For your safety

Read all instructions and mounting steps carefully. Keep the instructions for maintenance or disassembly work.

Explanation of the warning levels

Observe and follow the warnings. Non-observance of the warnings may lead to injuries or material damage!

| WARNING! Indicates dangers whichcan result in serious and/or fatal injuries.
---|---
| CAUTION! Indicates dangers which can result in injuries or health hazards.
| NOTICE. Indicates dangers whichcan result in material damage ormalfunctions.
| TIP. Indicates information containingadvice or a useful note.

Explanation of important symbols and pictograms

| Indicates professional personnel who are trained and authorised to carry out the electrical connection.
---|---
| Indicates professional personnel who are trained and authorised to carry out the mounting.

Safety notes

WARNING! Risk of electric shock! Never work with voltage applied.
WARNING! Risk of electric shock!
The light source of this luminaire shall only be replaced by the manufacturer or a service technician authorised by the manufacturer or a similar qualified person. If the light source malfunctions or fails, please contact TRILUX.
NOTICE. Wear clean installation gloves to prevent soiling.
NOTICE. Do not cover the product with insulating material.

Important information on electronic control gear units (ECG)

A neutral conductor interruption in the threephase circuit leads to overvoltage damage in the lighting system. Only open the neutral conductor isolating terminal in de-energised state, and close the neutral conductor isolating terminal before switching on again. Do not exceed the maximum permissible ambient temperature ta of the luminaire.
Exceeding this limit reduces the service life and in extreme cases there is a risk of premature failure of the luminaire. Design connection cables for the control inputs of DALI control gear (1-10 V, DALI etc.) to be 230 V mains voltage-proof (basic insulation).

Intended use

Intended for indoor use with a maximum ambient temperature of: ta 25°C
Safety class: II
Safety class: I SNS … ACT …
Protection rating of connection compartment: IP20
Protection rating on room side: IP44
Suitable for further wiring. Max. total current 10 A at 1,5 mm².
Suitable for further wiring. Max. total current 16 A at 2,5 mm².
Not suitable for further wiring.
SNS … T01 …

Disposal of waste electrical and electronic equipment

Always collect and dispose of old electrical and electronic equipment separately at the end of its service life. In case of doubt, seek information about environmentally-compliant waste disposal from your local district authority or special waste disposal companies. Current information on the energy efficiency class of the selected product version can be found in the corresponding data sheet for the luminaire. Instructions for replacing or removing the light source in accordance with Regulation 2019/2020/EU can be found at: www.trilux.com/EcoDesign

10172493 | 220921 | © trilux.com
TRILUX GmbH & Co. KG
Heidestraße
D-59759 Arnsberg
+49 2932 301-0
info@trilux.com
www.trilux.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals