victron energy M8 Lynx Distributor User Guide
- June 15, 2024
- victron energy
Table of Contents
Lynx Distributor M8 and M10
rev 01 – 10/2023
Safety Precautions
1.1. Safety Warnings Lynx Distribution System
- **** Do not work on live busbars. Ensure that the busbar is unpowered by disconnecting all positive battery poles prior to removing the Lynx front cover.
- Work on batteries should be carried out by qualified personnel only. Observe the battery safety warnings as listed in the battery manual.
1.2. Transport and Storage
Store this product in a dry environment.
The storage temperature should be: -40°C to +65°C.
No liability can be accepted for damage in transit if the equipment is not
transported in its original packaging.
Introduction
2.1. The Lynx Distributor
The Lynx Distributor contains a positive and a negative busbar. The positive
busbar has four fuse-protected connections with fuse monitoring. The negative
busbar has four connections and a ground connection. It is part of the Lynx
Distribution system and is available in two versions, with M8 or M10 busbar.
Note that M10 refers to the busbar connection joints where the modules are
connected to each other. The fuse and cable connections are always M8.
The Lynx Distributor has a power LED and four fuse status indication LEDs.
If connected to a Lynx Smart BMS, up to 4 Lynx Distributors can send fuse
status information to the Lynx Smart BMS. This feature is not available when
connected to a Lynx Shunt VE. Can.
The Lynx Distributor ships together with a 40cm RJ10 cable. This cable provides power to the Lynx Distributor and is also used to transmit data if connected to a Lynx Smart BMS.
The RJ10 cable
The Lynx Distributor is designed to hold MEGA fuses. These need to be
purchased separately.
For more information, see the Fuses & fuse holders product page.
A selection of MEGA fuses with a variety of current ratings
2.2. VictronConnect App
If the Lynx Distributor is connected to a Lynx Smart BMS, it can be monitored
and set up with the VictronConnect App.
For more information, see the VictronConnect App download
page and the
VictronConnect
manual.
2.3. GX device
Up to 4 connected Lynx Distributors can be monitored with a GX device if
connected to a Lynx Smart BMS.
For more information on the GX device, see the GX device product page.
The GX device can be connected to the VRM portal, allowing remote monitoring.
For more information on the VRM portal, see the VRM page.
2.4. The Lynx Distribution System
The Lynx Distribution System is a modular busbar system that incorporates DC
connections, distribution, fusing, battery monitoring and/or Lithium battery
management. For more information, see the DC Distribution Systems product
page.
The Lynx Distribution System consist of the following parts:
- Lynx Power In – A positive and negative busbar with four batteries or DC equipment connections, available in two versions, with M8 or M10 busbar.
- Lynx Distributor – A positive and negative busbar with four fused connections for batteries or DC equipment and fuse monitoring, available in two versions, with M8 or M10 busbar.
- Lynx Shunt VE. Can – A positive busbar with a space for a main system fuse and a negative busbar with a shunt for battery monitoring. It has VE. Can communication for monitoring and setup with a GX device.
- Lynx Smart BMS – For use together with Victron Energy Smart Lithium batteries. It contains a positive busbar with a contactor driven by a battery management system (BMS) and a negative busbar with a shunt for battery monitoring. It has Bluetooth communication for monitoring and setup via the VictronConnect App and VE. Can communication for monitoring with a GX device and the VRM portal. Available as a 500A model with M8 busbars or 1000A model with M10 busbars.
Features
3.1. Internal parts and wiring diagram Lynx Distributor
The internal physical parts and the wiring diagram of the Lynx Distributor
indicating the following parts:
- Positive busbar
- Negative busbar
- Fuses
- Positive connections
- Negative connections
- Ground connection
The Internal physical parts of the Lynx Distributor
The internal wiring diagram of the Lynx Distributor
3.2. Fuse detection
The Lynx Distributor monitors each fuse and will detect a blown fuse.
When a fuse blows, the red fuse LED will illuminate, the power LED will turn
red, and an alarm message is sent to a connected Lynx Smart BMS.
Fuse detection is possible from all fuses on the battery side or the load or
charger side. Be aware that the fuse detection has a particularity; when
batteries are connected to multiple Lynx Distributor circuits and if one of
the battery fuses blows, the fuse monitor will not measure a high enough
voltage over the fuse to trigger a broken fuse alarm until the battery is
being charged or discharged.
The fuse monitors in Lynx Distributor modules with older firmware (before
serial number HQ1909) cannot detect a blown fuse when batteries are connected.
It can only detect a blown fuse if loads are connected.
3.3. The RJ10 cable
The RJ10 cable supplies power to the Lynx Distributor from a Lynx Smart BMS or
Lynx Shunt VE.Can and transfers data between the Lynx Distributor and the Lynx
Smart BMS.
The Lynx Distributor does not have an in-built power supply to supply its fuse
detection circuit; it relies on this power to be supplied from a Lynx Shunt
VE.Can or a Lynx Smart BMS via the RJ10 cable. If the Lynx Distributor is used
without a Lynx Shunt VE. Can or a Lynx Smart BMS, it needs to be powered in an
alternative way so that the fuse detection circuit is operational.
To power the RJ10 cable for standalone use, do the following:
- Connect pin 1 of the RJ10 connector to 5V (4.5V-5.5V).
- Connect pin 4 to GND.
**** The RJ10 connection is not protected against reverse polarity. A wrong RJ10 connection can irreversibly damage the Lynx Distributor’s electronic circuits.
Figure 1. Pinout RJ10 connector
RJ10 connector contact side RJ10 connector – retainer clip side
The Lynx Distributor communicates the operational status and the status of
each fuse via the RJ10 cable to a Lynx Smart BMS.
The data can then be accessed via the VictronConnect App, GX device and the
VRM portal.
The communication feature has been implemented in the Lynx Distributor from
serial number HQ1909 or above.
**** Communication is not possible in combination with the Lynx Shunt VE.Can.
Communication and interfacing
4.1. Lynx Distributor fuse monitoring
Up to 4 Lynx Distributors can be connected to a Lynx Smart BMS. They
communicate via the RJ10 cable. The Lynx Distributors communicate fuse and
operational status to the Lynx Smart BMS. The Lynx Smart BMS can be used to
read out the Lynx Distributors and generate alarms in case a fuse is blown or
communication is lost.
For this functionality, the Lynx Distributor must have serial number HQ1909 or
later. Earlier produced Lynx Distributors do not communicate fuse status.
4.2. The VictronConnect App
The VictronConnect App communicates via Bluetooth. It is used for changing
settings, monitoring the Lynx Smart BMS and up to 4 connected Lynx
Distributors. For more information on the VictronConnect App see the
VictronConnect manual.
4.3. GX Device
If the Lynx Distributor is connected to a Lynx Smart BMS and the Lynx Smart
BMS is connected to a GX device via VE.Can, the GX device show Lynx
Distributor operational data and the status of each fuse. If the GX device is
connected to the internet, the Lynx Distributor can also be monitored remotely
via the VRM portal.
System Design
5.1. Lynx distribution system parts
A Lynx distribution system usually consists of a single Lynx Shunt VE.Can
module or a single Lynx Smart BMS module.
The choice between a Lynx Shunt VE. Can or a Lynx Smart BMS depends on what
type of batteries are used in the system. The Lynx Smart BMS can only be used
with the Victron Energy Lithium Smart Batteries, while the Lynx Shunt VE.Can
is suitable for all other batteries.
Then, single, multiple or a combination of Lynx Distributor modules and/or
Lynx Power In modules are added.
Together they form a continuous negative and positive busbar with DC
connections and, depending on the configuration, integrated fuses, a battery
monitor and/or lithium battery management.
It is also possible to just use Lynx Power In modules and/or Lynx Distributor
modules without a Lynx Smart BMS module or a Lynx Shunt VE.Can modules. This
for situations where battery monitoring or battery management is not needed.
5.1.1. Orientation of Lynx modules
If the Lynx System contains a Lynx Shunt VE. Can or Lynx Smart BMS, the
batteries always have to be connected to the left side of the Lynx System and
the rest of the DC system (loads and chargers) connect to the right side. This
so the battery state of charge can be correctly calculated.
The Lynx modules can be mounted in any orientation. Should they be mounted
upside down so that the text on the front of the units is upside down as well,
use the special stickers included with each Lynx module so that the text is
orientated the correct way.
5.1.2. Interconnecting Lynx modules
Each Lynx module can connect to other Lynx modules on the left side and on the
right side.
