INTERTHERM JT4BD 3-5 13+ SEER Extra High Efficiency Heat Pump Instruction Manual

June 15, 2024
Intertherm

JT4BD 3-5 13+ SEER Extra High Efficiency Heat Pump

Product Information: Outdoor Heat Pump

Specifications

  • SEER: 13
  • Refrigerant: R-410A
  • High Efficiency Split System

Product Usage Instructions

User’s Information

Read this owner information to become familiar with the
capabilities and use of your appliance. Keep this with literature
on other appliances where you have easy access to it in the future.
If a problem occurs, check the instructions and follow
recommendations given. If these suggestions don’t eliminate your
problem, call your servicing contractor.

Heat Pump Principle of Operation

WINTER HEATING:

  1. Outdoor air enters the heat pump.

  2. Cold, heat-transfer section (outdoor coil) extracts heat from
    outdoor air as refrigerant evaporates from a liquid to a gas.

  3. Refrigerant, compressed to a hot gas by the heat pump, carries
    the heat to the hot heat-transfer section (indoor coil).

  4. Hot, heat-transfer section (indoor coil) releases the heat to
    indoor air as refrigerant condenses from a gas to a liquid.

  5. Air handler circulates the heat throughout the home.

  6. Refrigerant returns to the outdoor coil and evaporates once
    again to absorb more heat.

SUMMER COOLING:

  1. Indoor air enters the air handler section.

  2. Cold, heat-transfer section (indoor coil) extracts heat from
    indoor air as refrigerant evaporates from a liquid to a cold
    gas.

  3. Refrigerant, drawn to the heat pump and compressed to a hot gas
    by the heat pump, carries the heat outdoors.

  4. Hot, heat-transfer section (outdoor coil) releases the heat as
    refrigerant condenses from a gas to a liquid.

  5. Heat pump (outdoor fan) discharges the heat to outside
    air.

  6. Refrigerant returns to the indoor coil and evaporates once
    again to absorb more heat.

Operating Instructions

TO OPERATE YOUR HEAT PUMP FOR COOLING —

  1. Set the thermostat system switch to COOL and the thermostat fan
    switch to AUTO. (See Figure 1)

  2. Set the thermostat temperature to the desired temperature level
    using the temperature selector. Please refer to the separate
    detailed thermostat user’s manual for complete instructions
    regarding thermostat programming. The outdoor unit and indoor
    blower will both cycle on and off to maintain the indoor
    temperature at the desired cooling level.

  3. NOTE: If the thermostat temperature level is
    re-adjusted, or the thermostat system switch is repositioned, the
    outdoor unit may not start immediately. The outdoor unit contains a
    protective timer circuit which holds the unit off for approximately
    five minutes following a previous operation or the interruption of
    the main electrical power.

TO OPERATE YOUR HEAT PUMP FOR HEATING —

FAQ

Q: Who should install this product?

A: These instructions are primarily intended to assist qualified
individuals experienced in the proper installation of heating
and/or air conditioning appliances. Some local codes require
licensed installation/service personnel for this type of
equipment.

Q: What should I do if a problem occurs?

A: Check the instructions and follow recommendations given. If
these suggestions don’t eliminate your problem, call your servicing
contractor.

Outdoor Heat Pump
User’s Information/Installation Instructions
13 SEER R-410A High Efficiency Split System
These units have been designed and tested for capacity and efficiency in accordance with A.R.I. Standards. Split System Heat Pump units are designed for use with a wide variety of fossil fuel furnaces, electric furnaces, air handlers, and evaporator coil combinations.
These instructions are primarily intended to assist qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local codes require licensed installation/service personnel for this type of equipment. Read all instructions carefully before starting the installation.
USER’S INFORMATION
IMPORTANT
Read this owner information to become familiar with the capabilities and use of your appliance. Keep this with literature on other appliances where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor.
Heat Pump Principle of Operation

54

1
2 3

6

WINTER HEATING
1. Outdoor air enters heat pump. 2. Cold, heat-transfer section (outdoor coil)
extracts heat from outdoor air as refrigerant evaporates from a liquid to a gas. 3. Refrigerant, compressed to a hot gas by heat pump, carries the heat to the hot heattransfer section (indoor coil). 4. Hot, heat-transfer section (indoor coil) releases the heat to indoor air as refrigerant condenses from a gas to a liquid. 5. Air handler circulates the heat throughout the home. 6. Refrigerant returns to outdoor coil and evaporates once again to absorb more heat.

5

21

3 4
6

SUMMER COOLING
1. Indoor air enters the air handler section. 2. Cold, heat-transfer section (indoor coil)
extracts heat from indoor air as refrigerant evaporates from a liquid to a cold gas. 3. Refrigerant, drawn to heat pump and compressed to a hot gas by heat pump, carries the heat outdoors. 4. Hot, heat-transfer section (outdoor coil) releases the heat as refrigerant condenses from a gas to a liquid. 5. Heat pump (outdoor fan) discharges the heat to outside air. 6. Refrigerant returns to indoor coil and evaporates once again to absorb more heat.

