National Air H8HK Series Electric Heater Kit Instruction Manual
- June 15, 2024
- National Air
Table of Contents
- INSTALLATION IN STANDARD & VARIABLE SPEED INDOOR AIR HANDLERS
- IMPORTANT
- IMPORTANT SAFETY INFORMATION
- ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
- GENERAL INFORMATION
- Clearances to Combustibles
- Electric Heater Kits with Circuit Breakers
- Electric Heater Kits without Circuit Breakers
- MOTOR SPEED SELECTION
- FIGURES & TABLES
- 1: 190F| –| –
- 1: 190F| –| –
- 1: 190F| #1: 190F#2: 190F| #1: 190F#2: 190F
- Wiring Diagrams
- Documents / Resources
National Air H8HK Series Electric Heater Kit Instruction Manual
INSTALLATION INSTRUCTIONS
INSTALLATION IN STANDARD & VARIABLE SPEED INDOOR AIR HANDLERS
IMPORTANT
ATTENTION INSTALLERS:
These instructions are primarily intended to assist qualified individuals
experienced in the proper installation of heating and/or air conditioning
appliances. Some local codes require licensed installation/service personnel
for this type equipment. All installations must be in accordance with these
instructions and with all applicable national and local codes and standards.
Read these instructions thoroughly before starting the installation. Follow
all precautions and warnings contained within these instructions and on the
unit. The instructions included with this heater kit are for installations in
air handlers only.
DO NOT DESTROY. PLEASE READ CAREFULLY & KEEP IN A SAFE PLACE FOR FUTURE
REFERENCE.
IMPORTANT SAFETY INFORMATION
INSTALLER : Please read all instructions before servicing this equipment.
Pay attention to all safety warnings and any other special notes highlighted
in the manual. Safety markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not be ignored.
WARNING indicates a potentially hazardous situation that if not avoided,
could result in personal injury or death. CAUTION indicates a potentially
hazardous situation that if not avoided, may result in minor or moderate
injury or property damage.
WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury or
property damage.
Improper servicing could result in dangerous operation, serious injury, death
or property damage.
- Before servicing, disconnect all electrical power to the unit.
- When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
- Verify proper operation after servicing.
GENERAL INFORMATION
About the heater kit
H8HK-A Series electric heater kit is approved for field installation in B6 Air
Handlers as replacement parts (only using 190°F Limits), and B64 air handlers.
All sizes are available with factory-provided circuit-breakers for short
circuit protection and to provide a disconnecting means. Also available are 5,
8, and 10 kW electric heater kits without circuit-breakers. Refer to the
National Electric Code (ANSI/NFPA 70) and applicable local codes for over-
current protection and disconnect requirements.
NOTES:
-
**** The 10, 15, 20 and 24 kW electric heater kits are NOT approved
for installation in A-cabinet B64 air handlers. -
The 20 and 24 kW heater kits are NOT approved for installation in B-cabinet B64 air handlers. For all heater kit applications, use **and Figure 1
**
- These instructions are written assuming the air handler is in the up flow position (outlet facing up). For horizontal and downflow applications, it is recommended that the electric heater kit be installed prior to installation of the air handler.
- Use caution when handling or installing this component. Personal injury can occur from sharp metal edges present in all sheet metal constructed equipment
Clearances to Combustibles
Standard Air Handler
All installations of H8HK-A electric heater kits in standard air handlers
are approved for zero-clearance to combustibles when the minimum electric heat
airflow is set as directed in these instructions.
Variable Speed Air Handlers
All installations of H8HK-A electric heater kits in variable speed air
handlers are approved for zero-clearance to combustibles when the minimum
electric heat airflow is set as directed in these instructions.
ELECTRICAL SUPPLY
- All electrical connections must be in compliance with all applicable local codes with the current revision of the National Electric Code (ANSI/NFPA 70). For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code (CSA C22.1 and/or local codes).
- If the air handler was previously installed without electric heat, the existing supply wiring may not be sufficient to carry the increased load. If installing electric heat in the air handler, the supply wiring can be aluminum or copper. The supplied circuit breakers and terminal blocks are approved for either wire type. Make sure to follow all of the rating information on the circuit breaker or terminal block and that the supply wiring is sized according to the current NEC codes and any other state or local codes. See the rating label or Table 3 for minimum circuit ampacities and maximum overcurrent protection.
