HUBBLE LITHIUM AM-10 Wall Mount Battery 10kW User Manual

June 16, 2024
HUBBLE LITHIUM

HUBBLE LITHIUM AM-10 Wall Mount Battery 10kW

Product Information

Technical Specifications

  • Model: AM-10
  • Battery Type: LiFePO4 (LFP)
  • Nominal Voltage (V): 51.2V
  • Nominal Energy (KWH): 10KWH
  • Design Capacity: 200AH
  • Design Years: 15 Years

Product Size

  • Size: 673618193mm
  • Weight: 89kg

Technical Parameters

  • Cycle Life: Unlimited Cycles within the 10-year warranty. T’s & C’s Apply.
  • Operating Voltage Range: 40V-58.4V
  • Charging Voltage: DC 58.4V
  • Charge/Discharge Current(A): Maximum 200A
  • Internal Resistance: 30m

BMS Parameters

  • Self-Consumption: 2W
  • Rated Voltage: 51.2V
  • Balance Current: 30-65(MA)
  • Communication Method: CAN/RS485/RS232
  • Intelligent Current Limiter: 20A

Ambient Temperature

  • Operating Temperature: -10°C ~ 50°C
  • Storage Temperature: 10°C ~ 50°C
  • Humidity: 15%-75%

Product Description

  • SMART: Every module is equipped with an independent BMS system.
  • EASY INSTALLATION: Just plug & play.
  • SAFE: Safe lithium iron phosphate battery cell.
  • CERTIFIED: CE IEC UN38.3 MSDS.
  • MODULAR: Modular expansion.
  • LONGER LIFETIME: 6000 cycles, 15 years design life.

Interface & Size
The product interface includes the following components:

  1. POWER SWITCH
  2. DRY CONTACT
  3. RESET
  4. ADDRESS
  5. RS485
  6. CAN
  7. RS232
  8. BATTERY LINK
  9. BATTERY +
  10. BATTERY –

Parallel Connection of Batteries
To parallel connect batteries, follow these steps:

  1. Connect the positive pole and positive pole in parallel, and the negative pole and negative pole in parallel.
  2. Refer to Diagram 1 for a maximum of 4 batteries in parallel or a maximum inverter current not exceeding 250Amps.
  3. Refer to Diagram 2 for the preferred method of battery paralleling, which is to connect each parallel battery to a busbar. Ensure all cables are the same length from each battery, and ensure the cable thickness is all the same to ensure even distribution of current and load.

Installation Notes

  1. Press the mounting structure on the wall surface, use a marker to draw the installation positioning hole of the fixed pendant, remove it from the wall and drill the holes. (Refer to Wall Position Punching *6PCS)
  2. Fix the attached six expansion bolts in the opening of the mounting structure, and tighten the nuts on the bolts.
  3. Lift up the AM-10 battery carefully and hook it into position securely onto the wall mount bracket.

FAQ

  • Q: Where can I find the latest version of the manual?
    A: You can find the latest version of the manual at www.hubblelithium.co.za.

  • Q: Is it safe to modify the inverter and battery setup?
    A: Working with high-voltage systems is dangerous. Do not attempt to modify your inverter and battery setup unless you are certain you understand the risk. Speak to a qualified electrician if you are unsure.

You must read this manual before attempting the installation of your battery. Please take note of certain steps to ensure correct inverter compatibility.
Please visit www.hubblelithium.co.za for the latest version of this manual.

WARNING: Working with high voltage systems is dangerous. Do not attempt to modify your inverter and battery setup unless you are certain you understand the risk. Speak to a qualified electrician if you are unsure.

Product Description

HUBBLE-LITHIUM-AM-10-Wall-Mount-Battery-10kW- \(1\)

TECHNICAL SPECIFICATIONS

Model| AM-10
Battery Type| LiFePO4 (LFP)
Norminal Voltage (V)| 51.2V
Norminal Energy (KWH)| 10KWH
Design Capacity| 200AH
Design Years| 15 Years
PRODUCT SIZE
Size| 673618193mm
Weight| 89kg
TECHNICAL PARAMETER
Cycle Life| Unlimited Cycles within the 10 year warranty. T’s & C’s Apply.
Operating Voltage Range| 40V-58.4V
Charging Voltage| DC 58.4V
Charge/Discharge Current(A)| Maximum 200A
lntermal Resistance| ≥30mΩ
BMS PARAMETERS
Self-Consumption| ≥2W
Rated Voltage| 51.2V
Balance Current| 30-65(MA)
Communication Method| CAN/RS485/RS232
Intelligent Current Limiter| 20A
AMBIENT TEMPERATURE
Operating Temperature| -10C ~ 50C
Storage Temperature| 10C ~ 50C
Humidity| 15%-75%

Lithium battery systems are widely used in residential energy storage systems, such as solar energy storage systems and UPS. The power wall LiFeP04 battery pack adopts the international advanced lithium iron phosphate battery application technology and BMS control technology.

