HUBBLE LITHIUM AM-10 Wall Mount Battery 10kW User Manual
- June 16, 2024
- HUBBLE LITHIUM
Table of Contents
HUBBLE LITHIUM AM-10 Wall Mount Battery 10kW
Product Information
Technical Specifications
- Model: AM-10
- Battery Type: LiFePO4 (LFP)
- Nominal Voltage (V): 51.2V
- Nominal Energy (KWH): 10KWH
- Design Capacity: 200AH
- Design Years: 15 Years
Product Size
- Size: 673618193mm
- Weight: 89kg
Technical Parameters
- Cycle Life: Unlimited Cycles within the 10-year warranty. T’s & C’s Apply.
- Operating Voltage Range: 40V-58.4V
- Charging Voltage: DC 58.4V
- Charge/Discharge Current(A): Maximum 200A
- Internal Resistance: 30m
BMS Parameters
- Self-Consumption: 2W
- Rated Voltage: 51.2V
- Balance Current: 30-65(MA)
- Communication Method: CAN/RS485/RS232
- Intelligent Current Limiter: 20A
Ambient Temperature
- Operating Temperature: -10°C ~ 50°C
- Storage Temperature: 10°C ~ 50°C
- Humidity: 15%-75%
Product Description
- SMART: Every module is equipped with an independent BMS system.
- EASY INSTALLATION: Just plug & play.
- SAFE: Safe lithium iron phosphate battery cell.
- CERTIFIED: CE IEC UN38.3 MSDS.
- MODULAR: Modular expansion.
- LONGER LIFETIME: 6000 cycles, 15 years design life.
Interface & Size
The product interface includes the following components:
- POWER SWITCH
- DRY CONTACT
- RESET
- ADDRESS
- RS485
- CAN
- RS232
- BATTERY LINK
- BATTERY +
- BATTERY –
Parallel Connection of Batteries
To parallel connect batteries, follow these steps:
- Connect the positive pole and positive pole in parallel, and the negative pole and negative pole in parallel.
- Refer to Diagram 1 for a maximum of 4 batteries in parallel or a maximum inverter current not exceeding 250Amps.
- Refer to Diagram 2 for the preferred method of battery paralleling, which is to connect each parallel battery to a busbar. Ensure all cables are the same length from each battery, and ensure the cable thickness is all the same to ensure even distribution of current and load.
Installation Notes
- Press the mounting structure on the wall surface, use a marker to draw the installation positioning hole of the fixed pendant, remove it from the wall and drill the holes. (Refer to Wall Position Punching *6PCS)
- Fix the attached six expansion bolts in the opening of the mounting structure, and tighten the nuts on the bolts.
- Lift up the AM-10 battery carefully and hook it into position securely onto the wall mount bracket.
FAQ
-
Q: Where can I find the latest version of the manual?
A: You can find the latest version of the manual at www.hubblelithium.co.za. -
Q: Is it safe to modify the inverter and battery setup?
A: Working with high-voltage systems is dangerous. Do not attempt to modify your inverter and battery setup unless you are certain you understand the risk. Speak to a qualified electrician if you are unsure.
You must read this manual before attempting the installation of your battery.
Please take note of certain steps to ensure correct inverter compatibility.
Please visit www.hubblelithium.co.za for the
latest version of this manual.
WARNING: Working with high voltage systems is dangerous. Do not attempt to modify your inverter and battery setup unless you are certain you understand the risk. Speak to a qualified electrician if you are unsure.
Product Description
TECHNICAL SPECIFICATIONS
Model| AM-10
Battery Type| LiFePO4 (LFP)
Norminal Voltage (V)| 51.2V
Norminal Energy (KWH)| 10KWH
Design Capacity| 200AH
Design Years| 15 Years
PRODUCT SIZE
Size| 673618193mm
Weight| 89kg
TECHNICAL PARAMETER
Cycle Life| Unlimited Cycles within the 10 year warranty. T’s & C’s Apply.
Operating Voltage Range| 40V-58.4V
Charging Voltage| DC 58.4V
Charge/Discharge Current(A)| Maximum 200A
lntermal Resistance| ≥30mΩ
BMS PARAMETERS
Self-Consumption| ≥2W
Rated Voltage| 51.2V
Balance Current| 30-65(MA)
Communication Method| CAN/RS485/RS232
Intelligent Current Limiter| 20A
AMBIENT TEMPERATURE
Operating Temperature| -10C ~ 50C
Storage Temperature| 10C ~ 50C
Humidity| 15%-75%
Lithium battery systems are widely used in residential energy storage systems, such as solar energy storage systems and UPS. The power wall LiFeP04 battery pack adopts the international advanced lithium iron phosphate battery application technology and BMS control technology.
INTERFACE & SIZE
- POWER SWITCH
- DRY CONTACT
- RESET
- ADDRESS
- RS485
- CAN
- RS232
- BATTERY LINK
- BATTERY +
- BATTERY –
PARALLEL CONNECTION OF BATTERIES
Connect the positive pole and positive pole in parallel, and the negative pole and negative pole in parallel, as shown in the figure below:
CORRECT METHODS OF BATTERY LINKING:
-
Note Diagram 1:
Maximum of 4 batteries in parallel or maximum inverter current not exceeding 250Amps. -
Note Diagram 2:
The preferred method for battery paralleling is to connect each parallel battery to a busbar. Ensure all cables are the same length from each battery, and ensure the cable thickness are all the same to ensure even distribution of current and load.
SOLUTION DIAGRAM:
INSTALLATION
NOTE:
- As shown in the figure below, press the mounting structure on the wall surface, use a marker to draw the installation positioning hole of the fixed pendant, remove from wall and drill the holes.
- As shown in the figure below, fix the attached six expansion bolts in the opening of the mounting structure, and tighten the nuts on the bolts.
- Lift up the AM-10 battery carefully and hook it into position securely onto the wall mount bracket.
LED WORKING STATUS INDICATION
TABLE 2 CAPACITY INDICATION INSTRUCTIONS
STATE | CHARGE | DISCHARGE |
---|---|---|
Capacity Indicator Light | L4 | L3 |
Battery Power (%) | 0 ~ 25% | OFF |
25 ~ 50% | OFF | OFF |
50 ~ 75% | OFF | Flash 2 |
75 ~ 100% | Flash 2 | Lighting |
Lighting | Lighting |
TABLE 3 LED FLASH INSTRUCTIONS
FLASH MODE | ON | OFF |
---|---|---|
FLASH 1 | 0.25 S | 3.75 S |
FLASH 2 | 0.5 S | O.5 S |
FLASH 3 | 0.5 S | 1.5 S |
Note: can enable or prohibit LED indicator light alarm through the upper machine, the factory default is enabled.
DIP SWITCH SETTINGS
Dialing code function area:
- Master/Slave Setting
- Slave Address Setting
- CAN Bus terminal resistance setting
From left to right, are 1#~8# dial switches, switch up is ON, and down is OFF.
Dip switch 8# Dial ON means that the end resistor of the CAN port (for CAN
inverters) is loaded; 8# Dial OFF means that the end resistor of the CAN port
(for CAN inverters) is unloaded.
The inverter communication protocol selects the DIP mode, which is only valid
for the master battery (the slave does not communicate with the inverter), set
the target PACK as the master battery through the dial. Then select different
inverter communication protocols through DIP 2#~6# ON/OFF. The corresponding
definition between the specific DIP status and the selection of the inverter
communication protocol is as follows:
NO. | 1# | 2# | 3# | 4# | 5# | 6# | Mark |
---|---|---|---|---|---|---|---|
0 | ON | ON | OFF | OFF | OFF | OFF | Master Battery \ Enable CAN BUS Port |
1 | OFF | OFF | OFF | OFF | OFF | OFF | Slave 2 |
2 | OFF | ON | OFF | OFF | OFF | OFF | Slave 3 |
3 | OFF | OFF | ON | OFF | OFF | OFF | Slave 4 |
4 | OFF | ON | ON | OFF | OFF | OFF | Slave 5 |
5 | OFF | OFF | OFF | ON | OFF | OFF | Slave 6 |
6 | OFF | ON | OFF | ON | OFF | OFF | Slave 7 |
7 | OFF | OFF | ON | ON | OFF | OFF | Slave 8 |
8 | OFF | ON | ON | ON | OFF | OFF | Slave 9 |
9 | OFF | OFF | OFF | OFF | ON | OFF | Slave 10 |
10 | OFF | ON | OFF | OFF | ON | OFF | Slave 11 |
11 | OFF | OFF | ON | OFF | ON | OFF | Slave 12 |
12 | OFF | ON | ON | OFF | ON | OFF | Slave 13 |
13 | OFF | OFF | OFF | ON | ON | OFF | Slave 14 |
14 | OFF | ON | OFF | ON | ON | OFF | Slave 15 |
INTERFACE
Definition
DIAGRAM OF THE COMMUNICATION INTERFACE
RS232 communication port definition:
INTERFACE | DEFINED DECLARATION |
---|---|
RJ12, RS232 pin layout | PIN 1 |
