Mains Powered Ionisation Smoke Alarm
User Guide
KF10
KF10LL
KF10R
Ionization| KF20
KF20LL
KF20R
Optical
---|---
EN14604:2005LICENSE NO. KM 738872
** 2797-CPR-53559515EN 14604:2005
PLEASE READ AND SAVE
INSTALLER:** Please leave this user guide with the product.
SMOKE ALARM DESCRIPTION
Model KF10, KF10LL| Ionization 230V AC smoke alarm with 9Vbattery backup and
Hush Button
---|---
Model KF10R| Ionization 230V AC smoke alarm with rechargeable battery backup
and HushButton
Model KF20, KF20LL| Optical 230V AC smoke alarm with 9V battery back-up with
Hush Button
Model KF20R| Optical 230V AC smoke alarm with rechargeable battery back-up and
Hush Button
SMOKE ALARM FEATURES
- Interconnects with up to 23 other models, KF1, KF1R, KF2, KF2R, KF3, KF3R, KF10, KF10LL, KF10R, KF20, KF20LL, KF20R, KF30, KF30LL, KF30R, 4870, 4881, 4973, 4985, 4892, 4899, 1SFW, 1SFWR, 2SFW, 2SFWR, 3SFW, 3SFWR, and 4MCO and 4MDCO Mains CO alarms. A unique power connector prevents interconnection with incompatible smoke alarms or security systems.
- Tamper-resist bracket quickly snaps into place and serves as a safeguard against tampering.
- Multi-purpose green and red LEDs indicate that the smoke alarm is receiving AC power, working under normal operation, in alarm, or under Hush Button.
- A loud alarm horn—85 decibels at 3 meters (10 feet)—sounds to alert you of an emergency.
- Test button checks smoke alarm operation.
- All models feature Hush Button, which, when activated, quiets unwanted alarms for up to 9 minutes.
- Models KF10, KF10LL, KF20, and KF20LL will not attach to the mounting bracket if a battery is not in the battery pocket. These models will also sound a short beep about once a minute if the battery is weak or improperly connected.
- Models KF10R, KF20R, KF10LL, and KF20LL have lithium batteries that will last the life of the alarm and a tamper-proof locking screw option.
- Models KF10R and KF20R include permanent rechargeable lithium batteries.
- Operating temperature: 0°C to 40°C
- Operates up to 93% humidity (non-condensing)
- Storage and Transport Conditions: -20° C to +60° C, 5-95%RH (non-condensing)
- Models KF10, KF10R, and KF10LL are designed to detect products of combustion using ionization technology. This product contains 0.9 microcuries of Americium 241, a radioactive material.
NOTE: Additional markings can be found on the back of the unit.
IMPORTANT SAFETY INFORMATION
PLEASE READ AND SAVE THESE INSTRUCTIONS
WARNING
- DO NOT paint or cover the smoke alarm with tape.
- This smoke alarm should be out of the reach of children.
- AC smoke alarms require constant 230V AC, and 50Hz power to operate properly. Mains-only powered smoke alarms WILL NOT work if AC power is not connected or has failed or been interrupted for any reason. Models KF10, KF10LL, and KF20, KF20LL require a working 9-volt battery to operate properly in the event of a power failure. Models KF10R and KF20R require a minimum of 2 full days under mains power to reach full backup capacity. DO NOT use any other kind of battery except as specified in this user guide. DO NOT connect this smoke alarm to any other type of smoke alarm or auxiliary device, except those listed in this user guide.
- DO NOT remove or disconnect the battery or turn off AC power to quiet unwanted alarms. This will remove your protection. Open windows or fan the air around the smoke alarm to silence it. KF10, KF10LL, KF10R, KF20, KF20LL, and KF20R smoke alarms feature a Hush Button which, when activated, will quiet unwanted alarms for up to 9 minutes.
- The Push-to-Test button accurately tests all smoke alarm functions. DO NOT use any other test method. Test smoke alarms weekly to ensure proper operation.
- This smoke alarm should be installed only by a qualified electrician.
- This smoke alarm is designed to be used inside a single-family household only. In multi-family buildings, each individual living unit should have its own smoke alarms. Do not install in non-residential buildings or places that house many people like hotels, motels, dormitories, hospitals, nursing homes, or group homes of any kind. This smoke alarm is not a substitute for a complete alarm system.
