Danfoss AVPL-F Pressure Control Valve User Guide

June 4, 2024
Danfoss

AVPL-F Pressure Control Valve
User Guide

Danfoss AVPL-F Pressure Control Valve

AVPL-F Pressure Control Valve

Danfoss AVPL-F Pressure Control Valve - Fig 1Danfoss AVPL-F Pressure Control Valve - Fig
2

DN| L1(mm)| L2 (mm)| L3 (mm)| H1 (mm)| H2 (mm)| a
ISO 228/1| b ISO 7/1| Weight (kg)
---|---|---|---|---|---|---|---|---
AVPL 15 (kvs 1.0)| 65| 120| 139| 104| –| G ¾ A| R ½| 0.64
AVPL 15 (kvs 1.6)| 0.69
AVPL 15 (kvs 2.5)| 105| 0.7
AVPL-F 15 (kvs 2.5)| 65| 120| 139| –| 63| G ¾ A| R ½| 0.63

Safety Notes

Prior to assembly and commissioning to avoid injury to persons and damage to the devices, it is absolutely necessary to carefully read and observe these instructions.
Necessary assembly, start-up, and maintenance work must be performed only by qualified, trained, and authorized personnel.
Prior to assembly and maintenance work on the controller, the system must be:

  • depressurized,
  • cooled down,
  • emptied and
  • cleaned.

Please comply with the instructions of the system manufacturer or system operator.

Definition of Application
AVPL(-F) is a self-acting differential pressure controller for PN 16 with adjustable or fixed differential pressure settings. The controller is supplied with an impulse tube, O-ring gasket, and tail-piece socket for pressure connection (fig. ❶).
The technical parameters on the product labels determine the use.
Assembly
Admissible Installation Positions ❷
– The controller can be installed in any position.

Installation:

The control valve body must be installed in the heating system and return with flow in the direction of the arrow (fig. ❹). The valve can be installed in any orientation position. The Danfoss strainer type FV or similar must be installed in the direction of the flow (fig. ❹) in front of the controller. The impulse tube must be mounted horizontally on the pipe to prevent impurities from flowing into the impulse tube. ❺

Starting up:

Filling the system, the first start-up

  1. Slowly open shut-off devices in the flow pipeline.
  2. Slowly open shut-off devices in the return pipeline.

Putting out of operation

  1. Slowly close shut-off devices in the flow pipeline.
  2. Slowly close shut-off devices in the return pipeline.

Setting:
(not relevant at fixed setting version AVPL-F)
The differential pressure can be set by means of an Allen key NV 3 (fig. ❻).
On delivery, the controller is set to 10 kPa (0.1 bar). 1 turn corresponds with 1 kPa (0.01 bar). The arrow on the controller top shows that the setting of the differential pressure is increased when it is turned clockwise.
Note that the stop is reached after 20 turns.
Seal: ❼
The set-point adjuster can be sealed by a seal wire, if necessary.
Fault location:
If the controller does not operate properly check whether:

  • the valve body is mounted correctly (arrow points in flow direction)
  • impulse tube is mounted correctly
  • impulse tube connection is blocked

Pressure testing:
Impulse tube and needle valves, if any, must be open during pressure testing.
Max. test pressure PN 16 …… 25 bar.

Danfoss A/S
Climate Solutions
danfoss.com
+45 7488 2222
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity, or any other technical data in product manuals, catalogs descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogs, brochures, videos, and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to the form, fit, or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

© Danfoss
DCS-SGDPT/SI
2022.09
73695140
AQ00008644555102-010202
www.danfoss.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals