Product Information
Technical Specifications
- Product Name: P6SD Series Single Packaged Air Conditioning
- SEER Rating: 13
- Refrigerant: R-410A
- Capacity: 3, 4, 5 Ton Units
- Installation: Roof or Slab
- Unit Design: Convertible
- ETL and ETLc Listed
Dimensions
- Height (with base rails): 37.7 inches
- Width: 30.0 inches
- Depth: 27.2 inches
- Weight: 405 lbs (3 Ton), 415 lbs (4 Ton), 480 lbs (5 Ton)
Specifications
Model Number| Performance Capacity – Cooling BTUH| Efficiency – SEER| EER
(Btuh/watt)| Electrical Rating – 60Hz Phase| Operating Voltage Range|
Compressor Data Volts| Rated Load Amps| Lock Rotor Amps| Indoor Blower Type /
No. of Speeds| Motor – HP / RPM| Motor – Amps| Outdoor Fan Motor – HP / RPM|
Motor – Amps| Fan Diameter / CFM| Refrigerant Charge – Oz.| Shipping Weight
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
X36K| 34,200| 13.3| 11.2| 1| 187 – 253| 208 / 230| 18.6| 79| DD / 3 1/4 –
1075| 1.3| 1/4 – 1100| 1.2| 20/3600| 110| 415
X48K| 46,000| 13.0| 11.5| 1| 187 – 253| 208 / 230| 24.3| 117| DD / 3 1/2 –
1080| 3.1| 1/4 – 1100| 1.2| 20/3800| 168| 425
X60K| 58,000| 13.3| 11.0| 1| 187 – 253| 208 / 230| 29.3| 134| DD / 3 1/4 –
1100| 3.1| 1/4 – 1100| 1.2| 20/3800| 192| 490
Product Usage Instructions
Installation
The P6SD Series single-packaged air conditioners can be installed either on a
roof or on a slab. The convertible unit design allows for easy installation in
all applications.
Electrical Connection
The electrical code for the P6SD Series is “K”, which corresponds to
208/230-60-1 voltage. Make sure to connect the unit to a power source within
this voltage range.
Duct Openings
The unit has both downflow supply duct and downflow return duct openings. The
dimensions of these openings are as follows:
- Downflow Supply Duct Opening: B – 13 3/10 inches, CG – 16 inches, A – 29.5 inches
- Downflow Return Duct Opening: C – 5.0 inches, A – 14.7 inches
Heater Kit
If you require heating in addition to cooling, you can purchase a heater kit
separately. The heater kit model and part numbers are provided in the manual.
Make sure to select the appropriate heater kit based on your desired heating
capacity.
FAQ
-
Q: Can I install the P6SD Series unit indoors?
A: No, the P6SD Series units are designed for outdoor installation on a roof or slab. -
Q: What is the SEER rating of the P6SD Series?
A: The P6SD Series has a SEER rating of 13. -
Q: Can I use a different refrigerant with the P6SD Series?
A: No, the P6SD Series is designed to be used with R-410A refrigerant only. -
Q: How do I select the appropriate heater kit for my P6SD unit?
A: Refer to the “Heater Application Matrix” in the manual to determine the nominal heating capacity required for your unit. Then, select the corresponding heater kit model and part number.
The P6 Series single packaged air conditioners are high efficiency self- contained cooling units that can be installed on a roof or on a slab. The convertible unit design makes installations simple in all applications. Units are ETL and ETLc listed.
WARRANTY
- 1-Year Limited Parts Warranty
- 1-Year Limited Labor Warranty
- 5 Year Limited Compressor Warranty
FEATURES and BENEFITS
- State-of-the-art Copeland Scroll compressor is standard equipment.
- R-410A Refrigerant is Environmentally friendly.
- Proven, Industry Standard Components Easier service and availability.
- TXV Externally equalized. Provides precise refrigerant control under varying load conditions.
- High and Low Pressure Switches Added compressor protection.
- Liquid Line Filter/Drier Ensures clean and dry refrigeration system.
- Externally Accessible Service Ports Quick access to the refrigerant system without disrupting operation.
- Compact Footprint/Low Profile Easy to handle and transport.
- Convertible Air Delivery Horizontal or downflow to accommodate rooftop or horizontal application.
- Heavy-Gauge, Full Perimeter Base Rails Facilitate forklift handling and curb mounting.
