MITSUBISHI ELECTRIC MXZ-SM72TAM-U1 Residential Outdoor Unit Owner’s Manual
- June 15, 2024
- Mitsubishi Electric
Table of Contents
MITSUBISHI ELECTRIC MXZ-SM72TAM-U1 Residential Outdoor Unit
Product Information
Specifications
- Model Name: MXZ-SM72TAM-U1, MXZ-SM96TAM-U1, MXZ-SM120TAM-U1
- HFC Utilized: R410A
- Revision: January 2023 OCH800 Revised Edition-A
Product Usage Instructions
Safety Precautions
2-1. Always observe for safety
Before obtaining access to the terminal, make sure to disconnect all supply circuits.
Preparation before the repair service:
- Ensure precautions during the repair service.
2-2. Cautions related to new refrigerant
Cautions for units utilizing refrigerant R410A:
- Use new refrigerant pipes.
- Ensure that the inside and outside of the refrigerant piping are clean and free from contaminants such as sulfur, oxides, dirt, shaving particles, etc.
- Use pipes with specified thickness.
- Store the piping indoors and keep both ends sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
- The refrigerant oil applied to flare and flange connections must be ester oil, ether oil, or alkylbenzene oil in a small amount.
- Charge refrigerant from the liquid phase of the refrigerant cylinder.
- Do not use refrigerant other than R410A.
Use a vacuum pump with a reverse flow check valve.
Use the following tools specifically designed for use with R410A refrigerant:
- Gauge manifold
- Charge hose
- Gas leak detector
- Torque wrench
- Flare tool
- Size adjustment gauge
- Vacuum pump adaptor
- Electronic refrigerant charging scale
Handle tools with care and do not use a charging cylinder.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Use the specified refrigerant only to prevent abrasive components contained in sandpaper and cutting tools from entering the refrigerant circuit, as they can cause failures of the compressor and valves.
Do not pump down the system when a gas leak has been detected.
2-2-1. Cautions for service
2-2-2. Additional refrigerant charge
Unit: Electronic weighing scale
2-2-3. Service tools
Use the following service tools as exclusive tools for R410A refrigerant:
No. | Tool Name |
---|---|
1 | Gauge manifold (Only for R410A) |
2 | Charge hose (Only for R410A) |
3 | Electronic weighing scale |
4 | Gas leak detector |
5 | Adaptor for reverse flow check (Use the detector for R134a, |
R407C, or R410A. Attach on vacuum pump.)
6| Refrigerant charge base
7| Refrigerant cylinder (Only for R410A Top of cylinder (Pink)
Cylinder with syphon)
8| Refrigerant recovery equipment
2-2-4. Cautions for refrigerant piping work
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is the same as for R22, exclusive tools are necessary so as not to mix with different kinds of refrigerant. Furthermore, as the working pressure of R410A is 1.6 times higher than that of R22, their sizes of flared sections and flare nuts are different.
Thickness of pipes:
- Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with a thickness shown below. (Never use pipes of 7/256 in [0.7 mm] or below.)
FAQs
Q: What refrigerant should I use with this product?
A: This product should only be used with R410A refrigerant. Do not use any other refrigerant.
Q: What precautions should I take during the repair service?
A: Before obtaining access to the terminal, make sure to disconnect all supply circuits. Follow the instructions provided in the user manual for preparation and precautions during the repair service.
Q: Can I use any tools for servicing this product?
A: No, you should use the specified tools designed for use with R410A refrigerant. These tools include a gauge manifold, charge hose, gas leak detector, torque wrench, flare tool, size adjustment gauge, vacuum pump adaptor, and electronic refrigerant charging scale.
Q: What should I do if there is a refrigerant leak during operation?
A: If a refrigerant leak occurs during operation, ventilate the room immediately. Contact a professional for assistance in repairing the leak.
SERVICE MANUAL
HFC
utilized
R410A
January 2023 OCH800
REVISED EDITION-A
· The installation manual has been added in REVISED EDITION-A.
OCH800 is void.
1 SERVICE REF.
MXZ-SM72TAM-U1 MXZ-SM96TAM-U1 MXZ-SM120TAM-U1
OCH800A_2
SAFETY PRECAUTION
2-1. Always observe for safety
Before obtaining access to terminal, all supply circuit must be disconnected.
Preparation before the repair service
· Prepare the proper tools. · Prepare the proper protectors. · Provide
adequate ventilation. · After stopping the operation of the air conditioner,
turn off the power-supply breaker. · Discharge the condenser before the work
involving the electric parts.
Precautions during the repair service
· Do not perform the work involving the electric parts with wet hands. · Do
not pour water into the electric parts. · Do not touch the refrigerant. · Do
not touch the hot or cold areas in the refrigerating cycle. · When the repair
or the inspection of the circuit needs to be done without turning off the
power, exercise great caution
not to touch the live parts. · When opening or closing the valve below
freezing temperatures, refrigerant may spurt out from the gap between the
valve stem and the valve body, resulting in injuries. · Be careful not to
expose the fusible plug to the braze torch flame or transfer heat to it. The
temperature of the fusible
plug must not become 140°F (60°C) or more while working. Protect the fusible
plug with a wet cloth when necessary. (The fusible plug breaks at 158°F
[70°C]).
2-2. Cautions related to new refrigerant
Cautions for units utilizing refrigerant R410A
Use new refrigerant pipes.
· Avoid using thin pipes.
Make sure that the inside and outside of refrigerant piping is clean and it
has no contaminants such as sulfur, oxides, dirt, shaving particles, etc.,
which are hazard to refrigerant cycle. In addition, use pipes with specified
thickness.
· Contamination inside refrigerant piping can cause deterioration of
refrigerant oil, etc.
Store the piping indoors, and keep both ends of the piping sealed until just
before brazing. (Leave elbow joints, etc. in their packaging.)
· If dirt, dust or moisture enters into refrigerant cycle, that can cause
deterioration of refrigerant oil or malfunction of compressor.
The refrigerant oil applied to flare and flange connections must be ester oil,
ether oil or alkylbenzene oil in a small amount.
· If large amount of mineral oil enters, that can cause deterioration of
refrigerant oil, etc.
Charge refrigerant from liquid phase of refrigerant cylinder.
· If the refrigerant is charged from gas phase, composition change may occur
in refrigerant and the efficiency will be lowered.
Do not use refrigerant other than R410A.
· If other refrigerant (R22, etc.) is used, chlorine in refrigerant can cause
deterioration of refrigerant oil, etc.
OCH800A_3
Use a vacuum pump with a reverse flow check valve.
· Vacuum pump oil may flow back into refrigerant cycle and that can cause
deterioration of refrigerant oil, etc.
Use the following tools specifically designed for use with R410A refrigerant.
· The following tools are necessary to use R410A refrigerant.
Gauge manifold Charge hose Gas leak detector Torque wrench
Tools for R410A Flare tool Size adjustment gauge Vacuum pump adaptor Electronic refrigerant charging scale
Handle tools with care.
· If dirt, dust or moisture enters into refrigerant cycle, that can cause
deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
· If a charging cylinder is used, the composition of refrigerant will change
and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes
into contact with a flame, poisonous gases will be released.
Use the specified refrigerant only.
· Never use any refrigerant other than that specified. · Doing so may cause a
burst, an explosion, or fire when the unit is being used, serviced, or
disposed of. · Correct refrigerant is specified in the manuals and on the spec
labels provided with our products. · We will not be held responsible for
mechanical failure, system malfunction, unit breakdown or accidents caused by
failure to follow the instructions.
Follow the instructions below to prevent abrasive components contained in
sandpaper and cutting tools from entering the refrigerant circuit because
those components can cause failures of the compressor and valves.
· To deburr pipes, use a reamer or other deburring tools, not sandpaper. · To
cut pipes, use a pipe cutter, not a grinder or other tools that use abrasive
materials. · When cutting or deburring pipes, do not allow cutting chips or
other foreign matters to enter the pipes. · If cutting chips or other foreign
matters enter pipes, wipe them off the inside of the pipes.
Do not pump down the system when a gas leak has been detected.
· The intake of air or other gases causes abnormally high pressure in the
refrigeration cycle, which may cause explosion or injury.
2-2-1. Cautions for service
· Perform service after recovering the refrigerant left in unit completely. ·
Do not release refrigerant in the air. · After completing service, charge the
cycle with specified amount of refrigerant. · If moisture or foreign matter
might have entered the refrigerant piping during service, ensure to remove
them.
2-2-2. Additional refrigerant charge
When charging directly from cylinder · Check that cylinder for R410A on the
market is a syphon type. · Charging should be performed with the cylinder of
syphon stood vertically. (Refrigerant is charged from liquid phase.)
Unit
Electronic weighing scale
OCH800A_4
2-2-3. Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.
Tool name
1 Gauge manifold
Only for R410A
Specifications
Use the existing fitting specifications. (UNF1/2) Use high-tension side pressure of 768.7 psig (5.3 MPa·G) or over.
2 Charge hose
Only for R410A
3 Electronic weighing scale
Use pressure performance of 738.2 psig (5.09 MPa·G) or over.
4 Gas leak detector 5 Adaptor for reverse flow check
Use the detector for R134a, R407C or R410A. Attach on vacuum pump.
6 Refrigerant charge base
7 Refrigerant cylinder
Only for R410A Top of cylinder (Pink) Cylinder with syphon
8 Refrigerant recovery equipment
2-2-4. Cautions for refrigerant piping work
New refrigerant R410A is adopted for replacement inverter series. Although the
refrigerant piping work for R410A is the same as for R22, exclusive tools are
necessary so as not to mix with different kind of refrigerant. Furthermore as
the working pressure of R410A is 1.6 times higher than that of R22, their
sizes of flared sections and flare nuts are different.
Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to
use refrigerant piping with thickness shown below. (Never use pipes of 7/256
in [0.7 mm] or below.)
Piping diameter and thickness
Nominal dimensions (in) Outside diameter (mm)
1/4 3/8 1/2 5/8 3/4 7/8
1 1-1/8
6.35 9.52 12.70 15.88 19.05 22.2 25.4 28.58
Thickness (in [mm])
R410A
R22
1/32 [0.8]
1/32 [0.8]
1/32 [0.8]
1/32 [0.8]
1/32 [0.8]
1/32 [0.8]
5/128 [1.0]
5/128 [1.0]
5/128 [1.0]*
5/128 [1.0]
5/128 [1.0]*
5/128 [1.0]
5/128 [1.0]*
5/128 [1.0]
5/128 [1.0]*
5/128 [1.0]
- Use 1/2 H or H pipes.
Dimensions of flare cutting and flare nut The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that, R410A is a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrigerants. Therefore, to enhance airtightness and strength, flare cutting dimension of copper pipe for R410A has been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also has partly been changed to increase strength as shown below. Set copper pipe correctly referring to copper pipe flaring dimensions for R410A below. For 1/2 and 5/8 inch pipes, the dimension B changes. Use torque wrench corresponding to each dimension.
Dimension A
Flare cutting dimensions
Nominal dimensions (in) Outside diameter (mm)
1/4
6.35
3/8
9.52
1/2
12.70
5/8
15.88
3/4
19.05
Dimension B
Dimension
A
(
0 -0.4
)
(in
[mm])
R410A
R22
11/32-23/64 [9.1]
32/11-23/64 [9.0]
1/2-33/64 [13.2]
1/2-33/64 [13.0]
41/64-21/32 [16.6]
5/8-41/64 [16.2]
49/64-25/32 [19.7]
3/4-49/64 [19.4]
29/32-59/64 [23.3]
Flare nut dimensions
OCH800A_5
Nominal dimensions (in) Outside diameter (mm)
1/4
6.35
3/8
9.52
1/2
12.70
5/8
15.88
3/4
19.05
Dimension
B
(
0 -0.4
)
(in
[mm])
R410A
R22
43/64 [17.0]
43/64 [17.0]
7/8 [22.0]
7/8 [22.0]
1-3/64 [26.0]
15/16 [24.0]
1-9/64 [29.0]
1-1/16 [27.0]
1-27/64 [36.0]
Tools for R410A (The following table shows whether conventional tools can be used or not.)
Tools and materials Gauge manifold Charge hose
Use
Air purge, refrigerant charge and operation check
R410A tools Tool exclusive for R410A Tool exclusive for R410A
Can R22 tools be used ? Can R407C tools be used ?
Gas leak detector
Gas leak check
Tool for HFC refrigerant
Refrigerant recovery equipment
Refrigerant cylinder
Refrigerant recovery Refrigerant charge
Tool exclusive for R410A Tool exclusive for R410A
Applied oil
Apply to flared section
Ester oil, ether oil and
alkylbenzene oil (minimum amount)
Safety charger
Charge valve Vacuum pump
Flare tool
Bender Pipe cutter Welder and nitrogen gas cylinder Refrigerant charging
scale Vacuum gauge or thermistor vacuum gauge and vacuum valve
Charging cylinder
Prevent compressor
malfunction when charging refrigerant by spraying liquid refrigerant
Tool exclusive for R410A
Prevent gas from blowing out Tool exclusive for R410A when detaching charge hose
Vacuum drying and air purge
Tools for other refrigerants
can be used if equipped with adopter for reverse flow check
Flaring work of piping
Tools for other refrigerants
can be used by adjusting flaring dimension
Bend the pipes
Tools for other refrigerants can be used
Cut the pipes
Tools for other refrigerants can be used
Weld the pipes
Tools for other refrigerants can be used
Refrigerant charge
Tools for other refrigerants can be used
Check the degree of vacuum. (Vacuum valve
prevents back flow of oil and refrigerant to thermistor
vacuum gauge)
Tools for other refrigerants can be used
Refrigerant charge
Tool exclusive for R410A
Ester oil, ether oil:
Alkylbenzene oil: minimum amount
(Usable if equipped with adopter for reverse flow)
(Usable if equipped with adopter for reverse flow)
(Usable by adjusting flaring dimension)
(Usable by adjusting flaring dimension)
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.) :
Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
- Follow the instructions below to prevent abrasive components contained in sandpaper and cutting tools from entering the refrigerant circuit because those components can cause failures of the compressor and valves. · To deburr pipes, use a reamer or other deburring tools, not sandpaper.
· To cut pipes, use a pipe cutter, not a grinder or other tools that use abrasive materials.
· When cutting or deburring pipes, do not allow cutting chips or other foreign matters to enter the pipes. · If cutting chips or other foreign matters enter pipes, wipe them off the inside of the pipes.
OCH800A_6
OVERVIEW OF UNITS
3-1. Auxiliary heating on/off control set-up
Auxiliary heating operation controls another heat source that depends on the
main system’s operations, which means the interlock operation shown in 2 below
will be possible.
1. Indoor unit must be R410A UL model for this function to operate. 2.
Different indoor unit applications that can be applied:
Outdoor unit DIPSW5-4 for auxiliary heating control: · Set DIP SW5-4 when the
power of the unit is turned off.
– OFF: Auxiliary heating function is disabled. (Initial setting) – ON :
Auxiliary heating function is enabled.
Determine required indoor fan speed during defrost mode: · To set the fan speed, see the chapter referring to heater control in the indoor unit’s Technical & Service Manual.
Determine fan speed setting during indoor thermo-OFF conditions: · These settings are done within indoor DIP SW1-7 and DIP SW1-8. See the chart below for options. · Recommended SW1-7 OFF and SW1-8 ON will determine airflow based on “Setting on the remote controller”.
Auxiliary heating signal
Fan speed setting
Fan speed setting
Thermo condition
OFF
ON
SW1-7 OFF ON OFF
SW1-8 OFF OFF ON
Very low
Low Setting on remote controller
Setting on remote controller
ON
ON
Stopped
Setting outdoor unit and auxiliary heat switch over temperatures When the DIP
SW 5-4 is set to “ON”, the outdoor unit and the contact output operates as
shown below. · Outdoor default setting and operations are shown below:
OCH800A_7
Amb. decreasing Amb. increasing
Stage 1 – Outdoor unit HP operation – Defrost : Heater contact ON signal –
Other than defrost : Contact OFF
Stage 2 – Outdoor unit HP operation – Heater contact ON signal
Stage 3 – Outdoor unit OFF (Standby) – Heater contact ON signal
a
b
c
d
TH7 = Outdoor temperature
-25°C
0°C
10°C
20°C
[-13°F] [32°F] [50°F] [68°F]
When the set temperature ranges overlap, the previously set pattern (1, 2 or 3) has a priority. The stage 1 has the highest priority, 2 the second and then 3. · Based on above chart listed the sequence of operation on “On ambient decrease”
– Stage 1: (TH7 = > 50°F [10°C]): the outdoor unit runs in HP mode.