2

OPERATING INSTRUCTIONS
TO OPERATE YOUR HEAT PUMP FOR COOLING —
1. Set the thermostat system switch to COOL and the thermostat fan switch to AUTO.(See Figure 1)
2. Set the thermostat temperature to the desired temperature level using the temperature selector. Please refer to the separate detailed thermostat user’s manual for complete instructions regarding thermostat programming. The outdoor unit and indoor blower will both cycle on and off to maintain the indoor temperature at the desired cooling level.
NOTE: If the thermostat temperature level is re-adjusted, or the thermostat system switch is repositioned, the outdoor unit may not start immediately.The outdoor unit contains a protective timer circuit which holds the unit off for approximately five minutes following a previous operation, or the interruption of the main electrical power.
TO OPERATE YOUR HEAT PUMP FOR HEATING —
1. Set the thermostat system switch to HEAT and the thermostat fan switch to AUTO. (See Figure 1)

2. Set the thermostat temperature to the desired temperature level using the temperature selector. Please refer to the separate detailed thermostat user’s manual for complete instructions regarding thermostat programming.The outdoor unit and indoor blower will both cycle on and off to maintain the indoor temperature at the desired heating level.
NOTE: If the thermostat temperature level is re-adjusted, or the thermostat system switch is repositioned, the outdoor unit may not start immediately.The outdoor unit contains a protective timer circuit which holds the unit off for approximately five minutes following a previous operation, or the interruption of the main electrical power.
Emergency Heat:
The thermostat includes a system switch position termed EM. HT. This is a back-up heating mode to be used only if there is a suspected problem with the outdoor unit. With the system switch set to EM. HT. the outdoor unit will be locked off, and supplemental heat (typically electric resistance heating) will be used as a source of heat.Sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs.
Defrost:
During cold weather heating operation, the outdoor unit will develop a coating

Figure 1. Typical Thermostat 3

of snow and ice on the heat transfer coil. This is normal, and the unit will periodically defrost itself. During the defrost cycle, the outdoor fan will stop, and the compressor will continue to run and heat the outdoor coil, causing the snow and ice to melt. After the snow and ice have melted, some steam may rise from the outdoor unit as the warm coil causes some melted frost to evaporate.
TO OPERATE YOUR HEAT PUMP FOR AUTOMATIC COOLING AND
HEATING —

equalize a temperature unbalance due to a sun load, cooking, or fireplace operation.
TO MAINTAIN YOUR HEAT PUMP —
CAUTION:
Be certain the electrical power to the outdoor unit and the furnace/air handler is disconnected before doing the following recommended maintenance.

1. Set the thermostat system switch to AUTO and the thermostat fan switch to AUTO.(See Figure 1)
Note: Thermostats will vary. Some models will not include the AUTO mode, and others will have the AUTO in place of the HEAT and COOL, and some will include all three.
2. Set the thermostat temperature to the desired heating and cooling temperature level(s). The outdoor unit and the indoor blower will then cycle on and off in either the heating or cooling mode of operation as required to automatically maintain the indoor temperature within the desired limits.

1. Regularly:
a. Clean or replace the indoor air filter at the start of each heating and cooling season, and when an accumulation of dust and dirt is visible on the air filter. Inspect the filter monthly.
b. Remove any leaves and grass clippings from the coil in the outdoor unit, being careful not to damage the aluminum fins.
c. Check for any obstruction such as twigs, sticks, etc.
CAUTION:

TO SHUT OFF YOUR HEAT PUMP —
Set the thermostat system switch to OFF and the thermostat fan switch to AUTO. (See Figure 1) The system will not operate, regardless of the thermostat temperature selector(s) setting.
TO OPERATE THE INDOOR BLOWER CONTINUOUSLY —
Set the thermostat fan switch to ON (See Figure 1). The indoor blower will start immediately, and will run continually until the fan switch is reset to AUTO.
The continuous indoor blower operation can be obtained with the thermostat system switch set in any position, including OFF.
The continuous indoor blower operation is typically used to circulate the indoor air to

Do not over-oil, or oil motors not factory-equipped with oil tubes. The compressor is hermetically “sealed” and does not require lubrication.
2. Before Calling a Service Technician, Be Certain:
a. The unit thermostat is properly set — see “To Operate Your Heat Pump for Cooling” and “To Operate Your Heat Pump for Heating.”
b. The unit disconnect fuses are in good condition, and the electrical power to the unit is turned on.
Read Your Warranty
Please read the separate warranty document completely. It contains valuable information about your system.

4

GENERAL INFORMATION

SAFETY CONSIDERATIONS

Read the following instructions completely before performing the installation.
CAUTION:
This unit uses refrigerant R-410A. DO NOT under any circumstances use any other refrigerant besides R-410A in this unit. Use of another refrigerant will damage this unit.
Outdoor Unit Section — Each outdoor unit is shipped with a refrigerant charge adequate to operate the outdoor section with an indoor matching coil or air handler. Units with braze connections include the proper amount of refrigerant for an additional 15 ft. of refrigerant lines the same size as the valve fittings.
NOTE: DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING.

Pressures within the System — Split system heat pump equipment contains liquid and gaseous refrigerant under pressure. Installation and servicing of this equipment should be accomplished by qualified, trained personnel thoroughly familiar with this type of equipment. Under no circumstances should the Homeowner attempt to install and/or service the equipment.
Labels, Tags, Precautions — When working with this equipment, follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
Brazing Operations — Installation of equipment may require brazing operations. Safety codes must be complied with. Safety equipment (e.g.; safety glasses, work gloves, fire extinguisher, etc.) must be used when performing brazing operations.

Matching coils and air handlers may be shipped with a small holding charge to pressurize them to keep out contaminants. To release the pressure, read the indoor section installation instructions carefully.
Liquid and Suction Lines — Fully annealed, refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
Field Connections for Electrical Power Supply — All wiring must comply with current provisions of the “National Electrical Code” (ANSI/NFPA 70) and with applicable local codes having jurisdiction. The minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label.
NOTICE:
Certain models have external panels fabricated from a premium grade of stainless steel designed to inhibit corrosion. For such units, if the unit is located in a coastal region or other area subjected to high concentrations of salt, then the unit should be hosed off after stroms and monthly otherwise to maintain its new appearance.

