PowMr SP5K Solar Inverter User Manual
- June 14, 2024
- PowMr
Table of Contents
- PowMr SP5K Solar Inverter
- Product Information
- Basic System Introduction
- Appearance
- Installation Precautions
- Important Safety Instructions
- General Information
- Installation Instructions
- Connection
- Operating Modes
- LCD screen Operating Instructions
- Other Functions
- Troubleshooting
- Technical parameters
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
PowMr SP5K Solar Inverter
Product Information
The product is an all-in-one solar charge inverter with various features and functions. It supports both inverter and mains power hybrid output and can be used without a battery. The inverter has two output modes: mains bypass and inverter output, providing an uninterrupted power supply. It offers 4 charging modes: Only Solar, Mains Priority, Solar Priority, and Mains and solar hybrid charging. The inverter incorporates advanced MPPT technology with an efficiency of 99.9%. It is designed with an LCD screen and 3 LED indicators for displaying system data and operating status. The inverter also features time slot control for setting the priority of using the mains and battery according to local peak and valley tariffs. It has a power-saving mode to reduce no-load loss and an intelligent variable speed fan for efficient heat dissipation. The inverter supports lithium battery activation by PV solar or mains and provides protection against overload and reverse current.
Basic System Introduction
The product is designed for use in a complete solar power system. The system consists of the following components:
- PV module: Converts light energy into DC power and charges the battery or directly converts it into AC power to drive the load.
- Mains or generator: Connects at the AC input to power the load and charge the battery.
- Battery: Ensures normal power supply to the system loads when solar energy is insufficient and the mains are not connected.
- Household load: Various household and office loads can be connected, including refrigerators, lamps, TVs, fans, and air conditioners.
- All-in-one solar charge inverter: The energy conversion unit of the system.
Appearance
The inverter has the following components:
- Overload protector
- ON/OFF rocker switch
- AC input port
- AC output port
- RS485-2 communication port
- Current sharing port (parallel module only)
- Parallel communication port (parallel module only)
- USB communication port
- RS485-1 communication port
- Dry contact port
- Cooling fan
- Battery port
- PV port
- Function key
- Indicator light
- LCD screen
Installation Precautions
Prior to installation, carefully read the manual to familiarize yourself with the installation steps. When installing the battery, take extra caution and wear safety goggles when dealing with lead-acid batteries.
Important Safety Instructions
Please save these instructions for future use! Read all of the instructions and cautions in the manual before beginning the installation ! This manual contains all safety, installation and operating instructions for the POW- SunSmart Series all-in-one solar charge inverter. Please read all instructions and precautions in the manual carefully before installation and use. Non- safety voltage exists inside the all-in-one solar charge inverter. To avoid personal injury, users shall not disassemble the all-in-one solar charge inverter themselves. Contact our professional maintenance personnel if there is a need for repair. Do not place the all-in-one solar charge inverter within the reach of children. Do not install the all-in-one solar charge inverter in harsh environments such as moist, oily, flammable or explosive, or heavily dusty areas. The mains input and AC output are high voltage, so please do not touch the wiring terminals. The housing of the all-in-one solar charge inverter is hot when it is working. Do not touch it. Do not open the terminal protective cover when the all-in-one solar charge inverter is working. It is recommended to attach proper fuse or circuit breaker to the outside of the all-in-one solar charge inverter. Always disconnect the fuse or circuit breaker near the terminals of PV array, mains and battery before installing and adjusting the wiring of the all-in-one solar charge inverter. After installation, check that all wire connections are tight to avoid heat accumulation due to poor connection, which is dangerous. The all-in-one solar charge inverter is off-grid. It is necessary to confirm that it is the only input device for load, and it is forbidden to use it in parallel with other input AC power to avoid damage.
General Information
Product Overview and Features
POW-SunSmart series is a new all-in-one hybrid solar charge inverter, which
integrates solar energy storage & means charging energy storage and AC sine
wave output. Thanks to DSP control and advanced control algorithm, it has high
response speed, high reliability and high industrial standard. Four charging
modes are optional, i.e. Only Solar, Mains Priority, Solar Priority and Mains
& Solar hybrid charging; and two output modes are available, i.e. Inverter and
Mains, to meet different application requirements. The solar charging module
applies the latest optimized MPPT technology to quickly track the maximum
power point of the PV array in any environment and obtain the maximum energy
of the solar panel in real time. Through a state of the art control algorithm,
the AC-DC charging module realizes fully digital voltage and current double
closed loop control, with high control precision in a small volume. Wide AC
voltage input range and complete input/output protections are designed for
stable and reliable battery charging and protection. Based on full-digital
intelligent design, the DC-AC inverter module employs advanced SPWM technology
and outputs pure sine wave to convert DC into AC. It is ideal for AC loads
such as household appliances, power tools, industrial equipment, and
electronic audio and video equipment. The product comes with a segment LCD
design which allows real-time display of the operating data and status of the
system. Comprehensive electronic protections keep the entire system safer and
more stable.
1.2 Features
Anti-backflow grid connection function, support for inverter and mains power
hybrid output, support for use without battery, can be set up for on-grid
power generation.
Two output modes: mains bypass and inverter output; uninterrupted power
supply. Available in 4 charging modes: Only Solar, Mains Priority, Solar
Priority and Mains & Solar
hybrid charging. Advanced MPPT technology with an efficiency of 99.9%.
Designed with a LCD screen and 3 LED indicators for dynamic display of system
data and
operating status. With time slot control, you can set the priority of using
the mains and battery according to the
time slot in conjunction with the local peak and valley tariffs. Power saving
mode available to reduce no-load loss. Intelligent variable speed fan
efficiently dissipate heat and extend system life. Lithium battery activation
by PV solar or mains, allowing access of lead-acid battery and lithium
battery. 360 ° all-around protection with a number of protection functions.
Complete protections, including short circuit protection, over voltage and
under voltage
protection, overload protection, reverse protection, etc.
5
1.3 Basic System Introduction
The figure below shows the system application scenario of this product. A
complete system consists of the following parts:
1. PV module: Convert light energy into DC power, and charge the battery
through the all-in-one solar charge inverter, or directly invert into AC power
to drive the load.
2. Mains or generator: Connected at the AC input, to power the load while
charging the battery. If the mains or generator is not connected, the system
can also operate normally, and the load is powered by the battery and PV
module.
3. Battery: Provided to ensure normal power supply to the system loads when
solar energy is insufficient and the Mains is not connected.
4. Household load: Allow connection of various household and office loads,
including refrigerators, lamps, TVs, fans and air conditioners.
5. All-in-one solar charge inverter: The energy conversion unit of the whole
system. Specific system wiring method depends on the actual application
scenario.
6
1.4 Appearance
Overload protector ON/OFF rocker switch AC input port AC output port RS485-2
communication port Current sharing port (parallel
module only) Parallel communication port
(parallel module only) USB communication port
RS485-1 communication port
Dry contact port Cooling fan Battery port Cooling fan PV port Function key
Indicator light LCD screen
7
1.5 Dimension Drawing 8
Installation Instructions
2.1 Installation Precautions
Please read this manual carefully prior to installation to familiarize
yourself with the installation steps. Be very careful when installing the
battery. Wear safety goggles when installing a lead-acid
liquid battery. Once coming into contact with the battery acid, rinse with
clean water timely. Do not place metal objects near the battery to prevent
short-circuit of the battery. Acid gas may be generated when the battery is
charged. So, please ensure good ventilation. When installing the cabinet, be
sure to leave enough space around the all-in-one solar charge inverter for
heat dissipation. Do not install the all-in-one solar charge inverter and
lead-acid
battery in the same cabinet to avoid corrosion by acid gas generated during
battery operation. Only the battery that meets the requirements of the all-in-
one unit can be charged. Poorly connected connections and corroded wires may
cause great heat which will melt the wire
insulation, burn the surrounding materials, and even cause fires. So, make
sure the connectors have been tightened, and the wires are secured with ties
to avoid looseness of connections caused by shaking of wires during mobile
application. The system connection wires are selected according to a current
density of not more than 5A/mm². Avoid direct sunlight and rainwater
infiltration for outdoor installation. Even after the power is turned off,
there is still high voltage inside the unit. Do not open or touch the internal
components, and avoid related operations until the capacitor completely
discharges. Do not install the all-in-one solar charge inverter in harsh
environments such as moist, oily, flammable or explosive, or heavily dusty
areas. Polarity at the battery input end of this product shall not be
reversed, otherwise it may damage the device or cause unpredictable danger.