INTERFACE & SIZE

HUBBLE-LITHIUM-AM-10-Wall-Mount-Battery-10kW- \(2\)

  1. POWER SWITCH
  2. DRY CONTACT
  3. RESET
  4. ADDRESS
  5. RS485
  6. CAN
  7. RS232
  8. BATTERY LINK
  9. BATTERY +
  10. BATTERY –

PARALLEL CONNECTION OF BATTERIES

Connect the positive pole and positive pole in parallel, and the negative pole and negative pole in parallel, as shown in the figure below:

CORRECT METHODS OF BATTERY LINKING:

  • Note Diagram 1:
    Maximum of 4 batteries in parallel or maximum inverter current not exceeding 250Amps.

  • Note Diagram 2:
    The preferred method for battery paralleling is to connect each parallel battery to a busbar. Ensure all cables are the same length from each battery, and ensure the cable thickness are all the same to ensure even distribution of current and load.

SOLUTION DIAGRAM:HUBBLE-LITHIUM-AM-10-Wall-Mount-Battery-10kW-
\(5\)

INSTALLATION

NOTE:

  1. As shown in the figure below, press the mounting structure on the wall surface, use a marker to draw the installation positioning hole of the fixed pendant, remove from wall and drill the holes.HUBBLE-LITHIUM-AM-10-Wall-Mount-Battery-10kW- \(6\)
  2. As shown in the figure below, fix the attached six expansion bolts in the opening of the mounting structure, and tighten the nuts on the bolts.HUBBLE-LITHIUM-AM-10-Wall-Mount-Battery-10kW- \(7\)
  3. Lift up the AM-10 battery carefully and hook it into position securely onto the wall mount bracket.HUBBLE-LITHIUM-AM-10-Wall-Mount-Battery-10kW- \(8\)

LED WORKING STATUS INDICATION

HUBBLE-LITHIUM-AM-10-Wall-Mount-Battery-10kW- \(9\)

TABLE 2 CAPACITY INDICATION INSTRUCTIONS

STATE CHARGE DISCHARGE
Capacity Indicator Light L4 L3
Battery Power (%) 0 ~ 25% OFF
25 ~ 50% OFF OFF
50 ~ 75% OFF Flash 2
75 ~ 100% Flash 2 Lighting
Lighting Lighting

TABLE 3 LED FLASH INSTRUCTIONS

FLASH MODE ON OFF
FLASH 1 0.25 S 3.75 S
FLASH 2 0.5 S O.5 S
FLASH 3 0.5 S 1.5 S

Note: can enable or prohibit LED indicator light alarm through the upper machine, the factory default is enabled.

DIP SWITCH SETTINGS

Dialing code function area:

  1. Master/Slave Setting
  2. Slave Address Setting
  3. CAN Bus terminal resistance setting

From left to right, are 1#~8# dial switches, switch up is ON, and down is OFF. Dip switch 8# Dial ON means that the end resistor of the CAN port (for CAN inverters) is loaded; 8# Dial OFF means that the end resistor of the CAN port (for CAN inverters) is unloaded.
The inverter communication protocol selects the DIP mode, which is only valid for the master battery (the slave does not communicate with the inverter), set the target PACK as the master battery through the dial. Then select different inverter communication protocols through DIP 2#~6# ON/OFF. The corresponding definition between the specific DIP status and the selection of the inverter communication protocol is as follows:

NO. 1# 2# 3# 4# 5# 6# Mark
0 ON ON OFF OFF OFF OFF Master Battery \ Enable CAN BUS Port
1 OFF OFF OFF OFF OFF OFF Slave 2
2 OFF ON OFF OFF OFF OFF Slave 3
3 OFF OFF ON OFF OFF OFF Slave 4
4 OFF ON ON OFF OFF OFF Slave 5
5 OFF OFF OFF ON OFF OFF Slave 6
6 OFF ON OFF ON OFF OFF Slave 7
7 OFF OFF ON ON OFF OFF Slave 8
8 OFF ON ON ON OFF OFF Slave 9
9 OFF OFF OFF OFF ON OFF Slave 10
10 OFF ON OFF OFF ON OFF Slave 11
11 OFF OFF ON OFF ON OFF Slave 12
12 OFF ON ON OFF ON OFF Slave 13
13 OFF OFF OFF ON ON OFF Slave 14
14 OFF ON OFF ON ON OFF Slave 15