- All heater kits are supplied from the factory configured for use with one or more supply circuits. 5 & 10 kW heater kits 10 are configured for use with a single supply circuit (Circuit A). 15 & 20 kW heater kits are configured for use with 2 circuits (Circuit A & Circuit B). 24 kW heater kits are configured for use with 3 circuits (Circuit A, Circuit B, & Circuit C). See Table for additional information.
NOTE : If a single supply is desired, accessory kit #913874 is required to convert to single circuit connection.
Power Wiring
All wiring must comply with the current revision of the National Electric
Code and must be sized for the minimum ampacities as listed on the unit data
label or in & Table 4. Refer to Figures 13 for proper connections.
If a single circuit adaptor kit is used it may need to be reconfigured for
some applications. Remove the single circuit
adaptor kit cover and verify that the lugs are configured correctly for the
application. If the lugs are not configured for the application, reference the
instructions included with the kit and modify the configuration. Install the
single circuit adaptor kit (if used) in the line side (“on” end) of the
circuit breakers. Tighten the lugs securely (45 in-lbs recommended).
Connect the supply wiring to the circuit breaker(s), single circuit adaptor
kit, or terminal block. Tighten the lugs securely.
When using multiple supply circuits verify that the supply sized for circuit
“A” is connected to the circuit breaker that is connected to the top element
assembly.
Install metal circuit breaker line cover on the left side of the circuit
breaker to cover the supply wires.
INSTRUCTIONS FOR SWAPPING LIMITS
- 1. Refer to the “Limit Switch Opening Temperatures Required for Each Heater Kit Combination” data in Table 2 (page 11), to identify if a limit needs to be swapped before installing heater kit.
- Set the thermostat to the lowest temperature setting.
- Turn off all electrical power to the air handler.
- Remove upper access door from the air handler.
- To swap a limit switch, disconnect all wires from the limit
- (you will connect the wires of the new limit in the exact same way).
- Remove the two screws that attach the limit to the metal plate and save them to install the new limit.
- Attach the new limit (as directed by Table 2) with the two screws and tighten until snug.
- Connect the wires to the spade connectors on the new limit switch in the same exact way that you removed them, or refer to the corresponding heater kit wiring diagram.
NOTE : On Table 2, Limit #1 is defined as the limit installed in the closest possible position to the blower, and Limit #2 is 2nd closest to the blower. Also keep in mind, the airflow direction label on the heater kit plate should always point in the direction of the airflow when installed.
ELEMENT INSTALLATION
-
Refer to “Limit Switch Opening Temperature(s) Required for Each Heater Kit Combination”, Table 2 , to identify if a limit needs to be swapped before installing Heater Kit.
-
Set the thermostat to the lowest temperature setting.
-
Turn off all electrical power to the air handler.
-
Remove the upper access door from the air handler.
-
Remove the screws securing the upper element close off plate from the back of the air handler control box.
-
Remove the element close-off plate and set the screws aside. Do not discard the screws. NOTE: For 2-tiered electric heater kits, remove two close-off plates. For 3-tiered electric heater kits remove all 3 close-off plates. The close off plates should be removed from the bottom up in ascending order.
-
Insert the element assembly into the opening in the air handler control box being careful not to damage the element wire or the ceramic element supports.
NOTE : Heating element alignment rods will slide into alignment holes in the back of the air handler element box.
NOTE : Install Heater Kit in the orientation where the airflow direction matches the airflow direction label on the Heater Kit plate. -
If blue blower limit wires are NOT present(This will be the case if you are replacing an old H8HK heater kit
Single Stage Board: Connect the W wires from the control board ( whit e), AC relay ( white ) and the W wire from the thermostat with one of the supplied wire nuts. Connect the C wires from the board ( gray ), AC relay ( gra y) and C wire (if supplied) from the thermostat with one wire nut
Two Stage Board : Place the W1 wire from the thermostat and the white wire from the AC relay under the W1 screw terminal on the board. Place the C wire from the thermostat (if present) and the gray wire from the AC relay underneath the C terminal on the control board.