WARNING:
Ensure all electrical power to the unit is off prior to installing or servicing the equipment. Failure to do so may cause personal injury or death.
SITE PREPARATION
Unpacking Equipment — Remove the cardboard carton and User’s Manual from the equipment. Take care to not damage tubing connections when removing from the carton.
Inspect for Damage — Inspect the equipment for damage prior to installing the equipment at the job site. Ensure coil fins are straight and, if necessary, comb fins to remove flattened and bent fins.
Preferred Location of the Outdoor Unit at the Job Site — Conduct a survey of the job site to determine the optimum location for mounting the outdoor unit. Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided. The
5

outdoor unit must be installed in such a manner that airflow through the coil is not obstructed and that the unit can be serviced.
Facility Prerequisites — Electrical power supplied must be adequate for proper operation of the equipment.The system must be wired and provided with circuit protection in accordance with local building codes and the National Electrical Code.
INSTALLING THE OUTDOOR UNIT
Slab Mount — The site selected for a slab mount installation requires a stable foundation and one not subject to erosion. The slab should be level and anchored (if necessary) prior to placing the equipment on the slab.
Cantilever Mount — The cantilever mount should be designed with adequate safety factor to support the weight of the equipment, and for loads subjected to the mount during operation. Installed equipment should be adequately secured to the cantilever mount and levelled prior to operation of the equipment.

General — Once outdoor and indoor unit placement has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices. Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing. Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation. Tubing should be kept clean of foreign debris during installation and installation of a liquid line filter drier is recommended if cleanliness or adequacy of system evacuation is unknown or compromised. Every effort should be made by the installer to ensure that the field installed, refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices so as to insure reliable system operation and longevity.
The maximum recommended interconnecting refrigerant line length is 75 feet, and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 feet. Consult long line application guide for installations in excess of these limits.

Roof Mount — The method of mounting should be designed so as not to overload roof structures nor transmit noise to the interior of the structure. Refrigerant and electrical line should be routed through suitably waterproofed openings to prevent water leaking into the structure.
INSTALLING THE INDOOR UNIT

Filter Dryer Installation — A filter dryer is provided with the unit and must be installed in the liquid line of the system. If the installation replaces a system with a filter dryer already present in the liquid line, the filter dryer must be replaced with the one supplied with the unit. The filter dryer must be installed in strict accordance with the manufacturer’s installation instructions.

The indoor section should be installed before proceeding with routing of refrigerant piping. Consult the Installation Instructions of the indoor unit (i.e.: air handler, furnace, etc.) for details regarding installation.
CONNECTING REFRIGERANT TUBING BETWEEN THE INDOOR AND OUTDOOR UNIT

Optional Equipment — Optional equipment (e.g.: liquid line solenoid valves, etc.) should be installed in strict accordance with the manufacturer’s installation instructions.
ELECTRICAL CONNECTIONS
WARNING:

CAUTION:
This system utilizes R-410A refrigerant with POE oil. When servicing, cover or seal openings to minimize the exposure of the refrigerant system to air to prevent accumulation of moisture and other contaminants.

Turn off all electrical power at the main circuit box before wiring electrical power to the outdoor unit. Failure to comply may cause severe personnel injury or death.

6

Wiring Diagram/Schematic — A wiring diagram/schematic is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram/schematic before making any electrical connections to the outdoor unit.
Outdoor Unit Connections — The outdoor unit requires both power and control circuit electrical connections. Refer to the unit wiring diagram/schematic for identification and location of outdoor unit field wiring interfaces.
Control Circuit Wiring — The outdoor unit is designed to operate from a 24 VAC Class II control circuit. Control circuit wiring must comply with the current provisions of the “National Electrical Code” (ANSI/NFPA 70) and with applicable local codes having jurisdiction.
Thermostat connections should be made in accordance with the instructions supplied with the thermostat, and with the instructions supplied with the indoor equipment. A typical residential installation with a heat pump thermostat and air handler are shown below.

Maximum Fuse/Circuit Breaker Size — Circuit protection for the outdoor unit must be compatible with the maximum fuse/circuit breaker size listed on the outdoor unit data label.
Disconnect Switch — An electrically compatible disconnect switch must be within line of sight of the outdoor unit. This switch shall be capable of electrically de-energizing the outdoor unit.
Optional Equipment — Optional equipment requiring connection to the power or control circuits must be wired in strict accordance with current provisions of the “National Electrical Code” (ANSI/NFPA 70), with applicable local codes having jurisdiction, and the installation instructions provided with the equipment. Optional Equipment (e.g.: liquid line solenoid valves, hard start kits, low suction pressure cutout switch kit, high pressure cutout switch kit, refrigerant compressor crankcase heater, etc.) should be installed in strict accordance with the manufacturer’s installation instructions.
STARTUP AND CHECKOUT

Electrical Power Wiring — Electrical power wiring must comply with the current provisions of the “National Electrical Code” (ANSI/NFPA 70) and with applicable local codes having jurisdiction. Use of rain tight conduit is recommended. Electrical conductors shall have minimum circuit ampacity in compliance with the outdoor unit rating label.The facility shall employ electrical circuit protection at a current rating no greater than that indicated on the outdoor unit rating label. Refer to the unit wiring diagram for connection details.

