Bard IZ ECONOMIZER Full Flow Modulating Low Leakage Instruction Manual
- June 14, 2024
- Bard
Table of Contents
Bard IZ ECONOMIZER Full Flow Modulating Low Leakage
General Economizer Information
Using an economizer provides economical cooling without the need for
running the compressor and refrigeration system when outdoor conditions are
acceptable to bring air into the building. By bringing in outdoor air to cool
a building, energy use is reduced to the power required to operate the indoor
fan and the economizer controls. Energy use is a fraction of the power
required to operate the refrigeration system.
The following benefits can be attributed to the economizer
- Reduced energy costs when outdoor conditions are acceptable to bring air into the building.
- Lengthen the life expectancy of the refrigeration components due to lower operating time.
- Provide a source of air for an occupied area to meet building code requirements.
- Reduce stress to refrigeration equipment during extremely cold outdoor temperatures by using outdoor air to cool.
Economizer usage is beneficial for several applications including equipment
cooling and keeping occupants comfortable while keeping energy costs at a
minimum.
The IZ factory-installed economizer uses the Honeywell JADE® W7220 control,
low leakage intake and exhaust dampers and direct-drive actuators. The
economizer uses a supply/mixed air sensor and outdoor changeover sensor
(either dry bulb or enthalpy sensor).
There are two distinct types of economizers that are factory provided
- The “fixed dry bulb” economizer allows outdoor air to enter the building when the outdoor temperature monitored by an outdoor sensor is below the user-selectable outdoor temperature setpoint in the JADE controller. Economizer cooling operation is based on outdoor temperature only.
- The “fixed dry bulb and enthalpy” economizer allows outdoor air to enter the building when the outdoor temperature and humidity monitored by an outdoor sensor is below the user-selectable enthalpy curve in the JADE controller. Economizer cooling operation is based on outdoor temperature and humidity.
Either of the above economizers can be converted to differential dry bulb or differential enthalpy by adding the field-installed return air sensor kit.
Basic Operation Using the JADE W7220 with 2-Speed Fan and Motorized Exhaust
- For occupied mode operation, the A terminal is energized with 24 volts at the unit low voltage terminal strip. At the same time, this powers G at the unit low voltage terminal strip and the OCC input at the W7220 which will command the fresh air damper to open to the minimum damper position setting and the supply air fan to low speed.
- If there is a call for cooling, Y1 is energized at the low voltage control board. If the outdoor temperature is below the setpoint of the outdoor sensor, the fresh air damper will open and attempt to cool the indoor space by using outdoor air while attempting to maintain the mixed air sensor setpoint ‘fixed dry bulb”. At the same time, when the fresh air damper reaches the exhaust fan setpoint, the exhaust damper will open and exhaust fan will start.
- If the call for cooling is not satisfied, Y2 at the low voltage control board is energized and 1st stage mechanical cooling along with economizer will attempt to satisfy the thermostat. If the thermostat
is not satisfied after 30 minutes, 2nd stage cooling is energized. If free cooling using outdoor air is not available, the unit cooling sequence will be controlled directly by the space thermostat and mechanical cooling.
W7220 stages are
- 1st Stage – Low speed supply blower
- 2nd Stage – 1st stage compressor
- 3rd Stage – 2nd stage compressor
JADE W7220 Controller Technical Specifications
The economizer system ships with standard settings pre-programmed from the factory. Normal use and operation may not require adjustments to the JADE settings. Advanced applications, however, may require additional setup and feature selection. The JADE model W7220 is used widely in the field, and heavily supported by the manufacturer. It is important to note that Bard does custom program the JADE for specific economizer models. If replacing the JADE is necessary, always order the JADE controller based on the Bard part number.
Environmental Information
- Operating Temperatur e: -40 to 150°F (-40 to 65°C). Exception of display operation down to -4°F with full recovery at -4°F from exposure to -40°F.
- Storage Temperature : -40 to 150°F (-40 to 65°C)
- Shipping Temperature : -40 to 150°F (-40 to 65°C)
- Relative Humidity : 5% to 95% RH non-condensing
Electrical Information
- Rated Voltage: 20 to 30 VAC RMS; 50/60 Hz
- Nominal Power Consumption (at 24 VAC, 60 Hz): 11.5 VA without sensors and actuator
- Relay Contact Rating at 30 VAC (maximum power from Class 2 input only): 1.5A run; 3.5A inrush @ 0.45PF (200,000 cycles) or 7.5A inrush @ 0.45PF (100,000 cycles)
- External Sensors Power Output : 21 VDC +/- 5% @ 48mA
Sensors
- Dry Bulb Sensor Temperature Range: -40 to 150°F (-40 to 65°C)
- Temperature and Humidity Sensor Range : Temperature -40 to 150°F (-40 to 65°C), humidity 0 to 100% RH with 5% accuracy.
- Optional CO2 Sensor Input: 2-10 VDC control signal ; minimum impedance >50k ohm.
JADE Economizer Controller
The JADE W7220 controller offers unparalleled flexibility and expansion in a
dependable and solid electronic platform.
- Multiple economizer applications from one controller.
- Nearly limitless customization of setpoints.
- Internal checkout menu provides fast performance assessment.
- Alarms menu provides assistance in troubleshooting.
Memory: User-defined setpoints remain in non-volatile flash memory
regardless of electrical outage duration. Control voltage below 18V may cause
erratic performance.
From the factory, the JADE economizer controller has been preset with
“default” values that were pre-determined as optimum for equipment buildings,
and these are shown in Tables 1 – 3 (on pages 8 and 9). However, it is
important to review and/or customize these operational values per owner
specifications in order to guarantee satisfactory performance.
The installing contractor can easily access the JADE programming by the integral keypad and LCD display.
There are six (6) basic MENU categories to navigate
- STATUS – provides real-time access to sensor input, damper and equipment operation.
- SETPOINTS – customizable operational parameters.
- SYSTEM SETUP – customizable application programming (see Review/Customize System Setup).
- ADVANCED SETUP – further application and operational options.
- CHECKOUT – instantly activate and verify economizer functions.
- ALARMS – displays alarms and pinpoints problem areas.
Economizer Quick Start
Quick Start Basic JADE Economizer Control Setup (SETPOINTS Menu)
This Bard IZ economizer is shipped with Bard settings pre-programmed into the
JADE controller, which includes 2-speed fan operation. The SETPOINTS menu
allows for basic user adjustment of several features including the following
Outdoor Temperature or Humidity Adjustment Procedure
- Units with “differential dry bulb” economizers are operated based on outdoor temperature only. The economizer will operate regardless of outdoor humidity. To adjust the outdoor temperature setting in the JADE controller that will initiate economizer operation, navigate to the SETPOINTS menu using the UP/DOWN buttons. Next, navigate to the DRYBULB SET menu using the UP/DOWN buttons. The default dry bulb setpoint is 70°F (21.1°C). The range of this setting is 48°F (8.8°C) to 80°F (26.6°C). Bard recommends gradual adjustment of the outdoor dry bulb setpoint if adjustment is necessary. It is always important to consider the indoor temperature requirements while maximizing economizer run time when adjusting the dry bulb setting. Once adjustment is made, monitor indoor conditions to verify the desired result.
- Units with “differential dry bulb and enthalpy” economizers are operated based on outdoor temperature and humidity. An enthalpy curve is used to control when conditions are acceptable for economizer use. Enthalpy curves provide a way to consider the amount of humidity it is acceptable to bring into the building based on outdoor temperature. To adjust the enthalpy curve in the JADE controller that will initiate economizer operation, navigate to the SETPOINTS menu using the UP/DOWN buttons. Next, navigate to the ENTH CURVE menu using the UP/DOWN buttons. The default enthalpy curve is ES3. The range of this setting is ES1 to ES5. Bard recommends gradual adjustment of the enthalpy curve setting if adjustment is necessary. A higher enthalpy curve setting will result in greater energy savings, but will allow additional humidity into the indoor area. A lower enthalpy curve setting will result in lower humidity being allowed into the indoor area, but will result in less economizer operation. It is always important to consider the indoor requirements while maximizing economizer run time when adjusting the enthalpy curve setting. Once adjustment is made, monitor indoor conditions to verify the desired result. See Enthalpy Settings on page 11.
Minimum Position Setting
-
Minimum position allows the user to program a blade setting that will allow a certain amount of outdoor air to enter the structure. Minimum blade ventilation occurs when the “A” terminal is energized on the IZ unit low voltage terminal strip. The blade setting is based on a voltage that is sent to the actuator motor.
2-Speed Fan Operation -
The JADE W7220 controller is programed for 2-speed fan. This does not control fan speeds but allows for two minimum positions, one for OCC and Y1 inputs, (vent min low “low speed”) and one for Y2 input (vent min high “high speed”). This allows a minimum position blade setting for low speed and minimum position blade setting for high speed. See Figure 2 for more information on 2-speed fan settings.
-
To set MINIMUM POSITION airflow, select the correct unit model airflow graph from the graphs provided on pages 19 and 20. Go to MENU, then SETPOINTS; set MIN POS LOW control voltage using continuous fan CFM and MIN POS HIGH control voltage using the full load speed CFM. These settings will allow for consistent minimum airflow at low and high speed fan. See Figure 2 for additional 2-speed fan information.
-
The voltage range is 2-10VDC, where 2VDC is a minimum amount of outdoor air being brought into the building and 10VDC is the maximum amount. Charts are provided on pages 19 and 20 to indicate an airflow amount that will be brought into the building at the various voltage settings. Pressure relief to the occupied space is provided by a power exhaust fan located in the lower section of the unit (see Economizer Exhaust on page 7).
Low Outdoor Temperature Compressor Lockout
- The JADE controller has the ability to disable refrigerant compressor cooling at a certain outdoor temperature. The JADE will monitor the outdoor temperature measurement using the outdoor sensor. When the outdoor temperature reading is below the compressor lockout temperature, the JADE will not call for compressor cooling operation and only use the economizer. This applies if Y1 or Y2 is energized. Refrigerant cooling with compressor use during extremely cold outdoor temperatures may shorten compressor life. To adjust the compressor lockout in the JADE controller that will disable compressor operation, navigate to the SETPOINTS menu using the UP/DOWN buttons. Next, navigate to the LOW T LOCK menu using the UP/DOWN buttons. The default minimum compressor lockout setting is 0°F (-17.7°C). The outdoor temperature range is -45°F (-42.7°C) to 80°F (26.6°C).
Mixed Air Temperature Setting
- As the economizer opens, indoor room air is mixed with the outdoor air entering the wall mount unit. The amount of indoor room air that is mixed with the outdoor air is dependent on the mixed air setpoint. During operation, the economizer will adjust the blade position to maintain a mixed air temperature. Bard has pre-programmed a mixed air temperature that allows for optimized cooling and energy savings while allowing for concurrent economizer and refrigerant compressor cooling. It is strongly recommended that for general use the mixed air temperature be kept at the default value. Adjustments may result in the indoor evaporator coil freezing or lower economizer cooling capacity. To adjust the mixed air setpoint in the JADE controller, navigate to the SETPOINTS menu using the UP/DOWN buttons. Next, navigate to the MAT SET menu using the UP/DOWN buttons. The default mixed air setting is 53°F (11.6°C). The mixed air temperature range is 38°F (3.3°C) to 65°F (18.3°C).
Operational Checkout (CHECKOUT Menu)
- It is always important to verify equipment functionality when using equipment to provide cooling to a space with equipment or occupants. A few simple steps will ensure that the economizer is functioning properly in the unit and will provide optimum performance. The following is provided as a basic checklist and additional steps may be required for advanced applications.
Checkout Procedure
- Make sure the unit power is OFF. Visually inspect the economizer assembly including the seals around the damper blade, damper motor linkage and wire harnesses are snug that connect the JADE.
- Apply power to the unit. Wait a few minutes for the JADE to energize. Verify no alarms are present on the JADE display. Next, navigate to the CHECKOUT menu using the UP/DOWN buttons. Once in the checkout menu, select the following
- DAMPER OPEN: This will force the economizer blade to open. Verify damper motor and linkage are functional.
- DAMPER CLOSE : This will force the economizer blade to close. Verify damper blade seals in the closed position.
- CONNECT Y1-O: This will force compressor cooling to operate. When energized, it may take several minutes for the compressor to energize.
- CONNECT Y2-O : This will force 2nd stage compressor cooling to operate. When energized, it may take several minutes for the compressor to energize.
- CONNECT EXH1 : This will force the exhaust fan to run.
- After completing checkout procedures, it is important that all panels are re-installed and secured before product use.
- NOTE: CHECKOUT functions bypass the normal 5-minute delay for compressor protection. Be sure to allow for enough time to pass between tests so the compressor is not damaged from extreme short-cycling.
- FIGURE 2 2-Speed Fan Operation
- The later versions of the JADE W7220 controller have the capability to work with a system using a 2-speed supply fan. The W7220 does not control the supply directly but uses the following input status to determine the speed of the supply fan and controls the OA damper to the required position.
State | Fan Speed |
---|---|
OCC | Low |
Y1 | Low |
Y2 | High |
W | High |
The W (heating mode) is not controlled by the W7220 but it requires the status
to know where to position the OA damper for minimum position for fan speed.
The 2-speed fan delay is available when the system is programmed for 2-speed
fan (in the System Setup menu item). The 2-speed fan delay is defaulted to 5
minutes and can be changed in the Advanced Setup menu item. When the unit has
a call for Y1 In and in the free cooling mode and there is a call for Y2 In,
the 2-speed fan delay starts and OA damper will modulate 100% open, the supply
fan should be set to high speed by the unit controller. After the delay, one
of the two following actions will happen
- The Y2 In call will be satisfied with the damper 100% open and the fan on high speed and the call will turn off. OR
- If the call for additional cooling in the space has not been satisfied, the first stage of mechanical cooling will be enabled through Y1 Out or Y2 Out.
Economizer Exhaust
- The variable speed exhaust fan is energized by the EHX1 terminal of the JADE W7220 when the outdoor air damper reaches 60% open. This setting opens the exhaust damper and turns the exhaust fan on and off. To change the setpoint, enter the SETTINGS menu and scroll to EXH1 H and EXH1 L (see SETPOINTS on page 9). The exhaust fan speeds are controlled by three adjustable pots on the control board (see Figure 3). Each stage of ventilation has its own exhaust fan speed. The factory exhaust fan settings are set to maintain an acceptable room pressure at each comfort blower speed while maintaining low sound levels. Each individual installation could vary, and exhaust fan speeds may need adjusted if the factory settings are not maintaining an acceptable room pressure. To field adjust the exhaust fan speeds, the outdoor conditions need to be suitable to economize and the economizer must be available and economizing. The thermostat will need to be set to OCC mode. Once the ACT POSITION reads 90% on the status screen, the OCC potentiometer on the board can be adjusted. Turn clockwise to increase or counterclockwise to decrease the exhaust fan speed (see Figure 3). The Y1 and Y2 potentiometers can only be adjusted when the thermostat is calling for economizer and cooling and ACT POSITION reads 90%. On the W7220 display, scroll through the STATUS MENU. When the Y1 OUT is ON and the Y2 OUT is OFF, set the Y1 potentiometer to desired speed. When both Y1 OUT and Y2 OUT are ON, adjust the Y2 potentiometer. If no exhaust is needed, simply turn all three potentiometers counterclockwise until they stop. The PP potentiometer is not used.
Exhaust Fan Off Delay Timer
There also is an exhaust fan off delay timer (see Figure 4). This timer is
pre-set from the factory. This timer allows the exhaust fan to continue to run
after the call for economizer is satisfied and allows the fresh air dampers
time to close before the exhaust fan shuts off. If any adjustment is needed
simply turn the red knob clockwise to increase the off-delay timing
counterclockwise to decrease the off-delay timing.
JADE Economizer Control Advanced Setup
Review/Customize System Setup
Before being placed in service, the JADE economizer controller programming
should be reviewed/customized through the following steps
-
SYSTEM SETUP : From the main screen, press the SCROLL (UP/DOWN) BUTTONS to navigate through the six (6) basic menu items to the SYSTEM SETUP menu.