If blue blower limit wires ARE present:
Single Stage Board : Connec t white wire from the AC relay to one of the blu e blower limit wires with a supplied wire nut. Then, connect the other blue blower limit wire to the W wire from the control board (white) with a supplied wire nut. Connect the C wire from the board (gray), AC relay (gray) and C wire (if supplied) from the thermostat with one wire nut.
Two Stage Board : Place the W1 wire from the thermostat and the white wire from the AC relay under the W1 screw terminal on the board. Place the C wire from the thermostat (if present) and the gray wire from the AC relay underneath the C terminal on the control board.
If blue blower limit wires ARE present : Single Stage Board: Connect white wire from the AC relay to one of the blue blower limit wires with a supplied wire nut. Then, connect the other blue blower limit wire to the W wire from the control board (white) with a supplied wire nut. Connect the C wire from the board ( gray ), AC relay ( gray ) and C wire (if supplied) from the thermostat with one wire nut.
Two Stage Board : Locate the supplied loose white wire with two stripped ends supplied with the air handler in it’s parts package. Place the W1 wire from the thermostat and one end of the supplied stripped white wire under the W1 screw terminal on the board. Connect the other end of the supplied stripped white wire with one of the blue blower limit wires using a supplied wire nut. Connect the other blue blower limit wire with the white wire from the AC relay using a supplied wire nut. Place the C wire from the thermostat (if present) and the gray wire from the AC relay underneath the C terminal on the
control board. -
Single Stage Board : Connect the W wires from the control board (white), AC relay (white) and the W wire from the thermostat with one of the supplied wire nuts. Connect the C wires from the board (grey), AC relay (grey) and C wire (if supplied) from the thermostat with one wire nut.
Two-Stage Board : Place the W1 wire from the thermostat and the white wire from the AC relay under the W1 screw terminal on the board. Place the C wire from the thermostat (if present) and the grey wire from the AC relay underneath the C terminal on the control board. -
Connect the 2-Pin Power plug from the element assembly into the unit’s 2-Pin power plug. Connect the 7-Pin Harness from the element assembly to the unit’s circuit board.
NOTE: A wiring diagram and a rating label are supplied with the electric heater kit. Affix the wiring diagram to the blower housing.
- When installing the electric heater kit into a standard air handler, affix the supplied rating label over the electrical data section of the air handler unit data label located on the lower access door.
- When installing the electric heater kit into a variable speed air handler, the rating label supplied with the kit will NOT be used. Check the appropriate block on the air handler ratings label located on the lower access door
-
Install the circuit breaker bracket inside of the air handler. Position the tab on the bottom of the bracket into the slot of the control panel box. See Figure 2 for proper location of bracket.
-
Slide the bracket forward and align the screw holes with the holes in the bottom of the control panel box. Secure the bracket to the air handler with the supplied screws.
Electric Heater Kits with Circuit Breakers
NOTE 1 : Circuit breakers supplied with the H8HK electric heater kit are
for short-circuit protection of the internal wiring and to serve as a unit
disconnect. They DO NOT provide over-current protection of the supply wiring.
Over-current protection of the supply wiring must be provided at the
distribution panel and sized as shown in Table 3 & Table 4or the unit
data label, and in accordance with the NEC and all applicable local codes.
NOTE 2: In some cases, the over-current protection specified in Table 3 &
Table 4 (or the unit data label) is less than the 60 amp rating of the circuit
breakers used in the H8HK-A electric heater kit. This difference may occur if
the function of the over-current protection required at the distribution panel
(field supplied) and the function of the circuit breakers in the H8HK-A
electric heater kit are different.
5, 8, & 10 kW Electric Heater Kits
- Snap the circuit breaker onto the circuit breaker bracket. The circuit breaker must be positioned with the 1/4″ tab terminals to the right as shown in **Figure 3 .
**
- Remove the lower circuit breaker knockout from the air handler upper access door.
15, 20 & 24 kW Electric Heater Kits
NOTE 1 : The heavy red and black supply leads are bundled by circuit with
wire ties at the factory. The bundle coming from the top element tier is
circuit “A”.