- Galvanized Steel Cabinet Polyurethane finish provides 950 hours of salt spray protection.
- Wire Guard Coated with Earth-Friendly Epoxy and Mesh Hail Guard Will never rust and protects the coil from being damaged by balls, lawnmowers, hail etc.
- Corrosion-Resistant Drain Pan Quickly drains away evaporator condensate.
- Quiet Operation and Vibration 20″ fan blade combined with custom venturi condenser fan.
- Access to Controls and Major Components Easy in and out service.
- Service Access Panels Allow easy access to all major components and the compressor. Designed to make servicing easier for the Contractor.
- Easy to Install Electric heat strip provides up to 20 KW of heat output.
- Accessories Roof curbs, economizers, fresh air dampers, and more.
MODEL IDENTIFICATION CODE
DIMENSIONS
Model Number P6SD| Unit Weight| Center of Gravity| Height (in inches)
C
|
---|---|---|---|---
A| B
with base rails|
X36| 405| 29.5| 26.0| 37.7|
X48| 415| 29.5| 26.5| 37.7|
X60| 480| 30.0| 27.5| 41.7|
SPECIFICATIONS
Model Number | P6SD |
---|---|
X36K | X48K |
Performance **** Capacity -Cooling BTUH Efficiency – SEER
EER (Btuh/watt)
| ****
34,200
13.3
11.2
| ****
46,000
13.0
11.5
| ****
58,000
13.3
11.0
Electrical Rating – 60 Hz
Phase
Operating Voltage Range
| ****
1
187 – 253
| ****
1
187 – 253
| ****
1
187 – 253
Compressor Data| | |
Volts| 208 / 230| 208 / 230| 208 / 230
Rated Load Amps| 18.6| 24.3| 29.3
Lock Rotor Amps| 79| 117| 134
Indoor Blower| | |
Type / No. of Speeds| DD / 3| DD / 3| Fixed Torque
Motor – HP / RPM| 1/4 – 1075| 1/2 – 1080| 3/4
Motor – Amps| 1.3| 3.1| 6.0
Outdoor Fan| | |
Motor – HP / RPM| 1/4 – 1100| 1/4 – 1100| 1/4 – 1100
Motor – Amps| 1.2| 1.2| 1.2
Fan Diameter / CFM| 20/3600| 20/3800| 20/3800
Refrigerant Charge – Oz.| 110| 168| 192
Shipping Weight| 415| 425| 490
BLOWER PERFORMANCE
Model Number | External Static Pressure Drop – inches water column |
---|---|
P6SD- | 0.1 |
0.7 | 0.8 |
X36
| High| 1610| 1562| 1504| 1442| 1365| 1295| 1214| 1109
Medium| 1367| 1320| 1271| 1205| 1138| 1065| 968| 845
Low| 1153| 1102| 1043| 990| 912| 831| 731| 618
X48
| High| 2361| 2278| 2218| 2141| 2066| 1976| 1870| 1758
Medium| 2026| 1982| 1935| 1889| 1822| 1744| 1660| 1554
Low| 1584| 1568| 1532| 1489| 1445| 1387| 1322| 1236
X60 *****
| Tap T1| 1515| 1450| 1380| 1350| 1280| 1250| 1200| 1160
Tap T2| 1580| 1520| 1460| 1400| 1300| 1280| 1260| 1230
Tap T3| 1740| 1690| 1650| 1600| 1360| 1500| 1460| 1390
Tap T4| 1960| 1910| 1840| 1820| 1540| 1740| 1700| 1600
Tap T5| 2090| 2050| 2010| 1975| 1780| 1900| 1850| 1790
- Denotes factory set cooling speed