-
Push the SELECT (ENTER) BUTTON to choose the SYSTEM SETUP menu.
-
Navigate through the multiple levels of SYSTEM SETUP by pushing the SCROLL (UP/DOWN) BUTTONS.
-
To change a specific parameter in the SYSTEM SETUP menu, press the SELECT (ENTER) BUTTON to display its current value. Press the SCROLL (UP/DOWN) BUTTONS to change or increase/decrease value. Press the SELECT
(ENTER) BUTTON to save the new customized value—“CHANGE STORED” will be displayed. Press the SELECT (ENTER) BUTTON again to return to current menu parameter. -
For specific SYSTEM SETUP level information, refer to TABLE 1.
-
NOTE: During an extended level of inactivity, the display of the JADE economizer controller will begin to automatically scroll through the various levels of the STATUS menu as a screensaver. Each level will stay for approximately 5 seconds before changing to the next level.
TABLE 1
Bard System Setup (As Shipped)
Parameter | Value | Range | Notes |
---|---|---|---|
INSTALL | 01/01/10 | Display Order = MM/DD/YY Setting Order = DD/MM/YY | |
UNITS DEG | °F | °F/°C | Sets controller to read in either measurement |
EQUIPMENT | HP OB | HP | Enables heat pump mode |
**** AUX IN | **** HP (B) | HP (O) HP (B | Energize heat pump on heat damper, |
closes to min position
FAN SPEED| 2 Speed|
- 1 Speed
- 2 Speed
| Allows for two min position settings
FAN CFM| 5000|
- 100 to
- 15000
| Not applicable
AUX1 OUT| SYS| NONE ERV EXH2 SYS| Product can be used to signal
other devices, SYS used for alarm signal
OCC| INPUT| INPUT or ALWAYS| INPUT is for dedicated OCC signal,
ALWAYS will be occupied signal all the time
FACTORY DEFAULT| NO| YES or NO| Resets to Honeywell factory defaults
- ADVANCED SETUP: From the main screen, press the SCROLL (UP/DOWN) BUTTONS to navigate through the six (6) basic menu items to the ADVANCED SETUP menu.
- Push the SELECT (ENTER) BUTTON to choose the ADVANCED SETUP menu.
- Navigate through the multiple levels of ADVANCED SETUP by pushing the SCROLL (UP/DOWN) BUTTONS.
- To change a specific parameter in the ADVANCED SETUP menu, press the SELECT (ENTER) BUTTON to display its current value. Press the SCROLL (UP/DOWN) BUTTONS to change or increase/decrease value. Press the SELECT (ENTER) BUTTON to save the new customized value—“CHANGE STORED” will be displayed. Press the SELECT (ENTER) BUTTON again to return to current menu parameter.
- For specific ADVANCED SETUP level information, refer to TABLE 2.
TABLE 2 Bard Advanced Setup (As Shipped)
Parameter | Value | Range | Notes |
---|---|---|---|
MAT LOW | 45°F | 35-65°F | Temp to activate freeze protection – Close Damper |
FREEZE POS | CLOSE | CLO or MIN | Damper position upon freeze protection |
CO2 ZERO* | 400 |
PPM
| 0 to 500 PPM| CO2 PPM level to match CO2 sensor start level
CO2 SPAN*| 1600
PPM
| 1000 to
3000 PPM
| CO2 PPM level to match CO2 sensor start level
STG3 DLY|
30 MIN
| ****
0 to 4.0h or OFF
| Delay for 3rd Stage Cooling – allows for 3 stages of cooling, one stage for
econ & two stages for compressor
SD DMPR POS| CLOSE| CLO or OPN| Where damper goes upon shutdown signal
DCVCAL ENA| MAN| MAN AUTO|
MAT CAL|
0°F
| +/-2.5°F
from actual reading
| Mixed Air Sensor temperature calibration
OAS CAL| 0| |
OAS H CAL| ****
0%
| +/-10% from actual reading| Outdoor Air Humidity Sensor calibration for
economizers using temp/humidity sensor
RA CAL| 0| |
DA CAL| 0°F| +/-2.5°F|
25P FAN DLY| O MIN| 0 to 20 MIN|
- SETPOINTS: From the main screen, press the SCROLL (UP/DOWN) BUTTONS to navigate through the six (6) basic menu items to the SETPOINTS menu.
- Push the SELECT (ENTER) BUTTON to choose the SETPOINTS menu.
- Navigate through the multiple levels of SETPOINTS by pushing the SCROLL (UP/DOWN) BUTTONS.
- To change a specific parameter in the SETPOINTS menu, press the SELECT (ENTER) BUTTON to display its current value. Press the SCROLL (UP/DOWN) BUTTONS to change or increase/decrease value. Press the SELECT (ENTER) BUTTON to save the new customized value—“CHANGE STORED” will be displayed. Press the SELECT (ENTER) BUTTON again to return to current menu parameter.
- For specific SETPOINTS level information, refer to TABLE 3.
TABLE 3 Bard Setpoints (As Shipped)
Parameter | Value | Range | Notes |
---|---|---|---|
**** MAT | **** 53°F | **** 38°F to 70°F | Mixed Air Temperature setpoint at |
which the economizer damper will begin to modulate to maintain setting
LOW T LOCK| 32°F| -45°F to 80°F| Low outdoor ambient temperature for
compressor lockout
DRYBLB SET| 70°F| 48°F to 80°F| Maximum outdoor temperature setting for
“free” economizer cooling
* DCV SET (See NOTE** under Table 6 on page 17)| 1100|
- 500 to
- 2000
| Displays only if a CO2 sensor is connected. Setpoint for Demand Control Ventilation of space. Above the setpoint,
the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint.
MIN POS H| 5V| 2 to 10 VDC| Minimum Position for high speed fan
MIN
POS L
| 6V| 2 to 10 VDC| Minimum Position for low speed fan
VENTMIN| 3.2V| 2 to 10 VDC| Displays only if a CO2 sensor is connected.
VENTMAX| 2.8V| 2 to 10 VDC| Displays only if a CO2 sensor is connected.
ERV OAT SP| 32°F| 0 to 50°F| For ERV only
EXH1 L SET| 60%| 0 to 100%| Damper position when exhaust
fan turns on for low speed fan
**** EXH1 H SET| 60%| 0 to 100%| Damper position when exhaust fan turns on
for high speed fan
ENTH CURVE| ES3| ES1 to ES5| Enthalpy curve boundary
-
- CO2 sensor connected
NOTE: Economizer assembly should be ready to put into service. At any point during operation, in economizer mode or idle, real-time information from sensors and integral components can be accessed from the STATUS menu.
STATUS: From the main screen, press the SCROLL (UP/DOWN) BUTTONS to navigate through the six (6) basic menu items to the STATUS menu.
- Push the SELECT (ENTER) BUTTON to choose the STATUS menu.
- Navigate through the multiple levels of STATUS by pushing the SCROLL (UP/DOWN) BUTTONS.
- As the STATUS menu simply gives input/output information in real-time, there is no way to change or otherwise alter the displayed criteria. It is simply a window into the operation of the economizer controller.
- For specific STATUS level information, refer to TABLE 4 on page 10.
NOTE : Upon power-up (or after power failure or low voltage condition), the controller will begin a 5-minute time delay before enabling mechanical cooling.