NOTE 2: The element assembly is right-side-up when the limits are on the
right side). The bundle coming from the second element tier is circuit “B”.
The bundle coming from the bottom element tier is circuit “C
- Snap the circuit breaker onto the circuit breaker bracket. The circuit breaker must be positioned with the 1/4″ tab terminals to the right as shown in Figure 3.
- Remove all necessary circuit breaker knockouts in the air handler upper access door.
Line Cover
Heater Kits with circuit breakers are supplied with a line cover shown in
Figure 4.
The line cover is required by code in order to protect installers from the line/supply wiring. The line cover should be installed as shown in Figure **5 .
**
Electric Heater Kits without Circuit Breakers
- Attach the supplied power terminal block to the circuit breaker bracket with the supplied screws as shown in **Figure 6 .
**
- Using the 1/4″ terminals, connect the red supply wire(s) from the element assembly to one pole of the terminal block and connect the black wires to the other pole.
Staged Heat
All Single-phase heater kits are internally staged using B6 and B64 air
handler circuit board logic. B6 and B64 single stage air handlers will not
stage the heater kit. B6 and B64 two-stage air handlers may stage the heat kW
turned on with either a low or high heat call. All 3-phase heater kits are not
equipped for internal staging. Refer to the installation instructions supplied
with the air handler for additional staging information.
Air Baffle Installation and Usage
-
To identify if a baffle needs to be installed into the blower housing, refer to the “Limit Switch Opening Temperatures Required for Each Heater Kit Combination ” Table 2. Asterisks in the table show where a baffle is used.
-
To install the baffle properly, find the paper template included in the heater kit packaging. Two copies have been provided in case a mistake occurs.
-
Set the thermostat to the lowest temperature setting.
-
Turn off all electrical power to the air handler.
-
Remove blower access door and coil access door from the air handler.
-
Remove mid-cabinet support bracket to be able to slide blower housing out of cabinet.
-
Be aware of where the blue blower limit wires on the blower housing are located and how the ends are located in the blower cabinet of the air handler. ( See Figure 8 to see blower limit wires on a blower housing)
-
Remove the blower housing by unscrewing all of the screws holding the blower to the blower deck, and then slide the blower housing out of the cabinet.
-
Pull blue blower limit wires out of electrical compartment, and disconnect any blower motor wires to make this process easier.
-
Lay the paper template onto the flat section of the blower housing, shown in the picture below, being sure to match the correct corner of the template to the corresponding corner of the blower housing, shown in Figure **9.
**
-
Tape to secure, or physically hold the template into the corner of the blower housing without bending it. The locations of the three dots on the template are where you will drill out three clearance holes with a 7/32” drill bit into the blower housing (5mm drill bit also works)
NOTE : Poking holes in the paper template beforehand will make it easy to mark the sheet metal when you overlay the template. -
Once the clearance holes are drilled, insert the baffle into the outlet of the blower housing, line up the holes,
and screw in the 3 supplied #10 self-drilling screws until snug, being sure not to strip any sheet metal. Reference Figure 11 and Figure 12 to see how this should look when completed. -
Slide the blower housing back into the cabinet and reconnect any blower limit wires according to the corresponding heater kit wiring diagram, as well as any blower motor wires according to their corresponding air handler wiring diagram.
-
Reattach mid-cabinet support bracket, and then replace the blower access door and coil access door
MOTOR SPEED SELECTION
Standard Air Handlers
The blower speed is preset at the factory for operation at the same speed
for heating and cooling, by using the blower motor jumping terminal on the
blower motor and connecting it to the desired speed with both the red and
black wires connected to the jumping terminal. For optimum system performance
and comfort, it may be necessary to change the factory set speed. To change
the blower speed:
WARNING:
To avoid the risk of electric shock, personal injury, or death,
disconnect all electrical power to the unit before performing any maintenance
or service. The unit may have more than one electrical power supply.
-
Disconnect all electrical power to the unit and remove the upper door.
-
Remove the black and red wires from the blower motor jumping terminal.
-
Connect the heating speed wire (red) and the cooling speed wire (black) to the desired blower speed marked on the terminal block of the blower motor. If needed, re-use the motor jumping terminal.