Minimum Circuit Ampacity — Electrical wiring to the equipment must be compatible and in compliance with the minimum circuit ampacity listed on the outdoor unit data label.

COPPER WIRE SIZE — AWG

(1% Voltage Drop)

Supply Wire Length-Feet

Supply Circuit

200 150 100

50

Ampacity

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

Wire Size based on N.E.C. for 60° type copper conductors.

WARNING:
Ensure electrical power to the unit is off prior to performing the following steps. Failure to do so may cause personal injury or death.
Air Filters — Ensure air filters are clean and in place prior to operating the equipment.
Thermostat — Set the room thermostat function switch to OFF, fan switch to AUTO, and adjust the temperature setpoint to its highest setting.
Prior to applying electrical power to the outdoor unit, ensure that the unit has been properly and securely grounded, and that power supply connections have been made at both the facility power interface and outdoor unit.
Outdoor Unit — Ensure the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/control panels are in place.
Using extreme caution, apply power to the unit and inspect the wiring for evidence of open, shorted, and/or improperly wired circuits.
7

Green G

Red

R

Brown W

Orange W 2
For 2-Stage Heater Kits

Thermostat
G R W2C E O Y
NOTE: Jumper betweenW2 and E is required when no OD T-Stat is used.
R W2
COY

Grey C

Air Handler

Heat Pump OD Section

Typical Heat Pump with Standard Air Handler

8

A typical installation with a heat pump thermostat, air handler, and heat pump with an outdoor thermostat.

Thermostat
G R W2C E O Y

Green G

Red

R

White W

Grey C

E
R W2 COY

Air Handler

Heat Pump OD Section

Typical Heat Pump with Outdoor Thermostat and Air Handler

9

Functional Checkout:
CAUTION:
If equipped with a compressor crankcase heater, wait 24 hours prior to performing a function checkout to allow for heating of the compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system.
Indoor Blower — Set the thermostat function switch to COOLING and the fan switch to ON. Verify that the indoor blower is operating and that airflow is not restricted. Set the fan switch back to AUTO.
Blower Time Delay Relay (Select Models): A time delay relay may be provided with the unit and must be installed in the indoor section. The relay will keep the indoor blower running an additional 40 seconds for increased cooling efficiency after the outdoor unit shuts off. The relay has four terminals and one mounting hole. Connect terminal “1” to load side of blower relay. Connect terminal: “2” to terminal “R” of T’stat. Connect terminal “3” to common terminal at blower relay or transformer. Connect terminal “4” to terminal “G” on T’stat.
Low-Pressure Switch (Select Models) — A low-pressure switch is factory- installed in select models only. If provided, this switch is located in the suction line internal to the outdoor unit. The switch is designed to protect the compressor from a loss of charge. Under normal conditions, the switch is closed. If the suction pressure falls below 5 psig, then the switch will open and deenergize the outdoor unit. The switch will close again once the suction pressure increases above 20 psig. Please note that the switch interrupts the thermostat inputs to the unit.Thus, when the switch opens and then closes, there will be a 5 minute short cycling delay before the outdoor unit will energize.
High-Pressure Switch — A high-pressure switch is factory-installed and located in the compressor discharge line internal to the outdoor unit. The switch is designed to de-energize the system when very high pressures occur during abnormal conditions. Under normal conditions, the switch is closed. If the discharge pressure

rises above 575 psig, then the switch will open and de-energize the outdoor unit. The switch will close again once the discharge pressure decreases to 460 psig.Please note that the switch interrupts the thermostat inputs to the unit.Thus, when the switch opens and then closes, there will be a 5 minute short cycling delay before the outdoor unit will energize.
Short Cycle Protection — With the system operating in COOLING mode, note the setpoint temperature setting of the thermostat, and gradually raise the setpoint temperature until the outdoor unit and indoor blower de-energize. Immediately lower the setpoint temperature of the thermostat to its original setting and verify that the indoor blower is energized and that the outdoor unit remains de-energized. Verify that, after approximately 5 minutes, the outdoor unit energizes and that the temperature of the air supplied to the facility is cooler than ambient temperature.
Comfort AlertTM Diagnostics (Select Models) — The Comfort AlertTM diagnostics module facilitates troubleshooting heat pump and air conditioning system failures. This Comfort AlertTM module is designed only for single-phase systems with scroll compressors that have internal overload protection. By monitoring and analyzing data from the compressor and the thermostat demand, the module can detect the cause of electrical and system related failures without any sensors. A flashing LED indicator communicates the ALERT code and guides the service technician more quickly and accurately to the root cause of a problem.
NOTE: This module does not provide safety protection! The Comfort AlertTM module is a monitoring device and cannot control or shut down other devices.
LED Description (See Figure 2) POWER LED (Green):indicates voltage is present at the power connection of the module.
ALERT LED (Yellow): communicates an abnormal system condition through a unique flash code. The ALERT LED will flash a number of times consecutively, pause and then repeat the process. The number of consecutive flashes, defined as the Flash Code, correlates to a particular abnormal condition. Detailed descriptions of specific ALERT Flash Codes are shown in Table 1 of this manual.