TABLE 4 Status Menu Levels
Menu Level | Default Value | Notes |
---|---|---|
ECON AVAIL | YES/NO | Indicates if conditions are favorable for economizing |
ECONOMIZING | YES/NO | Indicates if economizer is actively economizing |
OCCUPIED | YES/NO | Indicates if dedicated 24V occupied signal is being received |
on terminal OCC
HEAT PUMP| COOL/HEAT| Displays actual compressor use if in HEAT PUMP mode
COOL Y1-IN| ON/OFF| Indicates if 24V signal is being received on terminal Y1-I
COOL Y1-OUT| ON/OFF| Displays if controller is actively calling for mechanical
compressor cooling (24V on Y1-O)
COOL Y2-IN| ON/OFF| Indicates if 24V signal is being received on terminal Y2-I
COOL Y2-OUT| ON/OFF| Displays if controller is actively calling for Stg. 2
cooling (24V on Y2-O)
MA TEMP| 0° to 140°F| Current mixed air temp
OA TEMP| -40° to 140°F| Current outdoor air temp
OA HUM| 0% to 100%| Current outdoor air humidity for economizers using temp/
humidity sensor
DAMPER OUT| 2.0 to 10.0| Displays voltage to actuator
ACT POS| 0 to 100%| Current % of opening
ACT COUNT| N/A| Current count of actuator cycles from installation
ACTUATOR OK| YES/NO| Indicates potential fault
EXH1 OUT| ON/OFF| Output of EXH1 Terminal
MECH COOL ON| 0, 1, or 2| Stages of mechanical cooling currently active
NOTE: If there are any potential problems recognized by the economizer controller, it may be registered in the form of an alarm in the ALARM(S) menu. If there is a period of inactivity AND there is an alarm registering, the controller will randomly scroll through the ALARM(S) menu items as a screensaver.
ALARM(S) : from the main screen, press the SCROLL (UP/DOWN) BUTTONS to navigate through the six (6) basic menu items to the ALARM(S) menu.
- Push the SELECT (ENTER) BUTTON to choose the ALARM(S) menu.
- Navigate through the current alarms in ALARM(S) by pushing the SCROLL (UP/DOWN) BUTTONS.
- Once the alarm has been identified, and the cause has been removed (e.g., replaced faulty sensor), the alarm may erase itself. If a manual alarm-erasing is required, it can be cleared from the display by navigating to the desired alarm and pressing the SELECT (ENTER) BUTTON to choose that specific alarm. “ERASE?” will display. Press the SELECT (ENTER) BUTTON again. “ALARM ERASED” will appear. Press the MENU UP (EXIT) BUTTON to complete the action and return to the previous menu.
- For specific ALARM(S) information, refer to Table 5.
Alarm(s) | Notes |
---|---|
MA T SENS ERR | Malfunctioning mixed air sensor |
OA T SENS ERR | Malfunctioning outdoor air sensor |
ACT STALLED | Actuator cannot reach desired percentage of opening |
SYS ALARM | If AUX is set to SYS in SETPOINTS menu, SYS will display upon any |
registered alarm
| Alarm(s)| Notes
---|---
MA T SENS ERR| Malfunctioning mixed air sensor
OA T SENS ERR| Malfunctioning outdoor air sensor
ACT STALLED| Actuator cannot reach desired percentage of opening
SYS ALARM| If AUX is set to SYS in SETPOINTS menu, SYS will display upon any
registered alarm
NOTE: This is not a complete list of alarms. Additional alarms will
display depending upon the parameter settings and configuration and attached
equipment.
NOTE: When using the Bard 8403-096 CO2 controller, configure the sensor
to 2-10VDC output (see CO2 sensor instructions).
The JADE W7220 controller default setting is 1100 PPM. The economizer will
modulate to maintain this CO2 level in the room. The default setting can be
changed in the SETPOINT menu in the DCV SET option when the CO2 sensor is
connected.
- The CO2 controller is active at any time the A terminal is energized.
- The status of the CO2 input can be viewed at any time in the STATUS menu.
DVC with 2-Speed Fan
- Ventilation codes require that the same ventilation rates be provided regardless of supply fan speed. When the supply fan speed is reduced, the fresh air CFM also decreases.
- If the same outside air damper position is retained, the airflow rate through the OA damper decreases below the preset levels. To restore ventilation rates to design levels, the damper positions VENTMIN and VENTMAX must be automatically adjusted when the fan speed changes. The JADE W7220 controller provides this function when it is configured for 2-speed fan operation through a second set of damper position set points. During operation at high fan speed, the damper setpoint limits are designated VENTMIN H and VENTMAX H. During operation at low fan speed, the damper setpoint limits change to VENTMIN L and VENTMIN H. These settings are higher than the comparable high speed settings and cause the outside air damper to open more to allow the same airflow rates to be admitted to the space.
- Adjust the DCV setpoints VENTMAX H 9 volts and VENTMAX L 3.2 volts with supply fan speed in high speed and low speed respectively to provide the design load ventilation airflow rate by measuring outside air temperature, return air temperature and supply air temperature. Make damper position adjustments with at least 10°F temperature difference between the outdoor and return air temperatures.
NOTE : When using the 8403-096 CO2 sensor (or any 0-10 Vdc CO2 sensor) with the JADE W7220 controller, set the CO2ZERO to 400 ppm and CO2SPAN to 1600 ppm in the ADVANCED SETUP menu.
Enthalpy Settings
If economizer is enthalpy-based and was shipped with the temp/humidity sensor,
the economizer must be programmed for the specific enthalpy curve boundary
desired for “free” outdoor cooling (see Figure 5). The available enthalpy
boundaries are all subject to specific OA temperature, OA humidity and OA dew
points. If all of the OA conditions are below the specific points outlined in
each boundary, the conditions are good to economize and economizer mode is set
to “YES”. If some or all the OA conditions are above the specific points
outlined in each boundary, the conditions are not good to economize and the
economizer mode is set to “NO”. ES3 is factory default.
FIGURE 5 Enthalpy Curve Settings
FIGURE 6 CO2 Sensor Default and Final Settings Bard P/N 8403-096 CO2 Controller
Economizer Sequence of Operation
Condition – Cool/Dry OA Conditions
- 1st Stage Cooling closes and sends signal to JADE control. Since the air temperature outside is cooler than the preset DRYBULB SET setting, or is below the ENTH CURVE boundary in the SETPOINTS menu, the actuator will power the economizer damper to “economizer” mode as the indoor blower motor starts. The mixed air sensor senses a mixture of return air and cool outdoor air and modulates opening to achieve preset MAT SET setting in SETPOINTS menu. Compressor operation is inhibited.
- 2nd Stage Cooling closes and sends a signal to JADE control, which closes the Y1-O relay to begin mechanical cooling. The economizer damper REMAINS OPEN in tandem operation with the compressor as long as the OA conditions do not rise above the preset DRYBULB SET/ENTH CURVE settings in the SETPOINTS menu.
- 3rd Stage Cooling (if available) closes and sends a signal to JADE control, which closes the Y2-O relay to begin 2nd stage mechanical cooling. The economizer damper REMAINS OPEN in tandem operation with the compressor as long as the temperature outside does not rise above the preset DRYBULB SET setting in the SETPOINTS menu).
Condition – Warm/Humid OA Conditions
- 1st Stage Cooling closes and sends signal to JADE control. Since the OA conditions are above the preset DRYBULB SET/ENTH CURVE setting in the SETPOINTS menu, the control will simply close the Y1-O relay to initiate mechanical cooling. The economizer damper will remain closed or in a minimum ventilation setting depending upon occupied status.
- 2nd Stage Cooling (if available) closes and sends a signal to JADE control. Since the OA conditions are still above than the preset DRYBULB SET/ENTH CURVE setting in the SETPOINTS menu, the control will simply close the Y2-O relay to initiate 2nd stage mechanical cooling. The economizer damper will remain closed or in a minimum ventilation setting depending upon occupied status.
FIGURE 7 Vent Airflow Path
Service
IMPORTANT: Turn power off before performing any service to the unit.
Exhaust Damper and Actuator
The exhaust damper and actuator are located in the lower section of the unit
in the vent box (see Figure 8). To access the actuator, the vent box door must
be removed. The blower assembly can then be unplugged and removed to access
the actuator.
Intake Actuator
The intake section of the vent is located behind the control panel (see Figure
9). If the unit is installed against the wall, the intake actuator can be
accessed through a panel in the evaporator section of the unit. Unplug and
remove the unit blower from the unit. This will provide access to the panel on
the evaporator partition. Remove the panel to service the actuator.
FIGURE 8 Exhaust Damper Actuator Access
FIGURE 9 Intake Damper Actuator Access
FIGURE 10
Programmable Thermostat Connections for ECON-**5 with 2-Stage Heat Pumps
If not equipped with a ventilation option to plug in, a jumper plug must be installed.