INTERFACE

Definition
DIAGRAM OF THE COMMUNICATION INTERFACE
RS232 communication port definition:

INTERFACE DEFINED DECLARATION
RJ12, RS232 pin layout PIN 1
PIN 2 NC (empty)
PIN 3 TX protection board sends data (computer receiving data foot)
PIN 4 RX protection board receives data (computer sends data)
PIN 5 Ground signal ground
PIN 6 NC (empty)

RS 485-1 / CAN COMMUNICATION INTERFACE DEFINITON:

INTERFACE DEFINED DECLARATION DEFINED DECLARATION
X1- Communication port definition RJ45

CAN pin layout

| PIN 1| CANL| RJ45, RS485

pin layout

| PIN 1| RS485-B1
PIN 2| CGND| PIN 2| RS485-A1
PIN 3| NC (empty)| PIN 3| RS485-GND
PIN 4| CANH| PIN 4| RS485-B1
PIN 5| CANL| PIN 5| RS485-A1
PIN 6| NC (empty)| PIN 6| RS485-GND
PIN 7| CGND| PIN 7| NC (empty)
PIN 8| CANH| PIN 8| NC (empty)

RS485-2 COMMUNICATION INTERFACE DEFINITION:

INTERFACE DEFINED DECLARATION DEFINED DECLARATION
Battery link ports A part RS-485-2

Interface

| PIN 1| RS485-B2| B part RS-485-2

Interface

| PIN 1| RS485-B2
PIN 2| RS485-A2| PIN 2| RS485-A2
PIN 3| RS485-GND| PIN 3| RS485-GND
PIN 4| NC (empty)| PIN 4| NC (empty)
PIN 5| NC (empty)| PIN 5| NC (empty)
PIN 6| RS485-GND| PIN 6| RS485-GND
PIN 7| RS485-A2| PIN 7| RS485-A2
PIN 8| RS485-B2| PIN 8| RS485-B2

DRY CONTACT DESCRIPTION
This BMS can provide one channel of dry contact signal, all dry contact signals are passive switches, regardless of polarity.

KRY 1 (2P terminal)

BMS STATE| DESCRIPTION| REMARK
Normal Operation| 1/2 pin is disconnected|
BMS Alarm| 1/2 pin is connected| Output when SOC alarm, under voltage and over voltage alarm and BMS protection state, such as under voltage protection, over-voltage protection or short circuit protection;

BUTTON OPERATION INSTRUCTIONS

  • When the BMS is in sleep state, press the button for more than 1 S, the protection board is activated.
  • When the BMS is operating, pressing the button for more than 3 seconds and less than
  • 6 seconds, then the BMS will enter the sleep state. When the BMS is in a working state, the protection board will reset when the button is pressed for more than 6S.

BUZZER ACTION DESCRIPTION

  • In the case of short-circuit protection, the buzzer beeps every 2 seconds. If a short circuit is detected 3 times in a row then he short-circuit protection is locked, the buzzer will no longer beep. Disconnect the battery and wait a few minutes to switch it back on. It might take up to 5 minutes to redetect a clear condition and then the BMS will re-enable.

FUNCTIONS

WARNING
Interfacing or plugging in any 3rd party or non-approved Hubble products or peripherals into the RS232 (serial) or RS485 (Battery Link) ports, can cause damage to the BMS and cause the BMS to malfunction. This may also result in damaging the internal cells. Plugging in non-approved Hubble products into these ports can immediately void your warranty.

DESCRIPTION OF SLEEP FUNCTION
To reduce the power consumption of the whole system, the system has a sleep function.
When the following conditions are met, the system will enter the sleep mode:

  1. The over-discharge protection of the BMS has not been released for 5 minutes.
  2. The duration of the standby state has reached 24 hours (no communication, no charge and discharge, no charger connected).

DESCRIPTION OF WAKE-UP FUNCTION
Please note that the battery enters sleep mode due to single or overall over- discharge, and cannot be activated or switched on by the serial port or the comm ports.
The BMS will activate and wake from sleep when the following is detected:

  1. If a charge current is applied to the battery from the inverter/ups.
  2. If the power button is pressed.
  3. Through communication from the RS232 or CANBus in certain circumstances.