The mains input and AC output are high voltage, so please do not touch the
wiring terminals. When the fan is working, do not touch it to prevent injury.
Load equipment input power needs to confirm that this all-in-one solar charge
inverter is the only input device, and it is forbidden to use in parallel with
other input AC power to avoid damage. It is necessary to confirm that the
solar charge inverter is the only input device for load equipment, and it is
forbidden to use it in parallel with other input AC power to avoid damage.
9
2.2 Wiring Specifications and Circuit Breaker Selection
Wiring and installation must comply with national and local electrical codes.
Recommended PV array wiring specifications and circuit breaker selection: Since the output current
of the PV array is affected by the type, connection method and illumination angle of the PV module,
the minimum wire diameter of the PV array is calculated according to its short-circuit current; refer
to the short-circuit current value in the PV module specification (the short- circuit current is constant
when the PV modules are connected in series; the short-circuit current is the sum of the short-
circuit currents of all PV modules connected in parallel); the short-circuit current of the PV array
shall not exceed the maximum input current.
Refer to the table below for PV input wire diameter and switch:
Models
Recommended PV wiring diameter
Maximum PV input current
POW-SunSmart
6mm² /10AWG
22A
SP5K
Recommended circuit breaker type
2P–25A
Note: The voltage in series shall not exceed the maximum PV input open circuit voltage.
Refer to the table below for recommended AC input wire diameter and switch:
Models
Recommended AC Maximum bypass
input wiring diameter
input current
Recommended circuit breaker type
POW-SunSmart
10mm² /7AWG
63A
SP5K
2P–63A
Note: There is already an appropriate circuit breaker at the Mains input wiring terminal, so it is not
necessary to add one more.
Recommended battery input wire diameter and switch selection
Models
Recommended battery wiring
diameter
Rated battery Maximum discharge charge current
Recommended circuit breaker
type
POW-SunSmart SP5K
30mm² /7AWG
125A
100A
2P–200A
Recommended AC output wiring specifications and circuit breaker selection
Models
Recommended AC output wiring
Rated inverter AC output current
Maximum bypass output
current
Recommended circuit breaker type
POW-SunSmart 10mm² /7AWG
42A
63A
SP5K
2P–63A
10
NOTICE
The wiring diameter is for reference only. If the distance between the PV
array and the all-inone solar charge inverter or the distance between the all-
in-one solar charge inverter and the battery is relatively long, using a
thicker wire can reduce the voltage drop to improve system performance.
The above are only recommended wiring diameter and circuit breaker. Please
select the appropriate wiring diameter and circuit breaker according to actual
situations.
11
2.3 Select the Mount Location
Determine the installation position and the space for heat dissipation:
Determine the installation position of the all-in-one solar charge inverter,
such as wall surface; when installing the all-in-one solar charge inverter,
ensure that there is enough air flowing through the heat sink, and space of at
least 200mm to the left and right air outlets of the inverter shall be left to
ensure natural convection heat dissipation. Please refer to the installation
diagram of the whole machine as above.
WARNING
Danger of explosion! Never install the all-in-one solar charge inverter and
lead-acid battery in the same confined space!
Also do not install in a confined place where battery gas may collect.
12
2.4 Preparation
Before connecting all wirings, please take off bottom cover.
13
Connection
3.1 AC Input/Output Wiring
1. Prior to AC input/output wiring, opening the external circuit breaker and
confirm that the wire used is thick enough. Please refer to Section 2.2
“Wiring Specifications and Circuit Breaker Selection”;
2. Properly connect the AC input wire according to the wire sequence and
terminal position shown in the figure below. Please connect the ground wire
first, and then the live wire and the neutral wire; : Ground L: Live N:
Neutral
14
3. Properly connect the AC output wire according to the wire sequence and
terminal position shown in the figure below. Please connect the ground wire
first, and then the live wire and the neutral wire. The ground wire is
connected to the grounding screw hole on the cabinet through the O-type
terminal. : Ground L: Live N: Neutral
NOTICE
The grounding wire shall be as thick as possible (cross-sectional area is not
less than 4mm² ). The grounding point shall be as close as possible to the
all-in-one solar charge inverter. The shorter the grounding wire, the better.
3.2 PV Input Wiring
1. Prior to wiring, disconnect the external circuit breaker and confirm that
the wire used is thick enough. Please refer to Section 2.2 “Wiring
Specifications and Circuit Breaker Selection”;
2. Properly connect the PV input wire according to the wire sequence and
terminal position shown in the figure below: When used in parallel connection,
different machines need to be connected to different PV arrays or PV sources.
PV+: PV input positive pole PV-: PV input negative pole
15
3.3 Battery Wiring
1. Prior to wiring, disconnect the external circuit breaker and confirm that
the wire used is thick enough. Please refer to Section 2.2 “Wiring
Specifications and Circuit Breaker Selection”. The BAT wire needs to be
connected to the machine through the O-type terminal. The O-type terminal with
an inner diameter of 6mm is recommended. The O- type terminal shall firmly
press the BAT wire to prevent excessive heat generation caused by excessive
contact resistance;
2. Properly connect the BAT wire according to the wire sequence and terminal
position shown in the figure below. BAT+: Battery positive electrode BAT-:
Battery negative electrode
WARNING
Mains input, AC output and PV array will generate high voltage. So, before
wiring, be sure to opening the circuit breaker or fuse;
Be very careful during wiring; do not close the circuit breaker or fuse during
wiring, and ensure that the “+” and “-” pole leads of each component are
connected properly; a circuit breaker must be installed at the battery
terminal. Refer to Section 2.2 “Wiring Specifications and Circuit Breaker
Selection” to select a right circuit breaker. Before wiring, be sure to
disconnect the circuit breaker to prevent strong electric sparks and avoid
battery short circuit; if the all-in-one solar charge inverter is used in an
area with frequent lightning, it is recommended to install an external
lightening arrester at the PV input terminal.
16
3.4 Final Assembly
Check if the wiring is correct and firm. In particular, check if the battery
polarity is reversed, if the PV input polarity is reversed and if the AC input
is properly connected, install the terminals cover.
3.5 Start Up the All-in-one Solar Charge Inverter
- First, close the circuit breaker at the battery terminal. 2) And then turn
the rocker switch on the left side of the machine to the “ON” state.
The “AC/INV” indicator flashing indicates that the inverter is working normally. 3) Close the circuit breakers of the PV array and the Mains. 4) Finally, turn on AC loads one by one as the AC output is normal to avoid a
protection action caused by a large momentary shock due to simultaneous turning on the loads simultaneously. Now, the machine goes into a normal operation according to the set mode.
NOTICE
If power is supplied to different AC loads, it is recommended to first turn on the load with a large surge current. After the load is stable, turn on the load with a small surge current.
If the all-in-one solar charge inverter does not work properly or the LCD or indicator is abnormal, refer to Chapter 6 to handle the exceptions.