- Factory installed jumper. Remove jumper and connect to N.C fire alarm circuit if emergency shutdown required.
- Wire not needed below 15KW.
- Wire required for dehumidification models only.
- Do not connect “A” from thermostat if optional CO2 controller is used 5
- 0-10 VDC modulating C02 control signal for modulating ventilation control (optional for ECON only – see vent instruction manuals)
- Ensure model configuration is heat pump and not heat/cool. Must be configured to programmable and fan set to be programmed fan for the “” output to function during scheduled occupied I periods. Must be configured for multi-stage for Y1 output to be active 1st stage cooling. For dehumidification, must be configured for “No Economizer” for YO/D to be active for humidity control.
- Do not add these wires if setting up for modulating control.
**Unit Operation| ****Occ. Signal| ****Econ
Available| Low Voltage 24VAC| ****Fan Speed|
****Dampers
---|---|---|---|---|---
G| Y1| Y2| W1| W2| W3| A*
Blower Only| Yes| No| X| | | | | | X| Vent| Min. Pos. Low
Blower Only| Yes| Yes| X| | | | | | X| Vent| Min. Pos. Low
Blower Only| No| No| X| | | | | | | Vent| Closed
Part Load Cool| Yes| No| X| X| | | | | X| Part Load| Min. Pos. Low
Part Load Cool| Yes| Yes| X| X| | | | | X| Part Load| Open
Part Load Cool| No| No| X| X| | | | | | Part Load| Closed
Part Load Cool| No| Yes| X| X| | | | | | Part Load| Open
Full Load Cool| Yes| No| X| X| X| | | | X| Full Load| Min. Pos. High
Full Load Cool| Yes| Yes| X| X| X| | | | X| Full Load| Open
Full Load Cool| No| No| X| X| X| | | | | Full Load| Closed
Full Load Cool| No| Yes| X| X| X| | | | | Full Load| Open*
1st Stage Heat| Yes| No| X| X| | X| | | X| Part Load| Min. Pos. Low
1st Stage Heat| No| No| X| X| | X| | | | Part Load| Closed
2nd Stage Heat| Yes| No| X| X| X| X| | | X| Full Load| Min. Pos. High
2nd Stage Heat| No| No| X| X| X| X| | | | Full Load| Closed
2nd Stage Heat and EH| Yes| No| X| X| X| X| X| | X| Full Load| Min. Pos. High
2nd Stage Heat and EH| No| No| X| X| X| X| X| | | Full Load| Closed
Emergency EH| Yes| No| X| | | | X| X| X| Full Load| Min. Pos. Low
Emergency EH| No| No| X| | | | X| X| | Full Load| Closed
2-Stage Compressor Units – Economizer Operation – Part and Full Load Operation
GRAPH 1 I36Z2 Ventilation Delivery
GRAPH 2 I42Z2 Ventilation Delivery
GRAPH 3 I48Z2 Ventilation Delivery
GRAPH 4 I60Z2 Ventilation Delivery
Default Tables
TABLE 7A Menu Structure
Menu| Parameter| Parameter Default Value|
Parameter Range and Increment| Notes
---|---|---|---|---
STATUS| ECON AVAIL| NO| YES/NO| YES = economizing available; the system can
use outdoor air for free cooling when required.
ECONOMIZING| NO| YES/NO| YES = Outdoor air being used for 1st stage cooling.
OCCUPIED| NO| YES/NO| YES = OCC signal received from space thermostat or
unitary controller. YES = 24 Vac on terminal OCC No = 0 Vac on terminal OCC.
HEAT PUMP| N/A| COOL HEAT| Displays COOL or HEAT when system is set to heat
pump (non- conventional).
COOL Y1-IN| OFF| ON/OFF| Y1-I signal from space thermostat or unitary
controller for cooling stage 1. ON = 24 Vac on term Y1-I; OFF = 0 Vac on term
Y1-I
COOL Y1-OUT| OFF| ON/OFF| Cool Stage 1 Relay Output to mechanical cooling
(Y1-OUT terminal).
COOL Y2-IN| OFF| ON/OFF| Y2-I signal from space thermostat or unitary
controller for second stage cooling. ON = 24 Vac on term Y2-I; OFF = 0 Vac on
term Y2-I
COOL Y2-OUT| OFF| ON/OFF| Cool Stage 2 Relay Output to mechanical cooling
(Y2-OUT terminal).
MA TEMP| . ºF| -40 to 150 ºF| Displays value of measured mixed air from
MAT sensor. Displays –.-°F if not connected, short or out- of-range.
DA TEMP| . ºF| -40 to 150 ºF| Displays when Discharge Air Silk Bus sensor
is connected and displays measured discharge air temperature. Displays –.-°F
if sensor sends invalid value, if not connected, short or out-of-range.
OA TEMP| . ºF| -40 to 140 ºF| Displays measured value of outdoor air
temperature. Displays –.-°F if sensor sends invalid value, if not connected,
short or out-of-range.
OA HUM| %| 0 to 100%| Displays measured value of outdoor humidity from OA
Syllabus sensor. Displays –% if not connected, short or out- of-range.
RA TEMP| . ºF| 0 to 140 ºF| Displays measured value of return air
temperature from RA Syllabus sensor. Displays –.-°F if sensor sends invalid
value, if not connected, short or out-of-range.
RA HUM| %| 0 to 100%| Displays measured value of return air humidity from
RA Syllabus sensor. Displays –% if sensor sends invalid value, if not
connected, short or out-of-range.
IN CO2| _ ppm| “0 to 2000 ppm”| Displays value of measured CO2 from CO2
sensor. Invalid if not connected, short or out-of-range. May be adjusted in
Advanced menu by Zero offset and Span.
DCV STATUS| N/A| ON/OFF| Displays ON if above setpoint and OFF if below
setpoint, and ONLY if a CO2 sensor is connected.
DAMPER OUT| 2.0V| 2.0 to 10.0 V| Displays output voltage or position to the
damper actuator.
ACT POS| N/A| 0 to 100%| Displays actual position of actuator.
ACT COUNT| N/A| 1 to 65,535| Displays number of times actuator has cycled. 1
cycle equals the sum of 180° of movement in any direction.
N/A = Not Applicable
- Table 7 illustrates the complete hierarchy. Actual menu parameters may be different depending on the configuration. For example, if there is no DCV (CO2) sensor, then none of the DCV parameters appear.
- When values are displayed, pressing and holding the or button causes the display to automatically increment.
- When used with Honeywell communicating actuator, the damper out is reported in XX.X% open versus XX.X Vdc
TABLE 7B Menu Structure (cont.)
**Menu| ****Parameter| Parameter Default Value| Parameter Range and Increment| **
Notes
---|---|---|---|---
STATUS
(cont.)
| ACTUATOR| N/A| OK/Alarm (on Alarm menu)| Displays Error if voltage or torque
is below actuator range.
EXH1 OUT| OFF| ON/OFF| Output of EXH1 terminal. Displays ON when damper
position reaches programmed percentage setpoint. ON = 24 Vac Output; OFF = No
Output.
EXH2 OUT| OFF| ON/OFF| Output of AUX1 O terminal. Displays
ON when damper position reaches programmed percentage setpoint. ON = 24 Vac
Output; OFF = No Output. Displays only if AUX1 O = EXH2
ERV| OFF| ****
ON/OFF
| Output of AUX1 O terminal. ON = 24 Vac Output; OFF = No Output. Displays
only if AUX1 O = ERV
MECH COOL ON or
HEAT STAGES ON
| 0| 0, 1 or 2| Displays number of mechanical cooling stages that are active.
**** Displays the stage of heat pump heating that is active.
FAN SPEED| N/A| LOW or HIGH| Displays speed of fan on a 2-speed fan unit.
W (HEAT IN)| N/A| ON/OFF| Displays status of heat on a 2-speed fan unit.
SETPOINTS| MAT SET| 53ºF| 38 to 70 ºF; increment by 1| The economizer will
modulate the OA damper to maintain the mixed air temperature at the setpoint.
