DMTECH D9000 Series Conventional Detectors Instruction Manual

June 4, 2024
DMTECH

D9000 Series Conventional Detectors
Instruction Manual

Type Characteristics Sensitivity / Class
D9000 SR Optical smoke fire detector EN 54-7
D9000 T/A1R Rate of rising heat detector AIR, EN 54-5
D9000 T/A1S Fixed temperature heat detector A1S, EN 54-5
D9000 MSR Combined optical smoke and heat detector AIR, EN 54-5 / EN 54-7

Caution : Read this manual before attempting to install the detector.

TECHNICAL DATA

– Supply voltage 10-30 V DC
– Current consumption in Standby mode ≤ 130 µА
– Current consumption in Alarm condition 20 mА/ 24V DC
– Time to enter standby mode after reset          up to 35s
 – Reset time 2s
– Degree of protection IP 43
– Type of the connecting line to the base  0,5÷1,5 mm2 / two-wire
 – Output in Alarm condition (term. 3) limited to 2 kΩ, negative
– Operating temperature range minus 10ºС ÷ plus 50ºС
– Humidity (93 ± 3)% at 40ºС
– Dimensions with base Ø 100mm  h ≤ 52mm
– Weight ≤ 100g

INSTALLATION

  • Choose the place (according to the plans of the project) for the installation of the detector;

  • Mount the base with appropriate fixings;

  • Connect the electrical cables according to the attached diagram ( Figure 1);
    DMTECH D9000 Series Conventional Detectors - Figure 1

  • Place the detector base and rotate clockwise till matching markers;

  • If you want to lock the detector:
    • Pre removes the key from the base ( Figure 2).
    • Break the plastic at the specified location on the bottom of the sensor ( Figure 3 ).

DMTECH D9000 Series Conventional Detectors - Figure 2

  • Place the detector on the base and rotate it.
    – If the detector is locked to the base, to unlock it, insert first the key to the specified location (Fig. 4) and rotate the detector counterclockwise;
    – Test the detector to check the correct operation of the LED indication;
    – During normal operation, the LEDs blink every 16 seconds.

TESTING AND SERVICE SCHEDULE

  • Testing
    – Apply power;
    – Wait about a minute or until the detector begins to blink;
    – Operate the detector test spray and/or temperature course. The two red LEDs must illuminate permanently.

  • Service schedule
    – Visual inspection for mechanical damage and pollution
    – once a year;
    – Verification of performance
    – once a year;
    – Prophylactic cleaning – depends on the environment in which it is located.

Optical detectors D9000 SR/MSR are software tested and when the detector is contaminated, it is signaled by flashing LEDs for 2 seconds to 2 seconds.
D9000 Series detectors are compatible with all conventional power panels, that have met the requirements of standards EN54.
The detectors are available with three types of bases:

  • B 9000 – Standard base;
  • B 9000D – Standard base with a mounted diode for fault detection – removed detector;
  • B 9000R – Standard base with relay output 12V for security panels.

Warranty obligations

The warranty period is 36 months from the date of sale, provided that:

  • the conditions of storage and transport have been followed;
  • release is performed by authorized persons;
  • the requirements for operation stated in this instruction have been abode;
  • defects are not caused by natural phenomena and accidents of the plug socket.