10

TRIP LED (Red): indicates there is a demand signal from the thermostat but no current to the compressor is detected by the module.TheTRIP LED typically indicates the compressor protector is open or may indicate missing supply power to the compressor.
The scroll compressor’s run (R), common (C) and start (S) wires are routed through the holes in the Comfort AlertTM module marked “R,” “C” and “S.”
24 VAC Power Wiring — The Comfort AlertTM module requires a constant nominal 24 VAC power supply. The wiring to the module’s R and C terminals must be directly from the indoor unit or thermostat.
The Comfort AlertTM module requires a thermostat demand signal to operate properly.
NOTE: After the thermostat demand signal is connected, verify that 24 VAC across Y and C when demand is present.
TROUBLESHOOTING Interpreting The Diagnostic LEDs ­ When an abnormal system condition occurs, the Comfort AlertTM module displays the appropriate ALERT and/or TRIP LED will flash a number of

times consecutively, pause and then repeat the process. To identify a Flash Code number, count the number of consecutive flashes.
Every time the module powers up, the last ALERT Flash Code that occurred prior to shut down is displayed for one minute. The module will continue to display the LED until the condition returns to normal or if 24 VAC power is removed from the module.
Cooling — Gradually lower the thermostat temperature setpoint below the actual room temperature and observe that the outdoor unit and indoor blower energize. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If present, locate and determine the source of the noise and correct as necessary.
Heating — Lower the thermostat setpoint temperature to the lowest obtainable setting and set the thermostat function switch to HEATING. The indoor blower and outdoor unit should stop running.After a minimum of five minutes, increase the setpoint temperature of the thermostat to the maximum setting.Verify that the outdoor unit and indoor blower have energized. Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature. Listen

POWER

ALERT TRIP
Figure 2. Comfort AlertTM Diagnostics Module
11

Status LED Green “POWER” Red “TRIP”

Status LED Description
Module has power
Thermostat demand signal Y is present, but the compressor is not running

Yellow “ALERT” Flash Code 1

Long Run Time Compressor is running extremely long run cycles

Yellow “ALERT” Flash Code 2

System Pressure Trip Discharge or suction pressure out of limits or compressor overloaded

Yellow “ALERT” Flash Code 3
Yellow “ALERT” Flash Code 4

Short Cycling Compressor is running only briefly
Locked Rotor

Yellow “ALERT” Flash Code 5

Open Circuit

Yellow “ALERT” Flash Code 6

Open Start Circuit Current only in run circuit

Yellow “ALERT” Flash Code 7

Open Run Circuit Current only in start circuit

Yellow “ALERT” Flash Code 8
Yellow “ALERT” Flash Code 9

Welded Contactor Compressor always runs
Low Voltage Control circuit < 17VAC

Status LED Troubleshooting Information
Supply voltage is present at module terminals
1. Compressor protector is open 2. Outdoor unit power disconnect is open 3. Compressor circuit breaker or fuse(s) is open 4. Broken wire or connector is not making contact 5. Low pressure switch open if present in system 6. Compressor contactor has failed open
1. Low refrigerant charge 2. Evaporator blower is not running 3. Evaporator coil is frozen 4. Faulty metering device 5. Condenser coil is dirty 6. Liquid line restriction (filter drier blocked if present in system) 7. Thermostat is malfunctioning 8. Comfort Alert Failure
1. High head pressure 2. Condenser coil poor air circulation (dirty, blocked, damaged) 3. Condenser fan is not running 4. Return air duct has substantial leakage 5. If low pressure switch present in system, check Flash
Code 1 information
1. Thermostat demand signal is intermittent 2. Time delay relay or control board defective 3. If high pressure switch present go to Flash Code 2 information 4. If low pressure switch present go to Flash Code 1 information
1. Run capacitor has failed 2. Low line voltage (contact utility if voltage at disconnect is low)
· Check wiring connections 3. Excessive liquid refrigerant in compressor 4. Compressor bearings are seized
· Measure compressor oil level
1. Outdoor unit power disconnect is open 2. Compressor circuit breaker or fuse(s) is open 3. Compressor contactor has failed open
· Check compressor contactor wiring and connectors · Check for compressor contactor failure (burned, pitted or
open) · Check wiring and connectors between supply and
compressor · Check for low pilot voltage at compressor contactor coil 4. High pressure switch is open and requires manual reset 5. Open circuit in compressor supply wiring or connections 6. Unusually long compressor protector reset time due to extreme ambient temperature 7. Compressor windings are damaged · Check compressor motor winding resistance
1. Run capacitor has failed 2. Open circuit in compressor start wiring or connections
· Check wiring and connectors between supply and the compressor “S” terminal
3. Compressor start winding is damaged · Check compressor motor winding resistance
1. Open circuit in compressor run wiring or connections · Check wiring and connectors between supply and the compressor “R” terminal
2. Compressor run winding is damaged · Check compressor motor winding resistance
1. Compressor contactor has failed closed 2. Thermostat demand signal not connected to module
1. Control circuit transformer is overloaded 2. Low line voltage (contact utility if voltage at disconnect is low)
· Check wiring connections

· Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated. · TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation.
Table 1. Interpreting the Diagnostic LEDS

12

Miswired Module Indication

Recommended Troubleshooting Action

Green LED is not on, module does not power up

Determine if both R and C module terminals are connected. Verify voltage is present at module’s R and C terminals. Review 24VAC Power W iring (page 4) for R and C wiring.

Green LED intermittent, module powers up only when compressor runs

Determine if R and Y terminals are wired in reverse. Verify module’s R and C terminals have a constant source. Review 24VAC Power W iring (page 4) for R and C wiring.

TRIP LED is on but system and compressor check OK

Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor coil falls below 0.5VAC when off. Verify 24 VAC is present across Y and C when thermostat demand signal is present. If not, R and C are reverse wired.

TRIP LED and ALERT LED flashing together

Verify R and C terminals are supplied with 19-28VAC.