PIN 2 | NC (empty) |
PIN 3 | TX protection board sends data (computer receiving data foot) |
PIN 4 | RX protection board receives data (computer sends data) |
PIN 5 | Ground signal ground |
PIN 6 | NC (empty) |
RS 485-1 / CAN COMMUNICATION INTERFACE DEFINITON:
INTERFACE | DEFINED DECLARATION | DEFINED DECLARATION |
---|---|---|
X1- Communication port definition | RJ45 |
CAN pin layout
| PIN 1| CANL| RJ45, RS485
pin layout
| PIN 1| RS485-B1
PIN 2| CGND| PIN 2| RS485-A1
PIN 3| NC (empty)| PIN 3| RS485-GND
PIN 4| CANH| PIN 4| RS485-B1
PIN 5| CANL| PIN 5| RS485-A1
PIN 6| NC (empty)| PIN 6| RS485-GND
PIN 7| CGND| PIN 7| NC (empty)
PIN 8| CANH| PIN 8| NC (empty)
RS485-2 COMMUNICATION INTERFACE DEFINITION:
INTERFACE | DEFINED DECLARATION | DEFINED DECLARATION |
---|---|---|
Battery link ports | A part RS-485-2 |
Interface
| PIN 1| RS485-B2| B part RS-485-2
Interface
| PIN 1| RS485-B2
PIN 2| RS485-A2| PIN 2| RS485-A2
PIN 3| RS485-GND| PIN 3| RS485-GND
PIN 4| NC (empty)| PIN 4| NC (empty)
PIN 5| NC (empty)| PIN 5| NC (empty)
PIN 6| RS485-GND| PIN 6| RS485-GND
PIN 7| RS485-A2| PIN 7| RS485-A2
PIN 8| RS485-B2| PIN 8| RS485-B2
DRY CONTACT DESCRIPTION
This BMS can provide one channel of dry contact signal, all dry contact
signals are passive switches, regardless of polarity.
KRY 1 (2P terminal)
BMS STATE| DESCRIPTION| REMARK
Normal Operation| 1/2 pin is disconnected|
BMS Alarm| 1/2 pin is connected| Output when SOC alarm, under voltage and over
voltage alarm and BMS protection state, such as under voltage protection,
over-voltage protection or short circuit protection;
BUTTON OPERATION INSTRUCTIONS
- When the BMS is in sleep state, press the button for more than 1 S, the protection board is activated.
- When the BMS is operating, pressing the button for more than 3 seconds and less than
- 6 seconds, then the BMS will enter the sleep state. When the BMS is in a working state, the protection board will reset when the button is pressed for more than 6S.
BUZZER ACTION DESCRIPTION
- In the case of short-circuit protection, the buzzer beeps every 2 seconds. If a short circuit is detected 3 times in a row then he short-circuit protection is locked, the buzzer will no longer beep. Disconnect the battery and wait a few minutes to switch it back on. It might take up to 5 minutes to redetect a clear condition and then the BMS will re-enable.
FUNCTIONS
WARNING
Interfacing or plugging in any 3rd party or non-approved Hubble products or
peripherals into the RS232 (serial) or RS485 (Battery Link) ports, can cause
damage to the BMS and cause the BMS to malfunction. This may also result in
damaging the internal cells. Plugging in non-approved Hubble products into
these ports can immediately void your warranty.
DESCRIPTION OF SLEEP FUNCTION
To reduce the power consumption of the whole system, the system has a sleep
function.
When the following conditions are met, the system will enter the sleep mode:
- The over-discharge protection of the BMS has not been released for 5 minutes.
- The duration of the standby state has reached 24 hours (no communication, no charge and discharge, no charger connected).
DESCRIPTION OF WAKE-UP FUNCTION
Please note that the battery enters sleep mode due to single or overall over-
discharge, and cannot be activated or switched on by the serial port or the
comm ports.
The BMS will activate and wake from sleep when the following is detected:
- If a charge current is applied to the battery from the inverter/ups.
- If the power button is pressed.
- Through communication from the RS232 or CANBus in certain circumstances.
