novus Automation TL400-V Laser Level Transmitter User Guide
- June 13, 2024
- NOVUS AUTOMATION
Table of Contents
novus Automation TL400-V Laser Level Transmitter
SAFETY ALERTS
The symbols below are used in the device and throughout this manual to draw the user’s attention to valuable information related to device safety and use.
CAUTION
Read the manual fully before installing and operating the device.
CAUTION OR HAZARD
Risk of electric shock.
ATTENTION
Material sensitive to static charge. Check precautions before handling.
All safety recommendations appearing in this manual must be followed to ensure personal safety and prevent damage to the instrument or system. If the instrument is used in a manner other than that specified in this manual, the device’s safety protections may not be effective.
This product emits radiation in the infrared range and uses LASER technology. It has been developed to meet the class 1 requirements of IEC 60825-1:2014 (Third Edition). Provided that the user follows NOVUS recommendations described in this manual, the radiation emission will remain within the limits of class 1. Lenses or any form of optical device should not be used to alter the product performance.
PRESENTATION
TL400-V is a non-intrusive level transmitter with no moving parts, using an infrared laser technology (~920 nm) that is completely safe to the human eye (LASER CLASS-1). Its measurement principle is based on ToF (Time of Flight), providing an accurate and reliable distance measurement, regardless of the color or transparency of the surface1 . It can be used to measure from grains and solids to transparent liquids such as water and diesel. It has a robust housing, withstanding pressures up to 6 bar, and excellent resistance to flammable materials such as diesel, gasoline, or alcohol. With a measurement capacity up to 4 meters and 1 Hz sampling, TL400-V is an excellent alternative to level sensors based on ultrasonic, capacitive, or floating technology since it does not need to be in contact with the surface to be measured. The transmitter has a dedicated filter for non-static tank applications based on machine learning algorithms that have been validated in real-life situations and have configurable parameters for specific applications.The sensor allows you to configurate the opening angle, ranging from 12° degrees for irregular tank or reservoir applications to 27° degrees for tanks where the base diameter is half the height to be measured.
TL400-V has a BLE (Bluetooth Low Energy) interface. With it you can:
- Configure the analog output (0.5-4.5 V), according to the specific application
- Configure the opening angle of the sensor (from 12° to 27° opening degrees)
- Customize the tank with up to 20 points in level percentage
- Perform sensor diagnostics in real time
- Configure the dynamic filter based on the application
- Update the firmware to the most current version, which will always be available on NOVUS website
These functions can be adjusted through the SigNow app, available for Android and iOS. The sensor can retransmit the analog output in Level, Volume, or Distance. Level and distance are set in your preferred unit (mm, cm, m, inches, or feet) and volume is always displayed in percent.
IDENTIFICATION
OVERVIEW
The housing of the equipment is made of polycarbonate, an extremely resistant
material, and was built to meet the IP68 protection index. It has a gasket in
NBR material.
IDENTIFICATION
The identification label, located on the top of the housing, shows the model,
serial number, and product code. To make it easier to see the serial number,
you can also scan the QR Code.
TL400-V
TL400-V is suitable for vehicle installation. It has a cable with a Superseal
connector.
INSTALLATION
ELECTRICAL INSTALLATION
INSTALLATION RECOMMENDATIONS
- Electronic and analog signal drivers must run the plant separately from the output and power leads. If possible, in grounded conduits.
- The power supply for the electronic instruments must come from a proper power grid for instrumentation.
- It is recommended to use RC FILTERS (noise suppressors) in contactor coils, solenoids, etc.
- In control applications, it is essential to consider what can happen when any part of the system fails. The device internal security features do not guarantee full protection.