– Stage 2: (TH7 = 50 to -13°F [10 to -25°C]): the outdoor unit runs in HP mode with auxiliary heating.
– Stage 3: (TH7 = < -13°F [-25°C]): Auxiliary heating only (Outdoor unit is OFF).
· Based on above chart listed the sequence of operation on “On ambient increase”
– Stage 3: (TH7 = < 32°F [0°C]): Auxiliary heating only (Outdoor unit is OFF).
– Stage 2: (TH7 = > 32 to 68°F [0 to 20°C]): Auxiliary heating with outdoor unit in HP mode.
– Stage 1: (TH7 = > 68°F [20°C]): Outdoor unit in HP mode only.
Locally procured wiring · A basic connection method is shown.
(i.e. interlocked operation with the electric heater with the fan speed
setting on high)
Remote control Board
Relay circuit
Adapter Red 1
Indoor unit control board
CN24
Outdoor unit control board
Dip switch SW5-4 “ON”
Electric Heater power source Green Yellow
X
Electric Heater
X +
White 2 Red 1
Red 2
CN22
Preparations in the field
Maximum cable length is 10 m (32ft)
· For relay X, use the specifications given below operation coil. Use the
diode that is recommended by the relay manufacturer at both ends of the relay
coil. – Rated voltage: 12 V DC
– Power consumption: 0.9W or less · The length of the electrical wiring for
the PAC-YU24HT is 2 meters (6-1/2 ft) · To extend this length, use sheathed
2-core cable. Do not extend the cable more than 10 meters (32 ft).
– Control cable type: CVV, CVS, CPEV, or equivalent – Cable size: 0.5 mm² to
1.25 mm² (AWG22 to AWG16) · Recommended circuit
R
1-phase power supply
S
208V, 230V/60Hz R
S
Wiring diagram
Control board
88H
FS1
88H
FS2 FS1
FS2 88H
CN24
H1 H2 26H
FS1, 2 —– Thermal fuse
H1, H2 —– Heater
26H ——— Overheat protection thermostat
88H ——— Electromagnetic contactor
OCH800A_8
3-2. System construction
Outdoor unit
Applicable indoor unit
Capacity class Number of units Total system capacity range
8HP (6 ton) SM72TAM
04 to 72 1 to 23
10HP (8 ton) SM96TAM 04 to 96 1 to 30
50 to 130% of outdoor unit capacity
12HP (10 ton) SM120TAM
Model name Number of branches
CMY-Y62-G-E, CMY-Y62GA-E 2
CMY-Y64-G-E 4
CMY-Y68-G-E 8
Connectable indoor unit lineup
Model type
Model name
04 05 06 08 12 15 18 24 27 30 36 48 54 72 96
Ceiling Cassette
4-way flow PLFY-EP
2 by 2
PLFY-P
NEMU-E NFMU-E
1-way flow PMFY-P NBMU-E
Ceiling concealed
PEFY-P NMAU
NMSU-E
NMHU-E
NMHSU-E
Wall mounted
PKFY-P NKMU-E
NLMU-E
Ceiling suspended
PCFY-P NKMU-E
Floor standing Exposed PFFY-P NEMU-E
Concealed PFFY-P NRMU-E
Multi-position 4-way air handling unit
PVFY-P NAMU-E
Remote controller
Name Model name Functions
M-NET remote controller
PAR-F27MEA-E, PAR-U01MEDU
· A handy remote controller for use in conjunction with the Melans centralized
management system.
· Address setting is required.
MA remote controller PAR-21MAA, PAR-41MAA · Address setting is not required.
OCH800A_9
3-3. System construction (Branch box system)
Outdoor unit Applicable indoor unit
Horsepower
Model name
Nominal capacity Cooling
(kBtu/h)
Heating
Refrigerant
Capacity class
Number of units
Total system capacity range
Branch box that can be connected Number of units
8 HP (6 ton) SM72TAM
72 80
21 to 12 (6)2, 3, 4
36 to 93 kBtu/h
10 HP (8 ton) SM96TAM 96 108 R410A 06 to 36
2 to 12 (8)2, 3, *4 50 to 130% of outdoor unit capacity 48 to 124 kBtu/h
1 to 3
12 HP (10 ton) SM120TAM 120 135
2 to 12 (10)2, 3, *4
60 to 156 kBtu/h
Connectable indoor unit lineup (Heat pump inverter type)
Model type
Model name
06 09 12 15 18 24 30 36
Wall-mounted
Deluxe
MSZ-FH·NA
MSZ-FH·NA2
MSZ-FS·NA
Standard
MSZ-GL·NA
Designer
MSZ-EF·NA(W/B/S)
Ceiling concealed Low static pressure SEZ-KD·NA
P-series Middle static pressure
PEAD-A·AA
4-way ceiling cassette
P-series 2222 P-series 3333
SLZ-KF·NA PLA-A·EA
1-way ceiling cassette
MLZ-KP·NA(2)
Floor standing
MFZ-KJ·NA
Standard multi-position air handler
SVZ-KP·NA
Branch box
Number of branches (Indoor unit that can be connected)
PAC-MKA52BC 5 (MAX. 5 units)
Note: · A maximum of 3 branch boxes can be connected to 1 outdoor unit.
PAC-MKA32BC 3 (MAX. 3 units)
2-branch pipe (joint), optional parts Using 1 branch box Using 2 or more branch boxes
Model name PAC-SG71RJ-E PAC-SL02RJ-E MSDD-50AR-E MSDD-50BR-E CMY-Y62-GA-E
Note For SM72/96TAM For SM120TAM Connection method: flare Connection method: brazing Connection method: brazing
Note: Select the appropriate model based on the capacity and the connection method.
Option
Optional accessories of indoor units and outdoor units are available.
1. Only one unit connection is possible with SVZ-series unit. 2. The number enclosed in parentheses is the maximum number of units that can be connected when 1 or more PLA-
A·EA units is connected. 3. When connecting PEAD-A24/30/36AA or SVZ series
unit, the maximum total capacity of the units that can be con-
nected each branch box is 60 kBtu/h. 4. When connecting an SVZ-series
unit(s), set additional constraints as follows. For connections other than
those spec-
ified below, consult your dealer.
Number of connecting SVZ-series unit
Constraints (For each connected branch box)
2
Any indoor units other than SVZ-series units are not connectable.
1
Only 1 PEAD can be included in the connection.
For connections other than those specified in 1 and 2, including connections with SVZ-series units, consult a dealer.
OCH800A_10
3-4. System Specifications
3-4-1. Outdoor Unit
Outdoor unit Nominal capacity Compressor (kW)
Model name Cooling (kBtu/h) Heating (kBtu/h)
SM72TAM 72 80 4.1
SM96TAM 96 108 5.3
SM120TAM 120 135 7.0
Cooling/Heating capacity indicates the maximum value at operation under the
following condition. Cooling Indoor: D.B. 80°F/W.B. 67°F (D.B. 26.7°C/W.B.
19.4°C)
Outdoor: D.B. 95°F/W.B. 75°F (D.B. 35°C/W.B. 23.9°C) Heating Indoor: D.B.
70°F/W.B. 60°F (D.B. 21.1°C/W.B. 15.6°C)
Outdoor: D.B. 47°F/W.B. 43°F (D.B. 8.3°C/W.B. 6.1°C)
3-4-2. Method for identifying MULTI-S model
MXZ SM 72 T AM U1
Multi type heat pump inverter outdoor unit
Smart Multi
Indicates equivalent to nominal cooling capacity. (kBtu/h)
Sub number
Control and refrigerant A: New A control and R410A Power supply T: 3-phase,
3-wire 208/230 V 60 Hz
OCH800A_11
SPECIFICATIONS
OCH800A_12
Outdoor model
MXZ-SM72TAM-U1
MXZ-SM96TAM-U1
MXZ-SM120TAM-U1
Indoor Model
Cooling capacity (Nominal)*1
kW
Power input
Btu/h kW
Current input A
(Rated)
kW Btu/h
Power input kW
Current input A
Heating capacity (Nominal)*2
kW
Btu/h
Power input kW
Current input A
(Rated)
kW
Power input
Btu/h kW
Current input A
Power source Breaker size Minimum Circuit Ampacity
(ODU only/ODU+IDU) A (ODU only/ODU+IDU) A
Maximum Overcurrent Protection (ODU only/ODU+IDU) A
Indoor unit
Total capacity
connectable
Model/ Quantity CITY MULTI
*3
Branch box
Sound pressure level (SPL) (measured in anechoic room)
Refrigerant piping Liquid pipe
diameter
Gas pipe
in (mm) in (mm)
Fan*5
Type × Quantity
Airflow rate
m³/min L/s
cfm
Control, Driving mechanism
Motor output kW
External static press.
Compressor
Type × Quantity Manufacturer
Starting method
Motor output kW Case heater kW
Lubricant
External finish
External dimension H × W × D
mm
in
Protection devices
High pressure protection Inverter circuit (COMP./FAN)
Compressor
Fan motor
Refrigerant
Type × original charge
Control
Net weight
lb (kg)
Heat exchanger
HIC circuit (HIC: Heat Inter-Changer)
Defrosting method
Standard attachment
Document Accessory
Optional parts
Guaranteed
Cooling
operation range Heating
D.B. W.B.
Remarks
Non-Ducted Ducted Non-Ducted Ducted Non-Ducted Ducted
21.1
28.1
35.2
72,000
96,000
120,000
5.67
8.16
10.7
16.6-15.0
23.9-21.6
31.3-28.3
20.2
27
33.4
69,000
92,000
114,000
4.88
5.07
6.93
7.31
9.35
9.53
14.3-12.9 14.8-13.4 20.2-18.3 21.4-19.3 27.3-24.7 27.8-25.2
23.4
31.7
39.6
80,000
108,000
135,000
5.36
7.61
9.87
15.7-14.2
22.2-20.1
28.8-26.1
22.6
30.2
37.8
77,000
103,000
129,000
4.86
5.12
6.86
7.24
9.11
9.21
14.2-12.8 15.0-13.5 20.0-18.1 21.2-19.1 26.6-24.1 26.9-24.3
3-phase 3-wire 208-230V 60Hz
40/60
50/70
32/50
47/65
58/76
84/102
50 to 130% of outdoor unit cooling rated capacity
04 – 72 / 23
04 – 96 / 30
04 – 96 / 30
06 – 36 / 12
06 – 36 / 12
06 – 36 / 12
53/54
58/59
61/62
3/8 (9.52) *4
3/8 (9.52)
7/8 (22.2)
1-1/8 (28.58)
Propeller Fan × 2
149
169
208
2,480
2,820
3,470
5,260
5,965
7,345
DC control
0.285 + 0.285
0 in.WG (0 Pa) / 0.12 in.WG (30 Pa)
Scroll hermetic compressor× 1
Siam Compressor Industry Co., Ltd.
Inverter
4.1
5.3
7.0
0
FVC68D 101oz. (3.0L)
Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1
1,662 × 1,050 × 460 (+45)
65-7/16 × 41-11/32 × 187/64 (+ 1-49/64)
High pressure switch
Overcurrent detection, Overheat detection (Heat sink thermistor)
Compressor thermistor, Overcurrent detection
Overheating, Voltage protection
R410A 9.3 kg
Linear expansion valve
432 (196)
Cross fin and copper tube
Double pipe heat exchanger
Reversed refrigerant circuit
Installation Manual
Joint pipe×1 set, Grounding lead wire ×1
Joint: CMY-Y62-G-E/CMY-Y62-GA-E, Header: CMY-Y64/68-G-E
-5 to 46°C [23 to 115°F]67*8
-20 to 15°C [-4 to 59°F]
*1. Nominal cooling conditions:
Indoor:
80°F D.B. /67 °F W.B. (26.7°C D.B./19.4°C W.B.)
Outdoor:
95°F D.B. (35.0°C D.B.)
*2. Nominal heating conditions:
Indoor:
70°F D.B. (21.1°C D.B.)
Outdoor:
47°F D.B./43°F W.B. (8.3°C D.B./6.1°C W.B.)
*3. It cannot be connected to mixed CITY MULTI indoor unit and branch box indoor unit.
*4. Liquid pipe diameter: 12.7mm, when further piping length is longer than 90m, and when PEFY-P72 or P96 is connected.
*5. It is possible to set the external static pressure to 30 Pa by Dip Switch.
6. 5 to 115°F D.B. (-15 to 46°C D.B.), when an optional Air Outlet Guide is installed. However, this condition does not apply to the indoor units listed in 7.
*7. 50 to 115°F (10 to 46°C) D.B.: When connecting PKFY-P06NBMU, PKFY-P08NHMU, PKFY-P04/06/08/12NLMU, PFFY-P06/08/12NEMU, and
PFFY-P06/08/12NRMU type indoor unit.
*8. When the temperature is below 50°F D.B. (10 °C D.B.) with branch box system, noise could potentially occur.
Notes:
· Nominal conditions 1, 2 are subject to AHRI 1230. · Due to continuing
improvement, above specifications are subject to change without notice. · See
the following for unit conversion: kcal/h = kW × 860, Btu/h = kW × 3,412, cfm
= m³/min × 35.31, lb = kg × 0.4536
Above specification data is subject to rounding variation. · Refer to the
indoor unit’s service manual for the indoor units specifications. · Details on
foundation work, duct work, insulation work, electrical wiring, power source
switch, and other items shall be referred to the Installation
Manual.
DATA
5-1. Selection of indoor and outdoor units
How to determine the capacity when less than or equal 100% indoor model size
units are connected in total:
The purpose of this flow chart is to select the indoor and outdoor units. For
other purposes, this flow chart is intended only for reference.
Determine the load (L) and the indoor/outdoor temperature.
Temporarily select the indoor/outdoor units. Reselect the indoor units Reselect the outdoor units
Indoor Unit
n
Total indoor units capacity (CTi) = (Individual nominal (rated) indoor unit
capacity CTik ×
k=1
Individual indoor temperature correction coef. k) (Figure 1, 4)
n: Total number of indoor units k: Indoor unit number
Outdoor Unit
Outdoor unit capacity (CTo) = Nominal outdoor unit capacity × Outdoor
temperature correction coef. (Figure 2, 5) × Piping length correction coef.
(Figure 3, 6) × Defrost correction coef.
(In heating operation, Table 1)
CTo CTi Yes
(If indoor to outdoor connectable capacity ratio is less than 100%, the
capacity correction is set as 100% )
No
Maximum capacity (CTmax) = CTo
No L CTo
Yes
Want to change to
Yes
smaller indoor units?
No
CTik × k
Individual indoor unit capacity: CTik = CTmax ×
n
(CTim × m)
m=1
Maximum capacity (CTmax) = CTi
No L CTi
Yes
Need to select smaller
Yes
outdoor units?
No
Does it fulfill the load of
No
each room?
Yes
Capacity Determination
Does it fulfill the load of
No
each room?
Yes Selecting units is completed.
Selecting units is completed.
ck: Outdoor unit power input coef. of k indoor unit room temp. (Refer to 4-2.)
Mk: Number part of the k indoor unit model (e.g. P80 80)
Average indoor temp. power input Coef. (Cave)
n
n
Cave
=
k=1
{C k
×
(Mk/ Mk)}
k=1
Average indoor temp. power input Coef. (Cave)
n
n
Cave
=
k=1
{C k
×
(Mk/ Mk)}
k=1
Input Calculation
OCH800A_13
Outdoor unit input = Nominal outdoor unit input × Cave
Outdoor unit input = Nominal outdoor unit input × Cave × (CTi)
(x) is the approximate correction function when less than or equal 100% model
size units are input as connected.
How to determine the capacity when greater than 100% indoor model size units
are connected in total
The purpose of this flow chart is to select the indoor and outdoor units. For
other purposes, this flow chart is intended only for reference.
Determine the load (L) and the indoor/outdoor temperature.
Temporarily select the indoor/outdoor units. Reselect the indoor units Reselect the outdoor units
Indoor Unit
n
Total indoor units capacity (CTi) = (Individual nominal (rated) indoor unit
capacity CTik ×
k=1
Individual indoor temperature correction coef. k) (Figure 1, 4)
n: Total number of indoor units k: Indoor unit number
Outdoor Unit Outdoor unit capacity (CTo) = Nominal outdoor unit capacity × G
(CTi)
Outdoor temperature correction coef. (Figure 2, 5) × Piping length correction
coef. (Figure 3, 6) × Defrost correction coef. (In heating operation, Table 1)
G (x) is the approximate correction function when greater than 100% model size
units are connected. G (x) refers to “Standard capacity diagram”.
No CTo CTi
Yes
Maximum capacity (CTmax) = CTo
No L CTo
Yes
Want to change to
Yes
smaller indoor units?