CURRENT LIMITING FUNCTION
The BMS has an advanced current limiting function built in. The charge current
limiter is designed to activate if the charging current has reached the
maximum battery design charge limit. This ensures the battery does not
disconnect from the circuit and the current limiter takes over and reduces the
charge to 20Amps per battery.
The default start-up condition of the charging current limit is to start when the charging current is greater than 100A. After entering the current limit, the test will be performed again every 10 minutes. When the current is less than the current limit start value, the current limit function will be turned off. When the current is bigger than the current limit start value, then the current limiting mode with stay enabled.
COMMUNICATION DESCRIPTION
- The RS232 port is only for use with Hubble-specific peripherals or technicians or at a service centre to interface with the BMS. Attempting to use this port for anything else or 3rd party products can cause damage.
- The CAN Port is specifically to be used to any interfacing 3rd party equipment like inverters etc. This port is dedicated to inverters and other CAN bus ports for communication to get battery information.
- The RS485 communication port can be interfaced with 3rd party inverters that does not have a CAN port and is supported by Hubble.
- The Battery link ports are only for connecting more batteries of the same model to increase capacity and to enable multiple battery communications.
OPTIONAL CLOUDLINK DEVICE
The Hubble Cloudlink is an optional add-on to the Hubble X and AM range of
products. As long as the device is connected to Wi-Fi it will cloud, all
battery and inverter data to our cloud-server, enabling users to remotely
monitor their power system.
Learn more about the Hubble Cloudlink
here:https://www.hubblelithium.co.za/about-the-cloudlink
Access the latest Coudlink Setup Guide
here:https://www.hubblelithium.co.za/cloudlink-setup.html
PARALLEL
FUNCTIONS
PARALLEL (CASCADE) FUNCTION OF BATTERY PACKS
When the battery packs are cascaded, the one with the communication address of
0001 is called the master battery pack, and the other ones with the
communication address are called the slave battery packs. The slave battery
pack can communicate with the master battery pack through the RS485
communication interface, and the master battery pack centrally packs and
manages the data of each battery pack in this cascaded system. When the
battery packs are cascaded, only the main battery pack can communicate with
the host computer, upload the data, status and information of all battery
packs in the cascaded system, integrate monitoring and management, and realize
remote monitoring.
RS485 PARALLEL WIRING DIAGRAM
When performing multi-machine parallel communication operations, it is
necessary to configure the DIP address of each PACK first. See Dip Switch
Settings for more information.
WARNINGS
TO ENSURE PROPER USE OF THE BATTERY PLEASE READ THE MANUAL CAREFULLY BEFORE USING IT.
-
HANDLING
- Do not expose the battery to fire.
- Do not place the battery in a charger or equipment with the wrong terminals connected.
- Avoid shorting circuiting the battery.
- Avoid excessive physical shock or vibration.
- Do not disassemble or deform the battery.
- Do not immerse in water.
- Do not mix the battery with other different makes, types, or models of batteries.
- Keep out of the reach of children.
-
CHARGE AND DISCHARGE
- The battery must be charged with an appropriate charger/inverter only.
- Never use a modified or damaged charger.
-
STORAGE
Store the battery in a cool, dry and well-ventilated area. -
DISPOSAL
Regulations vary for different countries. Dispose of by local regulations.
Battery Operation Instruction
-
CHARGING
- Charging current: Do not surpass the specified charging current.
- Charging voltage: Do not surpass the specified charging voltage.
- Ensure correct DC polarity before connecting the terminals.
-
DISCHARGING CURRENT
The discharging current must not surpass this maximum battery specification. -
BATTERY STORAGE
The battery should store in the product specification book stipulation temperature range. If has surpassed above for six months the long time storage, suggests you should carry on additional charge to the battery.
COMPLETING SETUP
CONGRATULATIONS!
Once all the above steps have been completed you can proceed to follow the
start-up instructions given by your inverter manufacturer. If you have any
difficulties with setting up your system, please contact our Technical Support
Department via
support@hubblelithium.co.za. Be sure to
include the following information in your initial email so that we can provide
you with timely assistance:
- Inverter make & model
- Model & number of connected batteries
- Are your batteries in Series or Parallel?
- A brief description of your system and any issues you may be having
- If possible; images of your power system
- Contact Details, if we should need to contact you
VIEW OUR WEBSITE FOR MORE INFORMATION:www.hubblelithium.co.za
Information published on this manual is correct as of the date published on
this manual.
Please ensure you have the latest manual which can be obtained from our
website at www.hubblelithium.co.za
References