ELECTRICAL CONNECTIONS
DIMENSIONS
TL400-V
The figures below show the dimensions of the TL400-V and an overview of the
equipment:
5-HOLE TO 4-HOLE ADAPTER
The figure below shows the dimensions and drilling of the adapter for
attaching the equipment:
MECHANICAL INSTALLATION
To install the level sensor, the following tools are required:
- 4.0 to 4.2 mm drill for the screws
- 20 to 40 mm hole saw for the sensor
- Pencil for marking the hole points After that, you must follow the steps below:
- Perform the marking: While the tank is empty, use the gasket to mark the hole points of the 5 screws and the sensor in the center of the ring. When using an adapter, mark the hole points of the 4 screws and the sensor in the center of the ring.
- Install: Use a drill with the hole saw to drill the tank in the center, where the sensor will be installed. Then drill 4 mm holes at the marked positions. The gasket has a small cutout between the longer distance holes where the sensor output cable will be positioned.
- Make the connections: After placing the equipment in the desired location, tighten the screws and then make the electrical connections (see ELECTRICAL CONNECTIONS section).
- Configure: Use the SigNow app to configure the equipment (see SIGNOW APP chapter).
TL400-V WITH AND WITHOUT ADAPTER
The figures below show versions of the equipment with and without the adapter
(optional accessory):
To install the adapter and the gasket, the correct position must be observed:
INSTALLATION EXAMPLES
The figures below show examples of how to position the equipment, according to
the environment where it will be installed and considering the application:
- Install the equipment so that the laser is perpendicular to the surface of the substance to be monitored.
- Ensure that the equipment is positioned away from the area where the liquid or solid will be poured into the tank or reservoir.
The figures below show examples of situations to be avoided during the installation process:
- Do not install the equipment sideways or with the laser pointing into the area where the liquid or solid will be poured into the reservoir.
- Do not install the equipment over a faucet, which will completely block the laser.
Improper application will block the equipment from measuring the area to be monitored as intended. For this reason, you must always ensure that it is positioned perfectly perpendicular to the surface.
TL400-V is not recommended for applications in environments with direct sunlight. In such cases, measurement may be affected.
DEFINITIONS
This chapter presents definitions of terms to be considered throughout the manual.
TECHNICAL TERMINOLOGY
TL400-V uses a few specific terms, such as ullage, level, distance, and
height, which can be analyzed below:
- Ullage: Term used to describe the difference between the height of the tank and the surface of the liquid or solid.
- Level: Term used to describe the height of the liquid or solid when compared to the bottom of the tank.
- Distance: Term used to describe to the height between the surface of the liquid or solid and TL400-V (Offset = 0).
- Tank Heigh: Term used to describe the total tank height.
- Filter Type: The equipment allows using a static filter or a dynamic filter. The static filter is a moving average with a configurable response time of at least 1 second. The dynamic filter, on the other hand, constitutes a stable measurement algorithm for applications where the tank may be in motion with a fixed response time of 1 minute and 40 seconds. If you need to use the dynamic filter with another response time, please contact Technical Support.
- Angle of View: Also known as Field of View (FoV), this parameter allows you to define the field of view for the sensor. To achieve the best sensor performance, it is recommended that it always be as large as possible. When using a sensor based on optical principles, it is important that the installation ensures that the bottom of the sensor is directed at the liquid surface in a fixed and perpendicular way, as shown in the figure below.
- Installation Offset: Term used to describe the difference between the height where TL400-V was installed and the maximum tank height. The value must be inserted in the configured unit of measure. You must define an installation Offset when the maximum tank height and the height at which TL400-V is installed are not the same.
- Full Tank (URV): Term that corresponds to the height of the tank at which the analog output will show a maximum value.
- Empty Tank (LRV): Term that corresponds to the height of the tank at which the analog output will show a minimum value.
SOME TYPES OF TANKS
TL400-V can be used with several types of tanks, as shown in the examples
below:
If the options do not fit the type of tank being used, TL400-V also allows you to create custom tanks. This feature is useful for tanks that are shaped with curves, rises, and other irregularities. When you select this option, you will need to perform a linearization at specific points on the tank. Up to 20 linearization points are allowed. The data configured in these parameters will always be in centimeters.