IMPORTANT NOTE
After changing the blower speed setting, make sure to bundle and insulate any unused blower motor leads so that they will not make contact with the air handler cabinet or non-insulated live parts.
Standard 3 Speed Motors
Terminal 4 = Hi speed
Terminal 5 = Med speed
Terminal 6 = Low speed
For a Table of Minimum heating speeds, limit settings, and baffle usage, see Table 1. Also see Clearances to Combustibles.
-
Replace the upper door and secure it to the unit.
-
Restore power to the unit.
Variable Speed Air Handlers
The minimum electric heat airflow is selected by setting switches on the air
handler circuit board. Selecting the minimum electric heat airflow sets the
minimum air flow that will be produced whenever electric heater kits are
energized. When the electric heater kits are energized along with a heat pump,
the airflow may be higher depending on the basic cooling/heat-pump airflow
setting. Reference the installation instructions supplied with the air handler
for additional airflow information.
FIGURES & TABLES
Figure 1. Heater Kit Identification Code
Figure 2. Sample Installation (shown with access door removed)
Figure 3. Installation of Circuit Breakers
Figure 4. Line Cover
Figure 5. Line Cover Installed
Figure 6. Circuit Breaker Bracket with Terminal Block Installed
Figure 7. Blower Housing Air Baffle
Figure 8. Blower Limit Switches/Wires
Figure 9. Template for Air Baffle Installation
Figure 10. Installed Air Baffle, View 1
Figure 11. Installed Air Baffle, View 2
Figure 12. H8HK Heater Kit Installation
| MINIMUM RECOMMENDED HEATING BLOWER SPEED (ZERO CLEARANCE INSTALL)
---|---
Standard Air Handler Model| Blower Orientation| H8HK005H- 01A|
H8HK005H- 11A| H8HK008H- 01A| H8HK008H- 11A| H8HK010H- 01A| H8HK010H- 11A|
H8HK015H- 21A| H8HK020H- 21A
4.8 kW| 4.8 kW| 7.5 kW| 7.5 kW| 9.6 kW| 9.6 kW| 14.4 kW| 19.2 kW
B64BMMX 18K-A| Upflow| MED.| MED.| MED.| MED.| –| –| –| –
Horiz. Right| MED.| MED.| MED.| MED.| –| –| –| –
Horiz. Left| MED.| MED.| MED.| MED.| –| –| –| –
Downflow| MED.| MED.| MED.| MED.| –| –| –| –
B64BMMX 24K-A| Upflow| MED.| MED.| MED.| MED.| –| –| –| –
Horiz. Right| MED.| MED.| MED.| MED.| –| –| –| –
Horiz. Left| MED.| MED.| MED.| MED.| –| –| –| –
Downflow| MED.| MED.| MED.| MED.| –| –| –| –
B64BMMX 24K-B| Upflow| MED.| MED.| MED.| MED.| MED.| MED.| –| –
Horiz. Right| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| –| –
Horiz. Left| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| –| –
Downflow| MED.| MED.| MED.| MED.| MED.| MED.| –| –
B64BMMX 30K-B| Upflow| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| –| –
Horiz. Right| MED.| MED.| MED.| MED.| MED.| MED.| –| –
Horiz. Left| MED.| MED.| MED.| MED.| MED.| MED.| –| –
Downflow| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| –| –
B64BMMX 36K-B| Upflow| MED.| MED.| MED.| MED.| MED.| MED.| –| –
Horiz. Right| MED.| MED.| MED.| MED.| MED.| MED.| MED.| –
Horiz. Left| MED.| MED.| MED.| MED.| MED.| MED.| –| –
Downflow| MED.| MED.| MED.| MED.| MED.| MED.| –| –
B64BMMX 42K-C| Upflow| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH
Horiz. Right| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH
Horiz. Left| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH
Downflow| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH
B64BMMX 48K-C| Upflow| MED.| MED.| MED.| MED.| MED.| MED.| MED.| MED.
Horiz. Right| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| LOW| –
Horiz. Left| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| LOW| –
Downflow| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| HIGH| –
Included 25-Degree Air Baffle shall be installed in blower housing of air handler
Note: Dashes denote combinations that are not allowed
Note: All B64 Air Handlers have 2 blower housing limits installed (130F
opening temperature), field-wired into the low voltage circuit of the
H8HKA heater kit.