17
Operating Modes
4.1 Charging Mode
1. Solar First: Priority shall be given to charging by PV, and mains charging
will be started only when the PV has failed. It can fully utilize solar energy
to generate power in the daytime and then switch to mains charging to keep the
battery level, and can be used in regions where the grid is relatively stable
and the feed-in tariff is relatively expensive.
2. Mains First: Priority shall be given to charging by Mains Power, and
charging with PV power will be started only when the Mains has failed.
3. Hybrid Charging: Hybrid charging of PV and Mains Power, give priority to
PV MPPT charging, and supplement Mains Power when PV energy is insufficient.
When the PV energy is sufficient, the Mains Power will stop charging. This is
the mode of fast charging and suitable for unstable areas of power grid, and
can provide sufficient backup power at any time.
18
4. Only Solar: Only PV charging, no mains charging is initiated. This is the
most energy-efficient mode and the battery power comes from solar energy,
which is usually used in regions with good daylighting conditions.
4.2 Output Mode
1. Solar First: PV and battery will power the load, with diversified charging
modes available and output mode optional, when the Solar First Mode is
selected, the use of green solar energy can be maximized for energy efficiency
and emission reduction. Switch to Mains Power when PV has failed. This mode
can maximize the use of solar energy while maintaining the battery power,
which is suitable for regions with relatively stable power grid.
2. Mains First: Switch to inverter power supply only when Mains Power has
failed, which is equivalent to backup UPS and is used in regions with unstable
power grid.
19
3. Inverter First: Switch to Mains Power supply only when the battery is
under-voltage. This mode uses DC energy to the maximum extent and is used in
regions with stable power grid.
4. Hybrid output and gird connection: (need to be abled) In the utility
bypass state, when no battery is connected or when the battery is full, the
load power is supplied by the PV and the utility together if the hybrid
function is enabled, and the surplus PV energy is fed back to the grid if the
grid connection function is enabled.
20
LCD screen Operating Instructions
5.1 Operation and Display Panel
The operation and display panel is shown below, including one LCD screen, 3
indicator lights and 4 operation buttons.
Operation buttons introduction
Function Key
Description
Menu of Enter/Exit Settings
Page Number/Option Increase
Page Number/Option Decrease
Under the menu of Settings, OK/Enter Options
Indicators introduction
Indicator light
Color
Description
AC/INV
Yellow
Normally On: Mains Power output Flicker: Inverter output
CHARGE
Green
Flicker: The battery is being charged. Normally On: The charging is completed.
FAULT
Red
Normally On: Fault status
21
LCD screen introduction
Icon
Function
Indicates mains power
Indicates generator
Indicates solar power
Icon
Function
Indicates the inverter is working
Indicates home appliances
Indicates AC output is overload
Battery remaining capacity is below 5%
Battery remaining capacity is 5%~19%
Battery remaining capacity is 20%~39%
Battery remaining capacity is 40%~59%
22
Load percentage is below 5% Load percentage is 5%~19% Load percentage is 20%~39% Load percentage is 40%~59% Load percentage is 60%~79% Load percentage is 80%~100%
Battery remaining capacity is 60%~79%
Battery remaining capacity is 80%~100% Indicates that the machine is
communicating with the Surveillance Equipment Indicates that the battery is
fully charged Indicates that the current battery type of the machine is sealed
lead-acid battery Indicates that the current battery type of the machine is
gel battery Indicates that the current battery type of the machine is LFP
battery
Indicates that the machine is currently idle
Indicates that the machine is currently in an alarm or fault state Indicates
that the PV is in a direct load state Indicates that the AC is in a state of
charge Indicates that the system is enabled in the ECO mode
23
Indicates that the buzzer is not enabled
Indicates that the current battery type of the machine is user-defined
Indicates that the current battery type of the machine is flooded lead-acid
battery Indicates that the current battery type of the machine is NCM battery
Display the page number prompt of the main interface
Indicates the data page of the main display interface
Indicates that the machine is currently in normal operation
Indicates that the machine is currently in the parameter setting state
Indicates that the PV is in a state of charge Indicate that the Mains Power is
in the bypass state
Indicates that the output mode is Battery First
Indicates that the output mode is Mains Power first
The indicated output mode is Solar First.
Indicates battery under voltage
Indicates battery overvoltage
Indicates internal communication failure Indicates system over voltage
Indicates system over temperature Indicates BMS communication failure When the
system is in alarm or fault state, the main interface displays fault code;
display setting options when setting
Real-time data viewing method
Indicates system under voltage Indicates system low temperature
Indicates system over current
Indicates the direction of energy flow
Display parameters of PV, battery, mains power and load
Main Interface: display real-time time, date, total PV power generation, total
load power consumption, RS485 address, version number Setting Interface:
display setting contents
On the LCD main screen, press the
button for page turning to view the real-time data
of the machine.
Page
PV Side Parameters
Battery Side Parameters
Mains Side Parameters
Load Side Comprehensive Parameters Parameters
1
PV Voltage Battery Voltage AC Voltage Load Voltage Current Time
2
PV Current Battery Current AC Current Load Current Current Date
3
PV Power
BMS Batt SOC AC Power
Load Power PV Total kWh
4 PV Today kWh
BMS Batt Voltage
Reserved
Load Today kWh
Load Total kWh
5
PV Temperature
INV Temperature
AC Frequency
Load Frequency
RS485 Address
6
Maintenance Parm
Battery Rated Voltage
Reserved
Load kVA
Soft Version
7
PV Rated Voltage
Battery Rated Current
Reserved
Load Rated Power
Parallel Mode
24
5.2 Setup Parameters Description
Key Operation Instructions: Enter the setting menu and exit the set ting menu, please press .
After entering the setting menu, the parameter number [00] will flash. At this time, you can press the
and
key to select the parameter code to be set. Then press
to enter the parameter
editing state, at this time, the value of the parameter flashes, adjust the value of the
parameter through the
and , and finally press
to complete the editing of the
parameter and return to the parameter selection state.
No. Parameter Name
Setting options
Description
00 Exit
[00] ESC
Menu of Exit Settings
[01] AC1ST default
Mains Power First Mode: Switch to the Inverter only when the Mains Power has failed
Supply Priority 01
Mode
[01] BT1ST
Inverter First Mode: Switch to Mains Power only when the battery is under- voltage or lower than Parameter [04] Set Value.
[01] PV1ST
Solar First Mode: Switch to Mains Power when PV has failed or battery is lower than Parameter [04] Set Value.
[02] 50.0 02 Output Frequency
[02] 60.0 default
Bypass self-adaptation; when the mains is connected, it automatically adapts to the mains frequency; when the mains is disconnected, the output frequency can be set through this menu. The default output frequency of the 120V machine is 60HZ.
03 AC Input Voltage
[03] UPS default [03] APL
Mains input voltage range: 90~140V Mains input voltage range: 90~140V
25
04 Battery to Mains 05 Mains to Battery
06 Charging Mode
[04] 43.6V default [05] 56.8V default
[06] Hybrid default [06] AC1ST [06] PV1ST
When the Parameter [01] = BT1ST/PV1ST, the battery voltage is lower than the set value, and the output is switched from inverter to Mains Power, and the Setting Range is 40V~52V. When the Parameter [01] = BT1ST/PV1ST, the battery voltage is higher than the set value, and the output is switched from mains to inverter, and the Setting Range is 48V~60V. Hybrid charging by PV and under utility grid give priority to PV, and use utility grid for supplementary if PV energy is insufficient. When the PV energy is sufficient, the utility grid will stop charging. Note: PV and utility grid are available for charging at the same time only when the bypass output is loaded, and only PV charging can be activated when the inverter is working. The Mains Power is charged first, and PV charging is started only when the Mains Power has failed Priority shall be given to charging by PV and mains charging will be initiated only when the PV has failed.