ALERT Flash Code 3 (Compressor Short Cycling) displayed incorrectly

Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor coil falls below 0.5VAC when off.

ALERT Flash Code 5, 6 or 7 (Open Circuit, Open Start Circuit or Open Run Circuit) displayed incorrectly

Check that compressor run and start wires are through module’s current sensing holes. Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor coil falls below 0.5VAC when off.

ALERT Flash Code 6 (Open

Check that compressor run and start wires are routed

Start Circuit) displayed for Code 7 through the correct module sensing holes.

(Open Run Circuit) or vice versa

ALERT Flash Code 8 (Welded Contactor) displayed incorrectly

Determine if module’s Y terminal is connected. Verify Y terminal is connected to 24VAC at contactor coil. Verify 24VAC is present across Y and C when thermostat demand signal is present. If not, R and C are reverse wired. V erify
voltage at contactor coil falls below 0.5VAC when off. Review Thermostat Demand Wiring (page 4) for Y and C wiring.

Table 2. Module Wiring Troubleshooting

for any unusual noises. If present, locate and determine the source of the noise and correct as necessary.

Example 1. Dry climate of Southern Arizona. A 90 minute setting is recommended.

OUTDOOR THERMOSTAT (if supplied)
The outdoor thermostat prevents the electrical auxiliary heat (if used) from operating above a desired set point. Selection of the set point is determined from the building design heat load.
The thermostat is adjustable from 45°F to 0°F. The factory temperature setting is at 40°F.
Defrost Cycle Timer — The defrost cycle timer controls the time interval of the hot gas defrost after the defrost sensor closes. It is located in the lower left corner of the defrost control board. Three interval settings are available: 30 minutes, 60 minutes, and 90 minutes.Time setting selection is dependent on the climate where the unit is being installed.

Example 2. Moist climate of Seattle, Washington. A 30 minute setting is recommended.
To set the cycle timer, place the timing pin on the defrost control board to the desired time interval post.
Note: All units are shipped from the factory with the default time setting of 30 minutes. Maximum heating performance can be achieved by setting the time to 90 minutes.
Defrost Test Procedure
1. Terminals”R”-“C”must have 18-30v present between them in order for time delay and defrost sequences to be initiated.
13

2. With compressor running in heat mode, Note: If jumper is left on the “Test” to “common”

first jump the “T2”-“DFT” test pins. This pins permanently, the defrost cycle will become

will indicate to board that defrost T-stat is inoperable.

closed. Defrost T-stat closes at 32°, opens

at 68°.

Optional Equipment — A functional checkout

should be performed in accordance with

3. Next jump the “Test” pin to “C” on terminal the checkout procedures supplied with the

strip. This will initiate defrost test in 5, 10 or equipment.

15 seconds (This is determined by 30, 60

or 90 minutes defrost pin settings). Factory setting will be 30 minutes.

Adjustment of Refrigerant Charge:

4. When the reversing valve shifts to the defrost mode, quickly remove jumper from “Test”-“C”. If the jumper is not removed within a 5 second period, the defrost test will terminate. Unit will continue to stay in defrost mode Until : A) Board recognizes that defrost sensor has reached 68° and opened or B) “T2”-“DFT” jumper is removed or C) 10 minutes have elapsed (board override)
If the above steps will not initiate a defrost, replace the defrost board.
Anti Short Cycle Timer Test
The 5 minute time delay feature can be bypassed or shortened to 1 second by jumping the “Test” to “C” terminal.

CAUTION:
Split system heat pump equipment contains liquid and gaseous refrigerant under pressure. Adjustment of refrigerant charge should only be attempted by qualified, trained personnel thoroughly familiar with the equipment. Under no circumstances should the homeowner attempt to install and/or service this equipment. Failure to comply with this warning could result in equipment damage, personal injury, or death.
NOTE: The following Refrigerant Charging Charts are applicable to listed assemblies of equipment and at listed airflows for the indoor coil. Assemblies of indoor coils and outdoor units not listed are not recommended.

13 SEER SPLIT SYSTEM HEAT PUMP ORIFICE USAGE

Model Number 1-1/2 Ton 2 Ton 2-1/2 Ton 3 Ton 3-1/2 Ton 4 Ton 5 Ton

Restrictor Bore Size (in.)

Indoor

Outdoor

.050

.042

.055

.045

.065

.048

.073

.052

.077

.055

.080

.058

.089

.062

System Charge R-410A (oz.) 112 138 145 168 243 248 248

14

Refrigerant Charging Charts for Cooling Mode of Operation 13 SEER Split System Cooling Charts
REFRIGERANT CHARGING CHARTS LEGEND FOR COOLING/HEATING MODES OF OPERATION
*Note: All pressures are listed in psig. and all temperatures in deg. F. – Shaded boxes indicate flooded conditions – Rated design values. Suction Pressure will be lower than design value if indoor air flow, entering dry bulb, or
entering wet bulb temperatures are lower than design. – Discharge temperatures greater than charted values indicates a refrigerant undercharge.

018K

OUTDOOR TEMPERATURE ( deg. F )

70

75

80

85

90

95

100

105

Suc. Press. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. 133

135 232 89

137 233 100 251 99

139 235 112 253 109 270 107

141 236 120 255 119 273 116 291 116 308 118

143 237 137 258 128 277 120 294 122 312 125 329 124

145

259 142 279 133 299 125 315 134 333 131 350 130

147

281 147 301 137 320 137 337 138 354 136 371 136

149

303 152 322 146 342 141 359 142 376 141

151

325 157 344 151 364 147 381 147

153

347 161 366 156 385 152

155

368 166 388 161

157

390 170

159

15

16

Refrigerant Charging Charts for Cooling Mode of Operation 13 SEER Split System Cooling Charts

024K

OUTDOOR TEMPERATURE ( deg. F )

70

75

80

85

90

95

100

105

Suc. Press. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp.

