Danfoss GBCT 6s Shut Off Ball Valve Installation Guide

June 15, 2024
Danfoss

ENGINEERING
TOMORROW
Installation guide

Shut-off ball valve Type GBCT

Refrigerant: R744 (CO2)
Temperature range (TS): -40 °C – 149 °C / -40 °F – 300 °F
Max. working pressure (PS/MWP):140 bar / 2031 psig

CAUTION – RISK OF HIGH PRESSURE
This component shall be installed along with a pressure relief valve set to discharge at no higher than the rated pressure of this component. This component is intended for systems in which the critical pressure of the refrigerant will be exceeded. The relief valve shall comply with the requirements of ASME Section VIII, be marked “UV” and sized based on the refrigeration system capacity.
Warning: Applicable to A1, incl. R744, refrigerants as accepted by Danfoss excluding R717 and to noncorrosive gases/liquids dependent on sealing material compatibility. The design pressure shall not be less than the value outlined in Section 9.2 of ANSI/ ASHRAE 15 for the refrigerant used in the system. Only authorized persons are allowed to operate this valve, as closing can cause build-up of excessive pressure in the system. For the application use with R744 as part of a secondary loop or cascade system
should refer to the datasheet for more attentions.

** Danfoss recommends that valves are installed so that the HP side is oriented towards the highest pressure side of the system when the valve is in the closed position. The ball valve will only internally seal in closed position when flow direction is from HP to LP.Danfoss GBCT 6s Shut Off Ball
ValveDanfoss GBCT 6s Shut Off Ball Valve -
Parts Remove cap and access cap (if present)**

Danfoss GBCT 6s Shut Off Ball Valve - Brazing 2

Opening valve

Valve size Max. Operating Torque
Nm ft-lbs
GBCT 6 – 17 5
GBCT 18 – 22 7
GBCT 27 – 28 9
GBCT 34 – 35 11
GBCT 42 15
GBCT 48 – 60 34
OPEN Position CLOSED Position
--- ---

Danfoss GBCT 6s Shut Off Ball Valve - OPEN Position| Danfoss GBCT 6s Shut Off Ball Valve - CLOSED
Position
Brazing (Copper and Copper alloy)| Welding (stainless steel)
Danfoss GBCT 6s Shut Off Ball Valve - Brazing| Danfoss GBCT 6s Shut Off Ball Valve - Welding

Install valve core (if present) and capDanfoss GBCT 6s Shut Off Ball
Valve - Install valve core Install valve core with approx. torque 0.3 Nm / 0.2 ft-lbs
Tighten cap

Tighten the cap with approx. torque

Valve size Recommended Torque
Nm ft-lbs
GBCT 6 – 17 5-Apr
GBCT 18 – 22 8-Jul
GBCT 27 – 42 18-20
GBCT 48 – 60 54-61

| |
---|---|---
| |

009R8519