mars 7602-457 Communicating Programmable Thermostat Instruction Manual
- June 13, 2024
- MARS
Table of Contents
- 7602-457 Communicating Programmable Thermostat
- SAFETY CONSIDERATIONS
- User Menu Settings
- Installer Menu Settings
- System Configuration
- Accessory Configuration
- Input Dealer Information
- Humidity Configuration
- Temperature Algorithm
- Demand Reduction Configuration
- Service Mode
- Restore Defaults
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Installation Manual
7602-457
Communicating, Programmable Thermostat
7602-457 Communicating Programmable Thermostat
Caution:
These instructions are intended to be used by the installer or service
personnel. End users are NOT advised to change or modify any of these
settings. Doing so may cause the equipment to stop working properly and/or may
void the warranty on both the thermostat and the equipment.
Comfort-Aire and Century’s 7602-457 Communicating, Programmable Thermostat is
the perfect compliment to a Comfort-Aire and Century’s Geothermal Heat Pump
System and represents a significant advancement in thermostat communicating
technology. For homeowners, the 7602-457 provides highly customizable climate
control features designed to maximize comfort and reduce the amount of energy
consumed by the Comfort-Aire or Century Geothermal Heat Pump System. For
dealers, it represents a significant, industry leading advancement in
configuration, monitoring and diagnostics from the thermostat. Please read the
following instructions carefully to maximize the comfort and cost-saving
potential of your Comfort-Aire or Century Geothermal Heat Pump System.
SAFETY CONSIDERATIONS
Improper wiring or installation may damage thermostat. Wiring must conform to
local and national electrical codes
WARNING!
WARNING! Before installing thermostat, turn off all power to unit. There
may be more than one power disconnect. Electrical shock can cause personal
injury or death.
INSTALLATION CONSIDERATIONS
The thermostat requires no batteries. The thermostat is not a power stealing
device and MUST have both R and C terminals connected. See Diagram
INSTALLATION
THERMOSTAT LOCATION
Thermostat should be mounted:
- Approximately 5 ft. (1.5m) above floor.
- Close to or in a frequently used room, preferably on an inside partitioning wall.
- On a section of wall without pipes or duct work.
Thermostat should NOT be mounted:
- Close to a window, on an outside wall, or next to a door leading to the outside.
- Exposed to direct light and heat from a lamp, sun, fireplace, or other temperature-radiating object which may cause a false reading.
- Close to or in direct airflow from supply registers.
- In areas with poor air circulation, such as behind a door or in an alcove.
THERMOSTAT INSTALLATION
-
Turn off all power to unit.
-
If an existing thermostat is being replaced:
A. Remove existing thermostat from wall.
B. Disconnect wires from existing thermostat, one at a time. Be careful not to allow wires to fall back into the wall.
C. As each wire is disconnected, record wire color and terminal marking.
D. Discard or recycle old thermostat.
NOTE: Mercury is a hazardous waste and MUST be disposed of properly. -
Separate the thermostat from base.
-
Route thermostat wires through hole in base. Level base against wall (for aesthetic value only – thermostat need not be leveled for proper operation) and mark wall through 2 mounting holes.
-
Drill two 3/16-in. mounting holes in wall where marked. (Note: Mounting holes on thermostat are designed to fi t on a horizontal J-box).
-
Secure base to wall with 2 anchors and screws provided making sure all wires extend through hole in base.
-
Connect wires to proper terminal of the connector block in the thermostat.
-
Push any excess wire back into wall. Excess wire inside the thermostat case can interfere with proper air fl ow across the temperature sensor. Seal hole in wall to prevent air leaks. Leaks can affect operation.
-
Install thermostat on base.
-
Turn on power to the unit.
WIRING DIAGRAMS
All excess wire should be pushed back into the wall as far as possible. Excess
wire inside the thermostat plastic case may interfere with the air fl ow across
the temperature sensor.
Diagram 1: Thermostat Connections
Thermostat Connections
C | 24V Common for Control Circuit |
---|---|
R | 24V Supply for Control Circuit |
A+ | Communications (Positive) |
B – | Communications (Negative) |
GND | Ground |
OD | Outdoor Temperature Sensor |
ID | Indoor Temperature Sensor |
User Menu Settings
1.1 OFFSETS
If you fi nd that the temperature displayed on the thermostat does not
accurately represent the room temperature where the thermostat is located,
this offset function compensates for the difference. The thermostat will apply
an offset between what temperature the thermostat is measuring versus the
temperature that is displayed.
