tbs electronics RBS Remote Battery Switch Battery Protect Relay User Manual
- June 15, 2024
- tbs electronics
Table of Contents
DC Modular
Remote Battery Switch / Battery Protect Relay
Description
The DC Modular Remote Battery Switch (RBS) and Battery Protect Relay (TBP)
are smart high current magnetic latching contactors, that can handle
continuous DC currents of up to 500Amps. The contactors can easily be
installed in an engine room or battery compartment, while being controlled
from a more convenient location by a small panel mounted switch. The RBS / TBP
can however also be controlled by a battery monitor or managed lithium
battery.
Besides controlling the contactors remotely,buttons positioned at the top also
providea way to open or close the main contact locally, as required by Marine
Standards. A 5 wire interface cable is used to control the contactors
externally. For optimal flexibility, these can be configured to accepttwo wire
or single wire open and close commands. A wire for providing a contact status
feedback signal is also available.
Status LEDs on top clearly indicate whetherthe main contact is opened or
closed.
These indicators also provide additional visual feedback like operating- and
error modes.
A specially developed internal solenoid guarantees a powerful contact drive,
even when supplied by deeply discharged batteries.
Both the RBS and the TBP can be used to switch battery loads, through local
and/or external control. The TBP however, has a number of additional features.
The most important one being built-in battery protection.
The TBP will automatically open the main contact once the battery voltage has
dropped below a programmable low voltage level. When subsequently the battery
voltage has risen above the programmable reconnect voltage, the main contact
is closed again.
Another handy TBP feature is the Override mode. In situations where the TBP
has opened the main contact due to a battery undervoltage, long-pressing the
close button (local or external) will close the main contact for 1 minute.
This allows the user to jumpstart
a low battery system. When after this minute the battery voltage remains too
low, the contact will open up again. But it remains closed when during the
override time, a charger has been connected causing the battery voltage to
recover.
Being a member of the DC Modular product line up, the RBS and TBP can be
perfectly integrated into very compact DC distribution systems.
Features
- Electronically controlled magnetic latching contactor
- Extremely low power consumption (< 100µA)
- Up to 500Amp nominal current
- 60Vdc contact rating
- Local and external open / close control
- Visual status indicators
- Small footprint
- DC Modular grid compatible for compact and easy arrangements of multiple devices
- Selectable control modes
- Battery protection (TBP only)
- Override mode (TBP only)
Applications
- Battery management systems
- Marine applications
- Off grid solar power systems
- Battery load shedding applications
- Service vehicles
- Recreational vehicles
- Industrial systems
Technical specifications
GRID OPTIMIZED FOOTPRINTS
Parameter| DCM-RBS-12-500
(art # 5074510)| DCM-RBS-24-500
(art # 5074520)| DCM-RBS-48-350
(art # 5074540)| DCM-TBP-12-500
(art # 5074410)| DCM-TBP-24-500
(art # 5074420)| DCM-TBP-48-350
(art # 5074440)
---|---|---|---|---|---|---
Main contact circuit (electrical)| | | | | |
Rated voltage| | | 60Vdc| |
Nominal current| | | 500A| |
Cranking current (1min.)| | | 1000A| |
Nominal make / break current| | | 500A (0 – 34Vdc)| 350A (35 – 60Vdc)| |
Peak make / break current| | | 1600A (0 – 34Vdc)| 1200A (35 – 60Vdc)|
Control circuit (electrical)
Coil / supply voltage (+Vdc)| 7.5 – 17Vdc| 15 – 34Vdc| 34 – 68Vdc| 7.5 –
17Vdc| 15 – 34Vdc| 34 – 68Vdc
Coil / supply current (idle state)1)| | | < 100uA| |
Coil / supply current (state change)1)| < 6A| < 3A| < 1.5A| < 6A| < 3A| < 1.5A
Features
Remote battery switch function| •| •| •| •| •| •
Battery protect function| x| x| x| •| •| •
Local open / close controls| •| •| •| •| •| •
External open / close control wires| •| •| •| •| •| •
Contact status indicators| •| •| •| •| •| •
Contact status feedback wire| •| •| •| •| •| •
Override mode2)| x| x| x| •| •| •
Number of control modes| 5| 5| 5| 7| 7| 7
Programmable disconnect voltages| x| x| x| 9.0 – 12.2Vdc| 18.0 – 24.5Vdc| 36.0
– 49.0Vdc
Programmable reconnect voltages| x| x| x| 10.5 – 13.8Vdc| 21.0 – 27.5Vdc| 42.0
– 55.0Vdc
General
Remote control | By control wires |
---|---|
Local control³) | Top side buttons (On/Standby, Close contact, Open contact) |
Top side buttons (On/Standby, Close contact, Open contact, Override mode)
Indicators| Top side LEDs for Contact open, Contact closed, Error and Setup
Mechanical / Electrical life| 100000 cycles / 10000 cycles
Operating temperature range| -20..+60°C
Connection stud size| M10
DC Modular grid size| 1 x 3
Protection class| IP65
Dimensions| 150.0 x 50.0 x 94.0 mm
Weight| 800gr
Standards| CE certified (EMC Directives UNECE Regulation 10 (only 12V and 24V
models) and 2014/30/EU, Low voltage Directive 2014/35/EU, RoHS Directive
2011/65/EU and Ignition protection standard ISO 8846)
Note: the given specifications are subject to change without notice.
- Due to the magnetic latch construction, the DCM RBS and TBP draw virtually no current in the ON or OFF state. A current draw only exists shortly (500ms max) when changing the state of the contact.
- Override mode allows the contact to be temporarily closed, despite being automatically opened earlier due to a battery under voltage. This is intended for jumpstarting a low battery system.
- Using the top side buttons, one can manually override the switch state as commanded through the control wires. A dedicated ‘On/Standby’ button also allows the user to put the DCM RBS or TBP in a standby mode with open contact. In this mode any commands from the control wires and/or manual override buttons are ignored.
Accessories
Panel Switch Momentary SPDT + LED art# 5095000-1
With this optional panel switch you can send open and close commands to the
RBS and TBP contactors from a convenient location. The integrated LED
indicates when the contact is closed or when the contactor is running in a
certain mode.
Dimensions (Contactors)
Dimensions (Panel switch)
Basic application diagram
| Technical datasheet DCMD-RBS-TBP-EN-REVC
---|---
DC Modular Remote Battery Switch / Battery Protect Relay
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>