No
CTik × k
Individual indoor unit capacity: CTik = CTmax ×
n
(CTim × m)
m=1
Capacity Determination
Maximum capacity (CTmax) = CTi
No L CTi
Yes
Need to select smaller
Yes
outdoor units?
No
Does it fulfill the load of
No
each room?
Yes
Selecting units is completed.
Does it fulfill the load of
No
each room?
Nominal outdoor unit capacity
No
< Total indoor units capacity
Yes
Yes
Selecting units is completed. ck: Outdoor unit power input coef. of k indoor
unit room temp. (Refer to 4-2.) Mk: Number part of the k indoor unit model
(e.g. P80 80)
Outdoor unit input = Nominal outdoor unit input ×
Outdoor temperature correction coef. × (CTi )
(x) is the approximate correction function when less than or equal 100% model
size units are input as connected.
Average indoor temp. power input Coef. (Cave)
n
n
Cave
=
k=1
{C k
×
(Mk/ Mk)}
k=1
Average indoor temp. power input Coef. (Cave)
n
n
Cave
=
k=1
{C k
×
(Mk/ Mk)}
k=1
Input Calculation
Outdoor unit input = Nominal outdoor unit input × Cave × F (CTi)
Outdoor unit input = Nominal outdoor unit input × Cave × F (CTi)
F (x) is the approximate correction function when greater than 100% model size units are input as connected.
OCH800A_14
5-1-1. Cooling
Design condition Outdoor dry bulb temperature Total cooling load Room 1 Indoor
dry bulb temperature
Indoor wet bulb temperature Cooling load Room 2 Indoor dry bulb temperature
Indoor wet bulb temperature
Other
Cooling load Indoor/Outdoor piping equivalent length
98.6ºF (37.0ºC) 60.6 kBtu/h 80.6ºF (27.0ºC) 64.4ºF (20.0ºC) 27.2 kBtu/h 75.2ºF
(24.0ºC) 64.4ºF (19.0ºC)
33.4 kBtu/h 196 ft
Capacity of indoor unit
Model class of indoor unit 04 05 06 08 12 15 18 24 27 30 36 48 54 72 96 Model
capacity (kBtu/h) 4.0 5.0 6.0 8.0 12.0 15.0 18.0 24.0 27.0 30.0 36.0 48.0 54.0
72.0 96.0
Model name
06
SVZ
–
SLZ-KF
–
SEZ-KD
–
MFZ-KJ
–
MLZ-KP
–
MSZ-FH
6.0
MSZ-FS
6.0
MSZ-GL
6.0
MSZ-EF
–
PEAD
–
PLA
–
Capacity class
09
12
15
18
24
30
36
–
12.0
–
18.0 24.0 30.0 36.0
8.4 11.1 15.0
–
–
–
–
8.1 11.5 14.1 17.2
–
–
–
9.0 12.0 15.0 17.0
–
–
–
9.0 12.0
–
17.2
–
–
–
9.0 12.0 15.0 17.2
–
–
–
9.0 12.0 15.0 17.2
–
–
–
9.0 12.0 14.0 17.2 22.5
–
–
9.0 12.0 15.0 18.0
–
–
–
9.0 12.0 15.0 18.0 24.0 30.0 36.0
–
12.0
–
18.0 24.0 30.0 36.0
OCH800A_15
Cooling calculation
· Tentative selection of indoor units
Room1: PEFY-P30
30.0 kBtu/h (Nominal)
Room2: PEFY-P36
36.0 kBtu/h (Nominal)
In this case, the total capacity is 66.0. (30.0 + 36.0 = 66.0)
· Tentative selection of outdoor unit
Proper outdoor unit in this case is SM72TAM as the total capacity of the indoor units is 66.0.
SM72TAM
72.0 kBtu/h (Nominal)
· Calculation for the corrected capacity of the total indoor units (CTi)
Correction factor for indoor design wet bulb temperature: Room 1 (68.0°F) 1.02 (Refer to Figure 1 in 5-2-1.)
Room 2 (66.2°F) 0.95 (Refer to Figure 1 in 5-2-1.)
CTi = (Rated capacity of indoor unit × Correction factor for indoor temperature)
= 30.0 × 1.02 + 36.0 × 0.95
= 64.8 kBtu/h
· Calculation for the corrected capacity of the outdoor unit (CTo)
Correction factor for outdoor temperature (95.0°F)
1.00 (Refer to Figure 2 in 5-2-1.)
Correction factor for piping length (196 ft)
0.93 (Refer to Figure 5 in 5-5-1.)
CTo = Rated capacity of outdoor unit × Correction factor for outdoor temperature × Correction factor for piping length ×
G(CTi)*1
= 72.0 × 1.00 × 0.93
= 66.96 kBtu/h
*1. G(CTi) is used only when greater than 100% indoor model size are connected in total. Refer to Standard capacity diagram.
· Determination of maximum system capacity (CTx) Comparison between CTi and
CTo: CTi = 64.8 < CTo = 66.96, thus, select CTi. CTx = CTi = 64.8 kBtu/h
· Comparison with essential load Against the essential load 60.6 kW, the
maximum system capacity is 64.8 kW: A proper outdoor unit is selected.
· Calculation for the maximum indoor unit capacity of each room When CTx =
CTi, use the calculation formula below. Room1: Rated capacity of indoor unit ×
Correction factor for indoor design temperature = 30.0 × 1.02 = 30.6 kBtu/h
The capacity is enough for the cooling load of Room 1 (27.2 kBtu/h): A proper
indoor unit is selected. Room2: CTx × Indoor unit rating × Correction factor
for indoor design temperature = 36.0 × 0.95
= 34.2 kBtu/h The capacity is enough for the cooling load of Room 2 (33.4
kBtu/h): A proper indoor unit is selected.
Note: · Go on to the selection of units for heating after the selection for
cooling has successfully completed. If failed, try again until proper units
are selected.
5-1-2. Heating
Design condition
Outdoor wet bulb temperature
Total heating load
Room 1 Indoor dry bulb temperature
Heating load
Room 2 Indoor dry bulb temperature
Heating load
Other
Indoor/Outdoor piping equivalent length
35.6ºF (2.0ºC) 67.5 kBtu/h 69.8ºF (21.0ºC) 32.2 kBtu/h 73.4ºF (23.0ºC) 35.3 kBtu/h 196 ft
Capacity of indoor unit
Model class of indoor unit 04 05 06 08 12 15 18 24 27 30 36 48 54 72 96 Model
capacity (kBtu/h) 4.5 5.6 6.7 9.0 13.5 17.0 20.0 27.0 30.0 34.0 40.0 54.0 60.0
80.0 108.0
Model name
Capacity class
06
09
12
15
18
24
30
36
SVZ
–
–
12.0
–
18.0 27.0 34.0 40.0
SLZ-KF
–
10.2 13.7 17.1
–
–
–
–
SEZ-KD
–
10.9 13.6 18.0 17.2
–
–
–
MFZ-KJ
–
10.9 13.0 18.0 21.0
–
–
–
MLZ-KP
–
10.9 13.0
–
21.0
–
–
–
MSZ-FH
6.0 10.9 13.6 18.0 20.3
–
–
–
MSZ-FS
6.0 10.9 13.6 18.0 20.3
–
–
–
MSZ-GL
6.0 10.9 14.4 18.0 21.6 27.6
–
–
MSZ-EF
–
10.9 13.0 18.0 21.0
–
–
–
PEAD
–
10.9 13.5 15.7 18.0 26.0 34.0 40.0
PLA
–
–
13.5
–
18.0 26.0 34.0 40.0
Heating calculation
· Tentative selection of indoor units
Room1: PEFY-P30
34.0 kBtu/h (Nominal)
Room2: PEFY-P36
40.0 kBtu/h (Nominal)
In this case, the total capacity is 74.0. (34.0 + 40.0 = 74.0)
· Tentative selection of outdoor unit
Proper outdoor unit in this case is SM72TAM as the total capacity of the indoor units is 74.0.
SM72TAM
80.0 kBtu/h
· Calculation for the corrected capacity of the total indoor units (CTi)
Correction factor for indoor temperature: Room 1 (69.8°F)
1.00 (Refer to Figure 3 in 5-2-2.)
Room 2 (73.4°F)
0.92 (Refer to Figure 3 in 5-2-2.)
CTi = (Rated capacity of indoor unit × Correction factor for indoor temperature)
= 34.0 × 1.00 + 40.0 × 0.92
= 70.8 kW
· Calculation for the corrected capacity of the outdoor unit (CTo)
Correction factor for outdoor temperature (35.6°F WB)
1.00 (Refer to Figure 4 in 5-2-2.)
Correction factor for piping length (196 ft)
0.96 (Refer to Figure 8 in 5-5-2.)
Correction factor for defrosting
0.89 (Refer to Table 1.)
CTo = Rated capacity of outdoor unit × Correction factor for outdoor temperature × Correction factor for piping length ×
Correction factor for defrosting (× G(CTi))*1
= 80.0 × 1.00 × 0.96 × 0.89
= 68.35 kBtu/h
*1. G(CTi) is used only when greater than 100% indoor model size are connected in total. Refer to Standard capacity diagram.
OCH800A_16
Table 1 Table of correction factor for frosting and defrosting
Outdoor inlet air temp. [°F (°C) W.B.] 43(6) 37(4) 36(2) 32(0) 28(-2)
Correction factor
1.00 0.98 0.89 0.88 0.89
· Determination of maximum system capacity (CTx) Comparison between CTi and CTo: CTi = 70.8 > CTo = 68.35, thus, select CTo. CTx = CTo = 68.35 kBtu/h
25(-4) 0.90
21(-6) 0.95
18(-8) 14(-10) 5(-15) 0.95 0.95 0.95
-4(-20) -13(-25) 0.95 0.95
· Comparison with essential load Against the essential load 67.5 kBtu/h, the
maximum system capacity is 68.35 kBtu/h: Proper indoor units have been
selected.
· Calculation for the maximum indoor unit capacity of each room When CTx =
CTo, use the calculation formula below. Room1: CTx × Corrected capacity for
Room1/CTi = 68.35 × (34.0 × 1.00)/70.8 = 32.8 kBtu/h The capacity is enough
for the heating load of Room 1 (32.2 kW): A proper indoor unit is selected.
Room2: CTx × Corrected capacity for Room1/CTi = 68.35 × (40.0 × 0.92)/(70.8) =
35.5 kW The capacity is enough for the heating load of Room 2 (35.3 kW): A
proper indoor unit is selected.
Note: · The selection of units is completed when proper units are selected.
OCH800A_17
5-1-3. Power input of outdoor unit
· Outdoor unit: MXZ-SM72TAM · Indoor unit 1: PEFY-P30
Indoor unit 2: PEFY-P36
Cooling
· Nominal power input of outdoor unit
5.67 kW
· Calculation of the average indoor temperature power input coefficient
– Coefficient of the outdoor unit for indoor unit 1
(Outdoor temp. 98.6°F [37.0°C] D.B., Indoor temp. 64.4°F [18.0°C] W.B.)
0.93 (Refer to Figure 2 in 5-2-1)
– Coefficient of the outdoor unit for indoor unit 2
(Outdoor temp. 98.6°F [37.0°C] D.B., Indoor temp. 64.4°F [18.0°C] W.B.)
0.93 (Refer to Figure 2 in 5-2-1.)
n
n
– Average indoor temp. power input coefficient (Cave) =
{Ck × (Mk/ Mk)}
k=1
k=1
n: Total number of the indoor units
k: Number of the indoor unit
ck: Outdoor unit power input coefficient of k indoor unit room temp.
Mk: Number part of the k indoor unit model (e.g. P80: 80)
– Correction Coefficient of Indoor temperature = 0.93 × 30/(30 + 36) + 0.93 × 36/(30 + 36)
= 0.93
· Coefficient of the partial load (CTi)
Total indoor units capacity = 30 + 36 = 66, thus, (CTi) = 0.89 (Refer to the tables in 5-4. “Standard Capacity Dia-
gram”.)
· Outdoor power input (PIo)
Maximum System Capacity (CTx) = Total outdoor unit capacity (CTo), so use the following formula:
PIo = Outdoor unit cooling nominal power input × Correction coefficient of indoor temperature × (CTi)
= 5.67 × 0.93 × 0.89
= 4.69 kW
Heating
· Nominal power input of outdoor unit
5.36 kW
· Calculation of the average indoor temperature power input coefficient
– Coefficient of the outdoor unit for indoor unit 1 (Outdoor temp. 35.6°F [2.0°C] W.B., Indoor temp. 69.8°F [21.0°C]
D.B.)
1.20 (Refer to Figure 4 in 5-2-2.)
– Coefficient of the outdoor unit for indoor unit 2 (Outdoor temp. 35.6°F [2.0°C] W.B., Indoor temp. 73.4°F [23.0°C]
D.B.)
1.04 (Refer to Figure 4 in 5-2-2.)
n
n
–
Average
indoor
temp.
power
input
coefficient
(Cave)
=
{Ck
k=1
×
(Mk/ Mk)} k=1
n: Total number of the indoor units
k: Number of the indoor unit
ck: Outdoor unit power input coefficient of k indoor unit room temp.
Mk: Number part of the k indoor unit model (e.g. P80: 80)
– Correction Coefficient of Indoor temperature = 1.20 × 30/(30 + 36) + 1.04 × 36/(30 + 36)
= 1.11
· Coefficient of the partial load (CTi)
Total indoor units capacity = 30 + 36 = 66, thus, (CTi) = 0.9 (Refer to the tables in 5-4. “Standard capacity diagram”.)
· Outdoor power input (PIo)
Maximum System Capacity (CTx) = Total Indoor unit capacity (CTi), so use the following formula
PIo = Outdoor unit heating nominal power input × Correction coefficient of indoor temperature × (CTi)
= 5.36 × 1.11 × 0.9
= 5.35 kW
5-2. Correction by temperature
The outdoor units have varied capacity at different designing temperature.
With the nominal cooling/heating capacity value and the ratio below, the
capacity can be observed at various temperature.
5-2-1. Cooling
1.2
Correction factor of cooling capacity
1.0
0.8
0.6
0.459 15
60.8 62.6 64.4 66.2 68 69.8 71.6 73.4 75.2 [°FW.B.] 16 17 18 19 20 21 22 23 24 [°CW.B.] Indoor Temperature
<Figure 1> Indoor unit temperature correction
Correction factor of cooling capacity
1.3 1.2 1.1 1.0 0.9 0.8 0.7 0.6 0.5 0.4 5
-15
1.2
1.0
Indoor Temperature 67.0°F (19.4°C) W.B.
14
23
32
41
50
59
68
77
-10
-5
0
5
10
15
20
25
Outdoor Temperature
68.0°F (20.0°C) W.B. 75.2°F (24.0°C) W.B. 72.0°F (22.0°C) W.B.
86
95
104
113 [°F D.B.]
30
35
40
45 [°C D.B.]
Indoor Temperature
0.8
0.6
67.0°F (19.4°C) W.B.
64.0°F (18.0°C) W.B.
0.4
61.0°F (16.0°C) W.B.
0.2
0.0 5
14
23
32
41
50
59
68
77
86
95
104 113 118 [°F D.B.]
-15 -10
-5
0
5
10
15
20
25
30
35
40
45 48 [°C D.B.]
Outdoor Temperature
<Figure 2> Outdoor unit temperature correction
Correction factor of power input
OCH800A_18
Correction factor of heating capacity
5-2-2. Heating
1.3 1.2 1.1 1.0 0.9 0.8 0.7 0.6
59 60.8 62.6 64.4 66.2 68 69.8 71.6 73.4 75.2 77 78.8 80.6 [°F D.B.] 15 16 17
18 19 20 21 22 23 24 25 26 27 [°C D.B.] Indoor temperature
Correction factor of heating capacity
<Figure 3> Indoor unit temperature correction
1.4
1.3
1.2
1.1
1.0
0.9
0.8 0.7
0.6
0.5
0.4
-13
-4
5
14
23
32
-25
-20
-15
-10
-5
0
Outdoor Temperature
1.4
1.2 1.0
0.8
0.6
0.4
0.2
0.0
-13
-4
5
14
23
32
-25
-20
-15
-10
-5
0
Outdoor Temperature
70.0°F (21.1°C) D.B.
41
50
59 [°F W.B.]
5
10
15 [°C W.B.]
70.0°F (21.1°C) D.B. 61.0°F (16.0°C) D.B. 79.0°F (26.0°C) D.B.
41
50
59 [°F W.B.]
5
10
15 [°C W.B.]
