SQUARE D 8910DPA73RV09 Contactor Definite Purpose Instruction Manual

June 15, 2024
SQUARE D

SQUARE-logo

SQUARE D 8910DPA73RV09 Contactor Definite Purpose

Product Specifications

  • Class: 8910
  • Type: DPA
  • Model Numbers: DA1V, DA2V

Replacement Coils for Use with Class 8910 Type DPA Contactors

Instruction

HAZARDOUS VOLTAGE

  • Disconnect all voltage supplies before installing or removing the device.
  • Failure to follow this instruction will result in death or serious injury.

INSTALLATION

Coil replacement instructions: (see illustration)

  1.  Push the magnet clip (A) tabs in and slide the clip out.
  2. Remove the magnet (B) and the coil (C).
  3. Place the new coil in the device with coil terminal through the single wide slot.
  4. Replace the magnet with the shading coil on the same side as the coil terminals. (The shading coil on the armature, not shown, and magnet shading coil should not be aligned.)
  5. Snap the magnet clip firmly in place.
  6.  If the contactor buzzes or chatters when energized after reassembly, check for proper orientation of the magnet (B).

Replacement Coils for Use with Class 8910 Type DPA Contactors

NOTE : Shading coil must be on the same side as coil terminals for proper operation.

Square D and I are registered trademarks of Square D. Electrical equipment should be serviced only by qualified electrical maintenance personnel. No responsibility is assumed by Square D for any consequences arising out of the use of this material. Square D 8001 Highway 64 East Knightdale, NC 27545-9023 USA 919-266-3671
© 1997 Square D All Rights Reserved