26
[06] ONLYPV
Only PV charging, no mains charging is enabled.
Maximum Charging
07
[07] 60A default
Current
Setting Range of 0~100A
[08] USER
User-defined, all battery parameters can be set.
Sealed lead-acid battery with
[08] SLd
constant charge voltage of 57.6V and
floating charge voltage of 55.2V
Flooded lead-acid battery with
[08] FLd
constant charge voltage of 57.6V and
floating charge voltage of 55.2V
08 Battery Type
[08] GEL default
GEL lead-acid battery with constant charge voltage of 56.8V and floating
charge voltage of 55.2V
LFP14/LFP15/LFP16 are
corresponding to Battery Series of
[08]
14, 15 and 16, and their default
LFP14/LFP15/LFP16 constant charge voltages are 49.6V,
53.2V and 56.8V respectively, which
can be adjusted.
[08] NCM13/NCM14 NCM lithium battery, adjustable
Setting of Boost Voltage: Setting
09 Boost Voltage
[09] 57.6V default
Range of 48V~58.4V, Step 0.4V, available when the battery type is
user-defined and lithium battery.
Setting of Maximum Boost
Maximum Boost 10
Duration
[10] 120mins default
Duration, which is the maximum charging time when the voltage reaches the Parameter [09] when
charging at constant voltage, with
27
11 Float Charge Voltage [11] 55.2V default
Over-discharge 12
Voltage
[12] 42V default
Over-discharge 13
Delay Time
[13] 5s default
Battery under voltage
14
[14] 44V default
alarm point
28
the Setting Range of 5mins~900mins, and Step of 5mim. It is available when the battery type is user-defined and lithium battery. Floating Charge Voltage, with the Setting Range of 48V~58.4 V, Step of 0.4 V, and available when battery type is user-defined. Over-discharge Voltage: the battery voltage is lower than such criterion, and the Inverter output is turned off after the time delay parameter is set to [13], with the Setting Range of 40V~48V and Step of 0.4V. available when the battery type is user- defined and lithium battery. Over-discharge Delay Time: when the battery voltage is lower than the Parameter [12], the inverter output is turned off upon delay of time set by this Parameter, with the Setting Range of 5s~50s, Step of 5S, available when the battery type is custom and lithium battery. Battery under-voltage alarm point: when the battery voltage is lower than such criterion, under-voltage alarm will be given, the output will not be shut down, with the Setting
Range of 40V~52V, Step of 0.4V,
available when battery type is user-
defined and lithium battery.
Battery Discharge Limit Voltage:
the battery voltage is lower than
Battery Discharge 15
Limit Voltage
[15] 40V default
such criterion, output and shut down immediately. Setting Range of 40V~52V, Step of 0.4V,
available when the battery type is
user-defined and lithium battery.
[16] DIS
No equalization charging
16 Equalization Charge [16] ENA default
Enable equalization charging, only Flooded lead- acid batteries, sealed lead- acid batteries and user-
defined are effective
Equalization Charging Voltage,
with the Setting Range of 48V~58V,
17 Equalization Voltage [17] 58V default
Step of 0.4V, available for Flooded
lead-acid battery, sealed lead-acid
battery and user-defined
Equalization Charging Time, with the
Setting Range of 5mins~900mins,
Equalization Charging
18
[18] 120mins default Step of 5mins, available for
Time
Flooded lead-acid battery, sealed
lead-acid battery and user-defined
Equalization Charging Delay, with
the Setting Range of
Equalized Charging
5mins~900mins, Step of 5mins,
19
[19] 120mins default
Delay
available for Flooded lead-acid
battery, sealed lead-acid battery
and user-defined
29
Equalization Charge
20
[20] 30days default
Interval Time
[21] ENA Equalization 21 Charging Start-Stop
[21] DIS default
[22] DIS default
22 ECO Mode
[22] ENA [23] DIS
Overload Automatic 23
Restart
[23] ENA default
Auto restart upon 24
over-temperature
[24] DIS
Equalization Charge Interval Time, 0~30days, Step of 1days, available for Flooded lead-acid battery, sealed lead-acid battery and userdefined Start equalization charging immediately Stop equalization charging immediately NO ECO mode When the ECO mode is enabled, if the load is below 50W, the inverter output is delayed for 5 mins and then the output is turned off. When the hull switch is pressed to the “OFF” State, and then pressed to the “ON” State, the inverter will resume the output Overload automatic restart is disabled. If overload occurs, the output will be shut down, and the machine will not be restarted. Enable overload auto restart. If overload occurs, shut down output, delay the machine for 3 mins and then restart the output. After 5 times in total, no startup will be resumed. Over-temperature automatic restart is disabled. If overtemperature occurs, the output will
30
[24] ENA default
25 Buzzer Alarm
Mode Change 26
Reminder
[25] DIS [25] ENA default [26] DIS
[26] ENA default [27] DIS Inverter Overload to 27 Bypass
[27] ENA default
Current of charging
28
[28] 40A default
under grid electricity
RS485 Address 30
Setting
[30] 1 default [31] SIG default
AC Output Mode 31 (Can be set in the
[31] PAL
standby mode only) [31] 2P0/2P1/2P2
be shut down, and the machine will not be restarted for output. Enable automatic restart upon over-temperature. If overtemperature occurs, shut down output, and restart output after the temperature has dropped. No Alarm Enable alarm Alarm is disabled when the status of the main input source has change. Alarm is disabled when the status of the main input source has change. Automatic switch to Mains Power is disabled when the Inverter is overloaded. Automatic switch to Mains Power when the inverter is overloaded. AC output 120Vac, with the Setting Range of 0~40A RS485 communication address can be set within the range of 1~254 Single machine setting Single-phase parallel connection setting Split-phase parallel connection setting
31
When the parameter [38] setting item=120Vac. All connected P1-phase inverters are set to “2P0”
- If all connected P2-phase inverters are set to “2P1”, AC
output line voltage difference is 120 degrees (L1-L2), line
voltage is 120*1.732= 208Vac; Phase voltage is 120Vac (L1-N;
L2-N).
- If all connected P2-phase inverters are set to “2P2”, AC
output line voltage difference is 180 degrees (L1-L2), line
voltage is 120*2= 240Vac; Phase voltage is 120Vac (L1-N; L2-
N).
[31] 3P1/3P2/3P3
Three-phase parallel connection setting
All machines in phase 1 must be set as 3P1 All machines in phase 2 must be set as 3P2 All machines in phase 3 must be set as 3P3 When the output voltage set in the setting 38 is
120Vac:
At present the line voltage between L1 in phase 1 and L2 in
phase 2 is 120*1.732 = 208 Vac, similarly the line voltage
between L1-L3, L2-L3 is 208 Vac; the single phase voltage
between L1-N, L2-N, L3-N is 120 Vac.
Communication 32
Function
[32] SLA default [32] 485
RS485-2 port for PC or telecommunication control. RS485-2 port for 485-BMS communication.
When [32] enables BMS communication, the corresponding
lithium battery manufacturer brand should be selected for
BMS Communication communication:
33
Protocol
PAC=PACERDA=Ritar, AOG=ALLGRAND BATTERY
OLT=OLITERHWD=SUNWODA, DAQ=DAKING,
WOW=SRNE, PYL=PYLONTECHUOL=WEILAN
32
[34] DIS default
PV Grid-connected 34 Power generation
Function
[34] TOGRID [34] TOLOAD
Battery Under35 Voltage Recovery
Point
[35] 52V default
Max PV Charger 36
Current
[36] 80A default
Battery Recharge 37
Recovery Point
[37] 52V default
AC Output Rated 38
Voltage
Charge Current
Limiting Method 39
(When BMS is
enabled)
[38] 120Vac default [38] LC SET [38] LC BMS
Disable this Function In the utility bypass state, when no battery is
connected or when the battery is full, the surplus PV energy is fed back to
the grid. In the utility bypass state, when no battery is connected or when
the battery is full, the load power is supplied by the hybrid of PV and the
utility. When the battery is under-voltage, the battery voltage should be
greater than this set value to restore the inverter AC output of the battery,
and the Setting Range is 44V~54.4V. Max PV charger current. Setting range:
0~100A After the battery is fully charged, the inverter will stop charging,
and when the battery voltage is lower than this Value, the Inverter will
resume charging again. And the Setting Range is 44V~54V.