Correction factor of power input
<Figure 4> Outdoor unit temperature correction
OCH800A_19
5-3. Standard operation data (Reference data)
Operation
MXZ-SM72TAM-U1
MXZ-SM96TAM-U1
MXZ-SM120TAM-U1
Operating Ambient Indoor
DB/WB
80°F/67°F
70°F/60°F
80°F/67°F
70°F/60°F
80°F/67°F
70°F/60°F
conditions temperature
(26.7°C/19.4°C) (21.1°C/15.6°C) (26.7°C/19.4°C) (21.1°C/15.6°C) (26.7°C/19.4°C) (21.1°C/15.6°C)
Outdoor
95°F/75°F
47°F / 43°F
95°F/ 75°F
47°F/43°F
95°F/75°F
47°F/43°F
(35.0°C/23.9°C) (8.3°C/6.1°C) (35.0°C/23.9°C) (8.3°C/6.1°C) (35.0°C/23.9°C) (8.3°C/6.1°C)
Indoor unit No. of connected Unit units
6
8
10
No. of units in operation
6
8
10
Model
—
12 × 6
12 × 8
12 × 10
Piping
Main pipe
Ft (m)
15 (4.6)
15 (4.6)
15 (4.6)
Branch pipe
35 (10.7)
35 (10.7)
60 (18.3)
Total pipe length
225 (68.6)
295 (89.9)
615 (187.5)
Fan speed
—
Hi
Hi
Hi
Amount of refrigerant
LBS. OZ. (kg)
30 LBS. 39 OZ. (13.8)
33 LBS. 41 OZ. (15.2)
39 LBS. 116 OZ. (17.8)
Outdoor Electric current
A
16.6
15.7
23.9
22.2
31.3
28.8
unit
Voltage
V
230
230
230
Compressor frequency
Hz
46
55
63
77
79
97
LEV
Indoor unit
opening
Pulse
214
221
208
235
249
254
Pressure High pressure/Low pressure psig
403/148
330/99
403/145
335/93
442/139
331/88
(MPaG)
(2.78/1.02)
(2.28/0.68)
(2.78/1.00)
(2.31/0.64)
(3.05/0.96)
(2.28/0.61)
Temp. of Outdoor Discharge
°F (°C)
145.9
134.1
159.2
135.6
158.3
148.6
each
unit
(63.3)
(56.7)
(70.6)
(57.5)
(70.2)
(64.8)
section
Heat exchanger
103.4
31.3
98.9
29.0
103.7
28.8
outlet
(39.7)
(-0.4)
(37.2)
(-1.7)
(39.8)
(-1.8)
Accumulator inlet
52.6
31.3
52.0
29.0
50.0
28.8
(11.4)
(-0.4)
(11.1)
(-1.7)
(10.0)
(-1.8)
Compressor inlet
52.1 (11.1)
30.6 (-0.8)
51.0 (10.6)
27.7 (-2.4)
48.4 (9.1)
25.3 (-3.7)
Indoor unit LEV inlet
88.2
83.0
82.1
83.5
90.7
82.4
(31.2)
(28.3)
(27.8)
(28.6)
(32.6)
(28.0)
Heat exchanger
54.0
125.3
53.7
127.3
54.1
145.6
inlet
(12.2)
(51.8)
(12.0)
(52.9)
(12.3)
(63.1)
OCH800A_20
5-4. Standard capacity diagram
Before calculating the sum of total capacity of indoor units, please convert
the value into the Btu/h model capacity following the formula on “5-1.
Selection of indoor and outdoor units”.
MXZ-SM72TAM-U1
Cooling
G(x)
1.4
1.2
Ratio of capacity
1.0
0.8
0.6
0.4
0.2
0.0 0
6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96
Total capacity of indoor units (kBtu/h)
1.4
Ratio of power input
1.2
1.0
0.8
0.6
0.4
0.2
0.0 0
6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96
Total capacity of indoor units (kBtu/h)
Ratio of current
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0
6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96
Total capacity of indoor units (kBtu/h)
208, 230 V
OCH800A_21
Ratio of capacity
Ratio of power input
Heating G(x)
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0
6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96
Total capacity of indoor units (kBtu/h)
6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96
Total capacity of indoor units (kBtu/h)
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0
6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96
Total capacity of indoor units (kBtu/h)
208, 230 V
Ratio of current
OCH800A_22
MXZ-SM96TAM-U1
Cooling
G(x)
Ratio of capacity
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132
Total capacity of indoor units (kBtu/h)
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132
Total capacity of indoor units (kBtu/h)
Ratio of power input
Ratio of current
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132
Total capacity of indoor units (kBtu/h)
208, 230 V
OCH800A_23
Heating
G(x)
1.4 1.2
Ratio of capacity
1.0
0.8
0.6
0.4
0.2
0.0 0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132
Total capacity of indoor units (kBtu/h)
1.4
Ratio of power input
1.2
1.0
0.8
0.6
0.4
0.2
0.0 0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132
Total capacity of indoor units (kBtu/h)
Ratio of current
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132
Total capacity of indoor units (kBtu/h)
208, 230 V
OCH800A_24
MXZ-SM120TAM-U1 Cooling
G(x)
Ratio of capacity
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132 138
144 150 156 162
Total capacity of indoor units (kBtu/h)
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132 138
144 150 156 162
Total capacity of indoor units (kBtu/h)
Ratio of power input
Ratio of current
1.4
1.2
1.0
208, 230 V
0.8
0.6
0.4
0.2
0.0 0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132
138 144 150 156 162
Total capacity of indoor units (kBtu/h)
OCH800A_25
Ratio of capacity
Ratio of power input
Heating
G(x)
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132 138
144 150 156 162 Total capacity of indoor units (kBtu/h)
1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0
0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132 138
144 150 156 162 Total capacity of indoor units (kBtu/h)
1.4 1.2
208, 230 V 1.0 0.8 0.6 0.4 0.2 0.0
0 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120 126 132 138
144 150 156 162 Total capacity of indoor units (kBtu/h)
OCH800A_26
Ratio of current
5-5. Correcting capacity for changes in the length of refrigerant piping
During cooling, obtain the ratio (and the piping equivalent length) of the
outdoor units nominal capacity and the total inuse indoor capacity, and find
the capacity ratio corresponding to the standard piping length from Figure 5
to 7. Then multiply by the cooling capacity from Figure 1 and 2 in “5-2.
Correction by temperature” to obtain the actual capacity. During heating, find
the piping equivalent length, and find the capacity ratio corresponding to
standard piping length from Figure 8 to 10. Then multiply by the heating
capacity from Figure 3 and 4 in “5-2. Correction by temperature” to obtain the
actual capacity.
Capacity Correction Curve
5-5-1. Cooling MXZ-SM72TAM-U1
1.00
Total capacity of indoor unit [kBtu/h] 36
0.95 54
0.90
Capacity ratio
72 0.85
93.6 0.80
0.75
0.70 0
50
100
150
200
250
300
350
400
450
500
Piping equivalent length (ft)
<Figure 5> Correction of refrigerant piping length
MXZ-SM96TAM-U1
1.00 0.95 0.90
Total capacity of indoor unit [kBtu/h] 48
72
Capacity ratio
0.85
0.80
96
124.8 0.75
0.70 0
50
100
150
200
250
300
350
400
450
500
Piping equivalent length (ft)
<Figure 6> Correction of refrigerant piping length
OCH800A_27
MXZ-SM120TAM-U1
1.00 0.95 0.90 0.85
Total capacity of indoor unit [kBtu/h] 60 90
120 156
Capacity ratio
0.80
0.75
0.70 0
50
100
150
200
250
300
350
400
450
500
Piping equivalent length (ft)
<Figure 7> Correction of refrigerant piping length
5-5-2. Heating MXZ-SM72TAM-U1
1.00
0.95
0.90
Capacity ratio
0.85
0.80
0.75
0.70 0
50
100
150
200
250
300
350
400
450
500
Piping equivalent length (ft)
<Figure 8> Correction of refrigerant piping length
OCH800A_28
MXZ-SM96TAM-U1
1.00
0.95
0.90
Capacity ratio
0.85
0.80
0.75
0.70 0
50
100
150
200
250
300
350
400
450
500
Piping equivalent length (ft)
<Figure 9> Correction of refrigerant piping length
MXZ-SM120TAM-U1
1.00
0.95
0.90
Capacity ratio
0.85
0.80
0.75
0.70 0
50
100
150
200
250
300
350
400
450
500
Piping equivalent length (ft)
<Figure 10>Correction of refrigerant piping length
Method for obtaining the piping equivalent length Piping equivalent length = piping length to the farthest indoor unit + 0.3 × number of bends in the piping (m)
5-5-3. Correction of heating capacity for frost and defrosting
If heating capacity has been reduced due to frost formation or defrosting,
multiply the capacity by the appropriate correction factor from the following
table to obtain the actual heating capacity.
Correction factor diagram
Outdoor Intake temperature [°F(°C)WB] Correction factor
43(6) 37(4) 36(2) 32(0) 28(-2) 25(-4) 21(-6) 18(-8) 14(-10) 5(-15) 1.00 0.98 0.89 0.88 0.89 0.90 0.95 0.95 0.95 0.95
-4(-20) -13(-25)
0.95
0.95
OCH800A_29
5-6. Noise criterion curves
MXZ-SM72TAM-U1
MODE SPL(dB) COOLING 53 HEATING 54
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70 NC-70
60 NC-60
50 NC-50
40 NC-40
30 NC-30
APPROXIMATE
20 THRESHOLD OF
HEARING FOR CONTINUOUS NOISE
NC-20
10 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
MXZ-SM120TAM-U1
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
MODE SPL(dB) COOLING 61 HEATING 62
LINE
90
80
70 NC-70
60 NC-60
50 NC-50
40 NC-40
30 NC-30
APPROXIMATE
20 THRESHOLD OF
HEARING FOR CONTINUOUS NOISE
NC-20
10 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
MICROPHONE 3 ft (1m)
UNIT
4 ft (1.5m)
MXZ-SM96TAM-U1
90
MODE SPL(dB) COOLING 58 HEATING 59
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
80
70 NC-70
60 NC-60
50 NC-50
40 NC-40
30 NC-30
APPROXIMATE
20 THRESHOLD OF
HEARING FOR CONTINUOUS NOISE
NC-20
10 63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
OCH800A_30
GROUND
OUTLINES AND DIMENSIONS
Unit: mm
OCH800A_31
7 WIRING DIAGRAM
OCH800A_32
TROUBLESHOOTING
8-1. Checkpoints for test run
8-1-1. Procedures before test run
1. Before a test run, make sure that the following work is completed. ·
Installation related: Make sure that the panel of cassette type is installed
and electrical wiring is done. Otherwise electrical functions like auto vane
will not operate normally. · Piping related: Perform leakage test of
refrigerant and drain piping. Make sure that all joints are perfectly
insulated. Check stop valves on both liquid and gas sides are fully open. ·
Electrical wiring related: Check ground wire, transmission cable, remote
controller cable, and power supply cable for secure connection. Make sure that
all switch settings of address or adjustments for special specification
systems are correctly made.
2. Safety check: · With the insulation tester of 500 V, inspect the
insulation resistance. · Do not touch the transmission cable and remote
controller cable with the tester. · The resistance should be over 1.0 M. Do
not proceed inspection if the resistance is less than 1.0 M. · Inspect between
the outdoor unit power supply terminal block and ground first, metallic parts
like refrigerant pipes or the electrical box next, then inspect all electrical
wiring of outdoor unit, indoor unit, and all linked equipment.
3. Before operation: · For compressor protection, turn on the breaker for the
outdoor unit and wait at least 12 hours before a test run. – The unit might
NOT run, in order to protect the compressor, in the case of low outside air
temperature.* · Register control systems into remote controller(s). Never
touch the on/off switch of the remote controller(s). Refer to Special function
operation setting (for M-NET Remote Controller) as for settings. In MA remote
controller(s), this registration is unnecessary.
4. More than 12 hours later after turning on the power to the outdoor unit,
turn on all the power switches for the test run. Perform test run and make
test run reports.
Caution:
- The compressor may not operate immediately after recovery from power failure. Refer to “SW6-3” in 8-5. “Internal switch function table” for how to deal with it.
8-1-2. Test run for M-NET remote controller
Refer to “Test run” for operation procedure.
OCH800A_33
8-1-3. Countermeasures for error during test run
If a problem occurs during test run, a code number will appear on the remote
controller (or LED on the outdoor unit), and the air conditioning system will
automatically cease operating. Determine the nature of the abnormality and
apply corrective measures.
Make sure to turn the power OFF before connecting/disconnecting any
connectors, or replacing boards.
Error Error
code code (2 digits) (4 digits)
Trouble
Ed
0403 Serial communication error/Model selection SW error
U2
1102 Compressor temperature trouble
UE
1302 High pressure trouble or compressor protector trouble
U7
1500 Superheat due to low discharge temperature trouble
U2
1501 Refrigerant shortage trouble
Closed valve in cooling mode
P6
1503 Freeze protection of plate heat exchanger
Freeze protection of branch box or indoor unit
EF
1508 4-way valve trouble in heating mode
L6
2135 Circulation water freeze protection
PA
2500 Water leakage
P5
2502 Drain overflow protection
P4
2503 Drain sensor abnormality
–
3121 Out-of-range outside air temperature
UF
4100 Compressor current interruption (locked compressor)
Pb
4114 Fan trouble (Indoor unit)
UP
4210 Compressor overcurrent interruption/Failure in 12 VDC
power supply circuit on power circuit board
U9
4220 Voltage shortage/overvoltage/PAM error/L1 open
phase/primary current sensor error/power synchroni-
zation signal error
U5
4230 Heat sink temperature trouble
U6
4250 Power module trouble
U8
4400 Fan trouble (Outdoor unit)
Detected Unit
Indoor
Outdoor
Remote Controller
Remarks
Outdoor unit outdoor multi controller circuit
board Power circuit board communication
trouble, Incorrect setting of model selection
Check delay code 1202
Check delay code 1402
Check delay code 1600
Check delay code 1601
Check delay code 1501
Check delay code 1608
Check delay code 4350
Check delay code 4320
Check delay code 4330
Check delay code 4350
Check delay code 4500
Error Error
code code (2 digits) (4 digits)
Trouble
U3
5101 Air inlet thermistor (TH21) open/short
Compressor temperature thermistor (TH4) open/short
U4
5102 Liquid pipe temperature thermistor (TH22) open/short
Suction pipe temperature thermistor (TH6) open/short
U4
5103 Gas pipe temperature thermistor (TH23) open/short
U4
5105 Outdoor liquid pipe temperature thermistor (TH3)
open/short
U4
5106 Ambient temperature thermistor (TH7) open/short
U4
5109 HIC pipe temperature thermistor (TH2) open/short
U4
5110 Heat sink temperature thermistor (TH8) open/short
F5
5201 High pressure sensor (63HS) trouble
F3
5202 Low pressure sensor (63LS) trouble
UH
5300 Primary current error
P4
5701 Contact failure of drain float switch
A0
6600 Duplex address error
A2
6602 Transmission processor hardware error
A3
6603 Transmission bus BUSY error
A6
6606 Signal communication error with transmission proces-
sor
A7
6607 No ACK error
A8
6608 No response frame error
E0/E4 6831 MA communication receive error
E3/E5 6832 MA communication send error
E3/E5 6833 MA communication send error
E0/E4 6834 MA communication receive error
EF
7100 Total capacity error
EF
7101 Capacity code error
EF
7102 Connecting excessive number of units and branch
boxes
EF
7105 Address setting error
EF
7130 Incompatible unit combination
Detected Unit
Indoor
Outdoor
Remote Controller
Remarks
Check delay code 1202
Check delay code 1211
Check delay code 1205
Check delay code 1221
Check delay code 1222
Check delay code 1214
Check delay code 1402
Check delay code 1400
Check delay code 4310
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only M-NET Remote controller is detected.
Only MA Remote controller is detected.
Only MA Remote controller is detected.
Only MA Remote controller is detected.
Only MA Remote controller is detected.
Notes: · When the outdoor unit detects No ACK error/No response error, the
target indoor unit is treated as a stop, and not assumed to be abnormal. · The
error codes displayed on the units may be different between the error source
and others. In that case, please refer to the error code of error source by
displayed attribute and address. · Refer to the service manual of indoor unit
or remote controller for the detail of error detected in indoor unit or remote
controller.
Self-diagnosis function The indoor and outdoor units can be diagnosed
automatically using the self-diagnosis switch (SW1) and LED1, LED2 (LED
indication) found on the outdoor multi controller circuit board. LED
indication: Set all contacts of SW1 to OFF.
During normal operation The LED indicates the drive state of the controller in the outdoor unit.
Bit
1
2
3
4
5
6
Indication
Compressor operated
52C
21S4
SV1
(SV2)
SV3
· Example When the compressor and SV1 are on during cooling operation.
