roger MC16-PAC-5 Physical Access Controller Installation Guide

June 13, 2024
ROGER

Roger Access Control System
MC16 Installation Manual
Firmware version: 1.6.4 and newer
Document version: Rev. I

This document contains minimum information that is necessary for initial setup and installation of the device. The detailed description of configuration parameters and functionalities is specified in respective Operating manual available at www.roger.pl.

INTRODUCTION

MC16 controller is mainly dedicated to door access control in RACS 5 system.
The controller is master device for such peripheral devices as MCT and PRT series terminals, Wiegand interface readers and MCX series expanders. Inputs and outputs of the controller or connected peripheral device can be used to control such devices as door locks, exit buttons, alarm sirens, etc. Various versions and types of controllers are based on the same hardware module and differ with license on their memory cards. Most popular MC16-PAC controllers are offered in MC16-PAC-x-KIT sets.

CONFIGURATION WITH ROGERVDM PROGRAM

Low level configuration with RogerVDM software enables to define basic parameters of MC16 controller. Additionally it is necessary to define individual addresses for MCT and PRT series readers and MCX expanders according to their installation manuals.
MC16 programming procedure with RogerVDM software:

  1. Connect the controller to Ethernet network and define the IP address of your computer in the same subnetwork as the controller with 192.168.0.213 default IP address.
  2. Start RogerVDM program, select MC16 v1.x device, the latest firmware version and Ethernet communication channel.
  3. Select from the list or enter manually the IP address of controller, enter 1234 communication key and start the connection with the controller.
  4. In the top menu select Tools and then Set communication key to define your own password for the controller.
  5. In the main window specify your own IP address of the controller.
  6. Enable PRT or Wiegand readers if the controller is supposed to operate with them.
  7. Optionally enter comments for controller and its object to facilitate their identification during further configuration of the system.
  8. Optionally backup settings clicking Send to File…
  9. Click Send to Device to update the configuration of controller and disconnect by selection of Device in the top menu and then Disconnect.

CONFIGURATION WITH VISO PROGRAM

High level configuration with VISO software enables to define the logic of controller. More information on scenarios of operation and high level configuration is given in MC16 Operating manual as well as AN002 and AN006 application notes.

MEMORY RESET

Memory reset procedure resets all settings to default ones and results in 192.168.0.213 IP address and empty communication key. MC16 memory reset procedure:

  1. Disconnect power supply.
  2. Short CLK and IN4 lines.
  3. Restore power supply, all LEDs will flash and wait min. 6s.
  4. Remove connection between CLK and IN4 lines, LEDs will stop pulsating and LED2 will be on.
  5. Wait approx. 1.5 min till LED5+LED6+LED7+LED8 are pulsating.
  6. Restart the controller (switch power supply off and on).
  7. Start RogerVDM and make low level configuration.

FIRMWARE UPDATE

New firmware can be uploaded to the controller with RogerVDM software. The latest firmware file is available at www.roger.pl.
MC16 firmware update procedure:

  1. Connect with the controller using RogerVDM software.
  2. Backup settings by clicking Send to File…
  3. In the top menu select Tools and then Update firmware.
  4. Select firmware file and then click Update.
  5. After firmware update wait till LED8 is pulsating.
  6. Make or restore low level configuration in RogerVDM software.

Note: During the firmware update process, it is necessary to ensure continuous and stable power supply for the device. If interrupted, the device may require repair by Roger.

POWER SUPPLY

MC16 controller is designed for power supply from 230VAC/18VAC transformer with minimal power output 20VA, but it can also be supplied with 12VDC and 24VDC. In case of 12VDC power supply, backup battery cannot be directly connected to MC16 and in such case backup power supply must be provided by 12VDC power supply unit.roger MC16 PAC 5 Physical Access Controller - 1 MC16
power supply

APPENDIX

Table 1. MC16 screw terminals

Name Description
BAT+, BAT- Backup battery
AC, AC 18VAC or 24VDC input power supply
AUX-, AUX+ 12VDC/1.0 output power supply (for door lock)
TML-, TML+ 12VDC/0.2A output power supply (for readers)
IN1-IN8 Input lines
GND Ground
OUT1-OUT6 15VDC/150mA transistor output lines
A1,B1 RS485 bus
CLK, DTA RACS CLK/DTA bus
A2,B2 Not used
NO1, COM1, NC1 30V/1.5A DC/AC (REL1) relay
NO2, COM2, NC2 30V/1.5A DC/AC (REL2) relay

Table 2. MC16 LED indicators

Name Description
LED1 Normal mode
LED2 ON: Service mode (low level configuration) Pulsing: RAM or Flash SPI

memory error
LED3| ON: High level configuration error Pulsing: Low level configuration error
LED4| No memory card or memory card error
LED5| Event log error
LED6| License error
LED7| Not used
LED8| Pulsating: Proper functioning of the controller

Table 3. Specification

Supply voltage| 17-22VAC, nominal 18VAC 11.5V-15VDC, nominal 12VDC
22-26VDC, nominal 24VDC
---|---
Current consumption| 100 mA for 18VAC (no loads on AUX/TML outputs)
Inputs| Eight parametric inputs (IN1..IN3) internally connected to the power supply plus through a 5.6kΩ resistor. Approx. 3.5V triggering level for NO and NC inputs.
Relay outputs| Two relay outputs with single NO/NC contact 30V/1.5A rated
Transistor outputs| Six open collector transistor outputs, 15VDC/150mA rated. Max. total current sink by all outputs up to 3ADC.
Power supply outputs| Two power outputs: 12VDC/0.2A (TML) and 12VDC/1A (AUX)
Distances| 1200m for RS485
150m for and RACS CLK/DTA and Wiegand
IP Code| IP20
Environmental class (acc. to EN 50131-1)| Class I, indoor general conditions, temperature: +5°C to +40°C, relative humidity: 10 to 95% (no condensation)
Dimensions H x W x D| 72 x 175 x 30 mm
Weight| approx. 200g

roger MC16 PAC 5 Physical Access Controller - access
controller

  1. Max. cable distance between controller and any MCT/MCX device cannot exceed 1200m.
  2. Each MCT/MCX device must have individual address in 100..115 range.
  3. All devices connected to RS485 comm. bus must share the same GND reference level.
  4. For RS485 A and B lines the unshielded, twisted pair cabling (U/UTP cat. 5) is recommended.
  5. Except loop any other cable topology (star, tree, etc.) is allowed.

Fig. 2 Connection of readers and expanders to MC16 access controller

roger MC16 PAC 5 Physical Access Controller - Typical door control with MCT
readers

Fig. 3 Typical door control with MCT readers

roger MC16 PAC 5 Physical Access Controller - Typical door control with
Wiegand readers Fig. 4 Typical door control with Wiegand readers

Notes:

  • In case of read-in door, single reader is connected to the controller. MCT terminal can be then installed with default ID=100 address.
  • In case of PRT readers, the diagram is the same as in case of MCT readers except for connection to CLK and DTA lines instead of RS485 A and B lines.
  • In case of electrically incompatible Wiegand readers it might be necessary to install PR-GP-BRD modules.
  • Diagrams include doors with electric strikes. In case of electromagnetic lock, the NC terminal of relay is used instead of NO terminal.
  • Diagrams include exit buttons. In case of read-in/out doors they can be used for emergency door opening.

**** This symbol placed on a product or packaging indicates that the product should not be disposed of with other wastes as this may have a negative impact on the environment and health. The user is obliged to deliver equipment to the designated collection points of electric and electronic waste. For detailed information on recycling, contact your local authorities, waste disposal company or point of purchase. Separate collection and recycling of this type of waste contributes to the protection of the natural resources and is safe to health and the environment. Weight of the equipment is specified in the document.

Contact:
Roger Sp. z o. o. sp. k.
82-400 Sztum
Gościszewo 59
Tel.: +48 55 272 0132
Fax: +48 55 272 0133
ech. support: +48 55 267 0126
E-mail: [email protected]
Web: www.roger.pl

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

ROGER User Manuals

Related Manuals