You can set: 100/105/110/120Vac
Max. battery charging current not greater than the value of setting 07 Max.
battery charging current not greater than the limit value of BMS
33
1-section start 40
charging time 1-section end 41 charging time 2-section start 42 charging time
2-section end 43 charging time 3-section start 44 charging time 3-section end
45 charging time
Sectional Charging 46
Function
[38] LC INV [40] 00:00:00 default [41] 00:00:00 default [42] 00:00:00 default
[43] 00:00:00 default [44] 00:00:00 default [45] 00:00:00 default [46] DIS
default
[46] ENA
Max. battery charging current not greater than the logic judgements value of
the inverter.
Setting Range: 00: 00-23: 59: 00
Setting Range: 00: 00-23: 59: 00
Setting Range: 00: 00-23: 59: 00
Setting Range: 00: 00-23: 59: 00
Setting Range: 00: 00-23: 59: 00
Setting Range: 00: 00-23: 59: 00
Disable this Function After the sectioned charging function is enabled, the
power supply mode will change to BT1ST, and system will enable the mains power
charging only in the set charging period or battery over discharge; If the
sectioned discharge function is enabled at the same time, the power supply
mode of the system will change to AC1ST, which only enable the mains charging
in the set charging period, and switch to the battery inverter power supply
mode in the set discharge period or when the mains power is off
34
1-section start 47
discharging time
[47] 00:00:00 default Setting Range: 00: 00-23: 59: 00
1-section end 48
discharging time
[48] 00:00:00 default Setting Range: 00: 00-23: 59: 00
2-section start 49
discharging time
[49] 00:00:00 default Setting Range: 00: 00-23: 59: 00
2-section end 50
discharging time
[50] 00:00:00 default Setting Range: 00: 00-23: 59: 00
3-section start 51
discharging time
[51] 00:00:00 default Setting Range: 00: 00-23: 59: 00
3-section end 52
discharging time
[52] 00:00:00 default Setting Range: 00: 00-23: 59: 00 [53] DIS default
Disable this Function
After the sectioned discharge function
Sectional Discharge
53
Function
[53] ENA
is enabled, the power supply mode will change to AC1ST and the system will switch to battery inverter power
supply only during the set discharge
period or when the mains power is off
54 Current Date Setting [54] 00:00:00 default Setting Range: 00:01: 01-99:12:31
55 Current Time Setting [55] 00:00:00 default Setting Range: 00:00: 00-23:59: 59
Leakage Protection [56] DIS default
56
Function
[56]ENA
Disable this Function Enable leakage protection function
Stop Charging 57
Current
[57] 2A default
Discharge Aarm SOC
58
[58] 15 default
Setting
Cut-off Discharge 59
SOC Settings
[59] 5 default
Charging stops when the default charging current is less than this setting SOC alarm when capacity is less than this set value (valid when BMS communication is normal) Stops discharging when the capacity is less than this setting (valid when
35
Cut-off Charge SOC
60
[60]100 default
Settings
Switch to Mains SOC
61
[61] 10 default
Settings
Switch to Inverter
62
[62] 100 default
Output SOC Settings
BMS communication is normal) Stops charging when capacity is greater than or equal to this setting (valid when BMS communication is normal) Switch to mains when capacity is less than this setting (valid when BMS communication is normal) Switches to inverter output mode when capacity is greater than or equal to this setting (valid when BMS communication is normal)
36
5.3 Battery Type Parameters
For Lead-acid Battery:
Battery type
Parameters Overvoltage disconnection voltage
Sealed lead acid battery
(SLD)
60V
Colloidal lead acid battery
(GEL)
60V
Vented lead acid battery
(FLD)
60V
User-defined (User)
3660V (Adjustable)
Battery fully charged recovery
52V
point (setup item 37)
(Adjustable)
Equalizing charge voltage
58.4V
Boost charge voltage
57.6V
Floating charge voltage
Undervoltage alarm voltage (01 fault)
55.2V 44V
52V (Adjustable)
56.8V
56.8V
55.2V
44V
52V (Adjustable)
59.2V
58.4V
55.2V
44V
52V (Adjustable)
3660V (Adjustable)
3660V (Adjustable)
3660V (Adjustable)
3660V (Adjustable)
Undervoltage alarm voltage recovery point (01 fault) Low voltage disconnection
voltage (04 fault) Low voltage disconnection voltage recovery point (04 fault)
(setup item 35) Discharge limit voltage
Over-discharge delay time
Equalizing charge duration
Equalizing charge interval
Boost charge duration
Undervoltage alarm voltage+0.8V
3660V
42V
42V
42V
(Adjustable)
52V (Adjustable)
52V (Adjustable)
52V (Adjustable)
52V (Adjustable)
40V 5s 120 mins 30 days 120 mins
40V 5s 120 mins
40V 5s 120 mins 30 days 120 mins
3660V (Adjustable)
130s (Adjustable) 0600 mins (Adjustable) 0250 days (Adjustable) 10600 mins
(Adjustable)
37
For Lithium Battery:
Battery type Parameters
NCM13
NCM14
LFP16
LFP15
LFP14
Overvoltage 60V
disconnection voltage
Battery fully charged recovery point (setup item 37)
50.4V (Adjustable)
Equalizing charge
53.2V
voltage
(Adjustable)
Boost charge voltage
53.2V (Adjustable)
53.2V Floating charge voltage
(Adjustable)
Undervoltage alarm
43.6V
voltage (01 fault)
(Adjustable)
Undervoltage alarm
voltage recovery point
(01 fault)
Low voltage disconnection voltage (04 fault)
38.8V (Adjustable)
Low voltage
disconnection voltage
46V
recovery point (04 fault) (Adjustable) (setup item 35)
60V
60V
60V
60V
54.8V
53.6V
50.4V
47.6V
(Adjustable) (Adjustable) (Adjustable) (Adjustable)
57.6V (Adjustable)
57.6V (Adjustable)
57.6V (Adjustable)
46.8V (Adjustable)
56.8V
53.2V
49.2V
(Adjustable) (Adjustable) (Adjustable)
56.8V
53.2V
49.2V
(Adjustable) (Adjustable) (Adjustable)
56.8V
53.2V
49.2
(Adjustable) (Adjustable) (Adjustable)
49.6V
46.4V
43.2V
(Adjustable) (Adjustable) (Adjustable)
Undervoltage alarm voltage+0.8V
42V
48.8V
45.6V
42V
(Adjustable) (Adjustable) (Adjustable) (Adjustable)
49.6V
52.8V
49.6V
46V
(Adjustable) (Adjustable) (Adjustable) (Adjustable)
Discharge limit voltage
36.4V
39.2V
46.4V
43.6V
40.8V
Over-discharge delay time
Boost charge duration
30s (Adjustable)
120 mins (Adjustable)
30s (Adjustable)
120 mins (Adjustable)
30s
30s
30s
(Adjustable) (Adjustable) (Adjustable)
120 mins 120 mins 120 mins
(Adjustable) (Adjustable) (Adjustable)
38
Other Functions
6.1 Dry Contact
Working principle: This dry contact can control the ON/OFF of the diesel
generator to charge the battery. 1. Normally, the terminals are that the NC-N
point is closed and the NO-N point is
open; 2. When the battery voltage reaches the low voltage disconnection point,
the relay
coil is energized, and the terminals turn to that the NO-N point is closed
while NCN point is open. At this point, NO-N point can drive resistive loads:
125VAC/1A, 230VAC/1A, 30VDC/1A.
