FiDO2 Fire Damper Opener HVAC Jack Instruction Manual

June 14, 2024
fido

FiDO2 Fire Damper Opener HVAC Jack Instruction Manual

Instructions

  • Turn clockwise with ratchet, right-angle electric drill, or impact driver with ratchet bit.
  • Raise FiDO jaws completely to relieve pressure off of the fire link.
  • Do NOT overextend FiDO jaws (see other side for more information).
  • Remove fire link, then lower FiDO jaws down to “exercise” fire damper.
  • Slowly raise FiDO jaws back up, adjusting position to keep access to link clear.
  • Reinstall or replace fire link.
  • Lower FiDO jaws and remove FiDO from the duct through the access door.

Helpful Hints

  • Keep fingers and hands out of fire damper blades’ path except when jaws are completely raised and fire link is being removed/replaced.
  • Keep bottom jaw ends “hooked” over far bottom lip of fire damper.
  • On vertical ducts, be sure to attach FiDO with lanyard to avoid dropping down the duct.
  • As needed, re-apply rubber coating or adhesive tape on tips of FiDO jaws.

IMPORTANT! Do Not Overextend!

  • Stop raising the jaws when they are open as much as possible (when the linkage is completely vertical).
  • If you attempt to continue opening them further, they will actually begin to close instead.
  • Be sure that your tool is operating in reverse when lowering the jaws to avoid driving it further than intended.
  • When overextended, the FiDO will be difficult to reverse for true closure and may be damaged.
  • Warranty replacements will not be provided for units where it is evident that the FiDO has been overextended.

Scan by QR Code

Documents / Resources

| FiDO FiDO2 Fire Damper Opener HVAC Jack [pdf] Instruction Manual
FiDO2 Fire Damper Opener HVAC Jack, FiDO2, Fire Damper Opener HVAC Jack, Opener HVAC Jack, HVAC Jack, Jack
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals