Product Information: TRILUX twenty3 2330 G3 LED
The TRILUX twenty3 2330 G3 LED is a lighting fixture that provides bright and energy-efficient illumination. It is designed for professional use and offers various safety features to ensure proper installation and usage.
- Product Code: 10236493 | 230726
- Mounting Instructions: DE MONTAGEANLEITUNG, EN MOUNTING INSTRUCTIONS, FR INSTRUCTIONS DE MONTAGE, IT ISTRUZIONI DI MONTAGGIO, ES INSTRUCCIONES DE MONTAJE, NL MONTAGEHANDLEIDING, PL INSTRUKCJA MONTAU
- Safety Class: I, II
- Protection Rating: IP20 (for general protection) and IP40 (for protection on the room side)
Product Usage Instructions
Before using the TRILUX twenty3 2330 G3 LED, please read and understand the following instructions:
Electrical Connection
- WARNING! The electrical connection must be carried out by professional personnel who are trained and authorized. Never work with electrical voltage applied.
Installation
- WARNING! The assembly must be carried out by professional personnel who are trained and authorized. Always wear clean installation gloves to prevent soiling.
Safety Precautions
- Do not cover the product with insulating material.
- The light source of this luminaire cannot be replaced. When the light source has reached the end of its service life, the whole luminaire should be replaced.
Further Wiring
The TRILUX twenty3 2330 G3 LED is suitable for further wiring. The maximum
total current is 10 A at 1.5 mm2 or 16 A at 2.5 mm2.
Disposal of Waste Electrical and Electronic Equipment
Always collect and dispose of old electrical and electronic equipment
separately at the end of its service life. Seek information about
environmentally-compliant waste disposal from your local district authority or
special waste disposal companies. For more detailed information, refer to the
product data sheet available on the TRILUX website.
- Current information on the energy efficiency class of the selected product version can be found in the corresponding data sheet for the luminaire. Instructions for replacing or removing the light source in accordance with Regulation 2019/2020/EU can be found at: www.trilux.com/EcoDesign
Explanation of the warning levels
Observe and follow the warnings. Non-observance of the warnings may lead to injuries or material damage!
- WARNING: Indicates dangers which can result in serious and/or fatal injuries.
- CAUTION: Indicates dangers which can result in injuries or health hazards.
- NOTICE: Indicates dangers which can result in material damage or malfunctions.
- TIP: Indicates information containing advice or a useful note.
Explanation of warning messages and instructional pictogram
- WARNING: The electrical connection must be carried out by profession-al personnel who are trained and authorised.
- WARNING: The assembly must be carried out by professional personnel who are trained and authorised.
- WARNING: Risk of electric shock! Never work with electrical voltage applied.
- NOTICE: Wear clean installation gloves to prevent soiling.
Safety instructions and safety labels
- Insulating material
Do not cover the product with insulating material.
Type: ··· ETWD
- Light source
The light source of this luminaire can-not be replaced! When the light source has reached the end of its service life the whole luminaire shall be replaced.
Electronic control gear units (ECG) A neutral conductor interruption in the three-phase circuit leads to overvoltage damage in the lighting system. Only open the neutral conductor isolating terminal in de-energised state, and close the neutral conductor isolating terminal before switching on again. Do not exceed the maxi-mum permissible ambient temperature ta of the luminaire. Exceeding this limit reduces the service life and in extreme cases there is a risk of premature failure of the luminaire. De-sign connection cables for the control inputs of DALI control gear (1-10 V, DALI etc.) to be 230 V mains voltage-proof (basic insulation).
Intended use
-
Safety class: I
Type: ··· ET ; ··· ETDD -
Safety class: II
Type: ··· ETWD -
Protection rating: IP20
-
Protection rating on room side: IP40
-
Suitable for further wiring. Max. total current 10 A at 1,5 mm2.
-
Suitable for further wiring. Max. total current 16 A at 2,5 mm2.
Conformity
Directive 2014/53/EU
Simplified EU Declaration of Conformity according to the RED Directive if the
luminaire is equipped with a control gear unit with NFC interface or a radio
component:
TRILUX hereby declares that the radio system type 2330 G3 … complies with
Directive 2014/53/EU. The full text of the EU Declaration of Conformity is
available on the Internet at: www.trilux.com/eu-
conformity
TouchDim control (··· ETDD) TouchDim serves to control individual luminaires.
The maximum number of permissible electronic control gear units (ECG) for one
TouchDim control is max. 10. The overall cable length (push-button to last
luminaire) must not exceed max. 25 m. When using several luminaires with a
DALI control or a TouchDim control, TRILUX recommends using a DALI repeater.
Otherwise, a synchronizations are possible due to disturbances in the
building.
Mounting
Assembly
TRILUX GmbH & Co. KG
Heidestraße
D-59759 Arnsberg
+49 2932 301-0
info@trilux.com
www.trilux.com
www.trilux-twenty3.com
References
- LED lighting & individual lighting solutions | TRILUX
- TRILUX twenty3 LED Leuchten – professional lighting in daily business
- LED lighting & individual lighting solutions | TRILUX
- trilux.com/EcoDesign
- Service - TRILUX Simplify Your Light
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>