- Denotes factory set electric heating speed
- NOTE: Airflow performance is with a dry coil
MODEL IDENTIFICATION CODE
HEATER APPLICATION MATRIX
TONNAGE & PHASE| UNIT| NOMINAL
KW
| HEATER KIT MODEL| HEATER KIT PART NUMBER| BREAKERS
REQUIRED
---|---|---|---|---|---
3 Ton, Single Phase
| ****
P6SD
| 5| H3HK005H-01B| 917166B| None
8| H3HK008H-01B| 917167B| None
10| H3HK010H-01B| 917168B| None
15| H3HK015H-01B| 917169B| 2
15| H3HK015H-21B| 917172B| None
4 Ton, Single Phase
| ****
P6SD
| 5| H3HK005H-01B| 917166B| None
8| H3HK008H-01B| 917167B| None
10| H3HK010H-01B| 917168B| None
15| H3HK015H-01B| 917169B| 2
15| H3HK015H-21B| 917172B| None
20| H3HK020H-01B| 917170B| 2
20| H3HK020H-21B| 917173B| None
5 Ton, Single Phase
| ****
P6SD
| 5| H3HK005H-01B| 917166B| None
8| H3HK008H-01B| 917167B| None
10| H3HK010H-01B| 917168B| 2
15| H3HK015H-01B| 917169B| 2
15| H3HK015H-21B| 917172B| None
20| H3HK020H-01B| 917170B| 3
20| H3HK020H-21B| 917173B| 1
ELECTRICAL DATA
P6SD SERIES – 208/230V – SINGLE PHASE MODELS
MODEL NUMBER P6SD-
| ****
HEATER INSTALLED NOMINAL KW
| SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION
MCA
| ****
REC, WIRE GAGE (90° C CU)
| ****
MOP
| CIRCUIT A
(C ompressor & F an )
| CIRCUIT B
(B lower & H eater )
MCA
| REC, WIRE GAGE (90° C CU)| ****
MOP
| ****
MCA
| REC, WIRE GAGE (90° C CU)| ****
MOP
X36K
| 0| 25.8| 10| 40| –| –| –| –| –| –
5| 26.5| 10| 40| –| –| –| –| –| –
8| 41.2| 8| 45| –| –| –| –| –| –
10| 51.6| 8| 60| –| –| –| –| –| –
15| 76.6| 4| 80| 50.0| 8| 60| 26.6| 10| 30
X48K
| 0| 32.9| 8| 50| –| –| –| –| –| –
5| 32.9| 8| 50| –| –| –| –| –| –
8| 41.2| 8| 50| –| –| –| –| –| –
10| 51.6| 8| 60| –| –| –| –| –| –
15| 76.6| 4| 80| 51.6| 8| 50| 26.6| 10| 30
20| 101.6| 3| 110| 50| 8| 50| 51.6| 8| 60
MODEL NUMBER P6SD-
| ****
HEATER INSTALLED NOMINAL KW
| SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION
MCA
| ****
REC, WIRE GAGE (90° C CU)
| ****
MOP
| CIRCUIT A
(C ompressor , B lower , & F an )
| CIRCUIT B
(H eater o nly )
| CIRCUIT C
(H eater o nly )
MCA
| REC, WIRE GAGE (90° C CU)| ****
MOP
| ****
MCA
| REC, WIRE GAGE (90° C CU)| ****
MOP
| ****
MCA
| REC, WIRE GAGE (90° C CU)| ****
MOP
X60K
| 0| 43.8| 8| 70| –| –| –| –| –| –| –| –| –
5| 43.8| 8| 70| –| –| –| –| –| –| –| –| –
8| 43.8| 8| 70| –| –| –| –| –| –| –| –| –
10| 51.5| 8| 70| 43.8| 8| 70| 50| 8| 60| –| –| –
15| 76.5| 4| 80| 51.5| 8| 70| 25| 10| 30| –| –| –
20| 101.5| 3| 110| 43.8| 8| 70| 50| 8| 60| 50| 8| 60
NOTE:
P6SD 3 & 4 ton models have PSC motors. Since the power wires run through the
heater plug, keep the blower and heater on different circuits when adding a
heater kit.
ACCESSORIES
Description | Part Number |
---|---|
Roof Curb (8”) | 547830 |
Roof Curb (14”) | 547831 |
Roof Curb (18”) | 547850 |
Roof Curb (24”) | 547851 |
Supply/return transition, 16” | 547834 |
Supply/return transition, 18” | 547835 |
Concentric diffuser, flush, 16” | 547836 |
Concentric diffuser, flush, 18” | 547837 |
Concentric diffuser, step down 16” | 547838 |
Concentric diffuser, step down 18” | 547839 |
Manual Fresh Air Damper | 547832 |
Motorized Fresh Air Damper | 547840 |
Economizer, downflow w/filter (does not require filter kit) modulating | 558870 |
Economizer, horizontal modulating | 547841 |
Power Exhaust, downflow economizer (special order) | 547842 |
Power Exhaust horizontal economizer (special order) | 547843 |
HOOD TYPE HAIL GUARD 34” X 76” P6SD-X36, P6SD-X48 | 547846 |
HOOD TYPE HAIL GUARD 38” X 76” P6SD -X60 | 547847 |
DUCT SMOKE DETECTOR PHOTO ELEC | 558863 |
MULTI SIGNAL CONTROL | 547893 |
SAMPLING TUBE DST5, 2-4′ | 558864 |
SAMPLING TUBE DST5, 4-8′ | 558865 |
Filter Rack, All Downflow Applications (not required with economizer) | 547885 |
Filter Kit (not required with economizer) P6SD-X36, P6SD-X48 | 547888 |
Filter Kit (not required with economizer ) P6SD-X60 | 547889 |
Universal Hard Start Kit | 912933 |
Low Ambient Kit | 918837 |
Skirt Trim Kit | 919729 |
Extreme High Wind Kit – Roof Curb Mount | 903696 |
Extreme High Wind Kit – Ground Mount | 903695 |
Heater Kit – 4-Pole single circuit adaptor | 913350 |
Heater Kit – 6-Pole single circuit adaptor | 913556 |
Heater Kit – Circuit breaker single phase (2-pole) | 913554 |
Freezestat Kit | 917108 |
Duct Adopter, 14″ Round (2 each) | 913812A |
Control, CO2 sensor, wall mount | 547848 |
COOLING EXPANDED RATINGS
P6SD-X36
O.D.T | 85°F | 95°F | 105°F | 115°F |
---|---|---|---|---|
CFM | E.D.B. | E.W.B. | T.C. | S.C. |
T.C. | S.C. | K.W. | T.C. | S.C. |
S.C. | K.W. |
900
| 80| 62| 32.7| 26.3| 2.67| 31.2| 26.4| 2.95| 29.6| 27.2| 3.27| 27.9| 26.8|
3.64
80| 67| 35.6| 21.3| 2.70| 33.9| 20.7| 2.98| 32.1| 20.2| 3.30| 30.1| 19.5| 3.67
80| 72| 38.9| 16.3| 2.75| 37.1| 15.8| 3.03| 35.2| 15.2| 3.34| 33.1| 14.7| 3.71
75| 63| 33.1| 21.0| 2.68| 31.5| 21.1| 2.95| 29.8| 21.0| 3.28| 28.0| 20.6| 3.64
1000
| 80| 62| 33.5| 28.0| 2.68| 31.9| 29.0| 2.96| 30.3| 29.0| 3.28| 28.7| 28.7|
3.65
80| 67| 36.2| 22.5| 2.71| 34.4| 22.0| 2.99| 32.6| 21.4| 3.31| 30.7| 20.9| 3.67
80| 72| 39.6| 17.1| 2.76| 37.8| 16.6| 3.04| 35.8| 16.0| 3.35| 33.7| 15.5| 3.72
75| 63| 33.7| 23.1| 2.68| 32.0| 22.9| 2.96| 30.4| 22.8| 3.28| 28.6| 22.2| 3.65
1100
| 80| 62| 34.7| 31.2| 2.69| 33.1| 31.3| 2.97| 31.6| 31.6| 3.30| 29.9| 29.9|
3.66
80| 67| 37.3| 24.5| 2.73| 35.5| 23.9| 3.00| 33.6| 23.2| 3.32| 31.6| 22.6| 3.69
80| 72| 40.7| 18.2| 2.77| 38.8| 17.7| 3.05| 36.7| 17.2| 3.37| 34.5| 16.6| 3.73
75| 63| 34.8| 26.0| 2.70| 33.1| 25.6| 2.97| 31.3| 24.9| 3.29| 29.4| 24.2| 3.66
