FIREX KF30 Heat Alarm Instruction Manual
- June 4, 2024
- Firex
Table of Contents
KF30 Heat Alarm
Instruction Manual
KF30 Heat Alarm
KF30/ KF30LL/ KF30R
57°C TEMPERATURE RATING
KF30 LOOSE BATTERY
KF30LL SEALED-IN LITHIUM BATTERY
KF30R RECHARGEABLE
BS5446 pt 2: 2003
LICENSE NO. KM738879
PLEASE READ AND SAVE THIS USER GUIDE
Installer: Please leave this user guide with the occupier (or, in the case
of a house in multiple operations, with the owner).
NOTE: Additional markings can be found on the back of the unit.
WARNING: HEAT ALARMS ALONE ARE NOT SUFFICIENT FOR LIFE SAFETY AS THEY ARE
NOT DESIGNED TO DE-! TECH SMOKE. THEY ARE INTENDED TO DETECT TEMPERATURES OF
57°C AND ABOVE TO PROVIDE AN ADDI- TIONAL SOURCE OF INFORMATION THAT IS
SUPPLEMENTARY TO THAT PROVIDED BY SMOKE ALARMS TO INCREASE THE PROBABILITY
THAT AN EARLY WARNING WILL BE PROVIDED AND SO ENHANCE LIFE SAFETY AND PROPERTY
PROTECTION. SEE HEAT ALARMS HAVE LIMITATIONS IN THE IMPORTANT SAFETY
INFORMATION SECTION OF THIS USER GUIDE.
HEAT ALARM FEATURES
- This heat alarm is powered by a 230V AC supply and has a DC battery backup source. AC/DC heat alarms offer added protection in the event of a power failure.
- Unique power connector prevents interconnecting with incompatible heat alarms, CO alarms, smoke alarms, or security systems.
- Items KF30, KF30LL, and KF30R heat alarms can be interconnected with up to 23 other models as shown in the Specifications. Do not connect to any other type or model of smoke, CO, or heat alarm.
- Hush quiets unwanted alarms for up to 9 minutes.
- KF30R includes permanent rechargeable lithium batteries.
- Alarm memory identifies which alarm has activated
- Optional use of tamper-resistant features serves as a safeguard against tampering.
- The heat alarm will sound a short beep about once every 40 seconds if the battery is low.
- Multi-purpose green and red LEDs indicate that the heat alarm is connected to the AC supply, is working normally, or is in alarm.
- A loud alarm sounder – 85 decibels [dB(A)] at 3m – will sound to alert you to an emergency.
- Test button checks heat alarm operation.
- KF30LL is provided with a long-life lithium battery that lasts the full life of the alarm and a tamper-proof option using a screw provided
SPECIFICATIONS
ITEM (MODEL NUMBER) | KF30, KF30LL, KF30R |
---|---|
ELECTRICAL RATING | 230V AC, 50HZ, DC BACK UP (KF30: 9V REPLACEABLE, |
INTERCONNECTING FIRED | UP TO ANY COMBINATION OF 23 OTHER ALARM |
TEMPERATURE RATING | 57°C |
MAXIMUM AMBIENT | 37.8°C |
OPERATING TEMPERATURE | 0°C TO 40°C |
OPERATES UP TO 93% HUMIDITY | ON-CONDENSING) |
RECOMMENDED COVERAGE | 50M |
RECOMMENDED SPACING | 5.3M |
MAXIMUM DISTANCE FROM WALL | 7.7M |
MAXIMUM CEILING HEIGHT | 6M |
IMPORTANT SAFETY INFORMATION
PLEASE READ AND SAVE THESE INSTRUCTIONS
WARNING
- The KF30R requires constant 230V AC power AND fully charged batteries to operate properly. It requires 2 full days under mains power to reach full backup capacity. The batteries are not replaceable. Do not connect a heat alarm to any other type of device except those listed in this user guide.
- The KF30 and KF30LL heat alarm requires constant 230V AC power AND a healthy 9V DC battery to operate properly. Removal of battery and loss or disconnection of AC power will render the alarm inoperative. DO NOT use any other kind of battery except as specified in this user guide. Do not connect a heat alarm to any other type of device except those listed in this user guide.
- The TEST/FALSE ALARM CONTROL button accurately tests all heat alarming- tions. DO NOT use any other test method for routine testing. Test heat alarm weekly to ensure proper operation.