- Install a smoke alarm in every room and on every level of the home. Smoke may not reach the smoke alarm for many reasons. For example, if a fire starts in a remote part of the home, on another level, in a chimney, wall, roof, or on the other side of a closed door, smoke may not reach the smoke alarm in time to alert household members. A smoke alarm will not promptly detect a fire EXCEPT in the area or room in which it is installed.
- Interconnected smoke alarms installed in every room and on every level of the household offer maximum protection. We recommend interconnecting smoke alarms so that when one smoke alarm senses smoke and sound its alarm, all others will sound as well. Do not interconnect smoke alarms from one individual family living unit to another. Do not connect this smoke alarm to any other type of alarm or auxiliary device.
- Smoke alarms may not alert every household member every time. The alarm horn is loud in order to alert individuals of potential danger. However, there may be limited circumstances where a household member may not hear the alarm (i.e. outdoor or indoor noise, sound sleepers, drug or alcohol usage, the hearing impaired, etc.). If you suspect that this smoke alarm may not alert a household member, install and maintain specialty smoke alarms. Household members must hear the alarm’s warning sound and quickly respond to it to reduce the risk of damage, injury, or death that may result from fire. If a household member is hearing impaired, install special smoke alarms with lights or vibrating devices to alert occupants.
- Smoke alarms can only sound their alarms when they detect smoke. Smoke alarms detect combustion particles in the air. They do not sense heat, flame, or gas. This smoke alarm is designed to give an audible warning of a developing fire. However, many fires are fast-burning, explosive, or intentional. Others are caused by carelessness or safety hazards. Smoke may not reach the smoke alarm QUICKLY ENOUGH to ensure a safe escape.
- Smoke alarms have limitations. This smoke alarm is not fool-proof and is not warranted to protect lives or property from fire. Smoke alarms are not a substitute for insurance. Homeowners and renters should insure their lives and property. In addition, it is possible for the smoke alarm to fail at any time. For this reason, you must test the smoke alarm weekly and replace it every 10 years.
SMOKE ALARM PLACEMENT
It is recommended to achieve complete coverage protection by installing a
smoke alarm in every room of your home.
At a minimum, smoke alarms shall be installed outside or inside all bedrooms
and on each additional story of the family living unit including basements,
and converted loft spaces. Any home requires a minimum of two smoke alarms.
Typical Single Storey Home
- Install a smoke alarm on the ceiling or wall inside each bedroom and in the hallway outside each separate sleeping area. If a bedroom area hallway is more than 9 m long, install a smoke alarm at each end.
Typical Two-Storey Home
- Install a smoke alarm on the ceiling inside each bedroom and in the hallway outside each separate sleeping area. If a bedroom area hallway is more than 9 m long, install a smoke alarm at each end.
- Install a smoke alarm at the top and bottom of a first-to-second floor stairwell.
Key
**** Ionization Alarm
Optical Alarms
Heat Alarm
IMPORTANT SMOKE ALARM PLACEMENT AND EXCEPTION INFORMATION:
-
Install a smoke alarm as close to the center of the ceiling as possible. If this is not practical, mount no closer than 30cm (12 inches) from a wall or corner. Also, if local codes allow, install smoke alarms on walls, 30 cm (12 inches) from ceiling/wall intersections.
-
Install a minimum of two smoke alarms in every home, no matter how small the home. Any size home requires fitting a minimum of two smoke alarms.
-
Install a smoke alarm in each room that is divided by a partial wall (either coming down from the ceiling at least 20 cm (8 inches), or coming up from the floor).
-
Install smoke alarms on peaked, cathedral, or gabled ceilings 1 m from the highest point (measured horizontally).
-
Install a smoke alarm in lived-in attics or attics which house electrical equipment like furnaces, air conditioners, or heaters.
Locations to be Avoided (Smoke Alarms)
- Do not site within 3m of a steam source e.g. kitchen/bathroom or garage.
- Do not site within 1m of dimmer control cabling or cable alarm into any such cabling.
- Do not site adjacent to any heat source.
- Do not site within 300m (12”) of any lights fixture and 300mm from any wall.
- Do not sit near fluorescent lights; electronic noise may cause nuisance alarms.