133

135 247 144

137 248 156 269 142

139 250 167 271 152 291 140

141 248 200 274 162 294 149 312 141 329 136

143 249 217 273 187 294 164 315 147 333 144 349 137

145

274 201 296 178 316 158 336 152 353 144 369 138

147

297 191 318 171 338 161 357 150 373 144 389 140

149

320 185 341 170 360 158 378 150 393 145

151

343 181 362 168 382 157 398 151

153

365 178 384 166 403 156

155

387 175 406 165

157

408 174

159

030K

OUTDOOR TEMPERATURE ( deg. F )

70

75

80

85

90

95

100

105

Suc. Press. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp.

130

132 243 120

134 245 132 265 123

136 246 143 267 133 287 125

138 246 166 270 143 290 133 309 129 327 127

140 246 183 270 161 292 143 312 135 330 134 348 129

142

271 175 294 157 315 142 334 142 352 136 369 132

144

295 171 317 154 338 148 356 143 373 138 390 136

146

319 168 340 157 361 148 378 145 395 142

148

342 167 363 157 383 149 400 148

150

365 167 386 158 406 151

152

388 168 408 160

154

411 169

156

Refrigerant Charging Charts for Cooling Mode of Operation 13 SEER Split System Cooling Charts

036K

OUTDOOR TEMPERATURE ( deg. F )

70

75

80

85

90

95

100

105

Suc. Press. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp.

131

133 250 91

135 251 103 270 102

137 252 114 272 112 290 110

139 254 124 274 122 293 118 312 118 330 120

141 254 141 276 132 297 123 315 124 334 127 352 126

143

277 146 299 137 319 128 338 136 356 133 374 132

145

300 151 321 141 342 141 360 139 379 138 397 138

147

323 155 344 149 364 145 383 144 401 143

149

346 160 367 155 387 151 406 149

151

369 165 389 160 410 156

153

392 169 412 165

155

415 174

157

042K

OUTDOOR TEMPERATURE ( deg. F )

70

75

80

85

90

95

100

105

Suc. Press. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp.

132

134 241 132

136 242 144 262 133

138 243 155 264 143 283 132

140 243 180 266 152 286 141 304 135 320 131

142 243 197 267 172 288 152 307 141 324 138 340 133

144

268 186 289 165 310 148 328 147 344 139 360 134

146

291 179 312 160 332 153 349 146 365 141 380 137

148

314 175 334 161 353 150 369 147 385 143

150

336 172 356 160 375 150 389 149

152

358 170 377 160 397 150

154

380 169 399 159

156

402 168

158

17

18

Refrigerant Charging Charts for Cooling Mode of Operation

13 SEER Split System Cooling Charts

048K

OUTDOOR TEMPERATURE ( deg. F )

70

75

80

85

90

95

100

105

Suc. Press. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp.

130

132 246 144

134 248 155 269 143

136 249 166 271 153 290 142

138 248 196 273 163 293 151 311 144 329 140

140 249 213 272 185 294 164 315 150 332 147 349 141

142

274 199 296 178 317 159 336 155 353 148 369 142

144

297 191 318 172 339 163 357 154 374 148 389 145

146

320 186 341 172 361 160 378 155 394 151

148

343 183 363 170 383 160 399 156

150

365 180 385 169 404 160

152

387 179 407 169

154

409 178

156

060K

OUTDOOR TEMPERATURE ( deg. F )

70

75

80

85

90

95

100

105

Suc. Press. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp. Liq. Press. Dis. Temp.

124

126 260 140

128 261 151 282 142

130 263 162 284 152 304 144

132 262 186 287 162 307 153 327 148 345 146

134 263 202 287 181 309 164 330 154 349 154 367 149

136

288 195 311 177 333 162 353 162 371 156 389 152

138

312 191 334 175 356 169 375 162 393 158 411 156

140

336 189 358 178 379 168 397 164 415 161

142

360 188 381 178 402 170 420 167

144

383 188 404 179 425 172

146

407 189 427 181

148

430 190

150

Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Charts

018K

OUTDOOR TEMPERATURE (DEG. F)

0

10

20

30

40

50

60

Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.

Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.

37 212 108 52 232 111 66 252 114 81 273 117 96 285 125 114 311 139 131 338 153

38 219 106 53 238 109 67 257 112 82 276 115 97 292 123 115 318 135 132 345 147

39 226 104 54 244 107 68 262 110 83 280 113 98 299 120 116 325 130 133 352 141

40 233 102 55 250 105 69 267 108 84 284 111 99 306 117 117 332 126 134 359 134

41 240 100 56 256 103 70 271 106 85 287 109 100 313 114 118 339 121 135 366 128

42 247 98 57 261 101 71 276 104 86 291 107 101 320 111 119 346 117 136 373 122

43 254 96 58 267 99 72 281 102 87 295 105 102 327 108 120 353 112 137 380 116

024K

OUTDOOR TEMPERATURE (DEG. F)

0

10

20

30

40

50

60

Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.

Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.

