PLC Panel Level Rapid Shutdown
Installation Guide
Safety Precautions
1.1 Scope of Application
This User Manual describes instructions and detailed procedures for
installing, operating, maintaining, and troubleshooting of the following
Projoy Panel-level Rapid Shutdown Equipment:
PEFS-PL80P-11 PEFS-PL80P-21 PEFS-PLC-CN
Please keep this manual at all time available in case of emergency.
1.2 Safety Instructions
DANGER
- DANGER indicates a hazardous situation that, if not avoided, will result in death or serious injury.
WARNING
- WARNING indicates a hazardous situation that, if not avoided, can result in death or serious injury or moderate injury.
CAUTION
- CAUTION indicates a hazardous condition that, if not avoided, can result in minor or moderate injury.
NOTICE
- NOTICE indicates a situation that can result in potential damage, if not avoided.
1.3 Target Group
Only qualified electricians who have read and fully understood all safety
regulations contained in this manual can install, maintain and repair the
Panel-level rapid shutdown equipment.
Preparation
DANGER
- Do not disconnect PEFS-PL while the PVRSS is working. There is the possibility of dying due to electrical shock and high voltage.
- To prevent the risk of electric shock during installation and maintenance, please make sure that PEFS-PLC-CN or any other control unit, such as the DC switch of the inverter, is turned off.
WARNING
- The installation, service, recycling, and disposal of the PVRSS must be performed by qualified personnel only in compliance with national and local standards and regulations.
- Any unauthorized actions including modification of product functionality of any form may cause a lethal hazard to the operator, third parties, the units, or their property. Projoy is not responsible for the loss and these warranty claims.
- While PSFS-PL80P-11 or PEFS-PL80P-21 are used without PEFS-PLC-CN, be sure that this photovoltaic rapid shutdown equipment (PVRSE) does not perform all of the functions of a complete photovoltaic rapid shutdown system (PVRSS). This PVRSE must be installed with other equipment to form a complete PVRSS that meets the requirements of NEC (NFPA 70) section 690.12 for controlled conductors outside the array. Other equipment installed in or on this PV system may adversely affect the operation of the PVRSS. It is the responsibility of the installer to ensure that the completed PV system meets the rapid shut down functional requirements. This equipment must be installed according to the manufacturer’s installation instructions.
- While PSFS-PL80P-11 or PEFS-PL80P-21 are used with PEFS-PLC-CN, be sure that this photovoltaic rapid shutdown system (PVRSS) incorporates one or more pieces of equipment that exercise the rapid shutdown control of PV system conductors required by section 690.12 of the NEC (NFPA 70). other equipment installed in or on this PV system may adversely affect the operation of this PVRSS. it is the responsibility of the installer to ensure that the completed PV system meets the applicable rapid shut down functional requirements. this equipment must be installed according to the manufacturer’s installation instructions.
CAUTION
- The PSFS-PL80P-11 or PEFS-PL80P-21 will become hot during operation. Please do not touch the surface during or shortly after operation.
- Risk of damage due to improper modifications.
- All electrical installations must be done in accordance with the National Wiring Rules of Standard and local code.
2.2 Explanations of Symbols
Symbol | Description |
---|---|
Danger of high electrical voltage |
This device is connected in series to the solar inverter, thus all work to the
PVRSE shall only be carried out by qualified personnel.
| Danger of hot surface
The components inside the PVRSE will release a lot of heat during operation.
Do not touch the surface during operating.
| Read the User Manual First
Please read the User Manual first before the installation and operation.
| Recycling and Disposal
This device SHALL NOT be disposed of in the residential waste.
RoSH| RoHS Directive
This device complies with the RoHS Directive.
Product Information
3.1 Application Scope of Products
3.2 Specification for Product Model
PEFS – PL80P-11
PEFS: RSD represents Rapid Shutdown.
PL: Panel-level.
80: Voltage parameter.
P: Power carrier communication.
1/2: Input port.
1/2: Product Iteration.
3.3 System Diagram
3.4 Overview and Dimensions of products
The dimensions of PEFS-PL80P-11 and PEFS-PL80P-21 are shown in Figure 3.3.