6.2 RS485 Communication Port
This port is an RS485 communication port which comes with two functions: 1.
RS485-2 allows direct communication with the optional host computer
developed by our company through this port, and enables monitoring of the
equipment running status and setting of some parameters on the computer; 2.
RS485-1/RS485-2 also allows direct connection with the optional RS485 to
WiFi/GPRS communication module developed by our company through this port.
After the module is selected, you can connect the all-in-one solar charge
inverter through the mobile phone APP, on which you can view the operating
parameters and status of the device. As shown in the figure: RS485-1: Pin 1 is
5V power supply, Pin 2 is GND, Pin 7 is RS485-A1, and Pin 8 is RS485-B1;
RS485-2: Pin 1 is 5V power supply, Pin 2 is GND, Pin 7 is RS485-A2, and Pin 8
is RS485-B2;
6.3 USB Communication Port
This is a USB communication port, which can be used for USB communication with
the optional PC host software. To use this port, you should install the
corresponding “USB to serial chip CH340T driver” in the computer.
39
6.4 Parallel Communication Function (Parallel Operation Only)
a) This port is used for parallel communication, through which the parallel modules can
communicate with each other. b) Each inverter has two DB15 ports, one for the
male connector and the other for the female
connector. c) When connecting, make sure to connect the male connector of the
inverter with the female
connector of the inverter to be paralleled, or connect the female connector of the inverter to the
male connector of the inverter to be paralleled. d) Do not connect the male connector of the inverter to its female connector.
Female connector
Male connector
6.5 Current Sharing Detection Function (Parallel Operation Only)
a) This port is used for current sharing detection, through which the current
sharing of the parallel modules can be detected (parallel operation only).
b) Each inverter has two current sharing detection ports, which are connected
in parallel. When it is connected to other models to be paralleled, either
port can be connected for convenience. There is no special mandatory wiring
requirements.
40
7 Protection
7.1 Protections Provided
No.
Protections
Description
PV current/power 1
limiting protection
When charging current or power of the PV array configured exceeds the PV rated, it will charge at the rated.
PV night reverse2
current protection
At night, the battery is prevented from discharging through the PV module because the battery voltage is greater than the voltage of PV module.
Mains input over 3
voltage protection
When the mains voltage exceeds 140V, the mains charging will be stopped and switched to the inverter mode.
Mains input under When the mains voltage is lower than 90V the mains charging
will 4
voltage protection be stopped and switched to the inverter mode.
When the battery voltage reaches the overvoltage disconnection
Battery over voltage point, the PV and the mains will be automatically stopped to charge
5
protection
the battery to prevent the battery from being overcharged and
damaged.
When the battery voltage reaches the low voltage disconnection
Battery low voltage
6
point, the battery discharging will be automatically stopped to
protection
prevent the battery from being over-discharged and damaged.
Load output short 7
circuit protection
When a short-circuit fault occurs at the load output terminal, the AC output is immediately turned off and turned on again after 1 second.
Heat sink over 8 temperature
protection
When the internal temperature is too high, the all-in-one machine will stop charging and discharging; when the temperature returns to normal, charging and discharging will resume.
Output again 3 minutes after an overload protection, and turn the output off after 5 consecutive times of overload protection until the 9 Overload protection machine is re-powered. For the specific overload level and duration, refer to the technical parameters table in the manual.
PV reverse polarity
10
When the PV polarity is reversed, the machine will not be damaged.
protection
AC reverse 11
protection
Prevent battery inverter AC current from being reversely input to Bypass. (In off-grid mode)
12 Bypass over current Built-in AC input overcurrent protection circuit breaker.
41
protection
Battery input over 13
current protection
When the discharge output current of the battery is greater than the maximum value and lasts for 1 minute, the AC input would switch to load.
Battery input 14
protection
When the battery is reversely connected or the inverter is shortcircuited, the battery input fuse in the inverter will blow out to prevent the battery from being damaged or causing a fire.
Charge short 15
protection
When the external battery port is short-circuited in the PV or AC charging state, the inverter will protect and stop the output current.
CAN In parallel operation, an alarm will be given when CAN
16 communication loss communication is lost.
protection
Parallel connection In parallel operation, the equipment will be protected when the
17
error protection
parallel line is lost.
Parallel battery
In parallel operation, the equipment will be protected when the
18 voltage difference battery connection is inconsistent and the battery voltage is greatly
protection
different from that detected by the host.
Parallel AC voltage In parallel operation, the equipment will be protected
when the AC 19
difference protection IN input connection is inconsistent.
Parallel current
In parallel operation, the running equipment will be protected when
20 sharing fault
the load difference of each inverter is large due to improper
protection
connection of current sharing line or device damage.
Synchronization
The equipment will be protected when there is a fault in the
21 signal fault
guidance signal between parallel buses, causing inconsistent
protection
behavior of each inverter.
42
7.2 Fault Code
Fault code
Fault name
01
02
03 04 05 06 07 08 09 10 11 13 14 15 17 19
20
21 22 23
BatVoltLow
BatOverCurrSw
BatOpen BatLowEod BatOverCurrHw BatOverVolt BusOverVoltHw BusOverVoltSw
PvVoltHigh
PvOCSw PvOCHw OverloadBypass OverloadInverter AcOverCurrHw InvShort
OverTemperMppt
OverTemperInv
FanFail EEPROM ModelNumErr
Whether it affects the output or
not
Description
NO
Battery undervoltage alarm
Battery discharge average current Yes
overcurrent software protection
Yes
Battery not-connected alarm
Yes
Battery undervoltage stop discharge alarm
Yes
Battery overcurrent hardware protection
Yes
Charging overvoltage protection
Yes
Bus overvoltage hardware protection
Yes
Bus overvoltage software protection
No
PV overvoltage protection
No
Boost overcurrent software protection
No
Boost overcurrent hardware protection
Yes
Bypass overload protection
Yes
Inverter overload protection
Yes
Inverter overcurrent hardware protection
Yes
Inverter short circuit protection
No
Buck heat sink over temperature protection
Inverter heat sink over temperature Yes
protection
Yes
Fan failure
Yes
Memory failure
Yes
Model setting error
43
26 29
RlyShort BusVoltLow
30
BatCapacityLow1
31
BatCapacityLow2
32 BatCapacityLowStop
34 35 37 38
CanCommFault ParaAddrErr
ParaShareCurrErr ParaBattVoltDiff
39
ParaAcSrcDiff
40 41 42
ParaHwSynErr InvDcVoltErr SysFwVersionDiff
43
ParaLineContErr
44
Serial number error
Inverted AC Output Backfills to Bypass AC Yes
Input
Yes
Internal battery boost circuit failure
Alarm given when battery capacity rate is
No
lower than 10% (setting BMS to enable
validity)
Alarm given when battery capacity rate is
No
lower than 5% (setting BMS to enable
validity)
Inverter stops when battery capacity is low Yes
(setting BMS to enable validity)
CAN communication fault in parallel Yes
operation
Yes
Parallel ID mailing addresssetting error
Yes
Parallel current sharing fault
Large battery voltage difference in parallel Yes
mode
Inconsistent AC input source in parallel Yes
mode
Hardware synchronization signal error in Yes
parallel mode
Yes
Inverter DC voltage error
Inconsistent system firmware version in Yes
parallel mode
Parallel line connection error in parallel Yes
mode
If the serial number is not set by omission in
Yes
production, please contact the manufacturer
to set it
44
45
Error setting of splitphase mode
58
BMS communication error
59 60 61 62 63 64
BMS alarm
BMS battery low temperature alarm BMS battery over temperature alarm BMS
battery over
current alarm BMS battery undervoltage alarm BMS battery over voltage alarm
Yes
31Settings item setting error
Check whether the communication line is
connected correctly and whether [33] is set No
to the corresponding lithium battery
communication protocol
Check the BMS fault type and troubleshoot No
battery problems
No
BMS alarm battery low temperature
No
BMS alarm battery over temperature
No
BMS alarm battery over current
No
BMS alarm low battery
No
BMS alarm battery over voltage
45
7.3 Handling Measures for Part of Faults
Fault code
Faults
Remedy
Display No display on the screen
Check if the battery the PV air switch has been closed; if the switch is in the “ON” state; press any button on the screen to exit the screen sleep mode.