P6SD-X48
O.D.T | 85°F | 95°F | 105°F | 115°F |
---|---|---|---|---|
CFM | E.D.B. | E.W.B. | T.C. | S.C. |
T.C. | S.C. | K.W. | T.C. | S.C. |
S.C. | K.W. |
1250
| 80| 62| 44.1| 35.7| 3.45| 42.2| 36.0| 3.84| 40.0| 37.1| 4.27| 37.8| 36.6|
4.77
80| 67| 47.9| 28.8| 3.50| 45.5| 28.0| 3.87| 43.1| 27.2| 4.31| 40.6| 26.7| 4.80
80| 72| 52.1| 21.9| 3.54| 49.5| 21.2| 3.92| 46.9| 20.5| 4.35| 44.2| 19.8| 4.85
75| 63| 52.1| 16.3| 3.54| 49.5| 16.7| 3.92| 47.0| 16.7| 4.35| 44.2| 16.4| 4.85
1400
| 80| 62| 45.2| 38.2| 3.46| 43.1| 39.5| 3.85| 41.0| 39.5| 4.29| 39.0| 39.0|
4.78
80| 67| 48.7| 30.6| 3.51| 46.3| 29.8| 3.88| 43.9| 29.4| 4.32| 41.4| 28.6| 4.81
80| 72| 52.9| 23.1| 3.54| 50.4| 22.4| 3.93| 47.7| 21.6| 4.36| 44.9| 20.9| 4.86
75| 63| 53.1| 18.2| 3.55| 50.5| 18.2| 3.93| 47.7| 17.9| 4.36| 45.0| 17.4| 4.86
1550
| 80| 62| 46.2| 41.8| 3.47| 44.2| 41.9| 3.86| 42.2| 42.2| 4.30| 40.1| 40.1|
4.80
80| 67| 49.6| 32.7| 3.51| 47.1| 32.0| 3.89| 44.6| 31.2| 4.33| 42.0| 30.4| 4.82
80| 72| 53.8| 24.2| 3.55| 51.1| 23.5| 3.95| 48.4| 22.8| 4.37| 45.5| 22.0| 4.86
75| 63| 53.8| 20.3| 3.55| 51.1| 19.8| 3.95| 48.4| 19.2| 4.37| 45.5| 18.4| 4.87
P6SD-X60
O.D.T | 85°F | 95°F | 105°F | 115°F |
---|---|---|---|---|
CFM | E.D.B. | E.W.B. | T.C. | S.C. |
T.C. | S.C. | K.W. | T.C. | S.C. |
S.C. | K.W. |
1600
| 80| 62| 56.7| 45.9| 4.53| 54.1| 46.1| 5.02| 51.3| 47.5| 5.57| 48.4| 46.7|
6.19
80| 67| 61.2| 37.4| 4.62| 58.1| 36.4| 5.09| 55.0| 35.3| 5.65| 51.7| 34.2| 6.26
80| 72| 66.6| 28.6| 4.72| 63.1| 27.7| 5.20| 59.5| 26.8| 5.75| 55.7| 25.7| 6.36
75| 63| 57.0| 36.9| 4.54| 54.2| 37.0| 5.02| 51.2| 36.7| 5.57| 48.2| 36.0| 6.18
1750
| 80| 62| 57.8| 48.3| 4.59| 55.1| 49.9| 5.07| 52.2| 49.9| 5.62| 49.3| 49.2|
6.24
80| 67| 62.0| 39.2| 4.67| 58.9| 38.1| 5.14| 55.7| 37.0| 5.70| 52.3| 35.8| 6.31
80| 72| 67.1| 29.8| 4.77| 63.5| 28.8| 5.24| 59.9| 27.8| 5.79| 56.2| 26.8| 6.41
75| 63| 57.8| 40.1| 4.59| 54.9| 39.8| 5.07| 51.9| 39.1| 5.62| 48.8| 38.1| 6.23
1900
| 80| 62| 58.7| 52.1| 4.64| 56.0| 52.2| 5.13| 53.1| 53.0| 5.68| 50.4| 50.4|
6.30
80| 67| 62.7| 40.9| 4.72| 59.6| 39.8| 5.20| 56.3| 38.7| 5.75| 52.8| 37.5| 6.36
80| 72| 67.5| 30.9| 4.81| 64.0| 29.9| 5.29| 60.5| 28.8| 5.84| 56.7| 27.7| 6.46
75| 63| 58.5| 43.5| 4.64| 55.6| 42.7| 5.12| 52.5| 41.6| 5.66| 49.3| 40.3| 6.28
GENERAL TERMS OF LIMITED WARRANTY
- NORDYNE will furnish a replacement for any part of this product in accordance with the terms of the warranty.
- For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the NORDYNE warranty department for a copy.
8000 Phoenix Parkway | O’Fallon, MO 63368-3827
Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (09/2010) 800C-0910 (Replaces 800C-0808) www.millerac.com.
Trademark Miller® used under license. © Nortek Global HVAC, LLC. All Rights Reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>