The dimensions of PEFS-PLC-CN are shown in Figure 3.4.
3.5 Datasheet
MODEL | PEFS-PL80P-11 | PEFS-PL80P-21 |
---|---|---|
Max. Input Current [A] | 20 | 20/20 |
Input Vmax PV [Vdc] | 80 | 80/80 |
Output Vmax PV [Vdc] | 80 | 160 |
Max. System Voltage [V] | 1500 | 1500 |
Isc PV (absolute Max.) [A] | 20 | 20 |
Rapid Shutdown Time Limit [s] | 10 | |
Tripping | PLC Signal | |
Operating Temperature [Ti | -40 to +80 | |
Ingress Protection | Type 6P | |
Humidity | 0 – 90% | |
Communication | PLC | |
Overvoltage Category | II | |
Mounting | Clip | |
Dimension W” WD [mm] | 120 ” 44 * 20 | |
MODEL | PEFS-PLC-CN | |
--- | --- | |
Operating AC Voltage Range | 100 V-240 V | |
Nominal Frequency | 50/60 Hz | |
Power Consumption | <1W | |
DC Input Strings | 4 Strings | |
Operating Temperature Range | -30°C to +55°C | |
Protection Class | IP65 | |
Communication | PLC | |
Mounting | Wall Mounted | |
Connector | MC4 Compatible (DC), Plug-in Connector (AC) | |
Dimension(W*HD) | 210mm*174mm 101mm | |
Weight | 1800g |
Instructions for installation
4.1 Safety Instructions
DANGER
- To prevent risk of electric shock during installation and maintenance, please make sure that PEFS-PC or any other control unit, such as the DC switch of inverter, are turned off.
NOTICE
- All electrical installations must be done in accordance with the National Wiring Rules of Standard and local code.
4.2 Pre-installation Check
Although Projoy’s products have surpassed stringent testing and are checked
before they leave the factory, it is uncertain that the products may suffer
damage during transportation. Please check the package for any obvious signs
of damage, and if such evidence is present, do not open the package and
contact your dealer as soon as possible.
4.3 Installation of PEFS-PL80P-11/21
WARNING
While PEFS-PL80P-11/21 are used without PEFS-PLC-CN, be sure that this photovoltaic rapid shutdown equipment (PVRSE) does not perform all of the functions of a complete photovoltaic rapid shutdown system (PVRSS). This PVRSE must be installed with other equipment to form a complete PVRSS that meets the requirements of NEC (NFPA 70) section 690.12 for controlled conductors outside the array. Other equipment installed in or on this PV system may adversely affect the operation of the PVRSS. It is the responsibility of the installer to ensure that the completed PV system meets the rapid shutdown functional requirements. This equipment must be installed according to the manufacturer’s installation instructions.
-
Fix the rapid shutdown device (PEFS-PL80P-11/21) on the frame of solar module.
-
Connect the input of the rapid shutdown device to the solar module.
-
Connect the outputs of all the rapid shutdown devices one after another.
-
While PEFS-PL80P-21 are used without PEFS-PLC-CN, connect each string of the rapid shutdown devices to the solar inverter.
4.4 Installation of PEFS-PC
WARNING
While PEFS-PL80P-21 are used with PEFS-PLC-CN, be sure that this photovoltaic
rapid shutdown system (PVRSS) incorporates one or more pieces of equipment
that exercise the rapid shutdown control of PV system conductors required by
section 690.12 of the NEC (NFPA 70). other equipment installed in or on this
PV system may adversely affect the operation of this PVRSS. it is the
responsibility of the installer to ensure that the completed PV system meets
the applicable rapid shutdown functional requirements. this equipment must be
installed according to the manufacturer’s installation instructions.
Installers should determine the installation location of the rapid shutdown
controller according to local regulations.
-
Push out the bracket of the rapid shutdown controller. Fix the rapid shutdown controller (PEFS-PLC-CN) on the wall.
-
Plug each string of rapid shutdown devices to the rapid shutdown controller. Then plug each output cable to the solar inverter.
-
Multiple control boxes can be connected in series and can be controlled by a single master control box.
-
Put the warning label in the PV system as required in section 690.56(C) of NEC (NFPA70).
4.5 Start the PVRSS system
Turn on the power source of the rapid shutdown controller. The rapid shutdown
control system will start to work.
The status of the lights is shown below:
| On| Off
---|---|---
Power (Red)| The rapid shutdown controller is powered on and sends signals to
the rapid shutdown devices in each string. The status of the lights is shown
below:| The rapid shutdown controller is powered off or stops sending signals
to the rapid shutdown devices in each string.
Table 4.1 Light Status
Firefighters can push the button to cut off all the solar modules while in an
emergency.
After the emergency, users can rotate the button and the solar module will
work again.
System Test and Troubleshooting
5.1 System test
5.1.1 Function test
Please do the function test regularly.
- Push the button of the rapid shutdown controller. The status of light will be off. Check the solar inverter. The DC current will be cut off and the DC voltage will be lower than 30V in 30 seconds.
- Rotate the button of rapid shutdown controller. The status of light will be on. The solar will start to work again.
5.1.2 Maintain test
When the PEFS-PLC-CN stops working, the PEFS-PL80P-11 will have a continuous
0.9 V output and the PEFS-PL80P-21 will have a continuous 1.75 V output.
- Push the button and stop the PEFS-PLC-CN.
- Separate the DC cable and rapid shutdown controller. Test the voltage of each DC cable.
System Voltage = 0.9 V Quantities of PEFS-PL80P-11 or
System Voltage = 1.75 V Quantities of PEFS-PL80P-21| System Work Normally
---|---
System Voltage < 0.9 V Quantities of PEFS-PL80P-11 or
System Voltage < 1.75 V Quantities of PEFS-PL80P-21| System Work Abnormally
5.2 Troubleshooting
Description | Troubleshooting |
---|
The status light is always off.
PVRSS doesn’t work.| 1) Check if the button of the controller is turned to
off;
2) Check if the AC power supply is normal;
3) Check if the AC voltage is over the operating voltage range;
4) Contact Projoy.
The status light is on.
The DC voltage of the inverter is 0V.
PVRSS doesn’t work.| 1) Test the voltage of the DC cable. If the voltage of
the DC cable is zero, check the connection of the DC cable.
2) If the voltage of the DC cable is normal as described in §5.1.2, there is
something wrong with the DC input of the inverter. Contact the supplier of the
inverter.
3) Contact Projoy.
The status light is on.
The DC voltage of the inverter is 0V.
PVRSS doesn’t work.| 1) Check if the button of the controller is turned to
off;
2) Check if the AC power supply is normal;
3) Check if the AC voltage is over the operating voltage range;
4) Contact Projoy.
The status light is on.PVRSS works well.
DC voltage of the inverter is
abnormal (§5.1.2).| 1) Test the output voltage of each rapid shutdown device.
If the output voltage is not 0.9V or 1.8V. Replace the rapid shutdown device.
2) Contact Projoy.
Recycling and Disposal
This device should not be disposed of as residential waste. A rapid shutdown device or controller that has reached the end of its life and is not required is to be returned to your dealer or you must find an approved collection and recycling facility in your area.
Guarantee Service
Within the warranty period of the products, the invoice and date of purchase
are required for the service. Besides, the trademark on the product should be
clearly visible, otherwise, warranty is not available.
The product warranty covers all damage caused by design or production.
However, the followings are not covered:
- Beyond the warranty period;
- No valid warranty card and product serial number;
- Damage in transportation;
- Incorrect use, operation, and modification;
- Operation in a very harsh environment not as described in this manual;
- Out of the scope of installation and use specified in relevant international standards;
- Damage is caused by the abnormal natural environment.
Contact us
Projoy Electric Co., Ltd.
Tell: +86-512-6878 6489
Web: https://en.projoy-electric.com/
Add: 2nd Floor, Building 3, No. 2266, Taiyang Road, Xiangcheng District,
Suzhou
References
- Tric.com may be for sale - PerfectDomain.com
- Home - Projoy Electric
- DC Isolator, AC Isolator, DC Isolator Switch, Solar PV Isolator Switch manufacturer-Projoy Electric
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>