1 23 45 67 8
7
8
—
Always lit
OCH800A_34
0403 (Ed): Serial communication error / Model selection SW error
Abnormal points and detection methods
Serial communication between the outdoor multi controller circuit board and
outdoor power circuit board is defective.
Causes and checkpoints
· Wire breakage or contact failure of connector CN2 or CN4
· Malfunction of power board communication circuit on outdoor multi controller
circuit board
· Malfunction of communication circuit on outdoor power circuit board
· Incorrect setting of model selection
Diagnosis of failure
Check the connection of the communication line (CN2 and CN4) between the outdoor multi controller circuit board and power circuit board.
No
Are they connected normally?
Yes
Connect the CN2 and CN4 properly. Replace them in the case of breakage.
Check the wiring.
No
Is it connected normally?
Yes
No
Is the model setting correct?
Yes
Connect the wiring properly. Replace them in the case of breakage.
Correct the model settings.
The communication circuit of either the outdoor controller board or power
board is defective. If unable to identify the defective circuit; · Replace the
outdoor multi controller circuit
board if it does not recover. · Replace the outdoor power circuit board.
OCH800A_35
1102 (U2): Compressor temperature trouble
Chart 1 of 2
Abnormal points and detection methods
· TH4 falls into either of the following temperature conditions: – over 230°F
(110°C) continuously for 5 minutes – over 257°F (125°C)
· The saturation temperature converted from the pressure detected by the high
pressure sensor exceeds 104°F (40°C) during defrosting, and TH4 exceeds 230°F
(110°C)
TH4: Thermistor
Causes and checkpoints
· Malfunction of stop valve · Over-heated compressor operation caused by
shortage
of refrigerant · Defective thermistor · Defective outdoor multi controller
circuit board · LEV performance failure · Defective indoor controller board ·
Clogged refrigerant system caused by foreign object · Refrigerant shortage
(Refrigerant liquid accumulation in
compressor while indoor unit is OFF/thermo-OFF.)
Diagnosis of failure
Is the error code 5101 displayed when restarted?
No (1102)
Yes (5101)
Refer to the diagnosis of error code 5101.
Is the outdoor stop valve (liquid/gas)
No
fully open?
Yes
Open the stop valve (liquid/gas) fully.
Is there refrigerant leak?
No
Yes
Repair the refrigerant leakage.
Check the connection for thermistor wiring and indoor controller board connector.
Is there any abnormality on connectors/wires such as disconnection, half-
disconnection or breakage?
No
Continue to the next page.
Yes
Connect the connector properly (Repair or replace it in the case of breakage).
OCH800A_36
1102 (U2): Compressor temperature trouble
Diagnosis of failure
Continued from the previous page.
Chart 2 of 2
Disconnect the thermistor wiring to check the resistance.
No
Is the resistance detected?
Yes
Check the voltage(*) and appearance of the outdoor multi controller circuit
board.
Is the voltage normal value?
No
Is it free from any trace of overheating
or burning?
Yes
Disconnect the indoor LEV wiring and check the resistance.
No
Is the resistance detected?
Yes
*For the voltage, refer to “How to check the components”.
Replace the thermistor.
Replace the outdoor multi controller circuit board.
Replace the indoor LEV. Replace the indoor controller board.
OCH800A_37
1302 (UE): High pressure trouble
Chart 1 of 4
Abnormal points and detection methods
· High pressure abnormality (63H operation) 63H operates() during compressor
operation. ( 602 psig [4.15 MPaG])
· High pressure abnormality (63HS detected) – A pressure detected by 63HS is
625 psig (4.31 MPaG) or more during compressor operation. – A pressure
detected by 63HS is 600 psig (4.14 MPaG) or more for 3 minutes during
compressor operation.
63H: High pressure switch 63HS: High pressure sensor LEV: Linear expansion
valve SV1: Solenoid valve TH7: Thermistor
Causes and checkpoints
· Faulty operation of stop valve (not fully open) · Clogged or broken pipe ·
Malfunction or locked outdoor fan motor · Short-cycle of outdoor unit · Dirt
of outdoor heat exchanger · Remote controller transmitting error caused by
noise
interference · Contact failure of the outdoor multi controller circuit
board connector · Defective outdoor multi controller circuit board · Short-
cycle of indoor unit · Decreased airflow, clogged filter, or dirt on indoor
unit · Malfunction or locked indoor fan motor · Decreased airflow caused by
faulty inspection of out-
door temperature thermistor (It detects lower temperature than actual
temperature.) · Indoor LEV performance failure · Malfunction of fan driving
circuit · SV1 performance failure · Defective High pressure sensor · Defective
High pressure sensor input circuit on outdoor multi controller circuit board ·
High compressor temperature (Thermal protector TRS operated)
Diagnosis of failure
OCH800A_38
Turn OFF the power of indoor/outdoor unit, Fresh Master, Lossnay and remote
controller simultaneously for 10 minutes, then turn the power back ON. Is the
error code <6607> No ANC error displayed ?
No
Is the error code 5201 displayed when restarted?
No (1302)
Is the outdoor stop valve (liquid/gas) fully open?
Yes
Yes
Yes (5201)
No
Does the outdoor fan rotate during the
No
operation?
Yes
Does the indoor fan rotate during the operation?
Yes
Is the indoor unit short-cycled?
No
Yes (Short-cycled)
No (Not short-cycled)
Continue to the next page.
There is abnormality in circuit board or wiring connection on the outdoor
unit.
Refer to the diagnosis of error code 5201.
Open the stop valve (liquid/gas) fully.
Check the outdoor fan motor. Refer to “How to check the parts” on the outdoor
unit service manual.
Check the indoor fan motor. Refer to “How to check the parts” on the indoor
unit service manual.
Resolve the short-cycle.
1302 (UE): High pressure trouble
Diagnosis of failure
Continued from the previous page.
Is the indoor unit filter clogged?
No (Not clogged)
Yes (Clogged filter)
Clean the filter.
Is there dirt on the indoor heat exchanger?
No (Not dirty)
Yes (Dirty)
Wash the indoor heat exchanger.
Is the outdoor unit short-cycled?
Yes (Short-cycled)
No (Not short-cycled)
Resolve the short cycle.
Is there dirt on the outdoor heat exchanger?
No (Not dirty)
Yes (Dirty)
Wash the outdoor heat exchanger.
Are the pipes clogged or broken?
No
Yes
Check and repair piping.
Disconnect the TH7 wiring and check the resistance.
Continue to the next page.
Chart 2 of 4
OCH800A_39
1302 (UE): High pressure trouble
Diagnosis of failure
Continued from the previous page.
No
Is the resistance detected?
Yes
Disconnect the indoor LEV wiring to check the resistance.
No
Is the resistance detected?
Yes
Replace the TH7. Replace the indoor LEV.
Check the voltage(*) and appearance of the indoor controller board.
Is the voltage normal?
No
Is it free from any trace of overheating
or burning?
Yes
Check the resistance of SV1.
Replace the indoor controller board.
Continue to the next page. *For the voltage, refer to “How to check the components”.
Chart 3 of 4
OCH800A_40
1302 (UE): High pressure trouble
Diagnosis of failure
Continued from the previous page.
No
Is the resistance detected?
Yes
Replace the SV1.
Is the connector for outdoor multi controller circuit board 63H disconnected
or loose?
No
Yes
Check the 63HS voltage.
Reconnect the connector or connect it tightly.
Chart 4 of 4
No
Is the voltage() detected?
Yes
For the voltage, refer to “How to check the components”.
Replace the 63HS.
Replace the outdoor multi controller circuit board.
OCH800A_41
1500 (U7): Superheat due to low discharge temperature trouble
Chart 1 of 2
Abnormal points and detection methods
10 or more minutes after the compressor starts operation, if a discharge
superheat of -27°F (-15°C)* or less is detected for 5 consecutive minutes even
though the indoor LEV has the minimum open pulse.
LEV: Linear expansion valve TH4: Thermistor
- At this temperature, conditions for the abnormality detection will not be satisfied if no abnormality is detected on either TH4 or 63HS.
Causes and checkpoints
· Disconnection or loose connection of TH4 · Defective holder of TH4 ·
Disconnection of LEV coil · Disconnection of LEV connector · LEV performance
failure
Diagnosis of failure
Is the TH4 wiring disconnected?
Yes (Disconnected)
No (Connected properly)
Check the resistance of TH4.
No
Is the resistance normal?
Yes
Connect the wiring properly.
temp. – resistance characteristic
32°F (0°C)
700 k
50°F (10°C)
410 k
68°F (20°C)
250 k
86°F (30°C)
160 k
104°F (40°C)
104 k
Replace the TH4.
Check the connector contact and wiring of the indoor LEV.
Is there any abnormality such as half-disconnection or breakage?
No
Yes
Disconnect the indoor LEV wiring to check the resistance.
Connect the connector properly, or replace the LEV.
Continue to the next page.
OCH800A_42
1500 (U7): Superheat due to low discharge temperature trouble
Chart 2 of 2
Diagnosis of failure
Continued from the previous page.
No
Is the resistance detected?
Yes
Check the voltage and appearance of the indoor controller board.
Replace the indoor LEV.
Is the voltage normal?
No
Is it free from any trace of overheating
or burning?
Yes
Check the 63HS voltage.
Replace the indoor controller board.
No
Is the voltage() detected?
Yes
For the voltage, refer to “How to check the components”.
Replace the 63HS.
Replace the outdoor multi controller circuit board.
OCH800A_43
1501 (U2): Refrigerant shortage trouble
Chart 1 of 2
Abnormal points and detection methods
· All of the following conditions have been satisfied for 15 consecutive
minutes: – The compressor is operating in HEAT mode. – Discharge superheat is
144°F (80°C) or more. – Difference between TH7 and TH3 fits the formula of
TH7-TH3 < 9°F (5°C) – The saturation temperature converted from the pressure
detected by the high pressure sensor is below 95°F (35°C).
· All of the following conditions have been satisfied: – The compressor is in
operation. – When cooling, discharge superheat is 144°F (80°C) or more, and
the saturation temperature converted from the pressure detected by the high
pressure sensor is over -40°F (-40°C). – When heating, discharge superheat is
162°F (90°C) or more.
Causes and checkpoints
· Defective operation of stop valve (not fully open) · Defective thermistor ·
Defective outdoor multi controller circuit board · Indoor LEV performance
failure · Gas leakage or shortage · Defective 63HS
TH3: Thermistor
Diagnosis of failure
Is the outdoor stop valve (ball valve)
No
fully open?
Yes
Is there refrigerant leak?
Yes
No
Is the error code 5104 displayed when restarted?
No (1501)
Yes (5104)
Check relevant thermistor wirings and connector contacts of the outdoor multi
controller circuit
board.
Open the stop valve (ball valve) fully. Repair the refrigerant leak. Refer to the diagnosis of error code 5104.
Is there any abnormality on connectors such as disconnection, half-
disconnection or breakage?
No
Yes
Disconnect the thermistor wiring and check the resistance.
Connect the connector properly (Repair or replace it in the case of breakage).
Continue to the next page.
OCH800A_44
1501 (U2): Refrigerant shortage trouble
Diagnosis of failure
Continued from the previous page.
No
Is the resistance detected?
Yes
Replace the thermistor.
Check the 63HS voltage.
No
Is the voltage(*) detected?
Yes
Check the voltage and appearance of the outdoor multi controller circuit
board.
Is the voltage normal value?
No
Is it free from any trace of overheating
or burning?
Yes
Disconnect the indoor LEV wiring and check the resistance.
No
Is the resistance detected?
Yes
*For the voltage, refer to “How to check the components”.
Replace the 63HS.
Replace the outdoor multi controller circuit board.
Replace the indoor LEV. Replace the indoor controller board.
Chart 2 of 2
OCH800A_45
1501 (U2): Closed valve in cooling mode
Abnormal points and detection methods
Stop valve is closed during cooling operation. Both of the following
temperature conditions have been satisfied for 20 minutes or more during
cooling operation.
TH22j-TH21j -3.6°F (-2°C) TH23j-TH21j -3.6°F (-2°C)
Note: · For indoor unit, the abnormality is detected if an operating unit
satisfies the condition.
Causes and checkpoints
· Outdoor liquid/gas valve is closed. · Malfunction of outdoor LEV (LEV1)
(blockage)
TH21: Indoor intake temperature thermistor (RT11 or TH1) TH22: Indoor liquid
pipe temperature thermistor (RT13 or TH2) TH23: Indoor gas pipe temperature
thermistor (TH-A to E) LEV: Linear expansion valve
Diagnosis of failure
Is the outdoor stop valve (liquid/gas)
No
fully open?
Yes
Open the outdoor stop valve (liquid/gas) fully.
Disconnect the outdoor LEV wiring to check the resistance.
No
Is the resistance detected?
Yes
Replace the outdoor LEV.
Replace the outdoor multi controller circuit board.
OCH800A_46
1503 (P6): Freeze protection of plate heat exchanger / Freeze protection of branch box or indoor unit
Abnormal points and detection methods
The purpose of the error code is to prevent indoor unit from freezing or
condensation which is caused when a refrigerant keeps flowing into the indoor
unit that is not operating.
All of the following conditions have been satisfied: · The compressor is
operating in COOL mode. · 15 minutes have passed after the startup of the com-
pressor, or the change in the number of operating indoor units is made
(including a change by turning thermo-ON/OFF). · After the condition 2 above
is satisfied, the thermistor of indoor unit in STOP detects TH22j 23°F (-5 °C)
for 5 consecutive minutes.
Causes and checkpoints
· Wrong piping connection between indoor unit and branch box
· Miswiring between indoor unit and branch box · Miswiring of LEV in branch
box · Malfunction of LEV in branch box
Diagnosis of failure
Check the port to which the piping and
wiring between the indoor unit and branch
No
box is connected.
Is the piping and wiring connected to the
same port?
Yes
Connect the piping and wiring to the same port.
Check the port to which the LEV wiring of branch box is connected.
No
Is the wiring connected to the same port as
the corresponding branch box?
Yes
Check the LEV wiring of indoor unit that is
No
not via branch box is connected properly.
Yes
Connect the LEV wiring to the intended port properly.
Connect the LEV wiring properly.
Disconnect the LEV wiring of branch box or indoor unit to check the
resistance.
No
Is the resistance detected?
Yes
Replace the LEV coil.
Replace the LEV assy in branch box or the LEV of indoor unit that is not via branch box.
OCH800A_47
1508 (EF): 4-way valve trouble in heating mode
Abnormal points and detection methods
4-way valve does not operate during heating operation. Any of the following
temperature conditions is satisfied for 3 minutes or more during heating
operation when the outdoor temperature is -4°F (-20°C) or more:
TH22j-TH21j -18°F (-10°C) TH23j-TH21j -18°F (-10°C) TH22j 37.4°F (3°C) TH23j
37.4°F (3°C)
Note: · For indoor unit, the abnormality is detected if an operating unit
satisfies the condition.
TH21: Indoor intake temperature thermistor (RT11 or TH1) TH22: Indoor liquid
pipe temperature thermistor (RT13 or TH2) TH23: Indoor gas pipe temperature
thermistor (TH-A to E)
Causes and checkpoints
· 4-way valve failure · Disconnection or failure of 4-way valve coil · Clogged
drain pipe · Disconnection or loose connection of connectors · Malfunction of
input circuit on outdoor multi controller
circuit board · Defective outdoor power circuit board
Diagnosis of failure
Is the connector for outdoor multi controller circuit board or 4-way valve
coil disconnected or loose?
No
Yes
Reconnect the connector or connect it tightly.
Disconnect the connector for outdoor multi
controller circuit board or 4-way valve coil to check the resistance.
No
Is the resistance detected?
Yes
Check the voltage and appearance of the outdoor multi controller circuit
board.
Is the detected voltage normal?
No
Is it free from any trace of over-heat-
ing or burning?
Yes
Refer to ”How to check the parts” for ohm values.
Replace the 4-way valve coil.
Replace the outdoor multi controller circuit board. Replace the 4-way valve.
OCH800A_48
3121: Out-of-range outside air temperature
Abnormal points and detection methods
· When the thermistor temperature of -24°F (-31.1°C) or below has continuously
been detected for 3 minutes during heating operation (during compressor
operation), the unit makes an error stop and “3121” appears on the LED1 and
LED2.
· The compressor restarts when the thermistor temperature is -14°F (-25.6°C)
or above.
· If the unit is turned OFF, the outdoor temperature error will be canceled.
Causes and checkpoints
· Outdoor air temperature · Thermistor failure · Wire failure · Defective
outdoor controller board
Diagnosis of failure
Check the outdoor air temperature.
Is the outdoor air temperature -24°F
No
(-31.1°C) or higher?