The custom curve can also be used to correct a possible non-linearity of the level sensor’s measurement. To use the function for this purpose, you must go to the Diagnosis tab. In the example below, the measurement inferred in the Diagnosis tab with an empty tank was 80 cm; with the tank at 50 %, it was 40 cm. Regardless of the actual distance measured by other means, simply insert the points as follows to obtain a custom curve: When using the Diagnostics tab, you must take the measurements of the desired curve and write down the distance values versus the desired percentage. Once you have all the values from 0 to 100 % with the desired number of points (with a maximum of 20 points), follow the path Configuration > Advanced > Input > Tank Calibration and insert the points as shown in the figure to the side. To delete a calibration point, simply drag it to the right. After inserting all the points, follow the path Menu > Send.
- Before sending the configuration, it is suggested that you check the configured parameters. The parameters will be overwritten in the equipment.
To check if the curve is in accordance with the set value, you can follow the path Diagnostics > Advanced > Forcing and force a distance, which will allow you to analyze if the analog output response is adequate.
SIGNOW APP
SigNow app is the ideal tool to use your TL400-V on a daily basis. Available for Android and iOS smartphones, it allows you to configure or perform diagnostics on the equipment. Connection to the equipment can be made via the Bluetooth interface. SigNow can be downloaded for free from Google Play Store or App Store. If your smartphone does not support BLE technology, has an Android version lower than 9 or an iOS version lower than 12, the application will not be available for download. This manual provides basic information about configuring your TL400-V. For more information about SigNow features, see the specific manual.
BLUETOOTH INTERFACE
TL400-V has a Bluetooth Low Energy (BLE) interface, compatible with
smartphones that have Bluetooth modules with version 4.0 or higher. The
Bluetooth interface allows you to configure the equipment through the SigNow.
PAIRING TL400-V WITH YOUR SMARTPHONE
Once the SigNow app has been installed, you must enable the Bluetooth
interface of your smartphone to connect to the TL400-V. After that, simply
open the app and follow the steps below:
CONFIGURING YOUR TL400-V
INFORMATION
Upon successfully completing the pairing process between smartphone and
device, SigNow will display the configuration screens. The Information screen
is the first one:
The Info section of the Configuration screen presents information such as serial number, firmware version, BLE address and device tag, which can be set in the Device Tag parameter of the Basic section. None of this information is editable. By clicking the Home button, you will be redirected to the SigNow home page. By clicking the button, SigNow will display a set of buttons, as shown in the figure below.
By clicking the Manual button, you will be redirected to the online manual for the equipment. By clicking the Support button, you will be redirected to NOVUS Technical Support page. The Send button allows you to send the settings to the equipment. The Save button allows you to save these configurations in a file with a .sigc extension, which can be used later by clicking the Open Configuration button on SigNow.
BASIC CONFIGURATION
By clicking the Basic button, SigNow will display parameters regarding the
basic configuration of the equipment:
By default, the equipment is already configured with the magnitude Level (the magnitude can be changed in the Input subsection of the Advanced section, as will be shown later), which allows you to configure the following parameters:
- Device Tag: Allows you to define a tag with up to 20 characters for the equipment.
- Level and distance: Unit: Allows you to define the unit of measurement to be used (meters, centimeters, millimeters, inches, feet).
- Installation Offset: Allows you to define the installation Offset.
- Tank heigh: Allows you to define the height of the tank to be used.
- Reverse output polarity: Allows you to invert the output polarity.
- Output minimum value: Allows you to define a minimum level value.
- Output maximum value: Allows you to define a maximum level value.
ADVANCED CONFIGURATION
By clicking the Advanced button, SigNow will display sections regarding the
advanced configuration of the equipment:
Here you can select the parameter group to be configured: Input, Output, Advanced Filter, or Security. You can also change the equipment tag.