06
01 04
Battery overvoltage protection Battery undervoltage protection
Measure if the battery voltage exceeds rated, and turn off the PV array air switch and Mains air switch. Charge the battery until it returns to the low voltage disconnection recovery voltage.
21 Fan failure
Check if the fan is not turning or blocked by foreign object.
19 20
13 14
Heat sink over temperature protection
When the temperature of the device is cooled below the recovery temperature, normal charge and discharge control is resumed.
Bypass overload protection, 1. Reduce the use of power equipment;
inverter overload protection 2. Restart the unit to resume load output.
17
Inverter short circuit protection
1. Check the load connection carefully and clear the short- circuit fault
points;
2. Re-power up to resume load output.
09 PV overvoltage
Use a multimeter to check if the PV input voltage exceeds the maximum allowable input voltage rated.
03
40 43
Battery disconnected alarm Parallel connection fault
Check if the battery is not connected or if the battery circuit breaker is not closed. Check whether the parallel line is not connected well, such as loose or wrong connection.
35 Parallel ID setting error
Check whether the setting of parallel ID number is repeated.
37
Check whether the parallel current sharing line is not Parallel current
sharing fault
connected well, such as loose or wrong connection.
39
Inconsistent AC input source in parallel mode
Check whether the parallel AC inputs are from the same input interface.
42
Inconsistent system firmware version in parallel mode
Check whether the software version of each inverter is consistent.
46
Troubleshooting
In order to maintain the best long-term performance, it is recommended to
conduct following checks twice a year. 1. Make sure that the airflow around
the unit is not blocked and remove any dirt or debris from the
heat sink. 2. Check that all exposed wires are damaged by exposure to
sunlight, friction with other objects
around them, dryness, bite by insects or rodents, etc., and the wires shall be
repaired or replaced if necessary. 3. Verify for the consistency of indication
and display with the operation of the device. Please pay attention to the
display of any faults or errors, and take corrective actions if necessary. 4.
Check all wiring terminals for corrosion, insulation damage, signs of high
temperature or burning/discoloration, and tighten the screws. 5. Check for
dirt, nesting insects and corrosion, and clean up as required. 6. If the
arrester has failed, replace in time to prevent lightning damage to the unit
or even other equipment of the user.
WARNING
Danger of electric shock! When doing the above operations, make sure that all
power supplies of the all-in-one machine have been disconnected, and all
capacitors have been discharged, and then check or operate accordingly!
The company does not assume any liability for damage caused by: 1. Improper
use or use in improper site. 2. Open circuit voltage of the PV module exceeds
the maximum allowable voltage rated. 3. Temperature in the operating
environment exceeds the limited operating temperature range. 4. Disassemble
and repair the all-in-one solar charge inverter without permission. 5. Force
majeure: Damage that occurs in transportation or handling of the all-in-one
solar charge
inverter.
47
Technical parameters
Models Parallel Mode Permitted parallel number AC Mode Rated input voltage
Input voltage range Frequency
Frequency Range
Overload/short circuit protection Efficiency Conversion time (bypass and
inverter) AC reverse protection Maximum bypass overload current Inverter Mode
Output voltage waveform Rated output power Rated output power Power factor
Rated output voltage
Output voltage error Output frequency range Maximum Efficiency
Overload protection
POW-SunSmart SP5K
1~6
110/120Vac (90Vac~140Vac) ± 2% 50Hz/ 60Hz (Auto detection) 47 ± 0.3Hz ~ 55 ±
0.3Hz (50Hz); 57 ± 0.3Hz ~ 65 ± 0.3Hz (60Hz)
Circuit breaker >95%
10ms (typical)
Available
63A
Pure sine wave 5000VA 5000W 1 120Vac
(100/105/110Vac Settable) ± 5%
50Hz ± 0.3Hz; 60Hz ± 0.3Hz >92%
(102% < load <110%) ±10%: report error and turn off the output after 5
minutes; (110% < load < 125%) ± 10%: report error and turn off the output
after 10 seconds; (Load >125% ±10%): report error and turn off the output
after
48
5 seconds;
Peak power
10000VA
Loaded motor capability
4HP
Rated battery input voltage
Battery voltage range
Power saving mode selfconsumption AC Output (Grid)
48V (Minimum starting voltage 44V) Undervoltage alarm/ shutdown voltage/
overvoltage alarm/ overvoltage recovery… settable on LCD screen
Load 50W
Rated Output Power Max. apparent power Max. output current THDI Rated voltage Frequency AC Charging
5000W 5000VA
41.7A <3% 120Vac 50Hz/60Hz
Battery type
Maximum charge current (can be set) Charge current error
Lead acid or lithium battery 0-40A ± 3Adc
Charge voltage range Short circuit protection
4058Vdc Circuit breaker and blown fuse
Circuit breaker specifications
63A
Overcharge protection
Alarm and turn off charging after 1 minute
PV Charging
Maximum PV open circuit voltage
500Vdc
PV operating voltage range
120-500Vdc
MPPT voltage range
120-450Vdc
Battery voltage range
40-60Vdc
Maximum PV input power
5500W
49
Maximum PV input current
PV charging current range (can be set) Charging short circuit protection
22A 100A Blown fuse
Wiring protection
Reverse polarity protection
Hybrid charging Max charger current specifications (AC charger + PV charger)
Max charger current(can be set)
100A
Certified specifications
Certification
CE(IEC62109-1)
EMC certification level
EN61000
Operating temperature range
-10°C ~ 55°C
Storage temperature range
-25°C ~ 60°C
Humidity range
5% to 95% (Conformal coating protection)
Noise
60dB
Heat dissipation
Forced air cooling, variable speed of fan
Communication interface
USB/RS485(WiFi/GPRS)/Dry contact control
Dimension (LWD)