- Higher ceilings will increase the time needed by the heat alarm to detect a fire. In most dwellings, the ceiling height will keep this reaction time within acceptable limits. However, ceilings with a height of over 6m may delay the reaction time of the heat alarm significantly. Advice from your local distributor or Fire Brigade should be obtained when installing a heat alarm on a ceiling higher than 6m.
- This heat alarm should be installed only by a qualified electrician. The installation should comply with BS 7671 and all prevailing local, regional and national codes.
- This heat alarm is designed to be used only as part of the protection of a single-family dwelling or a house in multiple occupations (HMO) of no more than two stories. It also may be used in conjunction with smoke alarms within individual flats or apartments in larger houses in multiple occupations, to provide an early warning to occupants of a fire in a room within the dwelling, but a communal fire alarm system also should be provided in such cases. DO NOT install this heat alarm in any other buildings, such as hotels, motels, dormitories, hospitals, nursing homes,or group homes of any kind. In these occupancies, a complete automatic fire detection and alarm system, complying with BS 5839: Part 1, should be installed
- Heat alarms should be used only in conjunction with smoke alarms, with which the heat alarms should be interconnected, in order to provide early warning of heat, smoke, or fire. Smoke alarms should be installed on every level of the dwelling.
- Interconnected heat alarms and smoke alarms offer maximum protection. By interconnecting heat alarms and smoke alarms, when one unit senses heat, smoke, or fire, and sounds its alarm, all others will sound as well. DO NOT connect this heat alarm to any other type of alarm except those stated in this user guide or an approved auxiliary device.
- Heat alarms interconnected with smoke alarms may not alert every household member every time. The alarm sounder of the heat alarm is loud in order to alert individuals of potential danger. However, there may be limited circumstances where an occupant may not hear the alarm (e.g., outdoor or indoor noise, sound sleepers, drug or alcohol usage, impaired hearing, etc.). Household members must hear the alarm’s warning sound and quickly respond to it to reduce the risk of damage, injury, or death that may result from fire.
- Check carefully that, when any one device operates, the alarm signal given by interconnected devices is clearly audible throughout the building, particularly in bedrooms, where it is essential that the alarm signal will wake sleeping occupants.
- This heat alarm can sound an alarm only when it detects temperatures of 57°C or above. Heat alarms do not sense smoke or gas. In some fires, hazardous levels of toxic chemicals and smoke can build up before a heat alarm will operate. Temperatures may not reach 57°C to activate the heat alarm QUICKLY ENOUGH to ensure safe escape.
- Some fires are slow smoldering, low heat-producing, or are in a different room to that in which the heat alarm is located, or the heat from the fire may bypass the alarm – the heat alarm may not give a warning under these circumstances.
- HEAT ALARMS HAVE LIMITATIONS. This heat alarm is not guaranteed to protect lives or property. Heat alarms are not a substitute for insurance. Householders should insure their lives and property. In addition, as with any electronic device, it is possible for the heat alarm to fail at any time.
- Never paint this heat alarm.
HEAT ALARM LOCATION
Heat alarms give an audible warning when the temperature at the alarm reaches
57°C. Heat alarms are ideal for kitchens, garages, cellars, boiler rooms,
attics and other areas where there are normally high levels of fumes, smoke,
or dust which preclude the use of smoke alarms due to the risk of false
alarms. Guidance on fire detection in dwellings is contained in BS 5839: Part
6. For normalized bungalows, two-story houses, flats, and maisonettes, the
British Standard recommends that the minimum level of protection should
comprise smoke alarms in the hallways and staircases. This minimum standard
necessitates one smoke alarm in the hallway of a typical bungalow or one smoke
alarm on each level of a two-story house heat alarms should not be used in
these circulation areas. If there are, for example, long hallways, even the
minimum standard may necessitate additional interconnected smoke alarms. If,
however, the design of the dwelling does not comply with modern fire safety
standards, or if factors such as the presence of several young children,
elderly occupants or disabled people, or of smokers, the use of portable
heaters or solid fuel fires during the night, or the use of electric blankets,
particularly by the elderly, the British Standard advises that additional
detection devices, installed within rooms, may be necessary. The British
Standard recommends that, if the risk justifies the provision of detectors ia
the kitchen, boiler room, or another area (except a circulation area) in which
smoke alarms would be likely to give false alarms, heat alarms should be used.