Table 1. Blower Heating Speed
B64EMMX & B64VMMX
Air Handler tables:
Please scan QR Code for latest version of Installation Instructions for
B64EMMX & B64VMMX Air Handler/Heater Kit combinations.
Table 1. Blower Heating Speed
B64EMMX & B64VMMX
Air Handler tables:|
| Please scan QR Code for latest version of
Installation Instructions for
B64EMMX & B64VMMX Air Handler/Heater Kit combinations.
---|---|---
| MINIMUM RECOMMENDED HEATING BLOWER SPEED (ZERO CLEARANCE INSTALL)
---|---
Standard Air Handler Model| Blower Orientation| H8HK005H- 01A|
H8HK005H- 11A| H8HK008H- 01A| H8HK008H- 11A| H8HK010H- 01A| H8HK010H- 11A|
H8HK015H- 21A| H8HK020H- 21A
4.8 kW| 4.8 kW| 7.5 kW| 7.5 kW| 9.6 kW| 9.6 kW| 14.4 kW| 19.2 kW
B64BMMX 18K-A| Up flow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –| –|
–
Horiz. Right| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –| –| –
Horiz. Left| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –| –| –
Downflow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –| –| –
B64BMMX 24K-A| Up flow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –| –|
–
Horiz. Right| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –| –| –
Horiz. Left| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –| –| –
Downflow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –| –| –
B64BMMX 24K-B| Upflow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F|
1: 190F| –| –
Horiz. Right| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –
Horiz. Left| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –
Downflow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –
B64BMMX 30K-B| Upflow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F|
1: 190F| –| –
Horiz. Right| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –
Horiz. Left| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –
Downflow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –
B64BMMX 36K-B| Up flow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1:
190F| #1: 190F| –| –
Horiz. Right| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1:
205F#2: 205F| –
Horiz. Left| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –
Downflow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| –| –
B64BMMX 42K-C| Up flow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1:
190F| #1: 190F| #1: 190F#2: 190F| #1: 190F#2: 190F
Horiz. Right| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1:
205F#2: 190F| #1: 205F#2: 190F
Horiz. Left| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1:
205F#2: 190F| #1: 205F#2: 190F
Downflow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1:
190F#2: 190F| #1: 190F#2: 190F
B64BMMX 48K-C| Upflow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F|
1: 190F| #1: 190F#2: 190F| #1: 190F#2: 190F
Horiz. Right| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 215F| #1: 215F| #1:
190F#2: 190F| –
Horiz. Left| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 215F| #1: 215F| #1:
190F#2: 190F| –
Downflow| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1: 190F| #1:
205F#2: 205F| –
Included 25-degree Air Baffle shall be installed in blower housing of air handler
Note: Limit #1 is installed closest to blower. Limit #2 is installed in 2nd
closest position to blower.
Note : Dashes denote combinations that are not allowed.
Note: All B64 Air Handlers have 2 blower housing limits installed (130F
opening temperature), field-wired into t low voltage circuit of the
H8HKA heater kit.
B64EMMX & B64VMMX
Air Handler tables:
Please scan QR Code for latest version of Installation Instructions for
B64EMMX & B64VMMX Air Handler/Heater Kit combinations.
Table 2. Compatible Heater Kit Limit Switches for Air Handler
Combinations
B64EMMX & B64VMMX Air Handler tables:
Please scan QR Code for latest version of Installation Instructions for
B64EMMX & B64VMMX Air Handler/Heater Kit combinations.