- In locations where the temperature may fall below 0°C (40°F), or above 40°C (104°F). In areas with relative humidity (RH) above 93% (non-condensing).
- In very dusty/dirty/insect-laden areas.
- Any location where the free flow of smoke to the alarm could be interrupted (e.g. next/above a door/air vent/heater/air-con unit). Do not install where the ventilation openings in the unit could be impeded by items such as newspapers, tablecloths, curtains, etc.
- Areas where routine maintenance or operating hush/test button is difficult (e.g. top of stairwells).
- Siting should be in accordance with the current Building Regulations and/or BS5839 Pt6/current I.E.E. Regulations.
CAUTION: The alarm should not be exposed to dripping or splashing.
HOW TO INSTALL THIS SMOKE ALARM
DANGER:
ELECTRICAL SHOCK HAZARD. Turn off power at the main consumer unit or
circuit breaker by removing the fuse or switching the circuit breaker to the
OFF position and securing it.
WARNING:
Mains-operated smoke alarms should be installed by a qualified electrician in
accordance with the Regulations for Electrical Installations published by the
Institution of Electrical Engineers (BS). Failure to install this smoke alarm
correctly may expose the user to shock or fire hazards.
WARNING:
The smoke alarm, its associated supply and interconnect wiring must be
installed in accordance with BS 7671 published by the Institution of
Electrical Engineers.
WARNING:
If a Firex Rechargeable alarm is replacing an earlier non-recharge-able model,
the new cable harness with 4 strands must be used. Using the old 3-strand
harness will not allow the new rechargeable alarm to charge its batteries.
• Install a smoke alarm on the ceiling, standard electrical box, or surface
mounting pattress.
-
Align mounting plate with mounting holes of standard electrical box or surface mounting pattress. For sitting on the ceiling, use the mounting plate as a template to mark holes. Drill holes and insert supplied screw plugs into holes until flush with the ceiling. Ceiling mounting is always preferable over wall mounting.
-
Secure mounting plate to electrical box, pattress or ceiling. (Diagram illustrates fixing mounting plate to electrical box.)
-
Connect the blue cable from the connector plug of the smoke alarm to neutral and replace it with (N) mains power cable.
-
Connect the brown cable from the connector plug of the smoke alarm to the live (L) mains power cable.
-
If interconnection is desired, connect orange or white cable from connector to interconnect strand on the 3 core & earth cable. See section, “Interconnecting Smoke Alarms.”
NOTE: If this will be a single-station smoke alarm, cover orange or white cable with electrical tape and tuck into pattress. -
Attach connector plug to pins on back of smoke alarm. Plug will only fit one way and will snap into place.
-
Gently tug connector to be sure it is attached securely.
NOTE: Steps 8 and 9 for models KF10, KF10LL, KF20, and KF20LL only.
These models contain a battery pull tab for your convenience. Battery pull tab must be removed to activate battery backup and provide power to the unit in the event of mains power loss. -
Pull out the battery pull tab. Smoke alarm may beep briefly when battery is activated.
-
KF10LL and KF20LL include a tamper-proof locking option, using the screw provided.
-
Push the button and hold button on front cover of smoke alarm for five (5) seconds. Smoke alarm should sound its alarm horn if battery is connected.
NOTE: cover sounder vents with your hand or hold unit at arm’s length during testing to avoid ear discomfort. -
Position the smoke alarm to mounting plate so that key slot on side of smoke alarm is to the left of the tab on the mounting plate. Turn clockwise to lock into place. Smoke alarm will not mount to plate if battery is not installed (Models KF10, KF10LL, KF20, and KF20LL only).
-
Turn on power at main fuse box or circuit breaker. The green LED on the cover should be illuminated.
-
Test smoke alarm. See “TESTING THE SMOKE ALARM” MODELS KF10, KF10LL, KF20, KF20LL MODELS KF10R, KF20R (Rechargeable)
INTERCONNECTING SMOKE ALARMS
FOR INTERCONNECT: USE STANDARD 3 core & earth cable 1.5mm2 cable
- Use 1.5mm2 minimum solid or stranded cable with a rating of 230V. When interconnecting, the maximum cable length between any two is 450 m for 1.5mm2or 1200 m for 2.5mm2 (20 OHMS loop resistance).