However, the Standard also advises that heat alarms may be installed in other
rooms instead of smoke alarms, provided that the construction enclosing the
room (including the door can resist fire for a sufficient time after the
operation of a heat alarm to enable occupants to escape safely. However, a
heat alarm is unlikely to operate early enough to save the life of anyone
asleep in the room in which it is installed. Moreover, a heat alarm in the
room of fire origin may not give sufficient warning for occupants to escape
safely if the door to that room is open. A Heat Alarm is also recommended in
the Living Room, if a smoke alarm in that location, suffers nuisance alarms
from smokers.
HEAT ALARM SITING
FOR BEST PROTECTION, IT IS RECOMMENDED THAT YOU INSTALL A SMOKE OR HEAT
ALARM IN EVERY ROOM.
In addition, it is recommended that all smoke and heat alarms should be
interconnected.
Install heat alarm on a standard dry lining box or Firex pattress as close to
the center of the ceiling as possible. If the center is not practical, mount
the heat alarm no closer than 300mm away from a wall or corner.
In rooms with open joists or beams, all ceiling-mounted alarms should be
located
on the bottom of such joists or beams and not up in joist channels. On sloped,
peaked or gabled ceilings, install a heat alarm 90cm from the highest point.
If only wall placement is possible, install no further than 150mm from the
ceiling.
DO NOT install heat alarms:
-
Directly over the cooker, stove, or oven.
-
In areas with high humidity, like bathrooms or shower rooms, or areas near dishwashers or washing machines. Install heat alarms at least 3m away from these areas if possible.
-
Adjacent to, or directly above, heaters, air-conditioning vents or ceiling fans.
-
In an area where the temperature may fall below -30°C or rise above 37°C.
-
In areas above 93% relative humidity (RH), non-condensing.
-
Near fluorescent lights. Electrical noise and flickering may affect the operation of the heat alarm.
-
Closer than 300mm to light fittings.
-
In such a position that it is difficult or dangerous to reach for testing or maintenance.
-
Do not site the alarm in an area where water or other liquids may enter the alarm.
HOW TO INSTALL THIS HEAT ALARM
DANGER: ELECTRIC SHOCK HAZARD. TURN OFF POWER TO THE HEAT ALARM CIRCUIT
AT THE MAIN DIS- TRIBUTION BOARD BY REMOVING THE FUSE OR SWITCHING THE CIRCUIT
BREAKER TO THE OFF POSITION AND SECURING IT.
WARNING: THIS HEAT ALARM SHOULD BE INSTALLED ONLY BY A QUALIFIED
ELECTRICIAN IN ACCORDANCE WITH THE REGULATIONS FOR ELECTRICAL INSTALLATIONS
PUBLISHED BY THE INSTITUTION OF ELEC-TRIAL ENGINEERS (BS 7671) AND/OR ALL
PRESIDING LOCAL, REGIONAL, AND NATIONAL CODES.
WARNING: HEAT ALARMS SHOULD BE CONNECTED ON A SINGLE INDEPENDENT,
DEDICATED CIRCUIT AT THE MAIN DISTRIBUTION BOARD. NO OTHER ELECTRICAL
EQUIPMENT, EXCEPT COMPATIBLE SMOKE AND CO ALARMS, SHOULD BE CONNECTED TO THIS
CIRCUIT. IF YOUR HOME HAS RESIDUAL CURRENT DEVICE PRO- SECTION ON THE
ELECTRICAL INSTALLATION OR ON INDIVIDUAL CIRCUITS, CHECK WITH A QUALIFIED
ELECTRICIAN TO MAKE SURE THAT FAULTS ON CIRCUITS SERV- ING SOCKET OUTLETS, OR
PORTABLE APPLIANCES CAN NOT CAUSE INTERRUPTION TO THE SUPPLY TO THE HEAT
ALARMS.
-
Route the household AC supply/interconnect cable into the dry lining box or Firex surface pattress.
-
Using a suitably-rated terminal block, connect the neutral supply to the blue lead of the connector plug.
-
Using a suitably-rated terminal block, (supplied with Firex pattresses), connect the line supply to the brown lead of the connector plug.