MODEL NUMBER H8HK-| **VOLTAGE| HTR AMP A| HTR AMP B|
HTR AMP C| ****HTR AMP
---|---|---|---|---|---
None| 240/208V| –| –| –| –
005H- **A| 240/208V| 20.0/17.3| –| –| 20.0/17.3
008H- **A| 240/208V| 31.7/27.4| –| –| 31.7/27.4
010H- **A| 240/208V| 40.0/34.6| –| –| 40.0/34.6
015H- **A| 240/208V| 40.0/34.6| 20.0/17.3| –| 60.0/51.9
020H- **A**| 240/208V| 40.0/34.6| 40.0/34.6| –| 80.0/69.2
Table 3. Heater Kit Current
| ELECTRICAL DATA: STANDARD AIR HANDLERS|
---|---|---
VOLTAGE: 240V| VOLTAGE: 208V
MINIMUM CIRCUIT AMPACITY (MCA)| MAX OVER-CURRENT PROTECTION (MOP)|
MINIMUM CIRCUIT AMPACITY (MCA)| MAX OVER-CURRENT PROTECTION (MOP)
Cabinet| Capacity (×1000 BTU’s)| Model Number
H8HK-| CIRCUIT A| CIRCUIT B| CIRCUIT C|
SINGLE CIRCUIT| CIRCUIT A| CIRCUIT B| CIRCUIT
C| SINGLE CIRCUIT| CIRCUIT A| CIRCUIT B|
CIRCUIT C| SINGLE CIRCUIT| CIRCUIT A| CIRCUIT
B| CIRCUIT C| SINGLE CIRCUIT| VOLTAGE
A| 18| None| 1.6| –| –| 1.6| 15| –| –| 15| 1.6| –| –| 1.6| 15|
–| –| 15| 240/208V
005H-A| 26.625| –| –| 26.6| 30| –| –| 30| 23.260| –| –| 23.3| 25| –|
–| 25| 240/208V
008H-A| 41.208| –| –| 41.2| 45| –| –| 45| 35.880| –| –| 35.9| 40| –|
–| 40| 240/208V
A| 24| None| 3.1| –| –| 3.1| 15| –| –| 15| 3.1| –| –| 3.1| 15|
–| –| 15| 240/208V
005H-A| 28.125| –| –| 28.1| 30| –| –| 30| 24.760| –| –| 24.8| 25| –|
–| 25| 240/208V
008H-A| 42.708| –| –| 42.7| 45| –| –| 45| 37.380| –| –| 37.4| 40| –|
–| 40| 240/208V
B| 24| None| 3.1| –| –| 3.1| 15| –| –| 15| 3.1| –| –| 3.1| 15|
–| –| 15| 240/208V
005H-A| 28.125| –| –| 28.1| 30| –| –| 30| 24.760| –| –| 24.8| 25| –|
–| 25| 240/208V
008H-A| 42.708| –| –| 42.7| 45| –| –| 45| 37.380| –| –| 37.4| 40| –|
–| 40| 240/208V
010H-A| 53.125| –| –| 53.1| 60| –| –| 60| 46.394| –| –| 46.4| 50| –|
–| 50| 240/208V
B| 30| None| 2.6| –| –| 2.6| 15| –| –| 15| 2.6| –| –| 2.6| 15|
–| –| 15| 240/208V
005H-A| 27.625| –| –| 27.6| 30| –| –| 30| 24.260| –| –| 24.3| 25| –|
–| 25| 240/208V
008H-A| 42.208| –| –| 42.2| 45| –| –| 45| 36.880| –| –| 36.9| 40| –|
–| 40| 240/208V
010H-A| 52.625| –| –| 52.6| 60| –| –| 60| 45.894| –| –| 45.9| 50| –|
–| 50| 240/208V
B| 36| None| 3.1| –| –| 3.1| 15| –| –| 15| 3.1| –| –| 3.1| 15|
–| –| 15| 240/208V
005H-A| 28.125| –| –| 28.1| 30| –| –| 30| 24.760| –| –| 24.8| 25| –|
–| 25| 240/208V
008H-A| 42.708| –| –| 42.7| 45| –| –| 45| 37.380| –| –| 37.4| 40| –|
–| 40| 240/208V
010H-A| 53.125| –| –| 53.1| 60| –| –| 60| 46.394| –| –| 46.4| 50| –|
–| 50| 240/208V
015H-A| 50| 28.125| –| 78.1| 50| 30| –| 80| 43.269| 24.760| –| 68| 45|
25| –| 70| 240/208V
C| 42| None| 5.4| –| –| 5.4| 15| –| –| 15| 5.4| –| –| 5.4| 15|
–| –| 15| 240/208V
005H-A| 30.375| –| –| 30.4| 35| –| –| 35| 27.010| –| –| 27| 30| –| –|
30| 240/208V
008H-A| 44.958| –| –| 45| 45| –| –| 45| 39.630| –| –| 39.6| 40| –| –|
40| 240/208V
010H-A| 55.375| –| –| 55.4| 60| –| –| 60| 48.644| –| –| 48.6| 50| –|
–| 50| 240/208V
015H-A| 50| 30.375| –| 80.4| 50| 35| –| 90| 43.269| 27.010| –| 70.3|
45| 30| –| 80| 240/208V
020H-A| 50| 55.375| –| 105.4| 50| 60| –| 110| 43.269| 48.644| –| 91.9|
45| 50| –| 100| 240/208V
C| 48| None| 5.4| –| –| 5.4| 15| –| –| 15| 5.4| –| –| 5.4| 15|
–| –| 15| 240/208V
005H-A| 30.375| –| –| 30.4| 35| –| –| 35| 27.010| –| –| 27| 30| –| –|
30| 240/208V