If the Lynx module is the first in line, the last in line or is used by
itself, it is possible to connect batteries, loads or chargers directly to
these connections. However, we do not generally recommend this because
additional insulation and fusing are needed.
The example below shows a Lynx system consisting of a Lynx Power In, Lynx Shunt VE.Can and Lynx Distributor. Together, they form a continuous busbar with unfused battery connections, battery monitor, main system fuse and fused load connections.
Figure 2. Example of Interconnected Lynx modules without their covers (Lynx Shunt VE.Can)
The
example below shows a Lynx system consisting of a Lynx distributor, Lynx Smart
BMS and another Lynx Distributor.
Together, they form a continuous busbar with fused battery and load
connections, battery monitor, BMS system and contactor.
5.1.3. System example – Lynx Shunt VE.Can, Lynx Power In, Lynx Distributor
and lead acid batteries
This system contains the following components:
- Lynx Power In with 4 paralleled 12V lead acid batteries.
- Identical cable lengths for each battery.
- Lynx Shunt VE.Can with main system fuse and battery monitor.
- Lynx Distributor with fused connections for inverter/charger(s), loads and chargers. Note that additional modules can be added if more connections are needed.
- CCGX (or other GX device) to read out the battery monitor data.
System with Lynx Shunt VE.Can, lead acid batteries, a Lynx Shunt VE.Can and a Lynx Distributor
5.1.4. System example – Lynx Smart BMS, 2x Lynx Distributor and lithium
batteries
This system contains the following components:
- Lynx Distributor with 2 fused paralleled Lithium Smart batteries with identical cable lengths for each battery (up to 5 paralleled series strings can be used per system).
- Lynx Smart BMS with BMS, contactor and battery monitor.
- Lynx Distributor provides fused connections for inverter/charger(s), loads and chargers. Additional modules can be added if more connections are needed.
- A Cerbo GX (or other GX device) to read out the Lynx Smart BMS and Lynx Distributor data.
System with Lithium batteries, Lynx Smart BMS and two Lynx Distributors
5.1.5. System example – Lynx Distributor only
In this system it does not matter which side the batteries, the DC loads or
chargers are connected. Multiple Lynx Distributors and/or Lynx Power Ins can
be used.
Note that the Lynx Distributor LEDs are not operational without a Lynx Shunt
VE.Can or Lynx Smart BMS. However, it could be a design decision to use Lynx
Distributor unpowered because there is a need for a fused busbar but not
necessarily a need for broken fuse indication.
System with a Lynx Distributor only
5.2. System sizing
5.2.1. Current rating Lynx modules
The Lynx Distributor, Lynx Shunt VE.Can and the Lynx Power In are rated for a
nominal current of 1000A for 12, 24 or 48 System voltages.
See the table below for an idea of how much power the Lynx modules are rated
at different voltages. The power rating will indicate how big the connected
inverter/charger system can be. Remember that if inverters or
inverter/chargers are used, the batteries will power both the AC and DC
systems. Also, be aware that a Lynx Smart BMS or a Lynx Ion (now discontinued)
can have a lower current rating.
| 12V| 24V| 48V
---|---|---|---
1000A| 12kW| 24kW| 48kW
5.2.2. Fusing
The Lynx Distributor has spaces for 4 fuses, one for each DC circuit. These
spaces have been designed to fit MEGA fuses. For 12V and 24V systems use 36V-
rated MEGA fuses and for 48V systems use 58V-rated MEGA fuses. For more
information, see the Fuses & Fuse holders product page.
Always use fuses with the correct voltage and current rating. Match the fuse
rating to the maximum voltages and currents that potentially can occur in the
fused circuit. For more information on fuse ratings and fuse current
calculations see the Wiring Unlimited book.
The total value of the fuses of all circuits should not be more than the
current rating of the Lynx module or the Lynx model with the lowest current
rating in case of multiple Lynx modules are used.
5.2.3. Cabling
The current rating of the wires or cables used to connect the Lynx Distributor
to batteries and/or the DC loads, has to be rated for the maximum currents
that can occur in the connected circuits. Use cabling with a sufficient core
surface area to match the maximum current rating of the circuit.
For more information on cabling and cable thickness calculations, see our
book, Wiring Unlimited.