INPUT
By clicking the Input button, SigNow will display sections regarding the input
settings of the equipment:
By default, the parameter Magnitude related to the analog output is set as Level, which allows you to configure the following parameters:
- Level and distance: Unit: Allows you to define the unit of measurement to be used (meters, centimeters, millimeters, inches, feet).
- Installation Offset: Allows you to define the installation Offset.
- Tank heigh: Allows you to define the height of the tank to be used.
- Filter type: Allows you to define the type of filter to be used.
- Viewing angle: Allows you to define the viewing angle of the equipment: 15°, 17°, 19°, 21°, 24°, or 27°.
- Reading mode: Allows you to set the measurement mode: 1 − SHORT (for distances shorter than 1 meter), 2 − MEDIUM (for distances up to 3 meters) or 3 − LONG (for distances up to 4 meters). LONG mode is the most recommended mode for most applications. If the parameter Magnitude related to the analog output is set to Distance, these same parameters will be displayed.
When configuring the parameter Magnitude related to the analog output with the Volume option, in addition to the parameters shown in the previous figure, you can also change the parameter Tank Type (Vertical cylinder, Horizontal cylinder, Rectangular, or Custom). According to the tank type selected, SigNow will present configurable parameters to determine the size and measurement of the tank to be used. If none of the standard tank types suits your needs, you can select the Custom option.Here, you can add calibration points for the tank. You can set up to 20 linearization points by adding the desired values. The custom tank type can be useful for tanks that are shaped with curves, rises, or other irregularities. When configured to Custom, the calibrated points should go from the greatest distance to the smallest distance (smallest volume to greatest volume), as shown in the example below:
POINT | DISTANCE | VOLUME (%) |
---|---|---|
1 | 200 | 0 |
2 | 75 | 50 |
3 | 20 | 100 |
The figure at the side exemplifies the calibration points in a tank with an irregular form.
OUTPUT
By clicking the Output button, SigNow will display sections regarding the
output settings of the equipment:
The parameter Error action on analog output allows you to configure the error action of an equipment with 0.5-4.5 Vdc output. This parameter has the following options:
- Low (0.5 Vdc)
- High (4.5 Vdc)
- None
- Low/High (0.5 Vdc/ 4.5 Vdc)
In addition, you can set a minimum value and a maximum value for the output.
ADVANCED FILTER
By clicking the Advanced Filter button, SigNow will display parameters for
configuring the advanced filter:
- Size of the main vector: Allows you to define the number of samples to be collected by the filter. If the user sets this parameter to 100, for example, TL400 will only consider the first 100 values collected.
- Size of the distance vector: Allows you to select the best quality samples from among those collected by the filter (i.e., those with the least variation in values).
- Median index: Allows you to reorder the ideal samples, i.e., those already filtered by the Size of the distance vector parameter, now according to distance.
- Enable Blocking Filter: Allows you to enable the Blocking Filter. It prevents values that are too far off from the previous value from being displayed in the output.
- Acceptance percentage: Allows you to define the maximum percentage of variation between the previous value and the value to be accepted by the Enable Blocking Filter parameter.
- Percentage increase: Allows you to set the percentage of values to be incremented, according to the criterion and each time a new value outside this percentage occurs.
- Acceptance counts: Allows you to set the maximum number of times that the Blocking Filter, enabled in the Enable Blocking Filter parameter, can reject data outside the standard defined in the Acceptance ratio parameter.
- Acceptance ratio: Allows you to reduce the oscillation or data peaks of the analog output. The ADVANCED FILTER chapter provides more complex information on how the parameters of this filter work, as well as examples and graphs.
SECURITY
TL400 allows you to protect the device’s connection with a password. By
default, the password is disabled. However, it is possible to create a numeric
password of between 4 and 10 digits. Once the device has received a password,
the connection can only be made by entering it. This feature prevents access
by unauthorized users. If the configured password is lost, the master password
can be used, consisting of the number 9 + the last 3 digits of the serial
number.
- Master password = 9 + last three digits of the device’s serial number.
By clicking the Advanced Filter button, SigNow will display parameters referring to the security settings of the equipment:
DIAGNOSTIC
By clicking the Diagnostics button on the SigNow home screen, the app displays
information about the connected equipment:
The Info section of the Diagnostics screen presents information such as serial number, firmware version, BLE address and device tag, which can be set in the Configuration section. None of this information is editable. By clicking the Manual button, you will be redirected to the online manual for the equipment. By clicking the Support button, you will be redirected to NOVUS Technical Support page.
The Advanced button is in the lower right corner of the Info screen. By clicking on this button, you can access the advanced diagnostic settings, which allow you to force values to check the correct operation of the equipment and evaluate the settings applied to it.
The Advanced section of the Diagnostics screen allows you to:
- In the first part of the screen, you can see the current values of the equipment, according to the configuration.
- In the second part of the screen, in the Forcing subsection, you can force specific values by selecting any of the four available options:
- Distance: This parameter allows you to force a distance value for the equipment.
- Level: This parameter allows you to force a level value for the equipment.
- Volume: This parameter allows you to force a volume value for the equipment.
- Analog Output: This parameter allows you to force the analog voltage output. In either case, the output must be enabled to force test values.
By selecting one of the forcing options in the section above, you will be redirected to the appropriate screen, where you can set specific values for each parameter:
FIRMWARE UPDATE
To update the firmware, you must click on the Firmware button, located at the bottom of SigNow home screen. After that, you must select the equipment to be used and perform the pairing process.
By clicking on the Search Files button, located in the left corner of the screen, you can search for previously downloaded files on your smartphone. By clicking on the Check Files Online button, located in the right corner of the screen, you can check online for firmware files. After that, simply select the file to be used by SigNow and perform the update process. ADVANCED FILTER
WHEN USE THE ADVANCED FILTER
There are applications in which the sensor may show instabilities in level
measurement. In general, these instabilities are related to the optical
properties of the application, such as reflective walls and the incidence of
sunlight. In these cases, to improve the result, TL400 has a filtering
algorithm that is based on the quality of the measurements of a group of
samples. The advanced filter can be configured within the Advanced
Configuration section of SigNow app (see ADVANCED FILTER section of SIGNOW APP
chapter). By configuring certain parameters, this algorithm can significantly
reduce measurement instabilities. To better exemplify the need to use the
advanced filter in certain situations, below is a real example of a
measurement that doesn’t need the filtering algorithm (left) and one in which
it was necessary to use it (right). The raw measurement is in blue; the
filtered measurement is in orange.
Internally, the algorithm is based on a sample sorting logic that acts according to the quality measure of the measurement itself and based on sorting according to the distance to collect the most stable measure of the group (median). Below is a description of the parameters and their influence on the measurement result.
A MORE DETAILED EXPLANATION OF THE ADVANCED FILTER PARAMETERS
The Advanced Filter of SigNow app is composed of 8 parameters. Below, it is
possible to see a more complex explanation about their functioning.
“SIZE OF THE MAIN VECTOR” PARAMETER
This parameter allows you to define the number of samples to be collected by
the filter. If the user sets this parameter to 100, for example, TL400 will
only consider the first 100 values collected. The higher the value set, the
greater the number of samples, the more stable the result (since there is a
greater amount of data to analyze) and, consequently, the slower the filter.
“SIZE OF THE DISTANCE VECTOR” PARAMETER
This parameter allows you to select the best quality samples from among those
collected by the filter (i.e., those with the least variation in values). More
precisely, the vector will order the samples from the lowest standard
deviation to the highest standard deviation (always considering the value 1 as
the ideal standard deviation), creating an internal ordering, not visible to
the user. Thus, the first measurement on this list will always have the
smallest deviation and is theoretically the most accurate within this margin.
When performing an analysis from 1 up to the size configured in the Size of
the main vector parameter, the measurements in this set will be those that
survive after the other values have been discarded. If you put 100 in the Size
of the main vector parameter and 20 in Size of the distance vector, for
example, the parameter will select the 20 best of these 100 samples, rejecting
the others. This parameter must be smaller than the one configured in the Size
of the main vector parameter. The lower the value, the more selective the
filter will be, and the fewer samples will be considered. The more unstable
the behavior of the sensor, the “worse” samples should be discarded and
therefore the smaller the Size of the distance vector should be. When looking
for greater stability and in conditions where response time is relevant, it is
possible to increase the Size of the main vector and the Size of the distance
vector. By setting the Size of the main vector parameter to 400 and the Size
of the distance vector parameter to 350, for example, an 80 cm measurement
application will have an accuracy of 3 millimeters.
“MEDIAN INDEX” PARAMETER
This parameter allows you to reorder the ideal samples, i.e., those already
filtered by the Size of the distance vector parameter, now according to
distance. In this case, the Median index parameter will ignore the standard
deviation, opting instead to analyze the median, which would be thecentral
number of these values (the number of times that a value is repeated among the
number of samples), either increasing or decreasing. The Median index displays
the position of the value in relation to the median containing the output
value to be considered by the filter. The values that are most repeated among
the samples collected are given the position 0 as an index. Samples with lower
values receive negative indexers, while higher values receive positive
indexers. If the sensor is “missing too much” when collecting data, it is
possible to reduce this difference by selecting a smaller position, using a
Median index value that is less than 0. The figure below exemplifies the
position of the median, according to symmetrical situations (ideal situation
not in line with reality), distortion to the right (negative indexers) and to
the left (positive indexers):
ENABLE BLOCKING FILTER” PARAMETER
This parameter allows you to enable the Blocking Filter. The Blocking Filter
prevents values that are too far off from the previous value from being
displayed in the output. Whenever the TL400 collects a new sample, it assesses
whether it is within this acceptance percentage. If so, it will be accepted.
Otherwise, it will be ignored. Once Enable Blocking Filter has been enabled,
the maximum percentage of variation allowed must be set in the Acceptance
percentage parameter.
ACCEPTANCE PERCENTAGE” PARAMETER
This parameter allows you to define the maximum percentage of variation
between the previous value and the value to be accepted by the Enable Blocking
Filter parameter. If the current value exceeds the percentage set in this
parameter, the Blocking Filter will ignore the discrepant value. In situations
where the TL400 identifies variations of more than 5 % between samples and if
the Acceptance percentage parameter is set to this percentage, for example, it
will only accept variations of up to 5 % between one sample and another.
PERCENTAGE INCREASE” PARAMETER
This parameter allows you to set the percentage of values to be incremented,
according to the criterion and each time a new value outside this percentage
occurs. If values fluctuate outside the percentage defined in Percentage
increase, for example, certain measures will no longer be accepted, and the
acceptance rate will be increased by the increment. Whenever a new measure
fails to enter, the acceptance criterion is increased, increasing the chance
that the next sample will be accepted.
ACCEPTANCE COUNTS” PARAMETER
This parameter allows you to set the maximum number of times that the Blocking
Filter, enabled in the Enable Blocking Filter parameter, can reject data
outside the standard defined in the Acceptance ratio parameter. That is, it
will register the number of occurrences of new measures being blocked and,
when it reaches the maximum value configured, it will accept these new values
at a percentage defined in the Acceptance ratio. The Acceptance counts
parameter is complementary to the Percentage increase parameter. If the value
set in Acceptance counts is reached, the blocking filter will accept the next
values, even if they exceed the value set in the Percentage increase
parameter. This allows data to be collected even during sudden changes in
level. When filling the tank quickly, for example, this parameter prevents the
TL400 from taking too long to identify changes in the tank level, since it
will start accepting new samples after a sudden variation has occurred
repeatedly and has reached the value set in this parameter:
ACCEPTANCE RATIO” PARAMETER
This parameter allows you to reduce the oscillation or data peaks of the
analog output. When it collects a new value, it analyzes the acceptance rate,
which is why this new value will be accepted. If it is 1, the new value
accepted will be the new value itself. If it is 2, it will be half the new
value.
