threads
  • 0.138-32 x 0.375″ security screw (1) – alternative security screw for attaching the reader to the back plate

Recommended parts (not supplied)

  • Cable, 5-9 conductor (Wiegand or Clock-and-Data)
  • Certified LPS DC power supply
  • Security tool HID 04-0001-03 (for anti-tamper screw)
  • Drill with various bits for mounting hardware
  • Mounting hardware
  • Reader spacer (PN: 6132AKB) when mounting on or near metal or metal junction boxes – see How to Order Guide
  • IP65 Mounting gasket (PN: IP65GSKT-R10, 10 pcs per kit), recommended for outdoor installation

Specifications

INPUT VOLTAGE (VDC) 12 VDC
CURRENT
STANDBY AVG 1 46 mA
MAX AVG 2 60 mA
PEAK 3 250 mA
OPERATING TEMPERATURE -30° F to 150° F (-35° C to 66° C)
CABLE LENGTH 4 Communication Lines (Wiegand) 22 AWG: 500 ft

(152 m)
REGULATORY REF NUMBER| R10FKNN
FREQUENCY| BLE: 2.4 – 2.480 GHzHF: 13.56 MHz
FCC & IC IDS| FCC-ID: JQ6-iCLASSR10F IC-ID: 2236B-ICLASSR10F

  1. Standby AVG – RMS current draw without a card in the RF field.
  2. Maximum AVG – RMS current draw during continuous card reads. Not evaluated by UL.
  3. Peak – highest instantaneous current draw during RF communication.
  4. Wiegand Cable Lengths: 500 ft (152 m) 22 AWG @ STANDBY AVG 46 mA, MAX AVG 62.5 mA, PEAK 250 mA

Optional Features

Optical Tamper enabled by default – Once activated, when the mounting plate is removed, the optical tamper will
open the circuit between Tamper#1 and Tamper#2 reader control lines. Tamper#1 and Tamper#2 control lines are
interchangeable. Either of these lines can be connected with the reader ground line to reduce the number of cable cores required in the reader cable. Tamper#1 and Tamper#2 are rated 0-12VDC at 100mA.

Configuration Cards – The reader can be modified to meet the specific requirements of an installation. Configuration options include; audio visual, and CSN outputs. See the HID Reader Manager™ solution on www.hidglobal.com for further details.

This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice. © 2018 HID Global Corporation/ASSA ABLOY AB. All rights reserved. This document may not be reproduced, disseminated or republished in any form without the prior written permission of HID Global Corporation. HID GLOBAL, HID, the HID Brick logo, the Chain Design, HID Reader Manager, HID Mobile Access, and iCLASS SE are trademarks or registered trademarks of HID Global, ASSA ABLOY AB, or its affiliate(s) in the US and other countries and may not be used without permission. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.

Installation

Mount the backplate

ATTENTION
Observe precautions for handling ELECTROSTATIC SENSITIVE DEVICES

Mounting directly to the wall/mullion mount
Installation

Use supplied 0.138-20 x 1.5″ screws
Mounting to an enclosure (not supplied)
Installation
For Imperial (US):
Use supplied 0.138-32 x 0.375″ screws
For Metric (EU etc):
Use supplied M3.5 x 12mm screws

Wire the reader

Installation

PIGTAIL DESCRIPTION
Yellow Beeper Input
Orange LED Input (GRN)
Black Ground (GRN)
Red +VDC
Drain Unused
Violet *Tamper #1
Violet/White *Tamper #2
White Wiegand Data 1
Green Wiegand Data 0

Tamper Output. When activated or when the reader is unpowered, the circuit between Tamper#1 and Tamper#2 reader control lines will open.
Note: Wiring the reader incorrectly may permanently damage the reader.

Secure the reader to the backplate

Installation

  1. Align the top of the reader with the top of the backplate.
  2. Hook the top of the reader on the top of the backplate.
  3. Align the bottom of reader with the bottom of the backplate.
  4. Secure the reader to the backplate using one of the supplied screws:

Security/non-tamper screw: 0.138-32 x 0.375″ screw (supplied)
Non-security/standard screw: 0.138-32 x 0.375″ screw (supplied)

Power and test the reader

Turn on the power. The reader should beep and the light bar should flash.

Test the reader with a card. The buzzer should beep and the LED should flash.