LOW T LOCK| 32ºF| -45 to 80 ºF increment by 1| Setpoint determines outdoor
temperature when the mechanical cooling cannot be turned on. Commonly referred
to as the compressor lockout. At or below the setpoint, the Y1-O and Y2-O will
not be energized on the controller.
DRYBLB SET| 63ºF| -45 to 80 ºF increment by 1| Dry bulb setpoint will only
appear if using dry bulb change over. Setpoint determines where the
economizer will assume outdoor air temperature is good for free cooling; e.g.,
at 63 ºF setpoint unit will economizer at 62 ºF and below and not economize at
64 ºF and above. There is a 2 ºF dead band.
DRYBLB DIF
Available firmware 1.15, June 2018, and later.
| 0ºF| 0 to 6ºF; increment by 2| Dry bulb differential will only show if using
dual dry bulb, i.e., when an outdoor air temperature sensor C7250 is attached
to OAT terminals and a C7400S sensor is wired to S-Bus and configured for RAT
(return air). Free cooling will be assumed whenever OA Temp is below RAT minus
this dry bulb differential setting .
ENTH CURVE| ES3| ES1, ES2, ES3, ES4 or ES5| ES curve will only appear if using
enthalpy changeover. Enthalpy boundary “curves” for economizing using single
enthalpy. See page 11 for description of enthalpy curves.
DCV SET| 1100ppm| 500 to 2000 ppm; increment by 100| Displays ONLY if a CO2
sensor is connected. Setpoint for Demand Control Ventilation of space. Above
the setpoint, the OA dampers will modulate open to bring in additional OA to
maintain a space ppm level below the setpoint.
MIN POS| 2.8 V| 2 to 10| Displays ONLY if a CO2 sensor is NOT connected. With
2-speed fan units, MIN POS L (low speed fan) and MIN POS H (high speed fan)
settings are required. Default for MIN POS L is 3.2V and MIN POS H is 2.8V.
N/A = Not Applicable
- Table 7 illustrates the complete hierarchy. Actual menu parameters may be different depending on the configuration. For example, if there is no DCV (CO2) sensor, then none of the DCV parameters appear.
- When values are displayed, pressing and holding the or button causes the display to automatically increment
**Menu| ****Parameter| Parameter Default Value|
Parameter Range and Increment| ****Notes**
---|---|---|---|---
SETPOINTS
(cont.)
| VENTMAX| 2.8 V| 2 to 10 Vdc| Displays only if a CO2 sensor is connected.
Used for Vbz (ventilation max cfm) setpoint. VENTMAX is the same setting as
MIN POS would be if there is no CO2 sensor.
100 to 9990 cfm; increment by 10| If OA, MA RA and CO2 sensors are connected
and DCV CAL ENABLE is set to AUTO mode, the OA dampers are controlled by CFM
and displays from 100 to 9990 cfm.
2 to 10 Vdc| With 2-speed fan units, VENTMAX L (low speed fan) and VENTMAX H
(high speed fan) settings are required. Default for VENTMAX L is 3.2V and
VENTMAX H is 2.8V.
VENTMIN| 2.25 V| 2 to 10 Vdc| Displays only if CO2 sensor is connected. Used
for Va (ventilation min cfm) setpoint. This is the ventilation requirement for
less than maximum occupancy of the space.
100 to 9990 cfm; increment by 10| If OA, MA RA and CO2 sensors are connected
and DCV CAL ENABLE is set to AUTO mode, the OA dampers are controlled by CFM
and displays from 100 to 9990 cfm.
2 to 10 Vdc| With 2-speed fan units, VENTMIN L (low speed fan) and VENTMIN H
(high speed fan) settings are required. Default for VENTMIN L is 2.5V and
VENTMIN H is 2.25V.
ERV OAT SP| 32ºF| 0 to 50 ºF; increment by 1| Only when AUX1 O = ERV
EXH1 SET| 50%| 0 to 100%;
increment by 1
| Setpoint for OA damper position when exhaust fan 1 is powered by the
economizer. With 2-speed fan units, Exh1 L (low speed fan) and Exh1 H (high
speed fan) settings are required. Default for Exh1 L is 65% and Exh1 H is 50%.
EXH2 SET| 75%| 0 to 100%; increment by 1| Setpoint for OA damper position when
exhaust fan 2 is powered by the economizer. Only used when AUX1 O is set to
EHX2. With 2-speed fan units, Exh2 L (low speed fan) and Exh2 H (high speed
fan) settings are required. Default for Exh2 L is 80% and Exh2 H is 75%.
SYSTEM SETUP| INSTALL| 01/01/11| | Display order = MM/DD/YY Setting order =
DD, MM, then YY.
UNITS DEG| ºF| ºF or ºC| Sets economizer controller in degrees Fahrenheit or
Celsius.
EQUIPMENT| CONV| CONV HP| CONV = conventional. HP O/B = Enables Heat Pump
mode. Use AUX2 I for heat pump input from thermostat or controller.
AUX2 IN| Heat (W1)
NOTE : If field factory default is available, AUX2 IN will default back
to Shutdown (SD).| 0 to 6ºF; increment by 2|
- In CONV mode
- SD = Enables configuration of shutdown (default)
- W = Informs controller that system is in heating mode
NOTE: If using 2-speed fan mode, CONV mode must be programmed for W. Shutdown is not available in the two-speed fan mode. In HP O/B mode: HP(O) = energize heat pump on Cool (default) HP(B) = energize heat pump on Heat
- Table 7 illustrates the complete hierarchy. Actual menu parameters may be different depending on the configuration. For example, if there is no DCV (CO2) sensor, then none of the DCV parameters appear.
- When values are displayed, pressing and holding the or button causes the display to automatically increment.
- ERV Operation: When in cooling mode AND the conditions are NOT OK for economizing, the ERV terminal will be energized. In the heating mode, the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
- Default for AUX2 IN changed from SD to W1 with 1.15 firmware (June 2018).
**Menu| ****Parameter| Parameter Default Value|
Parameter Range and Increment| ****Notes
---|---|---|---|---
SYSTEM SETUP (cont.)| FAN SPEED| 2 speed
NOTE:** If field factory default is available, FAN SPEED will default back
to 1 speed.|
- 1 speed/
- 2 speed
| Sets economizer controller for operation of 1 speed or 2 speed supply fan. The controller does not control the fan but positions the OA and RA dampers to the heating or cooling mode. See Figure 2 on page 7 for modes and position.
NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In.
| FAN CFM| 5000 cfm| 100 to 50000 cfm; increment by 100| This is the capacity
of the RTU. The value is found on the label from the RTU manufacturer. The cfm
of the fan is only used with DCV CAL ENABLE AUO.
| AUX1 OUT| NONE| NONE ERV EXH2 SYS|
- NONE = not configured (output is not used
- ERV = Energy Recovery Ventilator
- EXH2 = second damper position 24 Vac out for second exhaust fan
- SYS = use output as an alarm signal
| OCC| INPUT| INPUT or ALWAYS| When using a setback thermostat with occupancy
out (24 Vac), the 24 Vac is input “INPUT” to the OCC terminal. If no occupancy
output from the thermostat then change program to “ALWAYS” OR add a jumper
from terminal R to OCC terminal.
| FACTORY DEFAULT| NO| NO or YES| Resets all set points to factory defaults
when set to YES. LCD will briefly flash YES and change to NO but all
parameters will change to factory default values.
ADVANCED SETUP| MA LO SET| 45 ºF| 35 to 65 ºF; increment by 1| Temp to
activate freeze protection (close damper or modulate to MIN POS if temp falls
below set value).
FREEZE POS| CLO| CLO MIN| Damper position when freeze protection is active
(closed or MIN POS).
CO2 ZERO| 0 ppm| 0 to 500 ppm; increment by 10| CO2 ppm level to match CO2
sensor start level.
CO2 SPAN| 2000 ppm| 1000 to 3000 ppm; increment by 50| CO2 ppm span to match
CO2 sensor; e.g.; 500-1500 sensor output would be 500 CO2 zero and 1000 CO2
span.