1.1.1 TEMPERATURE OFFSET
The Temperature Offset function allows for calibration of the temperature
sensor.
Adjust the Temperature Offset settings using the up/down arrow buttons. Press
the center button to save changes.
- Indoor Temperature (default 0°F): options: -5°F to +5°F (in 1°F increments)
- Remote Temperature (default 0°F): options: -5°F to +5°F (in 1°F increments)
- Outdoor Temperature (default 0°F): options: -5°F to +5°F (in 1°F increments)
- 1st Stage (default 1°F): options: 1°F to 4°F (in 1°F increments)
- 2nd Stage (default 1°F): options: 1°F to 4°F (in 1°F increments)
- Aux Heat (default 1°F): options: 1°F to 4°F (in 1°F increments)
NOTE 1: The thermostat must be configured for Multistage by installer to
access the 2nd Stage Differential setting. The thermostat must be configured
for Auxiliary Heat by installer to access the Auxiliary Heat Differential
setting.
NOTE 2: The temperature control algorithm must be configured for Differential
control to access the Differential settings by installer.
1.1.2 HUMIDITY OFFSET
If you fi nd that the Humidity level displayed on the thermostat does not
accurately represent the Humidity level of the room in which the thermostat is
located, use the Humidity Offset function to calibrate the humidity sensor.
Adjust the Humidity Offset setting using the up/ down arrow buttons. Press the
center button to save changes.
- Indoor Humidity (default 0%): options: -10% to +10% (in 1% increments)
1.2 AUTO CHANGEOVER TIME
When the thermostat is configured for AUTO mode, the thermostat automatically
selects heating or cooling mode depending on the indoor temperature.
The Auto Changeover Time is the amount of time that elapses before operation
switches from heating to cooling mode or from cooling to heating mode.
Adjust the Auto Changeover Time using the up/ down arrow buttons. Press the
center button to save changes.
- Auto Change Over Time (default 15 minutes):
options: 0 to 120 minutes (in 15 minute increments)
1.3 DEMO MODE
Demo mode is designed to showcase heat pump operation when the unit is
connected to an above ground water loop with the supply air being blown
directly over the water loop.
1.3.1 ENTER DEMO MODE
To enter Demo Mode, navigate to the Service Information screen
(Menu>Settings>Service Information) then press and hold the right arrow for 5
seconds
1.3.2 DEMO MODE OPERATION
Control Demo Mode operation parameters from the Demo Operation screen shown
below.
The starting mode (heating or cooling) depends on the loop temperature at the time when Demo Mode is entered. The unit will operate in heating or cooling based upon the following algorithm.
1.3.3 EXITING DEMO MODE
To exit demo mode, remove power to the thermostat.
Installer Menu Settings
2.1 INSTALLER MENU SETTINGS ACCESS
The Installer Settings can be accessed at any time from the Main Operating
screen by holding the up/down arrows simultaneously for 5 seconds while the
thermostat is in OFF Mode.
2.2 THERMOSTAT CONFIGURATION
Upon initial power up, the communicating thermostat will prompt the installer
for the thermostat configuration settings. Model number and software version of
thermostat and software version of connected DXM2 are also displayed on this
screen.
2.2.1 STAGING
Adjust the staging option using the up/down arrow buttons. Press the center
button to save changes.
- Single Stage – for control of a single stage compressor applications
- Multi-Stage (default) – for control of multistage compressor applications
2.2.2 AUXILIARY HEAT
Adjust the Auxiliary Heat options using the up/down arrow buttons. Press the
center button to save changes.
- Electric (default) – for control of a system with electric auxiliary heat
- Multi-Fuel – for control of a system with furnace for auxiliary heat
- No Auxiliary Heat – for control of a system with no auxiliary heat
2.2.2.1 AUXILIARY HEAT CONFIGURATION
Select Electric Auxiliary Heat mode
- Auxiliary Heat to Supplement Pump
- Auxiliary Heat for Emergency Heat Only
System Configuration
Use the System Configuration option on the start-up screen to adjust critical
equipment settings.
The System Configuration information will be automatically obtained from each
communicating control in the system.
Note 1: The Airflow Selection menu (section 3.1) will not be present if
the connected communicating control system has no blower.
Note 2: The Pump Configuration menu (section 3.4) will not be present if
the connected communicating control is configured for No Loop Configuration
(OTHER).
Note 3: The Valve Configuration menu (section 3.5) will not be present if
the connected communicating control is configured for No Loop Configuration
(OTHER).
3.1 AIRFLOW SELECTION
Adjust the airflow settings for each system operating mode using the up/down
arrow buttons. Press the center button to select each item.
- Airflow Settings (defaults stored in control) – valid range: obtained from control (in 25 CFM increments)
- Blower Off Delay (default 60 seconds) – valid range: 0 to 255 seconds (in 5 second increments)
NOTE 1: The Airflow Settings will only be present if the connected communicating control is configured for ECM blower.
NOTE 2: If multiple units are connected to one thermostat, refer to section 3.6 for unit selection.
3.2 OPTION SELECTION
This option allows the configuration of heat pump options to be modified.
Adjust the Option settings using the up/down arrow buttons.
Press the center button to select each item.
- Motorized Valve (defaults stored in control) –valid range: Off, On “On” delays compressor start until the valve is fully open.
NOTE: “Motorized Valve” used here refers to a two-position motorized water valve, not to be confused with the modulating motorized water valve found in the LOOP CONFIG.
- Compressor ASCD (Anti-Short Cycle Delay (default stored in control) – valid range: 5 to 8 (in 1 minute increments)
NOTE 1: The Compressor Anti-Short Cycle Delay setting provides equipment
protection by forcing the compressor to wait a few minutes before restarting.
NOTE 2: If multiple units are connected to one thermostat, refer to
section 3.6 for unit selection.
CAUTION!
CAUTION! This is a Commercial option only and does not alter Residential
unit operation.
3.3 UNIT CONFIGURATION
Adjust the Unit Configuration settings including Heat Pump Family, Heat Pump
Size, Blower Type, and Loop Configuration using the up/down arrow buttons.
Press the center button to select each item.
- Heat Pump Family (default stored in control) – valid range: TE, TY, TES, TEP, TRT, TSM
- Heat Pump Size (default stored in control) – valid range: depends on Heat Pump Family setting
- Blower Type (default stored in control) – valid range: NO BLOWER, 2-SPD PSC, COM ECM-V, 1-SPD PSC, 2-SPD CTM, PWM ECM, VFD
- Loop Config (default stored in control) – valid range: Other, VS PUMP, MOD VALVE
Airflow, pump and valves can be configured from ‘System Configuration’ screen.
Select ‘VS PUMP’ when applying an internal variable speed fl ow controller with
other fl ow controllers on a single loop in parallel.
NOTE: Refer to section 3.6.3 for multi-unit configuration instructions.
3.4 PUMP CONFIGURATION
Flow™ vs internal flow control pump can be controlled either through
temperature differential (Delta T) or can be set to specific speed (fixed; % of
full speed for each heat and cool stage).
Can be configured for either single pumping or parallel pumping.
Configure temperature differentials at the thermostat for Flow™ units with an
internal fl ow control pump. Adjust the Pump Configuration settings using the
up/down arrow buttons. Press the center button to select each item.
- Heating Delta T (default stored in control) – valid range: 4 to 12ºF (in 1ºF increments)
- Cooling Delta T (default stored in control) – valid range: 9 to 20ºF (in 1ºF increments)
Maximum Heat LWT (valid range based on specific model; refer to model IOM).
Minimum Cool LWT (valid range based on specific model; refer to model IOM).
NOTE: Refer to section 3.6.3 for multi-unit configuration instructions.
To control vs pump by fixed speed, select ‘Pump Control’, press , use down
arrow to select ‘Fixed’, and press to save.
Default stored in control. Valid range: 15% – 90% (in 1% increments)
Heating Stage 1
Cooling Stage 1
Heating Stage 2
Cooling Stage 2
If Loop Option is set to ‘PARALLEL’, valid range changes to 50-90% (in 1%
increments).
Equivalent Model Numbers
Heat Controller| Climate Master
HE-Series| TZ
HZ-Series| TE
HZS-Series| TES
HB-Series 0.5-5T| TC
HB-Series 7-25T| TL
HKV-Series| TL
HRC-Series| TRC
3.5 VALVE CONFIGURATION
Configure temperature differentials at the thermostat for flow™ units with a
motorized modulating valve.
Adjust the Valve Configuration settings using the up/down arrow buttons. Press
the center button to select each item.
- Heating Delta T (default stored in control) – valid range: 4 to 12ºF (in 1ºF increments)
- Cooling Delta T (default stored in control) – valid range: 9 to 20ºF (in 1ºF increments)
NOTE 1: Minimum and Maximum degree values are shown only when the control
is configured with the appropriate values.
NOTE 2: Refer to section 3.6.3 for multi-unit configuration instructions.
For certain commercial multi-unit applications, the modulating valve can be
kept slightly open by choosing an off position value between 3.3-4.0.
NOTE: Off position 0.0 means that the value is fully closed when the unit
is not operating.
3.6 MULTI-UNIT CONFIGURATION
If multiple units are connected to one ATC thermostat upon unit start-up, the
thermostat will automatically register the serial numbers of all units
connected to it.
NOTE: Multiple units may be connected directly to the ATC thermostat or
connected to one another in series, as shown by the figure below.
3.6.1 MULTI-UNIT AIRFLOW SELECTION
In section 3.1, when an installer selects “Airflow Selection” from the System
Configuration menu, the installer may choose the unit to configure by the last 4
digits of its serial number from the following screen.
3.6.2 MULTI-UNIT OPTION SELECTION
In section 3.2, when an installer selects “Option Selection” from the System
Configuration menu, the installer may choose the unit to configure by the last 4
digits of its serial number from the following screen.
3.6.3 Multi-Unit, Unit, Pump, & Valve Configuration
To configure Unit, Pump, and Valve options in sections 3.3- 3.5, the thermostat
must be connected to only one unit at a time.
Accessory Configuration
A service message will flash at the top of the Main screen when a service timer expires to alert the user that it is time to service these options. Refer to DXM2 AOM for instructions on configuring DIP switches to configure accessories. Follow the instructions below to set service timers.
4.1 AIR FILTER
This feature displays an alert to remind the user to change the air fi lter
after the selected time has passed. Adjust the Air Filter Reminder settings
using the up/down arrow buttons. Press the center button to save changes.
- Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
- Calendar Time (default Off) – valid range: Off, 3 to 48 months (in 3 month increments)
4.2 HUMIDIFIER
This feature displays an alert to remind the user to change the humidifier pad
after the selected time has passed.
Adjust the Humidifier Reminder settings using the up/down arrow buttons. Press
the center button to save changes.
- Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
- Calendar Time (default Off) – valid range: Off, 3 to 24 months (in 3 month increments)
4.3 UV LAMP
This feature displays an alert to remind the user to change the UV lamps after
the selected time has passed.
Adjust the UV Lamp Reminder settings using the up/down arrow buttons. Press
the center button to save changes.
- Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
- Calendar Time (default Off) – valid range: Off, 3 to 48 months (in 3 month increments)
4.4 AIR CLEANER
This feature displays an alert to remind the user to clean the fi lter(s) after
the selected time has passed.
Adjust the Air Cleaner Reminder settings using the up/down arrow buttons.
Press the center button to save changes.
- Cumulative Run Time (default Off) – valid range: Off, 400 to 3600 hours (in 100 hour increments)
- Calendar Time (default Off) – valid range: Off, 3 to 24 months (in 3 month increments)
Input Dealer Information
Enter/edit the Dealer Information settings, including Brand Name, Model Number, Serial Number, Contractor Name, and Contractor Phone number, using the up/down arrow buttons. Press the center button to save changes.
Humidity Configuration
Configure humidity control settings (dehumidification/ humidification).
Adjust the Humidity Control settings using the up/down arrow buttons. Press
the center button to save changes.
- Dehumidification – This logic will communicate a Dehumidification output when the humidity is greater than the setpoint (acts as a DE humidistat). The Dehumidification output will not be communicated when the humidity is below the setpoint.
- Humidification – This logic will communicate a Humidification output when the humidity is less than the setpoint (acts as a humidistat). When the Humidification output is active, the fan output will also be active. The Humidification output will not be communicated when the humidity is above the setpoint.
- Both – Incorporates both Dehumidification and Humidification logic.
- None (default) – Dehumidification and Humidification outputs will not be communicated.
Temperature Algorithm
7.1 TEMPERATURE CONTROL
Configure the logic the thermostat uses to meet the temperature setpoints.
- Proportional Integral (default) – This logic will use a combination of temperature differential and operating time to determine the appropriate heating or cooling stages for operation (see NOTE 1).