- NOTE: Maximum length under BS7671 17th Edition wiring regs amendment 1 for CB/RCBO type B is 72 meters for TN-S or TN-C-S systems (source “On-Site Guide” page 59)
- This smoke alarm may be interconnected with as many as 23other Models of smoke alarms, as listed on page 1. DO NOT connect to any other type or model smoke alarm.
- Connect smoke alarms to a single circuit. Wiring must conform to IEE Regulations for electrical installation.
RED AND GREEN LED INDICATORS
This smoke alarm features red and green LED indicators that can be seen
through the Push-to-Test button or the LED lens above the test button. The
LEDs indicate the following:
GREEN LED
ON — AC power is present.
OFF — AC power is not present.
RED LED
Blinks once every 5 minutes AND 20 SECONDS — indicating normal operation.
Blinks once a second — smoke alarm senses smoke and simultaneously sounds an
audible alarm.
Blinks once every 10 seconds — the smoke alarm is in hush mode.
3 rapid flashes at 40-second intervals — indicate which alarm previously
detected an alarm condition.
OFF and unit are sounding alarmed — Another interconnected smoke alarm has
sensed smoke and is signaling this alarm.
HUSH BUTTON
Models KF10, KF10LL, KF10R, KF20, KF20LL, and KF20R feature a Hush Button
that, when activated, quiets unwanted alarms for up to 9 minutes. To use the
Hush Button:
Press and release the test button during an unwanted alarm. The alarm should
stop within ten seconds. This means the smoke alarm is in Hush Button. If the
smoke alarm does not go into Hush and continues to sound its loud alarm horn,
or if it initially goes into Hush then resounds the alarm, the smoke is too
heavy and could be a dangerous ituation – take emergency action.
TESTING THE SMOKE ALARM
WARNING
- Test each smoke alarm to be sure it is installed correctly and operating properly.
- Test all smoke alarms in an interconnected system after installation.
- The Push-to-Test button accurately tests all functions. DO NOT use an open flame to test this smoke alarm. You may ignite and damage the smoke alarm or your home.
- Test smoke alarms weekly and upon returning from holiday or when no one has been in the household for several days.
- Stand at arm’s length from the smoke alarm when testing. The alarm horn is loud to alert you to an emergency and can be harmful to hearing.
Test all smoke alarms weekly by doing the following:
-
Check the Push-to-Test button. A constant green light indicates the smoke alarm is receiving 230V AC, 50Hz power. A red flashing LED about once every 5 minutes verifies operation. For models KF10, KF10LL, KF10R, KF20, KF20LL, and KF20R the red flashing LED also verifies that a working battery is present.
-
Firmly depress and hold the Push-to-Test button for at least five (5) seconds. The smoke alarm will sound 3 long beeps, a pause, 3 long beeps, repeating for up to 10 seconds after releasing the Push-to-Test button.
NOTE: If smoke alarms are interconnected, all smoke alarms should sound an alarm within three seconds after any test button is pushed and the tested smoke alarm sounds. -
If the smoke alarm does not sound, turn off power at the main fuse box or circuit breaker and check the wiring. Retest smoke alarm.
DANGER: If the alarm horn sounds and the smoke alarm is not being tested, the smoke alarm is sensing smoke. THE SOUND OF THE ALARM HORN REQUIRES YOUR IMMEDIATE ATTENTION AND ACTION.
MAINTENANCE AND CLEANING
In addition to weekly testing, Models KF10 and KF20 also require periodic
battery replacement. Regularly clean smoke alarms to remove dust, dirt, and
debris.
WARNING: The alarm comes equipped with a dust cover, which prevents dust
and debris from damaging the unit during construction or remodeling. Remove
dust cover before operation. The alarm will not operate properly while
covered.
DANGER: ELECTRICAL SHOCK HAZARD. Turn off the main power at the fuse box
or consumer unit by removing a fuse or switching the appropriate circuit
breaker to the OFF position before replacing the battery or cleaning the smoke
alarm.
BATTERY REPLACEMENT
(For Models KF10 and KF20 only):
CAUTION: Danger of explosion if the battery is incorrectly replaced.
Always turn off the power to the smoke alarm before replacing the battery.
