Introduction
Huawei UPS5000-A (400-600kVA) is an online double conversion UPS which can output pure sine wave with rated voltage of 380/400/415 Vac. UPS5000-A has a high efficiency of up to 96% and high power density of up to 300kVA per cabinet; all-digital control allows precise output at any input and load condition. It’s suitable to ensure continuous power supply to critical loads in large datacenters.
Scenarios
- Large data centers, server rooms, security systems of finance, telecom and other large enterprises.
- Data center of government or public institutions.
- Precision instruments.
Features
Reliable
- Wide input voltage range to minimize battery use: 485-305 V for 100% load; 305-138 Vac for 100%-40% load (derating linearly).
- Better load adaptability: high output power factor up to 1 and no derating for capacitive or inductive devices with a PF>0.5.
Efficient
-
High efficiency of up to 96%, reducing power consumption effectively.
-
High power density of up to 300kVA per rack, 50% footprint saving.
Simple -
Flexible battery configuration: 30-44 batteries per string allow customers to get the faulty battery out instead of replacing it.
Specifications
Rated Capacity | 400kVA/400kW | 500kVA/500kW | 600kVA/600kW |
---|---|---|---|
**Mains Input** | Input Wiring | 3Ph+N+PE | |
Rated Voltage | 380/400/415Vac | ||
Voltage Range | 138-485Vac | ||
Frequency Range | 40-70Hz | ||
Total Harmonic Distortion | THDi <3% for 100% linear |
load
Input Power Factor| 0.99
**Bypass Input| Input Wiring| 3Ph+N+PE
Rated Voltage| 380/400/415Vac
Input Frequency| 50/60 ± 6Hz
Battery| Rated Voltage| 360-528Vdc (The number of
batteries can be selected from 30 to 44; 40 batteries in default)
****Output| Output Wiring| 3Ph+N+PE
Rated Voltage| 380/400/415 Vac ± 1%
Frequency| Tracking the bypass input (Normal
mode); 50/60 Hz ± 0.05% (Battery mode)
Waveform| Sine wave (THDv <1% for 100% linear
load)
Overload Capacity| 110% overload for 60 minutes;
125% overload for 10 minutes; 150% overload for
1 minute
****System| Output Power Factor| 1
Efficiency| 96%
Expandability| Up to 8 units connected in
parallel
****Enviro- nment| Operating Temperature|
0-40ºC
Storage Temperature| -40 to 70ºC
Relative Humidity| 0%-95% (No condensing)
Operating Altitude| 0-1000m. Above 1000m, derating
rate based on EN/IEC 62040-3
Audible Noise| 66-75dB
****Others| Height × Width × De pth (mm)|
****2000 × 1200 × 850| ****2000 × 1400 × 850
Weight| 710kg| 850kg| 1100kg
Certifications| EN/IEC 62040-1; EN/IEC 62040-2;
EN/IEC 62040-3; CE;CB; RoHS, REACH,WEEE,etc.
Communications| Dry contacts, RS485, SNMP**
Remark: For important systems that are related to important economic interests
or public security, such as civil aviation management center, financial
clearing center, and
trading center, the Tier IV or Tier III power supply level specified in TI942
must be used. That is, two UPSs form dual-bus power supply or the UPS and
mains form dualbus power supply.