Installation
6.1. Mechanical connections
6.1.1. Lynx module connection features
The Lynx module can be opened up by unscrewing the 2 cover screws.
The contacts on the left side are covered by a removable rubber sleeve.
Red is the positive and black is the negative busbar.
Location of front cover screws and the removable sleeves
6.1.2. Mounting and interconnecting Lynx modules
This paragraph explains how to attach several Lynx modules to each other and
how to mount the Lynx assembly into its final location.
For a mechanical drawing of the housing with dimensions and the location of
the mounting holes, see the appendix of this manual.
These are the points to take into consideration when interconnecting and
mounting Lynx modules:
- If Lynx modules are going to be connected to the right and if the Lynx module is fitted with a plastic barrier on the right side, remove the black plastic barrier. If the Lynx module is located as the most right module, leave the black plastic barrier in place.
- If Lynx modules are going to be connected to the left, remove the red and black rubber sleeves. If the Lynx module is located as the most left module, leave the red and black rubber sleeves in place.
- If the Lynx system contains a Lynx Smart BMS or Lynx Shunt VE.Can, the left side is the battery and the right side is the DC system side.
- Connect all Lynx modules to each other using the M8 (M10) holes and bolts on the left and right. Take care that the modules correctly slot into the rubber joiner recesses.
- Place the washer, spring washer and nut on the bolts and tighten the bolts using a torque of 14Nm (17Nm for the M10 model).
- Mount the Lynx assembly in its final location using the 5mm mounting holes.
Figure 3. Connection sequence when connecting two Lynx modules
Correct placement of the M8 (M10) washer, spring washer and nut.
6.1.3. Addressing Lynx Distributor
These instructions only apply if the system contains a Lynx Smart BMS together
with multiple Lynx Distributors and the serial number of the Lynx Distributors
is HQ1909 or above.
- Name the Lynx Distributors from left to right: A, B, C, and D. Do this so that the fuse alarms correspond with the Lynx Distributor names.
Figure 4. Example of Lynx Distributor configuration and labelling
Set the 2-way DIP switch in each Lynx Distributor to correspond with its name. Up to 4 Lynx Distributors can be programmed this way. See the table below for how to set the DIP switches for each unit. By default, both DIP switches are set to off (A).
Figure 5. Location of the Lynx Distributor 2-way DIP switch
Table 1. Lynx Distributor DIP switch programming table
Distributor name | Switch 1 | Switch 2 | Configuration |
---|---|---|---|
A | Off | Off | |
B | On | Off | |
C | Off | On | |
D | On | On |
6.2. Electrical connections
6.2.1. Connect RJ10 cable(s)
These instructions only apply if the system contains Lynx distributor(s)
together with a Lynx Smart BMS or a Lynx Shunt VE.Can.
There are two RJ10 connectors in each Lynx Distributor, one on the left and
one on the right. See the drawing below.
To connect the RJ10 cables between the various Lynx modules, do the following:
- Plug one side of the RJ10 cable in the RJ10 connector of the Lynx Distributor with the retainer clip of the RJ10 connector facing away from you.
- Feed the RJ10 cable through the recess at the bottom of the Lynx Distributor; see the above picture.
- To connect to another Lynx Distributor, feed the cable through its bottom recess and plug the RJ10 cable into the RJ10 connector.
- To connect to a Lynx Shunt VE. Can, feed the cable through its bottom recess and plug the RJ10 cable into the RJ10 connector.
- To connect to a Lynx Smart BMS, plug the RJ10 cable into the RJ10 connector at the bottom of the Lynx Smart BMS.
6.2.2. Connect DC wires
This chapter might not apply if the Lynx module is connected to other Lynx
modules like this can be the case for the Lynx Smart BMS or the Lynx Shunt
VE.Can.
For all DC connections, the following applies:
- All cables and wires connected to the Lynx module need to have been fitted with M8 cable lugs.
- Pay attention to the correct placement of the cable lug, washer, spring washer and nut on each bolt when attaching the cable to the bolt.
- Tighten the nuts with a torque moment of 14Nm (17Nm for the M10 model).