-
If interconnecting is desired, connect the orange or white of connector plug to the designated interconnect conductor of the household cable. See note INTERCONNECTING HEAT ALARMS.
NOTE: If this is to be a single-station heat alarm, connect the orange or white wire to an unused terminal block -
Insert the completed connector block onto the mounting pins of the Firex Pat- tress or recess into the dry lining box.
-
Pass the connector plug through the mounting plate of the heat alarm, align slots, and fasten the mounting plate securely to the Pattress or dry lining box.
NOTE: If this is to be a single-station heat alarm, connect the orange or white wire to an unused terminal block. -
Attach connector plug to pins on the back of the heat alarm. The plug will only fit one way and will snap into place.
-
Gently tug the connector to be sure it is attached securely.
NOTE: Steps 9 and 10 for Models KF30, and KF30LL only. These models contain a battery pull tab for your convenience. The battery pull tab must be removed to activate battery backup and provide power to the unit in the event of mains power loss. -
Pull out the battery pull tab. The heat alarm may beep briefly when the battery is activated.
-
Push the button and hold the button on the front cover of the heat alarm for five (5) seconds. The heat alarm should sound its alarm horn if the battery is connected. NOTE: cover sounder vents with your hand or hold the unit at arm’s length during testing to avoid ear discomfort.
-
Position heat alarm to mounting plate and turn it clockwise to lock into place. The heat alarm will not mount to the plate if the battery is not installed (Models KF30, KF30LLonly).
-
Turn on power at the main fuse box or circuit breaker. The green LED on the cover should be illuminated.
-
Test heat alarm. See “TESTING THE HEAT ALARM”.
INTERCONNECTING HEAT ALARMS
Use 1.5mm2 minimum solid or stranded cable with a rating of 230V. When
interconnecting heat alarms, CO alarms or smoke alarms, the maximum cable
length between any two should be 450m for a 1.5mm2 cable (20-ohm loop
resistance.) DO NOT connect to any other type or model of heat alarm, CO
alarm, or smoke alarm. Connect all interconnected heat and smoke alarms to a
single final circuit. Wiring must conform to I.E.E. Regulations for Electrical
Installations (BS 7671).
RED AND GREEN LED INDICATORS
NOTE: Colors shown correspond to electrical codes in the United Kingdom.
Colors may vary in other countries.
This heat alarm features a red and green LED indicator that can be seen
through the clear light pipe on the top of the alarm. The LEDs indicate the
following:
GREEN
ON – AC power is present.
OFF – AC power is not present.
RED
BLINKS ONCE EVERY 5 MINUTES AND 20 SECONDS – Mains power is present
indicating normal operation.
BLINKS ONCE EVERY 10 SECONDS – False Alarm Control activated.
OFF – DC power is not present.
BLINKS ONCE A SECOND and the unit is sounding alarmed – senses 57°C
temperature or greater. OFF and the unit is sounding alarmed – Another
interconnected smoke/heat alarm in the network has sensed smoke or 57°C and is
signaling this alarm.
3 RAPID FLASHES AT 40 SECOND INTERVAL – Indicates which alarm has previously
detected an alarm condition.
HUSH CONTROL
WARNING: BEFORE USING THE ALARM’S HUSH FEATURE, FULLY IDENTIFY THE SOURCE
OF THE HEAT BUILD-UP AND MAKE SURE THAT THE AREA IS SAFE. TO ACTIVATE CONTROL
PUSH AND RELEASE THE TEST/FALSE ALARM CONTROL BUTTON IN THE CENTER OF THE
ALARM. THE ALARM WILL SILENCE IMMEDIATELY AND THE RED LIGHT (LED) WILL BLINK
APPROXIMATELY EVERY 10 SECONDS FOR THE NEXT 10 MINUTES. THIS FEATURE IS TO BE
USED ONLY WHEN A SAFE CONDITION IS KNOWN TO EXIST. The Hush feature will
silence the alarm for approximately 9 minutes. A rapid rise in temperature
will override the False Alarm Control and cause the unit to sound an alarm.
After 9 minutes the heat alarm will revert to normal operation. If the unit
still detects a dangerous situation the alarm will sound again. If
interconnected alarms are installed, the unit that detects the high
temperature and sounds the alarm cannot be inadvertently silenced by the
TEST/Hush button of other units. In this case, all of the alarms will continue
to sound for as long as a dangerous situation is detected or until the
TEST/Hush button of the initiating alarm is pressed. If the alarm does not go
into False Alarm Control and continues to sound its alarm, the heat in the
area is too high and a dangerous situation may exist – take emergency action.