Yes
Check the resistance of TH7.
Use in operation range, which is -14°F (-25.6°C) or more in heating mode.
No
Is the resistance normal?
Yes
Check for pinched lead wire, condition of wire coating and disconnected wire.
No
Is wire condition normal?
Yes
Replace the TH7.
Remove the abnormal point. Replace the outdoor controller board.
OCH800A_49
4100 (UF): Compressor current interruption (Locked compressor)
Chart 1 of 2
Abnormal points and detection methods
Overcurrent of DC bus or compressor is detected within 30 seconds after the
compressor starts the operation.
Causes and checkpoints
· Closed stop valve · Decrease of power supply voltage · Looseness,
disconnection, or wrong phase of compres-
sor wiring connection · Incorrect DIP-SW setting of model selection on the
outdoor controller board · Defective compressor · Defective outdoor power
circuit board
Diagnosis of failure
Check the stop valve.
Is the stop valve (liquid/gas) fully
No
open?
Yes
Check the power supply voltage.
No
Is the power supply voltage normal?
Yes
Check if the model selection switches are set correctly on the indoor
controller board or outdoor multi controller circuit board.
No
Are they set properly?
Yes
Turn the power OFF to check for looseness, disconnection, or wrong phase of
compressor wiring connection.
Continue to the next page.
Open the stop valve (liquid/gas) fully.
· Check the looseness, disconnection, or breakage of compressor wiring.
· Ensure power supply from the facility. (Check for power supply open phase.)
Set the model selection switches correctly, then restart.
OCH800A_50
4100 (UF): Compressor current interruption (Locked compressor)
Chart 2 of 2
Diagnosis of failure
Continued from the previous page.
No
Are they connected properly?
Yes
Connect the compressor wiring (U, V and W phase) properly, then turn the power back ON.
Check whether the compressor is faultily grounded or not.
No
Is the compressor faultily grounded?
Yes
Replace the outdoor power circuit board (Defective outdoor power circuit board).
Replace the compressor (Defective compressor).
OCH800A_51
4210 (UP): Compressor overcurrent interruption/Failure in 12 VDC power supply
circuit on power circuit board
Chart 1 of 2
Abnormal points and detection methods
· Overcurrent of DC bus or compressor is detected 30 or more seconds after the
compressor starts the operation.
· 12 VDC power is not supplied from the 12 VDC supply circuit on the power
circuit board.
Causes and checkpoints
· Closed outdoor stop valve · Decrease of power supply voltage · Looseness,
disconnection, or wrong phase of compres-
sor wiring connection · Model selection error on indoor controller board or
out-
door multi controller circuit board · Defective compressor · Defective outdoor
power circuit board · Defective outdoor multi controller circuit board ·
Malfunction of indoor/outdoor unit fan · Short-cycle of indoor/outdoor unit
Diagnosis of failure
Which sub code is displayed?
8
Check the outdoor stop valve.
7
Replace the outdoor power circuit board
(Defective outdoor power circuit board).
The sub codes are displayed by an operation of SW1 on the outdoor multi controller circuit board.
SW1 Setting
ON OFF
12345678
Display on LED1,2 1 23 45 67 8
7: 12 V power supply circuit trouble 8: Overcurrent trouble
Is the stop valve (liquid/gas) fully
No
open?
Yes
Check whether the power supply voltage is normal or not.
Open the stop valve (liquid/gas) fully.
No
Is the power supply voltage normal?
Yes
Check if the model selection switches are set correctly on the indoor
controller board or outdoor multi controller circuit board.
No
Are they set properly?
Yes
Turn the power OFF to check for looseness, disconnection, or wrong phases of
the compressor wiring.
Continue to the next page.
· Check the looseness, disconnection, or breakage of compressor wiring.
· Ensure power supply from the facility. (Check for power supply open phase.)
Set the model selection switches correctly.
OCH800A_52
4210 (UP): Compressor overcurrent interruption/Failure in 12 VDC power supply
circuit on power circuit board
Chart 2 of 2
Diagnosis of failure
Continued from the previous page.
No
Are they connected properly?
Yes
Connect the compressor wiring (U, V and W phase) properly, then turn the power back ON.
Check the operation of indoor/outdoor fan motors.
No
Does it operate normally?
Yes
Check for indoor/outdoor short-cycle.
Check the DC fan motor.
Are those units short-cycled?
Yes (Short-cycled)
Remove factor(s) causing the short-cycle.
No (Not short-cycled)
Disconnect the compressor wiring from the outdoor power circuit board, then
check the voltage among each phases U, V and W during test run (SW7-1 ON).
Make sure to perform a voltage check with the same performing frequencies.
Are the voltage among the phases
No
U-V, V-W and W-U different?
Yes
Replace the outdoor multi controller circuit board.
Replace the compressor.
No
Does it operate normally?
Yes
Replace the outdoor power circuit board. Complete
OCH800A_53
4220 (U9): Voltage shortage/Overvoltage/PAM error/L1 open phase/ Primary
current sensor error/Power synchronization signal error
Chart 1 of 2
Abnormal points and detection methods
Any of the following symptoms are detected; · Decrease of DC bus voltage to
200 V (1-phase), 200 V
(3-phase)
· Increase of DC bus voltage to 400 V (1-phase), 380 V
(3-phase) · DC bus voltage stays at 310 V or less for 30 consecu-
tive seconds when the operational frequency is over 20 Hz. Any of the
following conditions is satisfied while the detections value of primary
current is 0.1 A or less. · The operational frequency is 40 Hz or more. · The
compressor current is 6 A or more.
Causes and checkpoints
· Decrease/increase of power supply voltage · L1 open-phase (3-phase only) ·
Primary current sensor failure · Disconnection of compressor wiring ·
Malfunction of 52C relay · Defective outdoor power circuit board · Malfunction
of 52C relay driving circuit on outdoor multi
controller circuit board
· Disconnection of CN2 · Malfunction of primary current detecting circuit on
out-
door power circuit board · Malfunction of resistor connected to 52C relay on
out-
door power circuit board (3-phase only)
1-phase: 1-phase model 3-phase: 3-phase 3-wire model The black square ()
indicates a switch position.
Diagnosis of failure
7, 8
Is there any abnormality on wiring?
No
Which sub code is displayed?
3
Does the DC bus voltage rise to approx. 380 V at PAM driving?
No
Is there any abnormality on PAM wirings or reactor?
No
Is there any abnormality at the PAM circuit on the outdoor power circuit
board?
No
Is there any abnormality at the PAM power supply circuit or 52C relay drive
signal circuit on the outdoor multi controller?
No
Yes
a. L1 open-phase (3-phase model only) b. Disconnection of compressor wiring c.
Disconnection of terminal block for power supply d. Disconnection of noise
filter circuit board e. Disconnection of power circuit board f. Disconnection
of CN52C (1-phase model only)
g. Disconnection of CN2
TThheessuubbcocdoedseasreadreispdlaisypeldaybey danboypaenratoiopneoraf tion of SSWW11oonnthteheouotduotodrocoornmtroullletir cboanrtdro. ller circuit board.
SW1 Setting
ON OFF
12345678
Display on LED1,2 1 23 45 67 8
3: PAM error 6: Input sensor trouble
7: Shortage voltage trouble 8: Overvoltage trouble
6
Replace the outdoor power circuit board
(defective outdoor power board).
Yes
Check the power supply facility.
Yes Yes
Correct the wiring. Replace the reactor if it is broken.
Replace the outdoor power circuit board (defective outdoor power board).
Yes
Replace the outdoor multi controller circuit board (breakage of wiring for PAM
controlling power supply).
Replace the outdoor power circuit board (defective outdoor power circuit
board).
Continue to the next page. *Refer to “How to check the parts”. OCH800A_54
4220 (U9): Voltage shortage/Overvoltage/PAM error/L1 open phase/ Primary
current sensor error/Power synchronization signal error
Chart 2 of 2 The black square () indicates a switch position.
Diagnosis of failure
Continued from the previous page.
7, 8
Check the power supply voltage on the terminal block of the outdoor unit.
No
Is the power supply normal?
Yes
Check the power supply facility.
Check the bus voltage read by the microprocessor with an operation of SW1 on
the outdoor multi controller
circuit board.
The bus voltage can be displayed by an operation of SW1 on the outdoor multi controller circuit board.
SW1 Setting
Display on LED1,2 Unit
ON
OFF
09999
V
12345678
Check the bus voltage at the test points listed below on the outdoor power
circuit board using a multimeter.
Test points: CNDC 1-3 pin
No
Is the bus voltage normal?
Yes
Check the resistor connected to 52C relay and reactor. Replace it if the
resistor is broken. Replace the outdoor power circuit board if the resistor is
not broken.
Operate the unit and check if the problem occurs again.
OCH800A_55
4230 (U5): Heat sink temperature trouble
Abnormal points and detection methods
TH8 detects a temperature outside the specified range during compressor
operation.
TH8: Thermistor
Causes and checkpoints
· Blocked outdoor fan · Malfunction of outdoor fan motor · Blocked airflow
path · Rise of ambient temperature · Characteristic defect of thermistor ·
Malfunction of input circuit on outdoor power circuit
board · Malfunction of outdoor fan driving circuit
Diagnosis of failure
Is error code 5110 displayed when restarted?
No
Yes
Refer to the diagnosis of error code 5110.
Does the fan rotate during compressor operation?
Yes
Is there any obstacle which blocks an airflow around the heat sink?
No (no obstacle)
No
Refer to the diagnosis of error code 4400.
Yes (air path blocked)
Improve the airflow path.
Check the wiring and connector connection of TH8.
Is there any abnormality such as disconnection, looseness or breakage?
No
Yes
Check the resistance of TH8.
No
Is the resistance normal?
Yes
Connect the wiring/connector properly. Replace it in the case of breakage.
TH8 temp. – resistance characteristic
32°F (0°C)
180 k
77°F (25°C)
50 k
122°F (50°C)
17 k
158°F (70°C)
8 k
194°F (90°C)
4 k
Replace the thermistor (Defective thermistor).
Replace the outdoor power circuit board (Defective outdoor power circuit board).
OCH800A_56
4250 (U6): Power module trouble
Abnormal points and detection methods
Both of the following conditions have been satisfied: · Overcurrent of DC bus
or compressor is detected during
compressor operation. · Inverter power module is determined to be faulty.
Causes and checkpoints
· Short-circuit caused by looseness or disconnection of compressor wiring
· Defective compressor · Defective outdoor power circuit board
Diagnosis of failure
Turn the power OFF to check for looseness or disconnection of the compressor
wiring.
No
Is it connected properly?
Yes
1. Disconnect the compressor wiring (U-V-W phase).
2. Turn ON the SW7-1(*) on the outdoor multi controller circuit board.
3. Operate the unit.
Connect the compressor wiring (U, V and W phase) properly, then turn the power back ON.
No
Is error code 4250 still displayed?
Yes
- SW7-1 ON: Ignore 5300(UH) error.
Replace the compressor (Defective compressor).
Replace the outdoor power circuit board or the outdoor multi controller
circuit board (Defective outdoor power circuit board).
OCH800A_57
4400 (U8): Fan trouble (Outdoor unit)
Abnormal points and detection methods
No rotational frequency is detected, a value outside the specified range is
detected during fan motor operation.
Causes and checkpoints
· Malfunction of fan motor · Disconnection of CNF connector · Defective
outdoor multi controller circuit board
Diagnosis of failure
Check the fuse on the outdoor multi controller circuit board.
Has the fuse melted?
No (Not melted)
Yes (Melted)
Replace the outdoor multi controller circuit board. Replace the defective fan motor.*
Check the fan motor connector (CNF1 and CNF2) for disconnection or looseness.
Is there any abnormality such as disconnection, looseness or breakage?
No
Yes
1. While the breaker is OFF, disconnect the compressor wiring (U/V/W) from
the outdoor power circuit board.
2. While the breaker is OFF, disconnect the fan motor connector CNF1 and
CNF2.
3. When 5 minutes have passed since turning ON the breaker, turn SW7-1 ON.
4. Check the voltage of the outdoor multi controller circuit board.
Test points are; · VDC approx. 310 to 350 V DC (fan connector 14) · VCC
approx. 15 V DC (fan connector 54) · VCC approx. 06.5 V DC (fan connector
64)
Connect the wiring/connector properly. Replace it in the case of breakage.
No
Is the voltage normal?
Yes
Replace the outdoor multi controller circuit board (Malfunction of thermistor
circuit).
Replace the defective fan motor.
- For the detail, refer to “Check method of DC fan motor (fan motor/outdoor multi controller circuit board)”.
Note: · Set SW7-1 OFF after the troubleshooting completes. · The fan sometimes starts on-off cycle operation during low-load operation or cooling at low outside temperature. It is not abnormal; the operation ensures reliability of the product.
OCH800A_58
5101 (U3): Compressor temperature thermistor (TH4) open/short <Detected in outdoor unit>
Abnormal points and detection methods
TH4 is found to be open/short. (The open/short detection is disabled for 10
minutes after compressor starts, during defrosting operation, or for 10
minutes after returning from the defrosting operation. The detection is also
disabled when the outdoor temperature is 41°F (5°C) or less in cooling
operation, and -4°F (-20°C) or less in heating)
Open: 37.4°F (3°C) or less* Short: 422.6°F (217°C) or more TH4: Thermistor
Causes and checkpoints
· Disconnection or contact failure of connectors · Faulty thermistor ·
Defective outdoor multi controller circuit board
The black square () indicates a switch position.
Check the wiring and connector connection of TH4.
Is there any abnormality such as disconnection, looseness or breakage?
No
Yes
Disconnect the connector to check the resistance of TH4 using a multimeter.
Connect the wiring/connector properly. Replace the connector in the case of breakage.
Is the detected resistance normal?
Yes
Check the temperature of TH4.
No
Replace the thermistor.
The detected temperature of TH4 can be displayed by an operation of SW1 on the outdoor multi controller circuit board.
SW1 Setting
Display on LED1,2 Unit
ON
OFF
-99.9999.9
°F
12345678
No
Is the detected temperature normal?
Yes
Replace the outdoor multi controller circuit board (Malfunction of thermistor
circuit).
No abnormality (A connector contact failure is suspected.)
OCH800A_59
5102 (U4): Suction pipe temperature thermistor (TH6) open/short <Detected in outdoor unit>
Abnormal points and detection methods
TH6 is found to be open/short. (The open/short detection is disabled for 10
seconds to 10 minutes after compressor starts, during defrosting operation, or
for 10 minutes after returning from the defrosting operation.)
Open: -40°F (-40°C) or less Short: 194°F (90°C) or more TH6: Thermistor
Causes and checkpoints
· Disconnection or contact failure of connectors · Faulty thermistor ·
Defective outdoor multi controller circuit board
The black square () indicates a switch position.
Check the wiring and connector connection of TH6.
Is there any abnormality such as disconnection, looseness or breakage?
No
Yes
Disconnect the connector to check the resistance of TH6 using a multimeter.
Connect the wiring/connector properly. Replace it in the case of breakage.
Is the detected resistance normal?
Yes
Check the temperature of TH6.
No
Replace the thermistor.
The detected temperature of TH6 can be displayed by an operation of SW1 on the outdoor multi controller circuit board.
SW1 Setting
Display on LED1,2 Unit
ON
OFF
-99.9999.9
°F
12345678
No
Is the detected temperature normal?
Yes
Replace the outdoor multi controller circuit board (Malfunction of thermistor
circuit).
No abnormality ( A connector contact failure is suspected.)
OCH800A_60
5105 (U4): Outdoor liquid pipe temperature thermistor (TH3) open/ short
Abnormal points and detection methods
TH3 is found to be open/short. (The open/short detection is disabled for 10
seconds to 10 minutes after compressor starts, during defrosting operation, or
for 10 minutes after returning from the defrosting operation.)
Open: -40°F (-40°C) or less Short: 194°F (90°C) or more TH3: Thermistor
Causes and checkpoints
· Disconnection or contact failure of connectors · Faulty thermistor ·
Defective outdoor multi controller circuit board
The black square () indicates a switch position.
Check the wiring and connector connection of TH3.
Is there any abnormality such as disconnection, looseness or breakage?
No
Yes
Disconnect the connector to check the resistance of TH3 using a multimeter.
Connect the wiring/connector properly. Replace it in the case of breakage.
Is the detected resistance normal?
Yes
Check the temperature of TH3.
No
Replace the thermistor.
The detected temperature of TH3 can be displayed by an operation of SW1 on the outdoor multi controller circuit board
SW1 Setting
Display on LED1,2 Unit
ON
OFF
-99.9999.9
°F
12345678
No
Is the detected temperature normal?
Yes
Replace the outdoor multi controller circuit board (Malfunction of thermistor
circuit).
