Russell SP16AZ Vantix Line iM Heat Pumps User Manual
- June 13, 2024
- Russell
Table of Contents
Russell SP16AZ Vantix Line iM Heat Pumps User Manual
= A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance with
Department of Energy test procedures.
The Bluetooth® word mark and logos are registered trademarks owned by
Bluetooth SIG, Inc. and any use of such marks by Rheem® is under license.
Other trademarks and trade names are those of their respective owners.
Features and Benefits
-
EcoNet® Enabled: Automatic system configuration and optimization
-
Diagnostics & Bluetooth®1 Connectivity: With the Russell® By Rheem Contractor & EcoNet® Apps, built-in technology makes advanced set-up, monitoring, troubleshooting, and repairing the product easier than ever before
-
Variable Speed Twin Rotary Compressor & Inverter Drive:
— Features variable speed operation from 40 to 70% capacity, or 100% capacity via line voltage, with the EcoNet® Smart Thermostat
— 3-speed operation when installed with a 24V two-stage thermostat
— Provides precise temperature control, advanced humidity control and greater efficiency -
Brushless DC Condenser Motors (BLDC): Enhances reliability and allows for easier serviceability
-
Swept Wing Fan Technology: Features quieter operation and improved unit acoustics
-
7 mm Condenser Copper Coil2: Requires less refrigerant allowing for a smaller and lighter footprint while enhancing reliability
-
Inverted Reversing Valve: Allows for faster heat transfer with gravity assist shifting and reduced joint stress for increased reliability
-
Expanded Value Space: 3 in. – 4 in. – 5 in. service valve space – provides a minimum working area of 27-square inches for easier access
-
Triple Service Access: 15 in. wide, industry leading corner service access, two fastener, removeable corner and individual louver panels – makes repairs easier and faster
- The Bluetooth® word mark and logos are registered trademarks owned by
Bluetooth SIG, Inc. and any use of such marks by Rheem® is under license.
Other trademarks and trade names are those of their respective owners. - Does not apply to the 5 ton model.
Heat Pumps
- Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional refrigerant charge required.
- HACR type circuit breaker of fuse.
- Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.
Accessories
Weighted Sound Power Level (dBA)
NOTE : Tested in accordance with AHRI Standard 270-08 (not listed in AHRI)
Unit Dimensions
[ ] Designates Metric Conversions
CLEARANCES
Refrigerant Line Size Information
NOTES:
- Do not exceed 150 ft. linear line length.
- Do not exceed 50 ft. vertical separation between indoor and outdoor units.
- *3/4″ vapor line should only be used for 2 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.
- **1-1/8″ vapor line should only be used for 5 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.
- Always use the smallest liquid line allowable to minimize refrigerant charge.
- Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.
- Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.
- Some longer lineset installations will require additional POE oil to be added to the system. See table below for additional oil volume requirements.
NOTES
- Do not exceed 46 meters linear line length.
- Do not exceed 15 meters vertical separation between indoor and outdoor units.
- *19.05 mm [3/4 in.] vapor line should only be used for 2 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.
- **28.58 mm [1-1/8 in.] vapor line should only be used for 5 ton systems if outdoor unit is below or at same level as indoor unit to assure proper oil return.
- Always use the smallest liquid line allowable to minimize refrigerant charge.
- Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.
- Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.
- Some longer lineset installations will require additional POE oil to be added to the system. See table below for additional oil volume requirements.
Performance Data @ AHRI Standard Conditions – Cooling
NOTE : This data includes DTC (Designated Test Combination) ratings and is for reference purposes only. A full listing of official ratings and system match-ups, along with downloadable certificates, can be accessed from the AHRI website: www.ahridirectory.org.
Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
© 2023 Rheem Manufacturing Company. Russell By Rheem trademarks owned by Rheem
Manufacturing Company.
In keeping with its policy of continuous progress and product improvement,
Russell by Rheem reserves the right to make changes without notice.
Russell by Rheem • 5600 Old Greenwood Road
Fort Smith, Arkansas 72908 •
www.russellbyrheem.com
PRINTED IN U.S.A. 4/23 QG FORM NO. PRR-825 REV. 1
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>