TESTING THE HEAT ALARM
WARNING: TEST EACH HEAT ALARM AND SMOKE ALARM TO BE SURE THAT EACH IS
INSTALLED CORRECTLY AND IS OPERATING PROPERLY.
STAND AT ARM’S LENGTH FROM THE HEAT ALARM WHEN TESTING. THE ALARM SOUNDER IS
LOUD TO ALERT YOU TO AN EMERGENCY AND CAN BE HARMFUL TO HEARING.
TEST THE HEAT ALARM WEEKLY AND UPON RETURNING FROM HOLIDAY, OR WHEN THE HOUSE
HAS BEEN UNOCCUPIED FOR SEVERAL DAYS.
Test all heat alarms weekly by doing the following:
-
Check the TEST/HUSH button. If the green LED above the test button is ON, the heat alarm is receiving AC power.
-
Firmly depress and hold the TEST/Hush button for at least five (5) seconds. The heat alarm will sound 3 long beeps, pause, 3 long beeps, repeating for up to 10 seconds after the TEST/Hush button is released.
NOTE: If heat alarms are interconnected, all heat and smoke alarms should sound an alarm within three (3) seconds after any test button is pushed and the tested heat alarm sounds. -
If the heat alarm does not sound, turn off the power to the heat alarm circuit at the main distribution board and check the wiring. Retest the heat alarm.
WARNING: IF THE HEAT ALARM SOUNDS AND THE HEAT ALARM IS NOT BEING TESTED, THE HEAT ALARM IS SENSING A TEMPERATURE OF 57°C OR ABOVE. THE ALARM SOUND REQUIRES YOUR IMMEDIATE ATTENTION AND ACTION. EVACUATE THE DWELLING IMMEDIATELY!
MAINTENANCE AND CLEANING
In addition to weekly testing, this heat alarm must be cleaned periodically to
remove dust, dirt, and debris.
DANGER: ELECTRIC SHOCK HAZARD.
TURN OFF THE AC SUPPLY TO THE HEAT ALARM AT THE MAIN DISTRIBUTION BOARD BY
REMOVING THE FUSE OR SWITCHING THE APPROPRIATE CIRCUIT BREAKER TO THE OFF
POSITION BEFORE CLEANING THE HEAT ALARM.
WARNING: HEAT ALARMS ARE LIFE-SAVING DEVICES AND SHOULD BE CARED FOR
PERIODICALLY BY CLEANING
Clean the heat alarm at least once annually to remove dust, dirt and debris.
Always turn off the AC power to the heat alarm before cleaning it.
Using the soft brush or wand attachment to a vacuum cleaner, vacuum all sides
and the cover of the heat alarm. Be sure that all vents are free from debris.
If necessary, turn off the AC power and use a cloth dampened with warm water
to clean the heat alarm cover.
IMPORTANT: Do not attempt to remove the cover or clean inside the heat
alarm.
THIS WILL INVALIDATE YOUR GUARANTEE. Failure to properly clean and maintain
this heat alarm may result in impaired operation and possible failure and will
invalidate the guarantee.
WARNING: BATTERIES ARE NOT REPLACEABLE IN THE KF30LL OR KF30R. MODEL
KF30R HAS PERMANENTLY MOUNTED RECHARGEABLE LITHIUM BATTERIES THAT ARE
DESIGNED TO LAST THE USEFUL LIFE OF THE ALARM.
BATTERY REPLACEMENT – KF30 ONLY Always turn off the AC power to the heat
alarm before replacing the battery. Replace the battery at least once
annually, or immediately when the low battery signal sounds once a minute,
even though the heat alarm is receiving AC power. The low battery signal can
be hushed for 8 hours by pressing and releasing the Test button. NOTE:
constant exposure to extreme temperatures or humidity can reduce battery life.
Use only the following batteries as replacements in this heat alarm: Energizer
522 ; Duracell MN1604 or MX 1604; FDK CP-V9Ju; Ultralife U9VL-J-P.
CAUTION: DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY REPLACED. USE ONLY
THE BATTERIES SPECIFIED IN THE USER USER GUIDE.