CURRENT LIMITING FUNCTION
The BMS has an advanced current limiting function built in. The charge current limiter is designed to activate if the charging current has reached the maximum battery design charge limit. This ensures the battery does not disconnect from the circuit and the current limiter takes over and reduces the charge to 20Amps per battery.

The default start-up condition of the charging current limit is to start when the charging current is greater than 100A. After entering the current limit, the test will be performed again every 10 minutes. When the current is less than the current limit start value, the current limit function will be turned off. When the current is bigger than the current limit start value, then the current limiting mode with stay enabled.

COMMUNICATION DESCRIPTION

  1. The RS232 port is only for use with Hubble-specific peripherals or technicians or at a service centre to interface with the BMS. Attempting to use this port for anything else or 3rd party products can cause damage.
  2. The CAN Port is specifically to be used to any interfacing 3rd party equipment like inverters etc. This port is dedicated to inverters and other CAN bus ports for communication to get battery information.
  3. The RS485 communication port can be interfaced with 3rd party inverters that does not have a CAN port and is supported by Hubble.
  4. The Battery link ports are only for connecting more batteries of the same model to increase capacity and to enable multiple battery communications.

OPTIONAL CLOUDLINK DEVICE
The Hubble Cloudlink is an optional add-on to the Hubble X and AM range of products. As long as the device is connected to Wi-Fi it will cloud, all battery and inverter data to our cloud-server, enabling users to remotely monitor their power system.

Learn more about the Hubble Cloudlink here:https://www.hubblelithium.co.za/about-the-cloudlink
Access the latest Coudlink Setup Guide here:https://www.hubblelithium.co.za/cloudlink-setup.html

PARALLEL

FUNCTIONS

PARALLEL (CASCADE) FUNCTION OF BATTERY PACKS
When the battery packs are cascaded, the one with the communication address of 0001 is called the master battery pack, and the other ones with the communication address are called the slave battery packs. The slave battery pack can communicate with the master battery pack through the RS485 communication interface, and the master battery pack centrally packs and manages the data of each battery pack in this cascaded system. When the battery packs are cascaded, only the main battery pack can communicate with the host computer, upload the data, status and information of all battery packs in the cascaded system, integrate monitoring and management, and realize remote monitoring.

RS485 PARALLEL WIRING DIAGRAM
When performing multi-machine parallel communication operations, it is necessary to configure the DIP address of each PACK first. See Dip Switch Settings for more information.

WARNINGS

TO ENSURE PROPER USE OF THE BATTERY PLEASE READ THE MANUAL CAREFULLY BEFORE USING IT.

  • HANDLING

    • Do not expose the battery to fire.
    • Do not place the battery in a charger or equipment with the wrong terminals connected.
    • Avoid shorting circuiting the battery.
    • Avoid excessive physical shock or vibration.
    • Do not disassemble or deform the battery.
    • Do not immerse in water.
    • Do not mix the battery with other different makes, types, or models of batteries.
    • Keep out of the reach of children.
  • CHARGE AND DISCHARGE

    • The battery must be charged with an appropriate charger/inverter only.
    • Never use a modified or damaged charger.
  • STORAGE
    Store the battery in a cool, dry and well-ventilated area.

  • DISPOSAL
    Regulations vary for different countries. Dispose of by local regulations.

Battery Operation Instruction

  • CHARGING

    • Charging current: Do not surpass the specified charging current.
    • Charging voltage: Do not surpass the specified charging voltage.
    • Ensure correct DC polarity before connecting the terminals.
  • DISCHARGING CURRENT
    The discharging current must not surpass this maximum battery specification.

  • BATTERY STORAGE
    The battery should store in the product specification book stipulation temperature range. If has surpassed above for six months the long time storage, suggests you should carry on additional charge to the battery.

COMPLETING SETUP

CONGRATULATIONS!
Once all the above steps have been completed you can proceed to follow the start-up instructions given by your inverter manufacturer. If you have any difficulties with setting up your system, please contact our Technical Support Department via support@hubblelithium.co.za. Be sure to include the following information in your initial email so that we can provide you with timely assistance:

  1. Inverter make & model
  2. Model & number of connected batteries
  3. Are your batteries in Series or Parallel?
  4. A brief description of your system and any issues you may be having
  5. If possible; images of your power system
  6. Contact Details, if we should need to contact you

VIEW OUR WEBSITE FOR MORE INFORMATION:www.hubblelithium.co.za

Information published on this manual is correct as of the date published on this manual.
Please ensure you have the latest manual which can be obtained from our website at www.hubblelithium.co.za