STG3 DLY| 2.0h| 0 min, 5 min,15 min, then 15 min intervals. Up to 4h or OFF.|
Delay after stage 2 for cool has been active. Turns on 2nd stage of mechanical
cooling when economizer is 1st stage call and mechanical cooling is 2nd stage
call.
Allows three stages of cooling: 1 economizer and 2 mechanical. OFF = no
Stage 3 cooling.
SD DMPR POS| CLO| CLO OPN| Indicates shutdown signal from space thermostat or
unitary controller. When controller receives 24 Vac input on the SD terminal
in conventional mode, the OA damper will open if programmed for OPN and OA
damper will close if programmed for CLO. All other controls, e.g., Y1-O, Y2-O,
EXH1, etc. will shut off.
DA LO ALM| 45 ºF| NONE 35 ºF to 65 ºF in 5 ºF increments| Used for alarm for
when the DA air temperature is too low. Set lower range of alarm, below this
temperature the alarm will show on the display.
- Table 7 illustrates the complete hierarchy. Actual menu parameters may be different depending on the configuration. For example, if there is no DCV (CO2) sensor, then none of the DCV parameters appear.
- When values are displayed, pressing and holding the or button causes the display to automatically increment.
- Default for FAN SPEED changed from 1-speed to 2-speed with 1.15 firmware (June 2018).
- ERV Operation: When in cooling mode AND the conditions are NOT OK for economizing, the ERV terminal will be energized. In the heating mode, the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
**Menu| ****Parameter| Parameter Default Value|
Parameter Range and Increment| ****Notes
---|---|---|---|---
ADVANCED SETUP (cont.)| DA HI ALM| 80 ºF| NONE 70 ºF to 180 ºF in 5 ºF
increments| Used for alarm for when the DA air temperature is too high. Set
high range of alarm; above this temperature the alarm will show on the
display.
DCVCAL ENA| MAN| MAN (manual) AUTO| Turns on the DCV automatic control of the
dampers. Resets ventilation based on the RA, OA and MA sensor conditions.
Requires all sensors (RA, OA, MA and CO2). This operation is not operable with
a 2-speed fan unit.
MAT T CAL| 0.0 F°| +/- 2.5 F°| Allows for the operator to adjust for an out-
of-calibration temperature sensor.
OAS T CAL| 0.0 F°| +/- 2.5 F°| Allows for the operator to adjust for an out-
of-calibration temperature sensor.
OAS H CAL| 0% RH| +/- 10% RH| Allows for the operator to adjust for an out-of-
calibration humidity sensor.
RA T CAL| 0.0 F°| +/- 2.5 F°| Allows for the operator to adjust for an out-of-
calibration temperature sensor.
RA H CAL| 0% RH| +/- 10% RH| Allows for the operator to adjust for an out-of-
calibration humidity sensor.
DA T CAL| 0.0 F°| +/- 2.5 F°| Allows for the operator to adjust for an out-of-
calibration temperature sensor.
2SP FAN DELAY| 5 Minutes| 0 to 20 minutes in 1 minute increments| When in
economizing mode, this is the delay for the high speed fan to try to satisfy
the call for second stage cooling before the first stage mechanical cooling is
enabled.
CHECKOUT| DAMPER MINIMUM POSITION| N/A| N/A| The checkout for the damper
minimum positions is based on the system. See Table 8 on page 27.
DAMPER OPEN| N/A| N/A| Positions damper to the full open position. Exhaust fan
contacts enable during the DAMPER OPEN test. Make sure to pause in this mode
to allow for exhaust contacts to energize due to the delay in the system.
DAMPER CLOSE| N/A| N/A| Positions damper to the fully closed position.
CONNECT Y1-O| N/A| N/A| Closes the Y1-O relay (Y1-O). „
CONNECT Y2-O| N/A| N/A| Closes the Y2-O relay (Y2-O). „
CONNECT AUX1-O| N/A| N/A| Energizes the AUX1-O output.
If AUX1-O setting is:**
- NONE – no action taken.
- ERV – 24 Vac out. Turns on or signals an ERV that the conditions are not good for economizing but are good for ERV operation.
- SYS – 24 Vac out. Issues a system alarm.
CONNECT EXH1| N/A| N/A| Closes the power exhaust fan 1 relay (EXH1)
N/A = Not Applicable
- Table 7 illustrates the complete hierarchy. Actual menu parameters may be different depending on the configuration. For example, if there is no DCV (CO2) sensor, then none of the DCV parameters appear.
- When values are displayed, pressing and holding the or button causes the display to automatically increment.
- After 10 minutes without a command or mode change, the controller will change to normal operation.
- Be sure to allow enough time for compressor startup and shutdown between checkout tests so that the compressors are not short cycled.
- ERV Operation: When in cooling mode AND the conditions are NOT OK for economizing, the ERV terminal will be energized. In the heating mode, the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
TABLE 7F Menu Structure (cont.)
**Menu| ****Parameter| Parameter Default Value|
Parameter Range and Increment| ****Notes**
---|---|---|---|---
ALARMS(#)| | | | Alarms display only when they are active. The menu title
“ALARMS (#)” includes the number of active alarms in parenthesis (). When
using SYLK bus sensors, “SYLK” will appear on the screen, and when using 20k
OA temperature sensors, “SENS T” will appear on the screen.
MA T SENS ERR| N/A| N/A| Mixed air sensor has failed or become disconnected.
Check wiring then replace sensor if the alarm continues.
CO2 SENS ERR| N/A| N/A| CO2 sensor has failed, gone out of range or become
disconnected. Check wiring then replace sensor if the alarm continues.
OA SYLK T ERR| N/A| N/A| Outdoor air enthalpy sensor has failed or become
disconnected. Check wiring then replace sensor if the alarm continues.
OA SYLK H ERR| N/A| N/A
RA SYLK T ERR| N/A| N/A| Return air enthalpy sensor has failed or become
disconnected. Check wiring then replace sensor if the alarm continues.
RA SYLK H ERR| N/A| N/A
DA SYLK T ERR| N/A| N/A| Discharge air sensor has failed or become
disconnected. Check wiring then replace sensor if the alarm continues.
OA SENS T ERR| N/A| N/A| Outdoor air temperature sensor has failed or become
disconnected. Check wiring then replace sensor if the alarm continues.
ACT ERROR| N/A| N/A| Actuator has failed or become disconnected. Check for
stall, over voltage, under voltage and actuator count. Replace actuator if
damper is moveable and supply voltage is between 21.6 V and 26.4 V. Check
actuator count on STATUS menu.
FREEZE ALARM| N/A| N/A| Check if outdoor temperature is below the LOW Temp
Lockout on setpoint menu. Check if mixed air temperature on STATUS menu is
below the Lo Setpoint on Advanced setup menu. When conditions are back in
normal range then the alarm will go away.
SHUTDOWN ACTIVE| N/A| N/A| AUX2 IN is programmed for SHUTDOWN and 24 V has
been applied to AUX 2 IN terminal
DMP CAL RUNNING| N/A| N/A| If DCV Auto enable has been programmed, when the
JADE is completing a calibration on the dampers, this alarm will display. Wait
until the calibration is completed and the alarm will go away. Must have OA,
MA and RA sensors for DCV calibration; set up is in the Advanced setup menu.
DA SENS ALM| N/A| N/A| Discharge air temperature is out of the range set in
the ADVANCED SETUP Menu. Check the temperature of the discharge air.
SYS ALARM| N/A| N/A| When AUX1-O is set to SYS and there is any alarm (e.g.,
failed sensors, etc.), the AUX1-O terminal has 24 Vac out.
ACT UNDER V| N/A| N/A| Voltage received by actuator is above expected range.
ACT OVER V| N/A| N/A| Voltage received by actuator is below expected range.
ACT STALLED| N/A| N/A| Actuator stopped before achieving commanded position.
N/A = Not Applicable
- Table 7 illustrates the complete hierarchy. Actual menu parameters may be different depending on the configuration. For example, if there is no DCV (CO2) sensor, then none of the DCV parameters appear.
- When values are displayed, pressing and holding the or button causes the display to automatically increment.
TABLE 7G Menu Structure (cont.)