Figure 6. Correct mounting sequence DC wires
Correct placement of the M8 Cable lug, washer, spring washer and nut
6.2.3. Ground and Negative connections
Connect the ground wire
This only applies if the system requires a ground connection. There should
only be one ground connection per system. The ground connection should be made
after the Lynx Smart BMS, Lynx Shunt VE.Can or battery monitor shunt. For more
information on system grounding, see the Wiring Unlimited book.
The ground connection of the Lynx Distributor has a wire with a red cable lug
already connected to it. Leave this wire in place when connecting the ground
wire.
Connect the negative wires
Remove the cable separator post if the wire diameter exceeds 10mm.
To reach the negative connections, swing the black cable separators upwards. The black cable separators can be temporarily removed by pulling them away from the Lynx Distributor at a slight sideways angle in case better access is needed.
6.2.4. Place Lynx Distributor fuses
Before placing fuses, check if the middle row’s bottom nuts are tightened
correctly to a use torque moment of 10Nm.
Place all 4 fuses, even if not all 4 circuits are used. Placing dummy fuses in
the unused circuits will prevent the red warning LED from illuminating.
The second fuse connection has a wire with a cable lug that is already
connected to it. Lift the red cable lug, place the fuse against the busbar and
replace the red cable lug.
6.2.5. Positive connections
Before making any positive connections, make sure that the positive wires
are not powered. Disconnect all positive cables from the battery prior to
connecting them to the Lynx module. This to prevent accidental short circuits.
Connect all positive wires.
Power the Lynx system by connecting the positive battery pole(s).
6.3. Configuration and settings
6.3.1. Settings Lynx Distributor
These instructions only apply if the system contains one or more Lynx
Distributors.
Each Lynx distributor must be addressed and set to A, B, C or D. This is done
via a 2-way dip switch inside the Lynx distributor.
Refer to section 6.1.3. Addressing Lynx Distributor [13] in the Lynx
distributor manual.
Use the VictronConnect App to give each fuse a custom name (maximum 16
characters). If the fuse name is empty (0 characters), the fuse will be
disabled from monitoring and be ignored.
- Navigate to the settings page by clicking the gear symbol at the top right-hand corner.
- On the settings page, scroll down to the Lynx Distributor settings.
- Click on a fuse name; a window opens to rename the fuse.
Commissioning the Lynx Distributor
Commissioning sequence:
Check polarity of all DC cables. Check cross sectional area of all DC cables.
Check if all cable lugs have been crimped correctly.
Check if all cable connections are tight (don’t exceed maximum torque).
Tug slightly on each battery cable to check if the connections are tight and
if the cable lugs have been crimped correctly.
Check if the fuses have been placed and their connections are tight (don’t
exceed maximum torque).
Check if the fuse names of the Lynx Distributor (if applicable) are correctly
named
Operation Lynx Distributor
Powering up
When the Lynx Distributor is powered up by the Lynx Smart BMS, all LEDs will
light up for one second, after which the address briefly is shown via a fuse
LED. Fuse 1 LED illuminates for Distributor A, Fuse 2 LED illuminates for
Distributor B and so on. The power LED is orange during power up and will turn
green once power up is complete.
Older Lynx Distributors with a serial number below HQ1909 will only show all
LEDs light up for one second during power-up.
Normal operation
During normal operation the power LED is green, and all fuse LEDs are off.
This means everything is all right, the bus is powered, and all fuses are
okay.
Alarm operation
When a fuse blows (or is missing) the power LED turns red and the fuse LED of
the affected fuse turns red.
When the busbar is not powered, the power LED turns yellow. This can occur, for example, when the main fuse in the Lynx Shunt VE. Can has blown, and all downstream Lynx Distributors therefore have unpowered busbars.
LED overview
The operational status of the Lynx Distributor is communicated via LEDs. This
is the overview:
Table 2. Lynx Distributor LED overview
LED indication | Status |
---|---|
Power LED yellow + fuse LEDs off | No voltage supplied to the positive bus bar |
Power LED green + fuse LEDs off | Positive bus bar is powered, and all fuses |
are ok
Power LED red + fuse led(s) red| One or more fuses are blown
All LEDs light up for one second| Powering up
8.1. Monitoring Lynx Distributor
This paragraph only applies if the Lynx Distributor is connected to a Lynx
Smart BMS.
The VictronConnect app
The Lynx Distributor information can be viewed with the VictronConnect App via
the Lynx Smart BMS.