446.9mm350mm133mm
Weight
14kg
50
10 Parallel Installation Guide
10.1 Introduction
1. Up to six units connected in parallel.
2. When using the parallel operation function, the following connecting lines (package accessories)
shall be firmly and reliably connected:
DB15 Parallel communication line*1:
Current sharing detection line*1:
10.2 Precautions for Connecting the Parallel Connecting Lines WARNING
1. Battery wiring: Parallel connection in single or split phase: Ensure that
all all-in-one solar charger inverters are connected to the same battery, with
BAT + connected to BAT +, BAT – connected to BAT-, and that the connection is
correct with the same wiring length and line diameter before power on and
startup, so as to avoid the abnormal operation of parallel system output
caused by wrong connection. 2. AC OUT wiring: Parallel connection in single
phase: Ensure L-to-L, N-to-N and PE-to-PE connection for all all- inone solar
charger inverters, and that the connection is correct with the same wiring
length and line diameter before power on and start-up, so as to avoid the
abnormal operation of parallel system output caused by wrong connection. For
specific wiring, please refer to 2.4.3 Wiring Diagram Parallel connection in
split phase: Ensure N-to-N and PE-to-PE connection for all all-in-one solar
charger inverters. The L lines of all inverters connected to the same phase
need to be connected together. But L lines of different phases cannot be
joined together. Other connection precautions are the same as parallel
connection in single phase. For specific wiring, please refer to 2.4.4Wiring
Diagram
51
3. AC IN wiring: Parallel connection in single phase: Ensure L-to-L, N-to-N
and PE-to-PE connection for all all- inone solar charger inverters, and that
the connection is correct with the same wiring length and line diameter before
power on and start-up, so as to avoid the abnormal operation of parallel
system output caused by wrong connection. Meanwhile, it is not allowed to have
multiple different AC source inputs to avoid damage to the external equipment
of the inverter. The consistency and uniqueness of AC source input shall be
ensured. For specific wiring, please refer to 2.4.3 Wiring Diagram. Parallel
connection in split phase: Ensure N-to-N and PE-to-PE connection for all all-
in-one solar charger inverters. The L lines of all inverters connected to the
same phase need to be connected together. But L lines of different phases
cannot be joined together. Other connection precautions are the same as
parallel connection in single phase. For specific wiring, please refer to
2.4.4 Wiring Diagram. 4. Wiring of parallel communication line: Parallel
connection in single or split phase: Our company’s parallel communication line
is a DB15 standard computer cable with shielding function. Ensure the “one-in-
one-out” rule when connecting each inverter, that is, connect the male
connector (out) of this inverter with the female connector (in) of the
inverter to be paralleled. Do not connect the male connector of the inverter
to its female connector. In addition, make sure to tighten the parallel
communication line of each inverter with self-contained end screws of DB15 to
avoid the abnormal operation or damage of the system output caused by the
falling off or poor contact of the parallel communication line. 5. Wiring of
current sharing detection line: Parallel connection in single phase: Our
company’s current sharing detection line is a twisted connection line. Ensure
the “one-in-one-out” rule when connecting each inverter, that is, connect the
current sharing line of the inverter with the current sharing green port of
the inverter to be paralleled (choose one port from the two, and there is no
mandatory sequence requirement). The current sharing ports of the inverter
cannot be connected to each other. In addition, make sure that the red and
black current sharing connection lines of each inverter are not manually
exchanged, and make sure to tighten the lines with self-contained screws to
avoid the abnormal operation or damage of the system output caused by abnormal
parallel current sharing detection. For specific wiring, please refer to 2.4.3
Wiring Diagram. Parallel connection in split phase: The current sharing
detection lines of all inverters connected
52
to the same phase need to be connected together. But the current sharing
detection lines of different phases cannot be joined together. Other
connection precautions are the same as parallel connection in single phase.
For specific wiring, please refer to 2.4.4 Wiring Diagram. 6. Before or after
connecting the system, please carefully refer to the following system wiring
diagram to ensure that all wiring is correct and reliable before power on. 7.
After the system is wired, powered on and in normal operation, if a new
inverter needs to be
connected, make sure to disconnect the battery input, PV input, AC input and
AC output, and that all all-in-one solar charger inverters are powered off
before reconnecting into the system.
53
10.4 Schematic Diagram of Parallel Connection in Single Phase
1. The parallel communication line and current sharing detection line of the
all-in-one solar charger inverter need to be locked with screws after
connecting. The schematic diagram is as follows:
2. In case of parallel operation with multiple inverters, the schematic
diagram of parallel connection is as follows:
a) Two all-in-one solar charger inverters of the system connected in parallel:
54
b) Three all-in-one solar charger inverters of the system connected in
parallel: c) Four all-in-one solar charger inverters of the system connected
in parallel:
55
d) Five all-in-one solar charger inverters of the system connected in
parallel: e) Six all-in-one solar charger inverters of the system connected in
parallel:
56
10.6 Schematic Diagram of Parallel Connection in Two Phase
1. The parallel communication line and current sharing detection line of the
all-in-one solar charger inverter need to be locked with screws after
connecting. The schematic diagram is as follows:
2. In case of parallel operation with multiple inverters, the schematic
diagram of parallel connection is as follows:
Parallel Operation in two phase (only for U series model can be set): a) Two
all-in-one solar charger inverters of the system connected in two phase: 1+1
system:
57
b) Three all-in-one solar charger inverters of the system connected in two
phase: 2+1 system:
c) Four all-in-one solar charger inverters of the system connected in two
phase: 2+2 system:
58
3+1 system:
d) Five all-in-one solar charger inverters of the system connected in two
phase: 4+1 system:
59
3+2 system:
e) Six all-in-one solar charger inverters of the system connected in two
phase: 5+1 system:
60
4+2 system: 3+3 system:
61
10.7 Schematic Diagram of Parallel Connection in Three Phase
1. The parallel communication line and current sharing detection line of the
all-in-one solar charger inverter need to be locked with screws after
connecting. The schematic diagram is as follows:
2. In case of parallel operation with multiple inverters, the schematic
diagram of parallel connection is as follows:
Parallel Operation in three phase: a) Three all-in-one solar charger inverters
of the system connected in three phase: 1+1+1 system:
62
b) Four all-in-one solar charger inverters of the system connected in three
phase: 2+1+1 system:
c) Five all-in-one solar charger inverters of the system connected in three
phase: 3+1+1 system:
63
2+2+1 system:
d) Six all-in-one solar charger inverters of the system connected in three
phase: 2+2+2 system:
64
3+2+1 system: 4+1+1 system:
65
NOTICE
- Before starting up and running, please check whether the connection was correct to avoid any abnormalities in the system.
- All wiring must be fixed and reliable to avoid wire drop during use. 3)
When the AC output is wired to the load, it shall be properly wired according
to the
requirements of the electrical load equipment to avoid damage to the load equipment. 4) Settings [38] need to be set consistently or only for the host. When the machine is running, the
voltage set by the host shall prevail, and the master will force the rewrite of the other slave machines to keep the same set. Only can be set in the standby mode. 5) Machine factory default for single machine mode, if you use parallel, split-phase or threephase function, you need to set the [31] item parameters through the screen. The setting method is: power on one machine at a time, the rest of the machine off, and then set the [31] item parameters according to the site system operation mode. After this machine is set successfully, turn off the machine switch and wait for the machine to be powered down, then set the rest of the machines in turn until all machines are set, and then all machines are powered up again at the same time and enter the working state. The [31] setting item: When in single phase parallel connection: setting 31should be set as PAL When in single phase parallel connection, setting 31 should be set as follows When in three phase parallel connection, all machines in phase 1 must be set as 3P1, all machines in phase 2 must be set as 3P2 all machines in phase 3 must be set as 3P3, at present, the voltage phase difference between P1-P2, P1-P3 and P2-P3 is 120 degrees. When the output voltage set in the setting 38 is 120 Vac (U model), the line voltage between L1 in phase 1 and L2 in phase 2 is 1201.732 = 208 Vac, similarly the line voltage between L1-L3, L2-L3 is 208 Vac; the single phase voltage between L1-N, L2-N, L3-N is 120Vac. In split phase parallel connection, all connected P1-phase inverters are set to “2P0” i. If all connected P2-phase inverters are set to “2P1”, AC output line voltage difference is 120
degrees (L1-L2), line voltage is 1201.732= 208Vac; Phase voltage is 120Vac (L1-N; L2-N). ii. If all connected P2-phase inverters are set to “2P2”, AC output line voltage difference is 180
degrees (L1-L2), line voltage is 120*2= 240Vac; Phase voltage is 120Vac (L1-N; L2-N). 6) After the system runs, the output voltage is measured correctly, and then the load setting is
connected.
66
67
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>