- Proportional Integral (No Down Staging) – This logic includes the Proportional Integral logic, but in addition the logic keeps all active heating or cooling stages energized until the demand is fully satisfied (see NOTE 1).
- Differential – This logic will only use temperature differential to determine the appropriate heating or cooling stages for operation. This logic will keep all active heating or cooling stages energized until the demand is fully satisfied (see NOTE 2).
NOTE 1: The Proportional Integral options require fist stage heating or
cooling to be active for a minimum of 5 minutes, before energizing second
stage when configured for multi stage operation.
NOTE 2: The Differential option will activate first stage heating or
cooling when the temperature is more than the first stage differential value
(User Manual section 5.6.2.3), below or above the setpoint. Second stage
heating or cooling will be activated when the temperature is more than the
first and second stage differential values combined (User Manual section
5.6.2.3), below or above the setpoint. Third stage heating will be activated
when the temperature is more than the first, second, and third stage
differential values combined (User Manual section 5.6.2.3), below the
setpoint.
7.2 ANTICIPATOR
If you fi nd that the thermostat is overshooting or undershooting the
temperature setpoint value, the Anticipator setting allows for adjustment to
correct the temperature algorithm. When the Anticipator value is set to a
lower number, the thermostat becomes more sensitive and when the Anticipator
value is raised, the thermostat becomes less sensitive. If the thermostat is
overshooting the temperature setpoint, adjust the Anticipator value up to
reduce thermostat sensitivity. If the thermostat is undershooting the
temperature setpoint, adjust the Anticipator value down to increase thermostat
sensitivity.
Adjust the Anticipator setting using the up/down arrow buttons. Press the
center button to save changes.
- Anticipator (default 3): valid range: 1 to 9
7.3 DIFFERENTIAL
The Differential adjustment will vary the number of degrees from the setpoint
before a call for heating or cooling is made.
Use this function if you fi nd that the thermostat is starting a call too
soon/late or staging equipment up/down too quickly/ slowly. For example, with
a 1 ˚F 1st stage differential and a heating setpoint of 70˚F, your thermostat
will not call for heating until the temperature is 69˚F.
Adjust the Differential setting using the up/down arrow buttons. Navigate
between Differentials using the left/right arrow buttons. Press the center
button to save changes.
7.4 CYCLES PER HOUR
The thermostat allows the user to adjust the maximum number of on/off cycles
per hour to maintain the desired indoor temperature.
Adjust the Cycles per Hour setting using the up/down arrow buttons. Press the
center button to save changes.
- 4 (default): operation will start no sooner than 15 minutes after the previous call was initiated
- 6: operation will start no sooner than 10 minutes after the previous call was initiated (can provide tighter temperature control)
7.5 SMART HEAT STAGING
When there is auxiliary heating demand, Smart Heat Staging defines the minimum
amount of time to wait before activating auxiliary heating. If you fi nd that
the thermostat is operating auxiliary heating equipment too quickly/slowly,
this setting allows for adjustment to correct the temperature algorithm.
Adjust the Smart Heat Staging setting using the up/down arrow buttons. Press
the center button to save changes.
- Smart Heat Staging (default Off): options: OFF, 5 – 120 minutes (in 5 minute increments)
7.6 ELECTRIC HEAT LOCKOUT
Electric heat lockout keeps electric heat turned off if the outdoor
temperature is above the specified temperature so as only to use electric heat
when necessary.
Adjust the Electric Heat Lockout setting using the up/down arrow buttons.
Press the center button to save changes.
- Electric Heat Lockout (default Off): options: OFF, 5 – 60°F (in 5°F increments)
NOTE: An outdoor temperature sensor must be installed for this feature to work.
Demand Reduction Configuration
Demand Reduction is activated by an input signal at the unit control board to
reduce the electric load while peak utility rates are high. The Demand
Reduction Configuration mode selects which of the available unit control inputs
is to be used as the activation signal. While a physical input signal is
present at the selected input, the thermostat will implement load reduction by
limiting operation or capacity. Refer to section 5.6.9 in the user manual
(part number 97B0055N02) for more details on Demand Reduction.
Adjust the Demand Reduction Configuration setting using the up/down arrow
buttons. Press the center button to save changes.
- No Demand Reduction (default) – Demand Reduction operating mode will not be activated by a DXM2 input.
- DXM2 Inputs – Assigns a DXM2 input to activate Demand Reduction operating mode.