37 211 111 52 237 115 66 263 119 81 289 123 97 306 132 114 337 147 131 367 162

38 218 109 53 243 113 67 268 117 82 293 121 98 313 129 115 344 142 132 374 156

39 225 107 54 249 111 68 273 115 83 297 119 99 320 126 116 351 138 133 381 149

40 232 105 55 255 109 69 277 113 84 300 117 100 327 124 117 358 133 134 388 143

41 239 103 56 261 107 70 282 111 85 304 115 101 334 121 118 365 129 135 395 137

42 246 101 57 266 105 71 287 109 86 308 113 102 341 118 119 372 124 136 402 131

43 253 99 58 272 103 72 292 107 87 311 111 103 348 115 120 379 120 137 409 125

19

20

Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Charts

030K

OUTDOOR TEMPERATURE (DEG. F)

0

10

20

30

40

50

60

Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.

Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.

35 209 105 49 238 114 63 267 123 77 296 131 92 315 146 109 347 167 126 380 189

36 216 103 50 244 112 64 272 121 78 299 129 93 322 143 110 354 163 127 387 182

37 223 101 51 250 110 65 276 119 79 303 127 94 329 140 111 361 158 128 394 176

38 230 99 52 256 108 66 281 117 80 307 125 95 336 138 112 368 154 129 401 170

39 237 97 53 261 106 67 286 115 81 310 123 96 343 135 113 375 149 130 408 164

40 244 95 54 267 104 68 291 113 82 314 121 97 350 132 114 382 145 131 415 158

41 251 93 55 273 102 69 296 111 83 318 119 98 357 129 115 389 140 132 422 152

036K

OUTDOOR TEMPERATURE (DEG. F)

0

10

20

30

40

50

60

Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.

Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.

34 204 108 49 238 116 64 271 125 79 305 134 95 329 148 111 367 167 128 405 186

35 211 106 50 244 114 65 276 123 80 309 132 96 336 145 112 374 162 129 412 180

36 218 104 51 249 112 66 281 121 81 312 130 97 343 142 113 381 158 130 419 174

37 225 102 52 255 110 67 286 119 82 316 128 98 350 139 114 388 153 131 426 167

38 232 100 53 261 108 68 290 117 83 320 126 99 357 136 115 395 149 132 433 161

39 239 98 54 267 106 69 295 115 84 323 124 100 364 133 116 402 144 133 440 155

40 246 96 55 273 104 70 300 113 85 327 122 101 371 131 117 409 140 134 447 149

Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Charts

042K

OUTDOOR TEMPERATURE (DEG. F)

0

10

20

30

40

50

60

Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.

Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.

36 212 106 50 235 114 64 259 123 78 282 131 93 297 144 109 328 162 125 358 181

37 219 104 51 241 112 65 263 121 79 286 129 94 304 141 110 335 158 126 365 175

38 226 102 52 247 110 66 268 119 80 289 127 95 311 138 111 342 153 127 372 168

39 233 100 53 253 108 67 273 117 81 293 125 96 318 136 112 349 149 128 379 162

40 240 98 54 259 106 68 278 115 82 297 123 97 325 133 113 356 145 129 386 156

41 247 96 55 265 104 69 283 113 83 300 121 98 332 130 114 363 140 130 393 150

42 254 94 56 271 102 70 287 111 84 304 119 99 339 127 115 370 136 131 400 144

048K

OUTDOOR TEMPERATURE (DEG. F)

0

10

20

30

40

50

60

Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.

Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.

35 218 133 49 246 142 62 274 151 75 302 160 88 317 169 100 343 180 112 369 191

36 225 131 50 252 140 63 279 149 76 306 158 89 324 167 101 350 176 113 376 185

37 232 129 51 258 138 64 283 147 77 309 156 90 331 164 102 357 171 114 383 179

38 239 127 52 263 136 65 288 145 78 313 154 91 338 161 103 364 167 115 390 173

39 246 125 53 269 134 66 293 143 79 317 152 92 345 158 104 371 162 116 397 166

40 253 123 54 275 132 67 298 141 80 320 150 93 352 155 105 378 158 117 404 160

41 260 121 55 281 130 68 303 139 81 324 148 94 359 152 106 385 153 118 411 154

21

22

Refrigerant Charging Charts for Heating Mode of Operation 13 SEER Split System Heating Charts

060K

OUTDOOR TEMPERATURE (DEG. F)

0

10

20

30

40

50

60

Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.

Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.

31 223 131 44 253 143 57 283 155 70 313 166 82 329 179 95 355 193 107 381 206

32 230 129 45 259 141 58 288 153 71 316 164 83 336 176 96 362 188 108 388 200

33 237 127 46 265 139 59 292 151 72 320 162 84 343 173 97 369 184 109 395 194

34 244 125 47 271 137 60 297 149 73 324 160 85 350 171 98 376 179 110 402 188

35 251 123 48 277 135 61 302 147 74 327 158 86 357 168 99 383 175 111 409 181

36 258 121 49 282 133 62 307 145 75 331 156 87 364 165 100 390 170 112 416 175

37 265 119 50 288 131 63 312 143 76 335 154 88 371 162 101 397 166 113 423 169

23

INSTALLER: PLEASE LEAVE THESE INSTALLATION
INSTRUCTIONS WITH THE HOMEOWNER.

Powered by TCPDF (www.tcpdf.org)

¢708410p¤
708410A

www.intertherm.net

708410A (Replaces 7084100)
Specifications and illustrations subject to change without notice and without incurring obligations.
Trademark Intertherm® used under license.© NoPrteriknGtelodbailnHVUA.CS,.LALC. (.A0l1l R/0ig7ht)s Reserved.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Intertherm User Manuals

Related Manuals