Replace the battery at least once a year or immediately when the low battery
signal sounds once every 40 seconds, even though the smoke alarm is receiving
AC power. Use only the following 9V/(6F22) batteries as replacements in this
smoke alarm: Energizer 522; Duracell MN1604 or MX 1604; or FDK CP-V9Ju;
Ultralife U9VL-J-P
Replace only with the same or equivalent battery type recommended by the
manufacturer. Discard used batteries safely according to the manufacturer’s
instructions.
NOTE: Constant exposure to extreme temperatures and humidity may affect
battery life.
WHENEVER THE BATTERY IS REPLACED, TEST THE ALARM FOR CORRECT OPERATION BY
PUSHING THE TEST BUTTON.
WARNING: DO NOT USE ANY OTHER TYPE OF BATTERY, EXCEPT AS SPECIFIED IN THIS
USER GUIDE. DO NOT USE RECHARGEABLE BATTERIES.
-
Turn off power to smoke alarm at main consumer panel.
-
Insert a small screwdriver into the slot in the mounting plate. Depress locking tab with the screwdriver and turn smoke alarm counter-clockwise to detach from mounting
plate. -
Gently pull down smoke alarm. Be careful not to separate cable connections.
-
Pull out power plug from back of smoke alarm.
-
From the back of smoke alarm, lift tab to open battery pocket door.
-
Remove the battery from the pocket. Discard the drained battery.
-
Insert a fresh, 9-volt battery into battery pocket. The battery will fit only one way. Smoke alarm may sound a short beep when battery is installed. This is normal and means the battery is installed correctly.
-
Close the battery pocket door. Push down until it snaps into place.
-
Press and hold test button. The alarm will sound if the battery is properly connected and working.
-
Replace the connector plug. Connector will snap into place. Gently tug connector to be sure it is attached properly.
-
Reattach the smoke alarm to mounting plate by turning the smoke alarm clockwise until it snaps into place.
-
Turn on power and test the smoke alarm using test button.
The crossed-out wheeled bin symbol indicates that the batteries listed in this user guide should be disposed of separately from household waste.
(For Models KF10R and KF20R only):
NOTE: Rechargeable lithium batteries are permanently mounted and sealed
in the tamper-proof housing. These cells are designed to last the useful life
of the smoke alarm.
CLEANING
Clean the smoke alarm at least once a month to remove dust, dirt, or debris.
Always turn off the power to the smoke alarm before cleaning.
- Using the soft brush or wand attachment to a vacuum cleaner, vacuum all sides and cover of the smoke alarm. Be sure all the vents are free of debris.
- If necessary, turn off the power and use a damp cloth to clean the smoke alarm cover.
IMPORTANT: Do not attempt to remove the cover or clean inside the smoke
alarm. THIS WILL VOID YOUR GUARANTEE.
REPAIR
CAUTION: Do not attempt to repair this smoke alarm.
Doing so will void your guarantee.
If the smoke alarm is not operating properly, see “Troubleshooting”. If
necessary and if still under guarantee, return the smoke alarm to Kidde.
Pack it in a well-padded carton and send, postage prepaid to Kidde address at
the end of this user guide.
If the smoke alarm is no longer under guarantee, have a qualified electrician
replace the smoke alarm immediately with a comparable Firex smoke alarm.
PRACTICE FIRE SAFETY
If the smoke alarm sounds its alarm horn, and you have not pushed the test button, it is a warning of a dangerous situation. Your immediate response is necessary. To prepare for such occurrences, develop family escape plans, discuss them with ALL household members, and practice them regularly.
- Expose everyone to the sound of a smoke alarm and explain what the sound means.
- Decide on TWO exits from each room and an escape route to the outside from each exit.
- Teach all household members to touch the door and use an alternate exit if the door is hot. INSTRUCT THEM NOT TO OPEN THE DOOR IF THE DOOR IS HOT.
- Teach household members to crawl along the floor to stay below dangerous smoke, fumes, and gases.
- Decide on a safe meeting place for all members to meet outside the building.
WHAT TO DO IN CASE OF A FIRE
- Don’t panic; stay calm.
- Leave the building as quickly as possible. Touch doors to feel if they are hot before opening them. Use an alternate exit if necessary. Crawl along the floor, and DO NOT stop to collect anything.
- Meet at a pre-arranged meeting place outside the building.