No abnormality (A connector contact failure is suspected.)
OCH800A_61
5106 (U4): Ambient temperature thermistor (TH7) open/short
Abnormal points and detection methods
TH7 is found to be open/short Open: -40°F (-40°C) or less Short: 194°F (90°C)
or more TH7: Thermistor
Diagnosis of failure
Causes and checkpoints
· Disconnection or contact failure of connectors · Faulty thermistor ·
Defective outdoor multi controller circuit board
The black square () indicates a switch position.
Check the wiring and connector connection of TH7.
Is there any abnormality such as disconnection, looseness or breakage?
No
Yes
Disconnect the connector to check the resistance of TH7 using a multimeter.
Connect the wiring/connector properly. Replace it in the case of breakage.
Is the detected resistance normal?
Yes
Check the temperature of TH7.
No
Replace the thermistor.
The detected temperature of TH7 can be displayed by an operation of SW1 on the outdoor multi controller circuit board.
SW1 Setting
Display on LED1,2 Unit
ON
OFF
-99.9999.9
°F
12345678
No
Is the detected temperature normal?
Yes
Replace the outdoor multi controller circuit board (Malfunction of thermistor
circuit).
No abnormality (A connector contact failure is suspected.)
OCH800A_62
5109 (U4): HIC pipe temperature thermistor (TH2) open/short
Abnormal points and detection methods
TH2 is found to be open/short. Open: -40°F (-40°C) or less Short: 194°F (90°C)
or more TH2: Thermistor
Diagnosis of failure
Causes and checkpoints
· Disconnection or contact failure of connectors · Faulty thermistor ·
Defective outdoor multi controller circuit board
The black square () indicates a switch position.
Check the wiring and connector connection of TH2.
Is there any abnormality such as disconnection, looseness or breakage?
No
Yes
Disconnect the connector to check the resistance of TH2 using a multimeter.
Connect the wiring/connector properly. Replace it in the case of breakage.
Is the detected resistance normal?
Yes
Check the temperature of TH2.
No
Replace the thermistor.
The detected temperature of TH2 can be displayed by an operation of SW1 on the outdoor multi controller circuit board.
SW1 Setting
Display on LED1,2 Unit
ON
OFF
-99.9999.9
°F
12345678
No
Is the detected temperature normal?
Yes
Replace the outdoor multi controller circuit board (Malfunction of thermistor
circuit).
No abnormality (A connector contact failure is suspected.)
OCH800A_63
5110 (U4): Heat sink temperature thermistor (TH8) open/short
Abnormal points and detection methods
TH8 (Internal thermistor) is found to be open/short. · Y model
Open: -30.6°F (-34.8°C) or less Short: 215.6°F (102°C) or more TH8: Thermistor
Causes and checkpoints
· Disconnection or contact failure of connectors · Faulty thermistor ·
Defective outdoor multi controller circuit board
The black square () indicates a switch position.
Yes
Is it a model with internal thermistor?
No
Check the wiring and connector connection of TH8.
Is there any abnormality such as disconnection, looseness or breakage?
No
Yes
Connect the wiring/connector properly. Replace it in the case of breakage.
Disconnect the connector to check the resistance of TH8 using a multimeter.
Is the detected resistance normal?
Yes
Check the temperature of TH8.
No
Replace the thermistor.
The detected temperature of TH8 can be displayed by an operation of SW1 on the outdoor multi controller circuit board.
SW1 Setting
Display on LED1,2 Unit
ON
OFF
-99.9999.9
°F
12345678
No
Is the detected temperature normal?
Yes
Replace the outdoor multi controller circuit board (Malfunction of thermistor
circuit).
No abnormality (A connector contact failure is suspected.)
OCH800A_64
5201 (F5): High pressure sensor (63HS) trouble
Abnormal points and detection methods
· The detected pressure in the high pressure sensor is 14 psig (1kgf/cm2) or
less during operation, the compressor stops operation and enters into an anti-
restart mode for 3 minutes.
· The detected pressure is 14 psig (1kgf/cm2) or less immediately before
restarting, the compressor falls into an abnormal stop with error code 5201.
· For 3 minutes after compressor restarting, during defrosting operation, and
for 3 minutes after returning from defrosting operation, above mentioned
symptoms are not determined to be abnormal.
Causes and checkpoints
· Defective high pressure sensor · Decrease of internal pressure caused by gas
leakage · Disconnection or contact failure of connector · Malfunction of input
circuit on outdoor multi controller
circuit board
The black square () indicates a switch position.
Diagnosis of failure
Check the wiring and connector connection.
Is there any abnormality such as disconnection, looseness or breakage?
No
Yes
Check an internal pressure of the refrigerant circuit.
Connect the wiring/connector properly. Replace it in the case of breakage.
Is the detected internal pressure normal?
Yes
Check the detected pressure* in 63HS, then compare it with the internal
pressure.
No
Check the refrigerant circuit, and recharge
refrigerant after repairing the leakage.
The detected pressure in 63HS can be displayed by an operation of SW1 on the outdoor multi controller circuit board.
SW1 Setting
Display on LED1,2 Unit
ON
OFF
-99.9999.9
psig
12345678
No
Is the detected pressure normal?
Yes
*For the pressure, refer to “How to check the components”.
Replace the 63HS. Replace the outdoor multi controller circuit board.
OCH800A_65
5202 (F3): Low pressure sensor (63LS) trouble
Abnormal points and detection methods
· The detected pressure in the low pressure sensor is -33 psig (-2.3 kgf/cm2)
or less, or 329 psig (23.1 kgf/cm2) or more during operation, the compressor
stops operation with error code 5202.
· For 3 minutes after compressor restarting, during defrosting operation, and
for 3 minutes after returning from defrosting operation, above mentioned
symptoms are not determined to be abnormal.
Causes and checkpoints
· Defective low pressure sensor · Decrease of internal pressure caused by gas
leakage · Disconnection or contact failure of connector · Malfunction of input
circuit on outdoor multi controller
circuit board
The black square () indicates a switch position.
Diagnosis of failure
Check the wiring and connector connection.
Is there any abnormality such as disconnection, looseness or breakage?
No
Yes
Check the internal pressure of the refrigerant circuit.
Connect the wiring/connector properly. Replace it in the case of breakage.
Is the detected internal pressure normal?
Yes
Check the detected pressure in 63LS, then compare it with the internal
pressure.
No
Check the refrigerant circuit, and refill refrigerant
after repairing the leakage.
The detected pressure in 63LS can be displayed by an operation of SW1 on the outdoor multi controller circuit board.
SW1 Setting
Display on LED1,2 Unit
ON
OFF
-99.9999.9
psig
12345678
No
Is the detected pressure normal?
Yes
Replace the 63LS.
Replace the outdoor multi controller circuit board.
OCH800A_66
5300 (UH): Current sensor trouble
Abnormal points and detection methods
The detected current sensor input value (primary current) during compressor
operation is outside the specified range.
Causes and checkpoints
· Decrease/Trouble of power supply voltage · Disconnection of compressor
wiring · Input sensor trouble on outdoor power circuit board · Wiring through
current sensor (penetration type) is
not done.
Diagnosis of failure
Check the input current at the time of abnormal stop.
3-phase
Is the power supply 1-phase or 3-phase?
1-phase
Does it satisfy the condition 1 in the lower right?
No
Yes
Check the compressor wiring for disconnection or looseness.
The power supply voltage is decreased or abnormal.
Check the power supply facility.
Condition 1:
Model
1-phase model
Error detecting condition
37 A or more for 10 consecutive seconds, or 40 A or more
Is there any abnormality such as disconnection or looseness?
No
Yes
Connect the compressor wiring properly.
Replace the outdoor power circuit board (Malfunction of current sensor
circuit).
OCH800A_67
6600 (A0): Duplex address error
Abnormal points and detection methods
2 or more units with the same address exist.
Diagnosis of failure
Causes and checkpoints
· There are 2 units or more with the same address in their controller among
outdoor unit, indoor unit, Fresh Master, Lossnay or remote controller.
· Noise interference on indoor/outdoor connectors
Search for a unit with the same address as the source of abnormality.
Is there any unit with the same address?
No
Yes
Turn the power back ON.
Correct the address, and turn the power OFF of indoor/outdoor unit, Fresh Master or Lossnay simultaneously for 2 minutes or more, then turn the power back ON.
No
Does it operate normally?
Yes
Malfunction of sending/receiving circuit on indoor/outdoor unit is suspected.
There is no abnormality on the AC unit. It might be caused by an external
noise, so check the transmission line to remove the factor(s).
OCH800A_68
6602 (A2): Transmission processor hardware error
Abnormal points and detection methods
The transmission line shows “1” although the transmission processor
transmitted “0”.
Causes and checkpoints
· A transmitting data collision occurred because of a wiring work or polarity
change has performed while the power is ON on either of the indoor/outdoor
unit, Fresh Master or Lossnay.
· Malfunction of transmitting circuit on transmission processor
· Noise interference on indoor/outdoor connectors
Diagnosis of failure
A wiring work was performed while the
No
power was OFF.
Yes
If the wiring work was performed while the power was ON, turn the power OFF of indoor/outdoor unit, Fresh Master or Lossnay simultaneously for 2 minutes or more, then turn the power back ON.
Turn the power back ON.
No
Does it operate normally?
Yes
Replace the indoor/outdoor controller board.
There is no abnormality on the AC unit. It might be caused by an external
noise, so check the transmission line to remove the factor(s).
OCH800A_69
6603 (A3): Transmission bus BUSY error
Abnormal points and detection methods
· Transmission fails due to collision and it continues for 8 to 10 minutes.
· Data cannot be output on the transmission line because of noise etc.
consecutively for 8 to 10 minutes.
Causes and checkpoints
· The transmission processor is unable to transmit due to a short-cycle
voltage such as noise is mixed on the transmission line.
· The transmission processor is unable to transmit due to an increase of
transmission data amount caused by a miswiring of the terminal block
(transmission line) (TB3) and the terminal block (centralized control line)
(TB7) on the outdoor unit.
· The share on transmission line becomes high due to a mixed transmission
caused by a malfunction of repeater on the outdoor unit, which is a function
to connect/disconnect transmission from/to control system and centralized
control system.
Diagnosis of failure
Check whether the transmission line to the indoor unit, Fresh Master, Lossnay or remote controller is miswired to the terminal block (TB7) on outdoor unit or not.
Is the transmission line miswired?
Yes (miswired)
No (Wired correctly)
Check whether the transmission line with the other refrigerant system of the
indoor unit, Fresh Master or Lossnay is miswired to the terminal block (TB3)
on outdoor unit or not.
Is the transmission line miswired?
Yes (miswired)
No (Wired correctly)
Turn the power back ON.
Correct the wiring, then turn the power back ON. Correct the wiring, then turn the power back ON.
No
Does it operate normally?
Yes
Replace the indoor/outdoor controller board.
There is no abnormality on the AC unit. It might be caused by an external
noise, so check the transmission line to remove the factor(s).
OCH800A_70
6606 (A6): Signal communication error with transmission processor
Abnormal points and detection methods
· The data of unit/transmission processor were not normally transmitted.
· The address transmission from the unit processor was not normally
transmitted.
Diagnosis of failure
Causes and checkpoints
· Accidental disturbance such as noise or lightning surge · Hardware
malfunction of transmission processor
Turn the power OFF of indoor/outdoor unit, Fresh Master, Lossnay and remote controller simultaneously for 2 minutes or more, then turn the power back ON.
No
Does it operate normally?
Yes
Replace the controller. (Defect of error source controller).
There is no abnormality on the AC unit. It might be caused by an external
noise, so check the transmission line to remove the factor(s).
OCH800A_71
6607 (A7): No ACK error
Abnormal points and detection methods
Causes and checkpoints
Chart 1 of 4
Common to all
An abnormality detected by the sending side controller when receiving no ACK
from the receiving side, though signal was once sent. The sending side detects
the abnormality when that occurs 6 times in succession at 30 second intervals.
· The previous address unit does not exist since the ad-
dress switch was changed while power was on. · Decline of transmission
voltage/signal because the
transmission line exceeds the following limits. – Indoor/outdoor transmission
line maximum distance: 656 ft (200 m) – For remote controller line: 39 ft (12
m)
· Decline of transmission voltage/signal due to unmatched transmission line
types – Types for shield line: CVVS, CPEVS, or MVVS – Line diameter: AWG 16
(1.25 mm2) or more
· Decline of transmission voltage/signal due to excessive number of connected
units
· Malfunction due to accidental disturbance such as noise or lightning surge
· Defect of error source controller
The address/attribute of the outdoor unit was displayed:
An abnormality detected by the indoor unit if it received no · Contact failure of indoor/outdoor unit transmission line.
ACK when transmitting signal to the outdoor unit.
· Disconnection of transmission connector (CN2M) on
indoor unit.
· Malfunction of sending/receiving circuit on indoor/out-
door unit.
· Disconnection of the connectors on the circuit board
· Cut off of power supply for outdoor unit caused by high
pressure protection (63H).
The address/attribute of the indoor unit was displayed:
An abnormality detected by the remote controller if it re-
· While operating with the indoor units in a different refrig-
ceived no ACK when transmitting signal to the indoor unit.
erant system, an abnormality is detected when the in-
door unit transmits signal to the remote controller during
the other refrigerant-system outdoor unit is turned OFF,
or within 2 minutes after it turned back ON.
· Contact failure of indoor unit or remote controller trans-
mission line
· Disconnection of transmission connector (CN2M) on
indoor unit
· Malfunction of sending/receiving circuit on indoor unit or
remote controller
The address/attribute of the remote controller was displayed:
An abnormality detected by the indoor unit if it received no · While operating with the indoor units in a different refrig-
ACK when transmitting signal to the remote controller.
erant system, an abnormality is detected when the in-
door unit transmits signal to the remote controller during
the other refrigerant-system outdoor unit is turned OFF,
or within 2 minutes after it turned back ON.
· Contact failure of indoor unit or remote controller trans-
mission line
· Disconnection of transmission connector (CN2M) on
indoor unit
· Malfunction of sending/receiving circuit on indoor unit or
remote controller
OCH800A_72
6607 (A7): No ACK error
Abnormal points and detection methods
Causes and checkpoints
Chart 2 of 4
The address/attribute of Fresh Master was displayed:
An abnormality detected by the indoor unit if it received no · While the indoor unit is operating with the remote con-
ACK when transmitting signal to the Fresh Master.
troller in a different refrigerant system, an abnormality is
detected when the indoor unit transmits signal to the
remote controller while the outdoor unit in the same
refrigerant system as the Fresh Master is turned OFF,
or within 2 minutes after it turned back ON.
· Contact failure of indoor unit or Fresh Master transmis-
sion line
· Disconnection of transmission connector (CN2M) on
indoor unit or Fresh Master
· Malfunction of sending/receiving circuit on indoor unit or
Fresh Master
The address/attribute of Lossnay was displayed:
An abnormality detected by the indoor unit if it received no · An abnormality is detected when the indoor unit trans-
ACK when transmitting signal to the Lossnay.
mits signal to Lossnay while the Lossnay is turned OFF.
· While the indoor unit is operating with Lossnay in a
different refrigerant system, an abnormality is detected
when the indoor unit transmits signal to the Lossnay
while the outdoor unit in the same refrigerant system as
the Lossnay is turned OFF, or within 2 minutes after it
turned back ON.
· Contact failure of indoor unit or Lossnay transmission
line
· Disconnection of transmission connector (CN2M) on
indoor unit
· Malfunction of sending/receiving circuit on indoor unit or
Lossnay
The displayed address/attribute is not assigned to any controller. · The
previous address unit does not exist since the ad-
dress switch was changed while power was on. · The abnormality was detected
when the indoor unit sent
or received signal because the address of the Fresh
Master/Lossnay was changed after a setting for linking the Fresh
master/Lossnay was made on the remote controller.
OCH800A_73
6607 (A7): No ACK error
Chart 3 of 4
Diagnosis of failure
Note: · When the address of the outdoor unit is displayed as abnormal, the
outdoor circuit board may be faulty. If the unit is not restored after
conducting the following procedure, check the outdoor circuit board.
Procedure 1:
Turn the power OFF of indoor/outdoor unit, Fresh Master, Lossnay and remote
controller simultaneously for 10 minutes, then turn the power back ON.
No
Is the abnormality replicated?
Yes
Check the address switch on the source of abnormality.
Is the error code <1302> High pressure trouble displayed ?
Yes
No
There is no abnormality on the AC unit. It might be caused by an external noise, so
check the transmission line to remove the
factor(s).
Refer to the diagnosis of error code <1302> High pressure trouble.
No
Is it set properly?