In the VictronConnect App, click on the “DISTRIB.” tab to see the Lynx
Distributor status window.
All connected Distributors and their fuse status will be displayed here.
Fuse blown alarm
This alarm is raised if a fuse has blown. The fuse status will change in the
VictronConnect App and an alarm message is displayed. The alarm message will
also be shown on a connected GX device and the VRM portal. The fuses are
numbered from left to right.
NOTE: These alarm codes are a workaround until the Lynx Smart BMS is supported in VenusOS. The alarm message on the GX device or the VRM portal will be similar to the message shown in the VictronConnect App.
Table 3. Lynx Distributor fuse blown alarm codes
Alarm | Description |
---|---|
#201 | Distributor A, Fuse 1 blown |
#202 | Distributor A, Fuse 2 blown |
#203 | Distributor A, Fuse 3 blown |
#204 | Distributor A, Fuse 4 blown |
#205 | Distributor B, Fuse 1 blown |
#206 | Distributor B, Fuse 2 blown |
#207 | Distributor B, Fuse 3 blown |
#208 | Distributor B, Fuse 4 blown |
#209 | Distributor C, Fuse 1 blown |
#210 | Distributor C, Fuse 2 blown |
#211 | Distributor C, Fuse 3 blown |
#212 | Distributor C, Fuse 4 blown |
#213 | Distributor D, Fuse 1 blown |
#214 | Distributor D, Fuse 2 blown |
#215 | Distributor D, Fuse 3 blown |
#216 | Distributor D, Fuse 4 blown |
Communication lost alarm
This alarm is raised, if a Lynx Distributor was detected by the Lynx Smart BMS
on power up but the Lynx Smart BMS cannot see the Lynx Distributor any longer.
The Distributor status will change from OK to “communication lost” in the
VictronConnect App and an alarm message is displayed. The alarm message will
also be shown on a connected GX device and the VRM portal.
NOTE: These alarm codes are a workaround until the Lynx Smart BMS is supported
in Venuses’. The alarm message on the GX device or the VRM portal will be
similar to the message shown in the VictronConnect App.
Table 4. Lynx Distributor lost alarm codes
Alarm | Description |
---|---|
#221 | Distributor A, communication lost |
#222 | Distributor B, communication lost |
#223 | Distributor C, communication lost |
#224 | Distributor D, communication lost |
Troubleshooting and Support
For unexpected behavior or suspected product faults, refer to this chapter.
Start by checking the common issues described here. If the problem persists,
contact the point of purchase (Victron dealer or distributor) for technical
support.
If you’re unsure who to contact or if the point of purchase is unknown, refer
to the Victron Energy Support
webpage.
9.1. Cabling issues
Cables heat up
This can be caused by a wiring or connection issue. Check the following:
- Check if all cable connections are tightened with a torque moment of 14Nm (17Nm for the M10 model).
- Check if all fuse connections are tightened with a torque moment of 14Nm.
- Check if the surface area of the cable core is large enough for the current through that cable.
- Check if all cable lugs have been crimped correctly and are tight enough.
Other cabling issues
For additional information about issues that can arise from bad or incorrect
cabling, cable connections or wiring of battery banks refer to the Wiring
Unlimited Book.
9.2. Fuse issues
For additional information about issues that can arise from incorrect fuse
ratings or types refer to the Wiring Unlimited
Book.
Red fuse LED on
This is caused by a blown or missing fuse. It can also be caused by a
malfunctioning fuse or if the fuse connections are loose.
The Lynx Distributor measures the voltage over each fuse. As soon as it is
more than 0.5V the fuse is marked as blown and if the voltage is less than
0.3V it is marked as ok.
- In case of a blown or malfunctioning fuse – replace the fuse.
- In case of a missing fuse because the circuit is unused – place a dummy fuse in the unused fuse space.
- In case of a loose connection – check if both fuse connections have been tightened with a torque moment of 14Nm.
Red fuse LED intermittently on
This is most likely caused by a loose fuse or a bad fuse. Refer to the
previous paragraph.
Fuse is missing in the VictronConnect list
Check the fuse name with the VictronConnect App. When the fuse name field is
empty, the fuse will be disabled from monitoring and ignored.
Fuse blows as soon as a new fuse is installed
Check the DC circuit that is attached to the fuse for the following:
- Check if there is a short circuit.