WARNING: DO NOT USE ANY OTHER TYPE OF BATTERY, EXCEPT AS SPECIFIED IN
THIS USER GUIDE. DO NOT USE RECHARGEABLE BATTERIES. THE CROSSED-OUT WHEELED
BIN SYMBOL INDICATES THE BATTERIES LISTED IN THIS USER GUIDE SHOULD BE
DISPOSED OF SEPARATELY FROM HOUSEHOLD WASTE.
- Turn off the AC power supply to the heat alarm at the main distribution board.
- Insert a small screwdriver into the slot in the mounting plate and turn the heat alarm counterclockwise to detach the alarm.
- Gently pull down the heat alarm. Be careful not to separate any wire connections.
- Pull out the connector plug from the back of the heat alarm.
- From the back of the heat alarm, lift the tab to open the battery compartment door.
- Remove the battery from the compartment. Disconnect the drained battery from the battery compartment and discard.
- Insert a fresh, 9-volt battery into the battery pocket. The battery will fit only one way. The heat alarm may sound a short beep when hen battery is installed. This is normal and means the battery is installed correctly.
- Close the battery compartment door. Push down until it snaps into place.
- Using the TEST button, test the heat alarm to verify 9V DC battery back-up. 1
- Replace the connector plug. The connector will snap into place. Gently tug the connector to be sure it is attached properly.
- Reattach the heat alarm to the mounting plate by turning the heat alarm clockwise until it snaps into place.
- Turn on the AC power and test the heat alarm using the TEST button. See TESTING THE HEAT ALARM.
REPAIR
CAUTION: DO NOT ATTEMPT TO REPAIR THIS HEAT ALARM. DOING SO WILL
INVALIDATE YOUR GUARANTEE.
If the heat alarm is not operating properly, see TROUBLESHOOTING. If
necessary, and if the heat alarm is still under warranty, pack it in a well-
padded carton and send it, with Proof of Purchase postage prepaid, to the
address given at the end of this user guide.
If the heat alarm is no longer under guarantee, have a qualified electrician
replace the heat alarm immediately with a comparable Firex brand heat alarm.
FIRE SAFETY RULES AND PREVENTING HAZARDOUS SITUATIONS
Siting, testing, and taking care of heat and smoke alarms is just one step in
helping to protect your family and home from fires. You must also reduce the
chance that fires will start in your home and increase your chances of
escaping if a fire does start. At a minimum, your home fire safety program
should include the following guidelines:
- Use smoking materials properly – never smoke in bed or when sleepy or under the influence of alcohol or other drugs.
- Keep matches and other sources of ignition away from children.
- Store flammable materials in proper containers and never store or use them near open flames or sparks.
- Keep electrical appliances and their leads in good working condition, and do not overload electrical circuits.
- Keep fireplaces, chimneys, and barbecue grills clean, and make sure they are properly sited away from combustible materials.
- Keep portable heaters and open flames such as candles away from combustible materials.
- Do not allow rubbish to accumulate.
- Have the electrical wiring in your house checked by a qualified electrician at least every 10 years (or more often as it ages).
- Never leave cooking unattended.
FIRE PROCEDURE
If you hear the heat or smoke alarm sounding, and you have not pushed the test
button, it is warning you of a dangerous situation. You will need to respond
immediately. To prepare for such occurrences, develop family escape plans,
discuss them with all household members, and practice them regularly. For your
safety, as a minimum, you should do the following to have more effective fire
safety.
- Draw a floor plan of your home and find all ways to escape if there is a fire. On the ground floor, consider whether windows can be used for escape. On upper floors, consider whether external rescue will be possible if escape routes are blocked by fire or smoke.
- Expose everyone to the sounds of the heat alarm and of the smoke alarm and ex- plain what the sounds mean. Show them how to check to see if doors are hot be- fore opening them, how to stay close to the floor and crawl along the floor to stay below dangerous smoke, fumes, and gases, and how to use the alternative exit if a door is hot. Instruct them not to open the door if the door is hot.
- Decide on a meeting place a safe distance from your house and make sure all members of your household understand they should go and wait for you there if there is a fire. Explain to children that they must be ready to leave the house by themselves if necessary.
- Hold fire drills every six (6) months to make sure everyone, even small children, knows what to do to escape safely.