Yes
Check the transmission line for disconnection and looseness (on the terminal
board and connector).
The transmission line is connected
No
properly.
Yes
Check the transmission line whether it exceeds the limits or not.
Set the address properly, then perform the procedure 1.
Connect the transmission line properly, then perform the procedure 1.
It exceeds the limits.
Yes
No
Check whether the correct transmission line is used or not.
Continue to the next page.
Correct it within the limits, then perform the procedure 1.
OCH800A_74
6607 (A7): No ACK error
Diagnosis of failure
Continued from the previous page.
No
Is the correct transmission line used?
Yes
Is it operating different refrigerant
No
systems?
Yes
When operating in different refrigerant systems (2 or more outdoor units),
check if any of the indoor unit stores non-existing address informa-
tion.
No
Is the address information correct?
Yes
Check the wiring.
Is the wiring on the circuit board
No
connected properly?
Yes
Replace the controller board which the displayed address/attribute belongs to.
No
Does it operate normally?
Yes
Chart 4 of 4
Apply the correct transmission line, then perform the procedure 1.
When operating in a single refrigerant system (single indoor unit), the
controller of the displayed address/attribute is defective.
Delete the unnecessary address using a manual setting function on the remote
controller (Only for the system to which the Fresh Master/ Lossnay is
connected or the system in which a group setting involving different
refrigerant systems is made).
Connect the wiring properly.
Defective outdoor multi controller circuit board (repeater circuit) on the
outdoor unit is suspected. Replace the outdoor multi controller circuit board
one by one, then check for normal operation.
Complete.
OCH800A_75
6608 (A8): No response frame error
Abnormal points and detection methods
Although the sending side controller received ACK that notifies the reception
of signal, no response command is transmitted from the receiving side. The
sending side detects the abnormality when that occurs 6 times in succession at
30 second intervals.
Causes and checkpoints
· Continuous failure of transmission due to noise, etc. · Decline of
transmission voltage/signal because the
transmission line exceeds the following limits. – Indoor/outdoor transmission
line maximum distance: 656 ft (200 m) – On remote controller line: 39 ft (12
m)
· Decline of transmission voltage/signal due to unmatched transmission line
types – Types for shield line: CVVS, CPEVS, or MVVS – Line diameter: AWG 16
(1.25 mm2) or more
· Accidental malfunction of error source controller
Diagnosis of failure
Turn the power OFF of indoor/outdoor unit, Fresh Master, Lossnay and remote controller simultaneously for 2 minutes or more, then turn the power back ON.
No
Does it operate normally?
Yes
Check the transmission line for disconnection and looseness (on the terminal
board and connector).
Replace the controller board
(Defect of the controller which the displayed address/attribute belong to).
The transmission line is connected
No
properly.
Yes
Check the transmission line whether it exceeds the limits or not.
Connect the transmission line properly.
It exceeds the limits.
No
Yes
Check whether the correct kind of transmission line is used or not.
Is correct kind of transmission line
No
used?
Yes
Correct it within the limits.
Replace it with the correct kind of transmission line. There is no abnormality
on the AC unit. Check the transmission line for transmission wave and noise.
OCH800A_76
6831 (E0)/6834 (E4): MA communication receive error
Chart 1 of 2
Abnormal points and detection methods
Detected in remote controller or indoor unit: · The main or sub remote
controller cannot receive signal
from indoor unit which has the “0” address. · The sub remote controller cannot
receive signal. · The indoor controller board cannot receive signal from
remote controller or another indoor unit. · The indoor controller board cannot
receive signal.
Causes and checkpoints
· Contact failure of remote controller wiring · Irregular wiring
(A wiring length, number of connecting remote controllers or indoor units, or
a wiring thickness does not meet the conditions specified in the chapter
“Electrical Work” in the indoor unit Installation Manual.) · Malfunction of
the remote controller sending/receiving circuit in the indoor unit with the
LED2 blinking. · Malfunction of the remote controller sending/receiving
circuit · Remote controller transmitting error caused by noise interference
Diagnosis of failure
Disconnect and reconnect the connec-
tor CN3A, then turn the power back ON.
Is error code 6831 or 6834
No
still displayed?
Yes
Check the remote controller for main-sub setting.
No abnormality A connector or wiring contact failure is suspected.
Is there only 1 remote
No
controller set as the main
controller?
Yes
Set 1 remote controller to main remote controller, and the other to sub.
Conduct the remote controller diagnosis twice or more times.
Is “OK” displayed on all remote controllers?
Yes
Turn the power back ON.
Does “Please Wait” disappear within 6 minutes?
Yes
Continue to the next page.
No Yes
No
Is “NG” displayed?
No
Is “6832” or “ERC” displayed?
No
Yes No abnormality
Yes
It might be caused by an external noise, so
check the transmission line.
Replace the remote controller.
Replace the indoor controller board with the LED2 blinking.
Note: · It takes 6 seconds at maximum until the result is displayed.
OCH800A_77
6831 (E0)/6834 (E4): MA communication receive error
Diagnosis of failure
Continued from the previous page.
Chart 2 of 2
Refer to the chapter “Electrical Work”.
Is the wiring connected
No
properly and meeting the
conditions?
Yes
Connect the wiring properly as specified in the chapter “Electrical Work” in
the indoor unit Installation Manual.
No abnormality It might be caused by an external noise, so check the
transmission line to remove the factor(s).
OCH800A_78
6832 (E3)/6833 (E5): MA communication send error
Chart 1 of 2
Abnormal points and detection methods
Detected in remote controller or indoor unit.
Causes and checkpoints
· There are 2 remote controllers set as main. · Malfunction of remote
controller sending/receiving cir-
cuit · Malfunction of sending/receiving circuit on indoor con-
troller board · Remote controller transmitting error caused by noise
interference
Diagnosis of failure
Disconnect and reconnect the
connector CN3A, then turn the power back ON.
Is error code 6832 or 6833
No
still displayed?
Yes
No abnormality A connector or wiring contact failure is suspected.
Check the remote controller for main-sub setting.
Is there only 1 remote
No
controller set as the main
controller?
Yes
Conduct the remote controller diagnosis twice or more times.
Set 1 remote controller to main remote controller, and the other to sub.
Is “OK” displayed on all remote controllers?
Yes
Turn the power back ON
Does “Please Wait” disappear within 6 minutes?
Yes
No Yes
Is “NG” displayed?
No
Is “6832” or “ERC” displayed?
No
No
Yes
No abnormality It might be caused by an external noise, so check the transmission line.
Replace the remote controller.
Replace the indoor controller board with the LED2 blinking.
Continue to the next page.
Note: · It takes 6 seconds at maximum until the result is displayed.
OCH800A_79
6832 (E3)/6833 (E5): MA communication send error
Diagnosis of failure
Continued from the previous page.
Chart 2 of 2
Refer to the chapter “Electrical Work”.
No
Is the wiring connected properly and meeting the conditions?
Yes
Connect the wiring properly as specified in the chapter “Electrical Work” in
the indoor unit Installation Manual.
No abnormality It might be caused by an external noise, so check the
transmission line to remove the factor(s).
OCH800A_80
7100 (EF): Total capacity error
Abnormal points and detection methods
The sum of the model class of the connected indoor units exceeds the specified
value (130% of the outdoor unit model class), error code 7100 is displayed.
Diagnosis of failure
Causes and checkpoints
· The total of number on connected indoor unit model names exceeds the
specified capacity level.
· The setting of the model selection switches of the outdoor unit is
registered wrongly.
Check the total capacity of connected indoor units.
Is the total under 130% of outdoor
No
unit capacity?
Yes
Check the capacity code switch (SW2 on the indoor controller board) on the
connected
indoor unit.
Correct it so that the total capacity of connected indoor units is under 130% of the outdoor unit capacity.
No
Is it set properly?
Yes
Check the model selection switch (SW4 on the outdoor multi controller circuit
board) of the outdoor unit.
No
Is it set properly?
Yes
Set the switch properly.
Set the switch properly. Complete.
OCH800A_81
7101 (EF): Capacity code error
Abnormal points and detection methods
· A connected indoor unit is incompatible, error code 7101 is displayed.
Causes and checkpoints
The model name of connected indoor unit (capacity code) is read as
incompatible.
Diagnosis of failure
Check the model selection switch (SW4 on the indoor controller board) of the
connected indoor unit.
No
Is it set properly?
Yes
Set the switch properly.
The capacity code of the connected indoor unit can be displayed by an
operation of SW1 on the outdoor unit.
OCH800A_82
7102 (EF): Connecting excessive number of units and branch boxes
Abnormal points and detection methods
The number of the connected indoor units exceeds the limit, error code 7102 is
displayed.
Causes and checkpoints
Connecting more indoor units and branch boxes than the limit. If connecting
status does not comply with the following limit; · Maximum connectable indoor
unit. · Connect at least 1 indoor unit (Abnormal if connected
none). · Connectable up to 2 branch boxes
Diagnosis of failure
Check whether the number of the connected indoor units exceeds the limit or not.
Does it exceed the limit?
No
Yes
Check if at least 1 indoor unit is connected.
Reduce the number of the connected units to fall within the limit.
The capacity code of the connected indoor unit can be displayed by an
operation of SW1 on the outdoor unit.
No
Is an indoor unit connected?
Yes
Connect an indoor unit.
Check whether the M-NET line to the indoor unit is connected or not.
OCH800A_83
7105 (EF): Address setting error
Chart 1 of 2
Abnormal points and detection methods
The address setting is wrong.
Causes and checkpoints
There is a unit without correct address setting in the range specified in the
installation manual.
Diagnosis of failure
No
Is the address setting correct?
Yes
Set the address properly, then turn the power OFF of indoor/outdoor unit,
Fresh Master, Lossnay and remote controller simultaneously for 2 minutes or
more, and turn the power back ON.
Replace the outdoor multi controller circuit board.
No
Is the address setting correct?
Yes
Set the address properly, then turn the power OFF of indoor/outdoor unit,
Fresh Master, Lossnay and remote controller simultaneously for 2 minutes or
more, and turn the power back ON.
Replace the indoor controller board.
Set the address properly, then turn the power OFF of indoor/outdoor unit,
Fresh Master, Lossnay and remote controller simultaneously for 2 minutes or
more, and turn the power back ON.
Replace the branch box controller board.
Note: Branch box address
When setting the address, use a number within the range of 150. Ex. The set
address is (47) and there are 5 indoor units (A, B, C, D, and E). If A: (47),
B: (48), C: (49), D: (50), and E: (51), E is incorrect because it exceeds 50.
OCH800A_84
7105 (EF): Address setting error
Diagnosis of failure
<M-NET RC (main)>
Check whether the M-NET RC (main) address is set in 000, or in the range of
101 to 150.
No
Is the address setting correct?
Yes
<M-NET RC (sub)>
Check whether the M-NET RC (sub) address is set in 000, or in the range of 151
to 200.
No
Is the address setting correct?
Yes
Chart 2 of 2
Set the address properly, then turn the power OFF of indoor/outdoor unit,
Fresh Master, Lossnay and remote controller simultaneously for 2 minutes or
more, and turn the power back ON.
Replace the M-NET RC (main).
Set the address properly, then turn the power OFF of indoor/outdoor unit,
Fresh Master, Lossnay and remote controller simultaneously for 2 minutes or
more, and turn the power back ON.
Replace the M-NET RC (sub).
OCH800A_85
7130 (EF): Incompatible unit combination error
Abnormal points and detection methods
The connected indoor unit is not compatible with the outdoor unit, the outdoor
unit detects the error at startup.
Causes and checkpoints
Connecting indoor unit(s) which is not authorized to connect to the outdoor
unit.
Diagnosis of failure
Refer to the service manual of the outdoor unit or the connected indoor unit
for the authorized combination.
Is the indoor unit authorized to
No
connect with the outdoor unit?
Yes
Replace the indoor unit(s) to the connectable one.
Check whether the model selection
No
switches are set correctly.
Are they correct?
Yes
Set the model selection switches correctly, then restart.
Replace the outdoor multi controller circuit board.
OCH800A_86
8-2. Remote controller diagnosis
Refer to “Remote controller check” for MA remote controller system.
8-3. Remote controller trouble
8-3-1. M-NET remote controller systems
Symptom or inspection code
Though the content of operation is displayed on the remote controller, some
indoor units do not operate.
Though the indoor unit operates, the display of the remote controller goes out
soon.
Cause
· The power supply of the indoor unit is not on. · The address of the indoor
units in the same group or
the remote controller is not set correctly. · The indoor units connected in
the other system are not
set in the same group by the remote controller. · The fuse on the indoor unit
controller board is blown.
· The power supply of the indoor unit is not on. · The fuse on the indoor unit
controller board is blown.
The display of the remote controller does not come up.
“Startup screen” keeps being displayed or it is displayed periodically.
(“Startup screen” is usually displayed about 3 minutes after the power supply
of the outdoor unit is on.)
The remote controller does not operate.
· The power supply of the outdoor unit is not on. · The connector of
transmission outdoor power board is
not connected. · The number of connected indoor units in the refrigera-
tion system is over the limit or the number of connected remote controller is
over the limit. · M-NET remote controller is connected to MA remote controller
cable. · The transmission line of the indoor/outdoor unit is shorted or down.
· M-NET remote controller cable is shorted or down. · Transmission outdoor
power board failure.
· The power supply for the feeding expansion unit for the transmission line is
not on.
· The address of the outdoor unit remains “00”. · The address of the indoor
unit or the remote controller
is not set correctly. · MA remote controller is connected to the transmission
line of the indoor/outdoor unit.
· The transmission line of the indoor/outdoor unit is connected to TB15.
· The transmission line of the indoor/outdoor unit is shorted down or badly
contacted.
Inspection method and solution
Check the part where the abnormality occurs.
1. The entire system 2. In the entire refrigerant system 3. In same group
only 4. 1 indoor unit only
In the case of the entire system or in the entire refrigerant system · Check
the self-diagnosis LED of the outdoor unit. · Check the items shown in the
left that are related to the
outdoor unit.
In the case of in the same group only or 1 indoor unit only · Check the items
shown in the left that are related to the
indoor unit.
OCH800A_87
8-3-2. For MA remote controller systems
Symptom or inspection code
Though the content of operation is displayed on the remote controller, some
indoor units do not operate.
Though the indoor unit operates, the display of the remote controller goes out
soon.
The display of the remote controller does not come up.
“Please Wait” keeps being displayed or it is displayed periodically. (“Please
Wait” is usually displayed for 3 minutes after the power supply of the outdoor
unit is on.)
The remote controller does not operate.
Cause
· The power supply of the indoor unit is not on. · Wiring between indoor units
in the same group is not
finished. · M-IC and A-IC are connected in the same group. · The fuse on the
indoor unit controller board is blown.
· The power supply of the indoor unit (Main) is not on. · In the case of
connecting the system controller, the
setting of the system controller does not correspond to that of MA remote
controller. · The fuse on the indoor unit (Main) controller board is blown.
The remote controller is not fed until the power supply of both indoor unit
and outdoor unit is on and the startup of both units is finished normally. ·
The power supply of the indoor unit is not on. · The power supply of the
outdoor unit is not on. · The number of connected remote controllers is over
the
limit (Maximum: 2 units) or the number of connected indoor units is over the
limit (Maximum: 16 units). · The address of the indoor unit is “00” and the
address for the outdoor unit is the one other than “00”. · The transmission
line of the indoor/outdoor unit is connected to TB15. · MA remote controller
is connected to the transmission line of the indoor/outdoor unit. · The remote
controller cable is shorted or down. · The power supply cable or the
transmission line is shorted or down. · The fuse on the indoor unit controller
board is blown.
· The power supply of the outdoor unit is not on. · The power supply of the
feeding expansion unit for the
transmission line is not on. · The setting of MA remote controller is not main
remote
controller, but sub-remote controller. · MA remote controller is connected to
the transmission
line of the indoor/outdoor unit.
· The power supply of the indoor unit (Main) is not on. · The transmission
line of the indoor/outdoor unit is con-
nected to TB15. · The transmission line of the indoor/outdoor unit is short-
ed, down or badly contacted. · The fuse on the indoor unit controller board is
blown.
Inspection method and solution
· Check the part where the abnormality occurs.
1. The entire system 2. In the entire refrigerant system 3. In the same group
only 4. 1 indoor unit only
In the case of the entire system or in the entire refrigerant system · Check
the self-diagnosis LED of the outdoor unit. · Check the items shown in the
left that are related to the
outdoor unit.
In the case of in the same group only or 1 indoor unit only · Check the items
shown in the left that are related to the
indoor unit.
OCH800A_88
8-4. The following symptoms do not represent product failure
Symptom
Even the cooling (heating) operation selection button is pressed, the ind
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>