- Call the fire brigade (Dial 999) from OUTSIDE the building.
- DO NOT GO BACK INSIDE A BURNING BUILDING. Wait for the fire brigade to arrive.
These guidelines will assist you in the event of a fire. However, to reduce the chance that fires will start, practice fire safety rules and prevent hazardous situations
TROUBLESHOOTING
DANGER:
Always turn off power at the main fuse box or consumer unit before taking
trouble-shooting action.
WARNING:
DO NOT disconnect the battery or mains power to quiet an unwanted alarm. This
will remove your protection. Fan the air or open a window to remove smoke or
dust. For Models KF10, KF10LL, KF10R, KF20, KF20LL, and KF20R you may also use
the Hush Button feature to quiet unwanted alarms.
PROBLEM | SOLUTION |
---|
Smoke alarm does not sound when tested.
NOTE: Push and hold test button for at least five (5) sec- onds while
testing!| 1. Check that AC power is turned
on. Green LED should be illuminated.
2. Turn off power. Remove smoke alarm from mounting plate and:
a.check that connector plug is securely attached.
b.check that battery is properly installed.
3. Clean smoke alarm.
Smoke alarm beeps once every 40 seconds The low battery signal can be hushed
for 8 hours by pressing and releasingthe Test button.| 1.Turn off power and
replace battery. (KF10, KF20 only). See MAINTENANCE AND CLEANING section.
2.Clean smoke alarm.
3.Verify that unit has been under mains operation for a minimum of 2 full days
(KF1OR and KF2OR ). If the beeping persists after required charging period,
return the unit for service.
Smoke alarm sounds unwanted alarms when residents are cooking,taking showers,
etc.| 1. Hire an electrician to move smoke alarm to a new location. See
‘SMOKE ALARM PLACEMENT’.
Interconnected smoke alarms do not sound when sys- the tem is tested.| 1.Press
and hold test button for at least five seconds after the first unit sounds.
2.Hire an electrician to ensure smoke alarms are properly connected.
3 chirps every 40 seconds| 1.Before 10 years of operation: unit is in fault
mode. Contact customer service.
2. After 10 years of operation: end of life waming. Alarm must be replaced
(REPLACE IMMEDIATELY!)
NOTE: Contact customer support at 0800 917 0722 if your alarm does not
seem to operate correctly.
Leading authorities recommend that both Ionisation and photoelectric smoke
alarms be installed to insure maximum detection of the various types of fires
that can occur within the home. Ionization sensing alarms may detect invisible
fire particles (associated with fast flaming fires) sooner than photoelectric
alarms. Photoelectric sensing alarms may detect visible fire particles
(associated with slow smoldering fires) sooner than Ionisation alarms.
GUARANTEE
The manufacturer warrants to the original consumer purchaser each new smoke
alarm to be free from defects in material and workmanship under normal use and
service for a period of six (6) years in the United Kingdom and the Republic
of Ireland from the date of purchase. We agree to repair or replace, at its
option, any defective smoke alarm, provided that it is returned with the
postage prepaid and with proof of purchase date to the manufacturer. This
warranty does not cover damage resulting from accident, misuse or abuse, or
lack of reasonable care of the product. This warranty is in lieu of all other
express warranties, obligations, or liabilities. THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED TO A PERIOD
OF SIX (6) YEARS FROM THE PURCHASE DATE. IN NO CASE SHALL THE MANUFACTURER
BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES FOR BREACH OF THIS OR
ANY OTHER WARRANTY, EXPRESS OR IMPLIED, WHATSOEVER, EVEN IF THE LOSS OR DAMAGE
IS CAUSED BY ITS NEGLIGENCE OR FAULT.
Return units freight prepaid to your local reseller. For information on your
local reseller in the U.K. and Republic of Ireland, contact:
FOREX PRODUCTS
KIDDE SAFETY EUROPE LIMITED
ASH HOUSE, LITTLETON ROAD, ASHFORD, TW15 1TZ, UK
Tel.:0800 917 0722
www.smoke-alarms.co.uk
Made in China
Manufactured By:
Walter Kidde Portable Equipment Inc.
1016 Corporate Park Drive, Mebane, NC 27302, USA
EU Authorised Representative:
Carrier Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, NL