**Menu| ****Parameter| Parameter Default Value|
Parameter Range and Increment| ****Notes
---|---|---|---|---
Features Adjustable Only by Use of the W7220 PC MOD Tool**
| ACT STALL ALARM SUPPRESSION| Disabled| Enabled or Disabled| If enabled,
this feature allows the operator to suppress the stall alarm in a specific
range of the actuator stroke.
SELECT TYPE OF CONTROLLER| W7220| “W7220, W7218 or Pre- programmed special”|
The operator can configure a program for a customer or job and save the
program in the file. Found on the configuration page of the Trade version.
ACTUATOR SLIPPAGE ALARM| Enabled| Enabled or Disabled|
- Alarms if the actuator becomes disconnected from the damper or is slipping on the shaft.
- If Enabled, the JADE system will complete a system air temperature check.
- If there is the expected change in system air temperature, then JADE assumes the actuator is connected to the damper.
- If the expected system air temperature changes do not occur, then an actuator slippage alarm is displayed on the JADE LCD. Found on the configuration page of the Trade version.
ACTUATOR SLIPPAGE ALARM SENSITIVITY| Low| Low, Standard or High| Sensitivity
can be set to HIGH, STANDARD or LOW. High means the system will check 5 times
for the damper to move before displaying the alarm. Standard is 10 times
before the alarm is displayed. Low is 20 times before the alarm is displayed.
Found on the economizer page of the Trade version.
LOCATION OF ECONOMIZER CONTROL SENSOR| Before the cooling coil| Before coil or
AUTO| The operator can choose if the economizer control sensor (normally
referred to as the mixed air sensor) is placed in the mixed air (before the
coil) or Auto in the case the sensor is placed after the cooling coil. Found
on the configuration page of the Trade version.
DAMPER AIA THRESHOLD| 15 degrees| 5 to 40 degrees| Damper threshold feature
(Adaptive Integral Action) is the difference in the mixed air temperature
reported by the MAT sensor and the MAT setpoint. Lower (2 degrees) transfer
rate between the actual MAT sensor reading and the MAT setpoint normally means
the damper is closing and opening faster. Larger transfer rate (up to 20
degrees) between the sensor reading and the setpoint normally means the damper
is opening and closing slower. Used in applications where there is a large MA
space or there is a long duct between the OA and the MA causing a delay. Found
on the economizer page of the Trade version.
- Table 7 illustrates the complete hierarchy. Actual menu parameters may be different depending on the configuration. For example, if there is no DCV (CO2) sensor, then none of the DCV parameters appear.
- When values are displayed, pressing and holding the or button causes the display to automatically increment.
TABLE 8 Damper Minimum Position Settings and Readings on Checkout Menu
Fan Speed| Demand **Control ****Ventilation
****(CO 2 Sensor)| Setpoints| Checkout**
---|---|---|---
1| NO| MIN POS| VMAX-HS
1| NO| N/A| N/A
2| NO| MIN POS H| VMAX-HS
2| NO| MIN POS L| VMAX-LS
1| YES| VENT MIN| VMAX-HS
1| YES| VENT MAX| VMAX-LS
2| YES| VENT MIN H| VMAX-HS
2| YES| VENT MAX H| VMAX-LS
2| YES| VENT MIN L| N/A
2| YES| VENT MAX L| N/A
TABLE 9 Dry Bulb Operation No DCV (CO2 Sensor) – 2 Speed Fan
DCV| OA Good to economize?| Y1- I| Y2- I| FAN
SPD| Y1- O| Y2- O| Occupied| Unoccupied
---|---|---|---|---|---|---|---|---
None| No| Off| Off| Low| 0-v/Off| 0-v/Off| MIN POS L| Closed
On| Off| Low| 24-v/On| 0-v/Off| MIN POS L| Closed
On| On| High| 24-v/On| 24-v/On| MIN POS H| Closed
None| Yes| Off| Off| Low| 0-v/Off| 0-v/Off| MIN POS L| Closed
On| Off| Low| 0-v/Off| 0-v/Off| MIN POS L to Full- Open| Closed to Full- Open
On| On| High| DELAY 24-v/On| 0-v/Off| MIN POS H to Full- Open| Closed to
Full- Open
- With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode, there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
- With stage 3 delay (STG3 DLY) in Advanced setup menu, can turn on 2nd stage of mechanical cooling Y2–O after the delay if the call for Y1-I and Y2-I have not been satisfied.
TABLE 10 Dry Bulb Operation with DCV (CO 2 Sensor) – 2 Speed Fan
DCV| OA Good to economize?| Y1- I| Y2- I| FAN
SPD| Y1- O| Y2- O| Occupied| Unoccupied
---|---|---|---|---|---|---|---|---
Below Set| No| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L| Closed
On| Off| Low| 24-v/On| 0-v/Off| VENTMIN L| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN H| Closed
Yes| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L| Closed
On| Off| Low| 0-v/Off| 0-v/Off| “VENTMIN L to Full-Open”| Closed to Full- Open
On| On| High| 24-v/On| 0-v/Off| “VENTMIN H to Full-Open”| Closed to Full- Open
Above Set| No| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| Off| Low| 24-v/On| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN H to VENTMAX| Closed
Yes| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| Off| Low| 0-v/Off| 0-v/Off| “VENTMIN L to Full-Open”| Closed to Full- Open
On| On| High| DELAY 24-v/On| 0-v/Off| “VENTMIN H to Full-Open”| Closed to
Full- Open
- With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode, there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
- With stage 3 delay (STG3 DLY) in Advanced setup menu, can turn on 2nd stage of mechanical cooling Y2–O after the delay if the call for Y1-I and Y2-I have not been satisfied.
TABLE 11 Enthalpy Operation No DCV (CO2 Sensor) – 2 Speed Fan
DCV| OA Good to economize?| Y1- I| Y2- I| FAN
SPD| Y1- O| Y2- O| Occupied| Unoccupied
---|---|---|---|---|---|---|---|---
NO CO2 SENSOR| No| Off| Off| Low| 0-v/Off| 0-v/Off| MIN POS L| Closed
On| Off| Low| 24-v/On| 0-v/Off| MIN POS L| Closed
On| On| High| 24-v/On| 24-v/On| MIN POS H| Closed
Yes| Off| Off| Low| 0-v/Off| 0-v/Off| MIN POS L| Closed
On| Off| Low| 0-v/Off| 0-v/Off| MIN POS L to Full- Open| Closed to Full- Open
On| On| High| DELAY 24-v/On| 0-v/Off| MIN POS H to Full- Open| Closed to
Full- Open
- With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode, there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
- With stage 3 delay (STG3 DLY) in Advanced setup menu, can turn on 2nd stage of mechanical cooling Y2–O after the delay if the call for Y1-I and Y2-I have not been satisfied
TABLE 12 Enthalpy Operation with DCV (CO 2 Sensor) – 2 Speed Fan
DCV| OA Good to economize?| Y1- I| Y2- I| FAN
SPD| Y1- O| Y2- O| Occupied| Unoccupied
---|---|---|---|---|---|---|---|---
Below Set| No| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L| Closed
On| Off| Low| 24-v/On| 0-v/Off| VENTMIN L| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN H| Closed
Yes| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L| Closed
On| Off| Low| 0-v/Off| 0-v/Off| “VENTMIN L to Full-Open”| Closed to Full- Open
On| On| High| 24-v/On| 0-v/Off| “VENTMIN H to Full-Open”| Closed to Full- Open
Above Set| No| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| Off| Low| 24-v/On| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| On| High| 24-v/On| 24-v/On| VENTMIN H to VENTMAX| Closed
Yes| Off| Off| Low| 0-v/Off| 0-v/Off| VENTMIN L to VENTMAX| Closed
On| Off| Low| 0-v/Off| 0-v/Off| “VENTMIN L to Full-Open”| Closed to Full- Open
On| On| High| DELAY 24-v/On| 0-v/Off| “VENTMIN H to Full-Open”| Closed to
Full- Open
- With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode, there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
- With stage 3 delay (STG3 DLY) in Advanced setup menu, can turn on 2nd stage of mechanical cooling Y2–O after the delay if the call for Y1-I and Y2-I have not been satisfied.