legrand 310085 External Charger Instruction Manual
- June 13, 2024
- Legrand
Table of Contents
External Charger 1-3 kVA
3 100 85
Installation manual
Part. LE13332AA-12/21-01 WP
Introduction
The battery charger 3 100 85 is an accessory designed for the UPS range 1-3kVA
to shorten the charging time of the battery banks connected to the UPS.
You are advised to read carefully this manual and the safety instruction sheet
included in the packaging before installing the battery charger.
Please visit the website www.ups.legrand.com to
download the latest version of the manual and discover the complete Legrand
UPS offer.
Condition of use
- This product is designed for indoor use only in a controlled environment away from excess moisture, temperature extremes, conductive contaminants, dust, corrosive agents or direct sunlight.
- Do not install and operate the Charger when water condensation happen which may occur if the charger is moved directly from a cold to a warm environment.
- Do not install or use this equipment in the presence of flammable substances.
- The air flow required for safe operation of the equipment should not be compromised. Ensure enough space on each side for ventilation and install the charger in a location with good aeration.
- Installation and wiring must be performed in accordance with the local electrical laws and regulations.
- The charger must be securely grounded. Ensure earth connection and its reliability before connecting the power wires to the wiring terminal of the building. Make sure the battery cabinets have the equipotential earth bonding to the charger main cabinet.
- An appropriate switch device as backup protection for over-current or short circuit should be provided in the input utility.
- Select the Battery Charger suitable for your battery bank by reading the Chargers specifications included in this manual. Pay attention to the battery bank voltage rating and capacity. The connection with wrong battery voltage may cause permanent damage to the Charger, the connection with wrong capacity may cause permanent damage to the batteries.
- In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
CAUTION
Legrand reserve at any time the right to modify the content of this manual and
to communicate in any form and modality, the changes brought to the same.
Installation
Package Contents
- Cable type L1 +A3 : used to connect Keor LP , it is included only in the references 310958,310960,310961
- Cable type L2 +A2 : used to connect Daker DK, it is included only in the references 310959,310961
Wiring installation guide
CAUTION
Only a licensed and expert electrician is authorized to install the Battery
Charger.
-
Switch off all the power sources that supply UPS, battery banks and chargers. Ensure that the Battery Charger is unplugged.
-
Turn off the battery banks breakers.
-
Remove the terminal cover by means of a screwdriver (picture 1).
-
Connect the battery cables to the battery box terminal (picture 2).
Make sure +/- wires position is correct (not reverse no short circuit).
CAUTION : tighten screws and SELECT THE RIGHT OUTPUT VOLTAGE.
CAUTION : fix L1/L2 to the charger box through the cable ties (A4).
CAUTION : Assembly the terminal cover and fix it to the charger box by screw (picture 3). -
Connect the battery charger to the battery bank through the DC cable L1, L2, L3, L4, L5 (picture 4,5).
-
Ensure the installation is safe for the final user applying to the battery cabinet terminal block insulating cover and cables glands.
-
Plug the power cable to the AC mains socket.
-
Switch on the battery banks breakers.
-
Turn on the mains that supply UPS, battery banks and battery chargers.
CAUTION
Before uninstalling the battery charger, switch off the mains and the battery banks and ensure no dangerous voltage is present in the terminal block.
Installation
Application
Standard Connection example
Battery chargers in parallel :
Max 4 Units
CAUTION
- Recommended cables (max 2 battery chargers in parallel) : UL 1015 14AWG
- Recommended cables (max 3/4 battery chargers in parallel) : UL 1015 12AWG
Specifications
MODEL | 3 100 85 |
---|
AC INPUT
Input Voltage range| 100 V-240 V
Max Input Current| 2.3 A Max
Nominal Input Frequency| 50 Hz/60 Hz±10%
Input Power Factor| >0.9
Input Phases| Single phase
DC OUTPUT
Nominal DC Output Voltage| 24 V| 36 V| 48 V| 72 V| 96 V
Nominal DC Output Current| 8.1 A| 6.6 A| 5.5 A| 3.9 A| 3 A
Nominal Output Power| 250 W Max
PROTECTIONS
Input over voltage| YES
Over temperature| YES
Output short circuit| YES
ENVIRONMENT
Operating temperature range| 0 °C ~ 40 °C
Cooling| Forced air ventilation by DC fan
Relative Humidity| 10% ~ 90% (without condensation)
PHYSICAL
Unit Dimensions (WxHxD) mm| 252x94x196
Packing Dimensions (WxHxD) mm| 328x179x204
Export Box Dimensions (WxHxD) mm| 350x392x430
STANDARD COMPLIANCE
Certification| CE, EAC, CMIM
Safety| EN 60950-1
EMC| EN 61000-6-4, IEC 61000-3-2, EN 61000-3-3,
EN 61000-6-2 (EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6,
EN 61000-4-8, EN 61000-4-11)
Warning : This is a product for commercial and industrial area. In a
different environment-installation restrictions or additional measures may be
needed to prevent disturbances
LEGRAND
Pro and Consumer Service
BP 30076 – 87002
LIMOGES CEDEX FRANCE
www.legrand.com