Service Mode
9.1 MANUAL OPERATION
Manual Operation mode allows the service personnel to manually command
operation for any of the thermostat outputs, blower speed, as well as pump
speed or valve position to help troubleshoot specific components.
NOTE 1: The ECM Airflow adjustment will not be present if the connected
communicating control (DXM2) is not configured for ECM (section 3.3).
NOTE 2: The Pump Speed adjustment will not be present if the connected
communicating control (DXM2) is not configured for Pump (section 3.3).
NOTE 3: The Valve Position adjustment will not be present if the
connected communicating control (DXM2) is configured for Valve (section 3.1).
NOTE 4: If multiple units are connected to one thermostat, refer to
section 9.6
9.2 CONTROL DIAGNOSTICS
Control Diagnostics mode allows the service personnel to view the status of
all physical inputs, switches, temperature sensor readings, as well as the
operational status of the pump at the thermostat.
Navigate between diagnostic screens using the left/right arrow buttons.
NOTE 1: The Pump Status will not be present if the connected
communicating control (DXM2) is not configured for Pump (section 3.3).
NOTE 2: If multiple units are connected to one thermostat, refer to
section 9.6.
9.3 DIPSWITCH CONFIGURATION
Dipswitch Configuration mode allows the service personnel to view the status of
all dipswitch settings for the connected communicating control (DXM2/AXM) at
the thermostat.
Navigate between configuration screens using the left/right arrow buttons.
NOTE 1: The unit control dipswitch settings cannot be changed from the
thermostat.
NOTE 2: If multiple units are connected to one thermostat, refer to
section 9.6.
9.4 FAULT HISTORY
Fault History mode displays the fi ve most recent stored fault codes for the
connected communicating control (DXM2).
Navigate between control fault codes using the up/down arrow buttons. Press
the center button to view more information about the highlighted fault code.
NOTE: If multiple units are connected to one thermostat, refer to section
9.7.
9.4.1 Temperature Conditions
Displays detailed temperature readings that were recorded at the time the
fault occurred.
NOTE: If multiple units are connected to one thermostat, refer to section
9.6.
9.4.2 Flow Conditions
Displays detailed blower and pump speed / valve position readings that were
recorded at the time the fault occurred.
NOTE: If multiple units are connected to one thermostat, refer to section
9.7.
9.4.3 Input/Output Conditions
Displays the status of all physical and communicated inputs, switches, and
control outputs that were recorded at the time the fault occurred.
NOTE: If multiple units are connected to one thermostat, refer to section
9.7.
9.4.4 Confi guration Conditions
Displays the status of all dipswitch settings that were recorded at the time
the fault occurred.
NOTE: If multiple units are connected to one thermostat, refer to section
9.7.
9 .4.5 Possible Causes
Possible causes as to why the fault occurred
NOTE: If multiple units are connected to one thermostat, refer to section
9.7.
9.5 CLEAR FAULT HISTORY
Clear Fault History will clear all fault codes stored in the thermostat as
well as the fault history in any connected communicating controls (DXM2/AXM).
9.6 MULT-UNIT DIAGNOSTICS
If multiple units are connected to one thermostat when Manual Operation,
Control Diagnostics, or Dip Switch Configuration is selected, the service
personnel will see a screen to select a specific unit by the last 4 digits of
its serial number.
NOTE: Multiple units may be connected directly to the ATC thermostat or
connected to one another in series, as shown by the figure below.
9.7 MULT-UNIT FAULT INFO
When multiple units are connected to one thermostat, UNLIKE Mult-Unit
Diagnostics, the service personnel views each units’ fault information by
selecting the next option.
Restore Defaults
The thermostat will reset all settings, excluding the thermostat configuration
settings (section 2), to their factory defaults.
Due to ongoing product improvements, specifications and dimensions are subject
to change and correction without notice or incurring obligations. Determining
the application and suitability for use of any product is the responsibility
of the installer. Additionally, the installer is responsible for verifying
dimensional data on the actual product prior to beginning any installation
preparations.
Incentive and rebate programs have precise requirements as to product
performance and certification. All products meet applicable regulations in
effect on date of manufacture; however, certifications are not necessarily
granted for the life of a product. Therefore, it is the responsibility of the
applicant to determine whether a specific model qualifies for these
incentive/rebate programs.
1900 Walworth Ave., Jackson, MI 49203
Ph. 517-787-2100
www.marsdelivers.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>