- Check if there is a malfunctioning load.
- Check if the current in the circuit is not larger than the fuse rating.
Blown battery fuse not being detected straight away
When batteries are connected to multiple Lynx Distributor circuits and if one
of the battery fuses blows, the fuse monitor will not measure a high enough
voltage over the fuse to trigger a broken fuse alarm, until the battery is
being charged or discharged.
Blown battery fuse not being detected
The fuse monitors in Lynx Distributor modules with older firmware (pre HQ1909)
cannot detect a blown fuse when batteries are connected to multiple Lynx
Distributor circuits.
9.3. Lynx Distributor operational issues
Does not power up (No LEDs)
The electronics that drive the fuse detection circuits and the Lynx
Distributor receives its power from a Lynx Smart BMS or from a Lynx VE.Can via
the RJ10 cable. When correctly powered up, the power LED should illuminate
either green yellow or red. If no LEDs are illuminated at all check the
following:
- Check if the RJ10 cable is connected and if there is a Lynx Shunt VE.Can or a Lynx Smart BMS in the system.
- In case of a Lynx Smart BMS it could also be that the Lynx Smart BMS has depowered the Lynx Distributor because of an empty battery or the Lynx Smart BMS remote on/off switch has been switched to off. For more information see the Lynx Smart BMS manual.
Yellow power LED
This happens when there is no voltage supplied to the positive busbar, but the
Lynx Distributor is still receiving power via the RJ10 cable. A common cause
is when the main fuse in the Lynx Shunt VE.Can or an external main fuse has
blown.
Unable to communicate
Communication with the Lynx Distributor is only possible together with a Lynx
Smart BMS. Connect with the VictronConnect App to the Lynx Smart BMS and check
if the Lynx Distributor shows up on the app. Check the serial number of all
Lynx Distributors, it needs to be HQ1909 and above for it to be able to
communicate.
- Check if all Lynx Distributors are powered; the power LED needs to be on.
- Check the integrity of all RJ10 cables and check if they are all correctly plugged in.
- Check how many Lynx Distributors are used. It is not possible to communicate with more than 4 Lynx Distributors at the same time.
- Check the addressing of each Lynx Distributor and check if all the DIP switches have been set correctly. Each of the 4 Lynx
Distributors will need a unique address. If multiple Lynx Distributors have the same address, only one will appear. The others with the same address will be missing.
Lynx Distributor names not sequential
An addressing mistake has been made when setting the DIP switches.
The VictronConnect App “DISTRIB” list shows Distributor not in use
This can be because the Lynx Smart BMS has turned the Lynx Distributor off or
the Lynx Distributor is not connected with the RJ10 cable.
Communication lost
This alarm is raised if a Lynx Distributor is detected by the Lynx Smart BMS
on power up but cannot see the Lynx Distributor anymore. The Lynx Smart BMS
sends a message to all Lynx Distributors every 250ms and if the Lynx
Distributor does not answer the communication lost alarm is raised. The most
likely cause of this alarm is that the RJ10 cable has been disconnected.
Technical specifications Lynx Distributor
Power
Voltage range| 9 – 60Vdc
Supported system voltages| 12, 24 or 48V
Reverse polarity protection| Yes (1)
Current rating| 1000Adc continuous
Power consumption-2| Maximum 100mA (with all LEDs illuminated)
(1) The RJ10 cable connection is not protected against reverse polarity
(2) Powered from Lynx Shunt VE. Can or Lynx Smart BMS
Connections
Busbar| M8 or M10
Fuses| M8
Power (3) and data (4)| 40 cm RJ10 cable (included)
(3) Powered from Lynx Shunt VE. Can or Lynx Smart BMS
(4) Data can only be received by a Lynx Smart BMS
Physical
Enclosure material| ABS
Enclosure dimensions (hxlxw)| 290 x 170 x 80 mm
Unit weight| 2.2 kg
Busbar material| Tinned copper
Busbar material (hxw)| 8 x 30mm
Environmental
Operating temperature range| -40°C to +60°
Storage temperature range| -40°C to +60°
Humidity| Max. 95% (non-condensing)
Protection class| IP22
Enclosure dimensions Lynx Distributor M8 and M10
Lynx Distributor M8 and M10
Enclosure dimensions Lynx Distributor
M8 and M10