USAGE EXAMPLES
EXAMPLE 1: 3-METER HIGH AND 2-METER WIDE WATER TANK
In one application, the user intends to apply the sensor to measure a tank in
a water tank with a tank height of 3 meters, the maximum level being 2.8
meters and with the bottom of the tank as the minimum level. It is also
expected to get the current measurement proportional to the level, i.e. 20 mA
at the maximum level (minimum distance) and 4 mA at the minimum level (maximum
distance). Here is an example of parameter configuration for this application:
- Magnitude related to the analog output: Level
- Unit: cm
- Tank height: 300 cm
- Offset: 0 cm
- Filter type: Static
- Filter time constant in seconds: 20
- Angle of view: 27°
- Reading mode: Long
- Error action on analog output: None
- Invert output polarity: No
- Value for minimum output : 0
- Value for maximum output : 280
EXAMPLE 2: 80 CM OIL TANK
When performing the diagnosis of the measurements that fill the tank of an oil
tank with 80 cm high and 10 cm wide, it was verified that, although
proportional to the level, the informed measurement did not match the real
value. In this case, as shown in the information below, the user intends to
correct the sensor reading with a 5-point curve:
PERCENTAGE OF VOLUME FILLED (PERCENT)| DISTANCE MEASURED ON DIAGNOSTIC
TAB (CM)| REAL DISTANCE (CM)
---|---|---
0 % – Empty tank| 100| 80
25 %| 85| 60
50 %| 50| 40
75 %| 25| 20
100 %| 10| 0
In this case, you must insert the points through the following path: Configuration > Advanced > Input > Tank Calibration, as shown in Figures 36 and 37. Then, in Diagnostic > Advanced, you can check the volume according to the distance, depending on the configured calibration. When using the custom curve, the tank height value will be ignored for the volume calculation.
TECHNICAL SPECIFICATIONS
FEATURES | TL400-V |
---|---|
Dimensions | 241.7 x 66 x 31 mm |
Distance Measurement | Configurable from 0 to 4000 mm. |
Resolution | Maximum of 30 mm but can reach a minimum of 1 mm if in good |
measuring conditions.2
Sampling| 1 Hz
Output| 0.5 – 4.5 Vdc with 1 mV resolution.
Assembly| Standard SAE 5 holes or adapter for standard 4 holes.
Consumption| <70 mA @ 12V or <40 mA @ 24V
Power Supply| 8 – 33 Vdc
Storage Temperature| -20 to 80 °C
Operation Temperature| -20 to 80 °C
Protection Index| IP68
Housing| Polycarbonate
Configuration Application| SigNow (for smartphones)
Certifications| CE, FCC, Anatel (13883-22-07089), UKCA, LASER CLASS 1
CERTIFICATIONS
FCC
This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Any changes or modifications not
expressly approved by the party responsible for compliance could void the
user’s authority to operate this equipment.
RF Exposure: 20 cm shall be maintained between the antenna and users, and the transmitter module may not be co-located with any other transmitter or antenna. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
CE MARK / UKCA
This is a Class A product. In a domestic environment, this product may cause
radio interference in which case the user may be required to take adequate
measures.
ANATEL
This device is homologated by ANATEL, according to the regulated procedures
for conformity assessment of telecommunications products, and meets the
technical requirements applied. This equipment is not subject to the
protection from harmful interference and may not cause interference with duly
authorized systems. For more information, see the ANATEL website:
www.anatel.gov.br.
A good measuring environment consists of a tank where the sensor can work at a maximum opening angle of 27°, without the incidence of sunlight. Factors that worsen the measurement conditions involve the reflectivity of the walls and bottom of the tank and the incidence of sunlight.