008H-A| 44.958| –| –| 45| 45| –| –| 45| 39.630| –| –| 39.6| 40| –| –|
40| 240/208V
010H-A| 55.375| –| –| 55.4| 60| –| –| 60| 48.644| –| –| 48.6| 50| –|
–| 50| 240/208V
015H-A| 50| 30.375| –| 80.4| 50| 35| –| 90| 43.269| 27.010| –| 70.3|
45| 30| –| 80| 240/208V
020H-A| 50| 55.375| –| 105.4| 50| 60| –| 110| 43.269| 48.644| –| 91.9|
45| 50| –| 100| 240/208V
Table 4. Electrical Ratings
Wiring Diagrams
INSTALLER: PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER
10437110 (NEW)
Wiring Diagrams
(Air Handler with Circuit Breaker(s)) Figure 13. Single Phase, 5 kW W.D
NOTES:
-
If any of the original wire supplied with this unit must be replaced, it must be replaced with wiring material of the same gauge size and temperature rating.
-
The installation of this heater kit may require a change in the blower speed tap connection. See Installation
Instructions for details. -
Use copper conductors with a minimum temperature rating of 60°C for supply connections.
| H8HK005H-01A (with circuit breaker)
H8HK005H-11A (without circuit breaker)| 5 kW, 1-Phase Electric Heater Kit
---|---|---
LEGEND:
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
NOTES:
- If any of the original wire supplied with this unit must be replaced, it must be replaced with wiring material of the same gauge size and temperature rating.
- The installation of this heater kit may require a change in the blower speed tap connection. See Installation Instructions for details.
- Use copper conductors with a minimum t rating of 60°C for supply connections.
| H8HK008H-01A (without circuit breaker) H8HK008H-11A (with circuit breaker)
H8HK010H-11A (with circuit breaker) H8HK010H-01A (without circuit breaker)|
8W, 10kW, 1-Stage, 240 VAC, 1-Phase Electric Heater Kit
---|---|---
NOTES
- If any of the original wire supplied with this unit must be replaced, it must be replaced with wiring material of the same gauge size and temperature rating.
- The installation of this heater kit may require a change in the blower speed tap connection. See Installation Instructions for details.
- Use copper conductors with a minimum temperature rating of 60°C for supply connections.
NOTES.
- If any of the original wire supplied with this unit must be replaced, it must be replaced with wiring material of the same gauge size and temperature rating.
- The installation of this heater kit may require a change in the blower speed tap connection. See Installation Instructions for details.
- Use copper conductors with a minimum temperature rating of 60°C for supply connections.
NOTES
- If any of the original wire supplied with this unit must be replaced, it must be replaced with wiring material of the same gauge size and temperature rating.
- The installation of this heater kit may require a change in the blower speed tap connection. See Installation Instructions for details.
- Use copper conductors with a minimum temperature rating of 60°C for supply connections
INSTALLER: PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER
Documents / Resources
|
National Air H8HK Series Electric Heater
Kit
[pdf] Instruction Manual
H8HK Series Electric Heater Kit, H8HK Series, Electric Heater Kit, Heater Kit,
Kit
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>