- Know where to go to call the Fire Brigade from outside your house.
- Provide emergency equipment, such as fire extinguishers, and teach your family how and when to use this equipment.
WHAT TO DO IN CASE OF A FIRE
After you have prepared family escape plans and practiced them with your family, you have increased their chances of escaping safely. Review the following rules with your family when you have fire drills, so everyone will remember them in a real fire.
- Don’t panic, stay calm. Your safe escape may depend on thinking clearly and remembering what you have practiced.
- Get out of the house, following your planned escape route, as quickly as possible. Do not stop to collect anything or to get dressed.
- Open doors carefully only after feeling to see if they are hot. Do not open a door if it is hot; use an alternative escape route. If your escape route is blocked, go to a window and shout for help. If necessary, stuff clothing or other materials in the gaps around the room door to stop smoke from entering until help arrives.
- Stay close to the floor; smoke and hot gases rise toward the ceiling.
- Keep doors and windows closed unless you open them to escape.
- Meet at your pre-arranged meeting place after leaving the house.
- Call the Fire Brigade as soon as possible from outside your house. Give your full address, including the name of the town or village.
- Always call the Fire Brigade as soon as possible, even if a fire seems small.
- Never re-enter a burning or smoke-filled building.
These guidelines will assist you in the event of a fire. However, to reduce the chance that fires will start, practice fire safety rules and prevent hazardous situations. Con- tact your local Fire Brigade for more information.
TROUBLESHOOTING
PROBLEM | SOLUTION |
---|
The heat alarm does not sound when tested.
NOTE: Push and hold test button for at least five (5) seconds while
testing!| 1. Check that the AC power is turned on.
2. Turn the off power. Remove heat alarm from mounting plate and:
a. check the hat connector plug is securely attached.
b. Check that battery is installed correctly (KF30, KF3OLL only).
3. Clthe ean smoke alarm.
The heat alarm beeps about once every 40 seconds| KF3OR. Verify that unit has
been under the main operation for a minimum of 2 full days. If the beeping
persists after the required charging period, return the unit for service.
KF3OLL: This alarm has a long-life lithium battery to last the full life of
the alarm. If the alarm beeps every 40 seconds there is a unit fault and it
needs replacing. KF30: Turn off AC power and replthe ace battery. See “Battery
Replacement” in the MAINTENANCE CLEANING section.
Heat alarm soundalike nds unwanted alarms.| 1. Hire an electrician to the
over Heat alarm to a new location. See the HEAT ALARM SITING section of this
user guide.
Interconnected heat alarms do not sound when the system is tested.|
1. Press the old button for at least five seconds after the first unit
sounds.
2. Turn off AC power or circuit breaker and check the interconnect wiring.
See INTERCONNECTING HEAT ALARMS section of this user guide.
3 chirps every 40 seconds| 1. Before 10 years of operation: the unit is in
fault mode. Contact customer service.
2. After 10 years of operation: end of life warning. The alarm must be
replaced (REPLACE IMMEDIATELY!)
NOTE: Contact customer support at 03337 722227 if your alarm does not seem to operate correctly.
GUARANTEE
The manufacturer guarantees this product to be free from defects in and
workmanship under normal use and service (“Defects”) for a period of six (6)
years from the date of purchase (the “Guarantee Period”). Should any Defects
be discovered within the Guarantee Period, the Company will, at its option,
repair or replace the defective product provided that: (a) it is returned
during the Guarantee Period with postage prepaid and with proof of purchase
date to the address shown below and (b) the Company verifies that the claim is
proper. This Guarantee does not cover damage resulting from accident, improper
installation, maintenance or repair, misuse, abuse, or product modification.
This Guarantee does not confer any rights other than those expressly set out
above and does not cover any claims for consequential loss or damage. This
Guarantee is offered as an extra benefit and does not affect your statutory
rights as a consumer. Return units in a padded carton, postage prepaid, to:
FOREX PRODUCTS KIDDE SAFETY EUROPE LIMITED
Ash House, Littleton Road, Ashford, TW15 1TZ, UK
Tel.: 0800 917 0722
www.smoke-alarms.co.uk
** Manufactured By**
Walter Kidde Portable Equipment Inc.
1016 Corporate Park Drive, Mebane, NC 27302, USA
Made in China
EU Authorised Representative:
Carrier Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, NL
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>