VIESSMANN Vitodens 100-W/111-W Wall Mounted Gas Condensing Boilers User Guide

June 13, 2024
VIESSMANN

VITODENS 100-W / 111-W
Commissioning Quickstart Guide 

This guide highlights the new and unique process for commissioning. For installation, please refer to the detailed steps in the Installation & Service Instructions.

User interface

VIESSMANN Vitodens 100 W111 W Wall Mounted Gas Condensing Boilers - User
interface

| Heating circuit 1 and 2
---|---
| DHW temperature
| System pressure
| DHW ECO function
| Reduced temperature level
| Wifi connection
| Service menu
| Fault display
| Burner status

VIESSMANN Vitodens 100 W111 W Wall Mounted Gas Condensing Boilers - User
interface 2

| OK > confirm settings
---|---
| Menu > opens the main menu
| Up & down > change parameter

Getting started

On the following pages you will find a step by step guide to commission the product by using the control panel. The default parameters are highlighted for each step. Note that you can also use ViGuide – our mobile application – to carry out the commissioning. Important: If you want to connect the boiler to the internet – using ViGuide monitoring – or connect a Viessmann ViCare Thermostat or Vitotrol 100-E you have to use ViGuide. Please refer to the last page of this document to receive more information.

Commissioning steps:

Access Point AP
Indicates the boiler is ready to be set up press 4 seconds to start commissioning from the panel
C.1 Filling programme
ON > moves diverter valve to mid position for ease of filling via filling loop, OFF – default > skips filling programme, press OK to confirm the setting, press 4 seconds to interrupt the filling programme
C.2 Venting programme
ON > pump runs in intervals and diverter moved to mid position, this can take up to 20 mins, OFF – default > skips venting programme, press OK to confirm the setting, press 4 seconds to interrupt the venting programme
C.3 Gas Type
2 – default > natural gas, 3 > liquid gas, press OK to confirm the setting
C.5 Flue System Type
1 > room air dependent (60 mm), 2 – default > room sealed (60 mm / 100 mm), 3

room air dependent (80 mm), 4 > room sealed (80 mm / 125 mm), press OK to confirm the setting
C.6 Flue System Length
press to adjust the length in metres – the default setting is 1 m (an additional length of 1 m must be factored in for every flue bend), press OK to confirm the setting
C.7 Operating Mode
1 > built in time program, 4 > weather comp.,
13 – default > constant operation (switch live) with optional room thermostat,
14 > OpenTherm, press OK to confirm the setting
C.8 Hydraulic/System Scheme
1 > combi or system boiler on S/Y plan, 3 – default > system boiler with 4 pipe cylinder sensor or demand box, additional options for mixed circuits and low loss header are available, please refer to the commissioning section in the manual, press OK to confirm the setting
C.9 Activating Switch Live with Weather Compensation (only available if C.7 = 4)
To activate plug 96 switch live with weather compensation select 1
For additional options, please refer to the commissioning section in the installation manual, press OK to confirm the setting
C.10 EM-EA1 settings
0 – default > no function, for additional options, please refer to the manual (refer to the commissioning section in the installation manual), press OK to confirm the setting
C.11 Date
press to adjust the date > day, month, year, press OK to confirm each setting
C.12 Time
press to adjust the time > hours, minutes, press OK to confirm each setting
C.13 Summer/ Winter Time changeover
ON > time will be changed automatically OFF – default > constant time, press OK to confirm the setting
C.14 Plug 96 additional options
For additional options, please refer to the commissioning section in the installation manual.
Note: This step does not need to be adjusted for switch live activation.
C.15 Vitotrol 200-E
Only when C.7 is set to 4 (weather comp.) select ON to activate Vitotrol 200-E, press OK to confirm the setting
End
After completing the last step the arrow will appear indicating commissioning is complete press OK to confirm the setting and start the flue gas sensor check. The boiler will restart.
FST will appear (the boiler is carrying out flue gas sensor check & will fire for a few seconds to raise sensor temperature). Please wait for this to complete. Once completed the boiler set temperature will appear on the screen and boiler is ready to run.

Viessmann Controls & ViGuide Monitoring

ViGuide

  • Full text explanation assisting you in commissioning the product
  • Connect the appliances to the internet and monitor the product remotely
  • Add Viessmann thermostat solutions to the system like the Vitotrol 100-E
  • Guided spare part replacement supporting you with step by step instructions

The application can be downloaded from the Google Play Store or Apple App Store. For further information scan the QR code:

VIESSMANN Vitodens 100 W111 W Wall Mounted Gas Condensing Boilers -
ViGuide https://play.google.com/store/apps/details?id=com.viessmann.vizard.presentation.release&hl=en&gl=US&pli=1
https://apps.apple.com/gb/app/viguide/id1421720639

Viessmann Account
The Viessmann Account is our single sign on for all of our applications. Once set up you will get access to all our tools including ViGuide & our PartnerPortal. To sign up for a Viessmann account, simply scan the QR code or visit www.viessmann.co.uk/account. It will take you directly to the application form. Once processed you will receive an email. Please confirm your settings in order to verify your account.

VIESSMANN Vitodens 100 W111 W Wall Mounted Gas Condensing Boilers - ViGuide
2 https://docs.google.com/forms/d/e/1FAIpQLScXzz7dAvkQcP38FF5MmVAbiNED
PntQ8t8NlIMeynggs2hOQw/viewform

PartnerPortal

  • Stay informed by receiving the latest news & access our video content
  • Register your installations with Gas Safe
  • Benefit from our VPlus loyalty scheme & collect points with every installation
  • Book courses with our academy team or use our library of video tutorials
  • Discover all of our software applications, tools & services

Once your Viessmann Account is set up, you can access the Partner Portal via the QR code:

VIESSMANN Vitodens 100 W111 W Wall Mounted Gas Condensing Boilers -
PartnerPortal https://partnerportal.viessmann.com/gb/en.html?redirect=https%3A%2F%2
Fpartnerportal.viessmann.com%2Fgb%2Fen%2Fstart.html

Further Information & Support
If further information is needed visit our support page. Here you will find detailed explanations, FAQs & video tutorials. Just scan the QR code to access the page or visit viessmann.co.uk/vitodensgetstarted

VIESSMANN Vitodens 100 W111 W Wall Mounted Gas Condensing Boilers -
PartnerPortal 2 https://www.viessmann.co.uk/en/products/gas-heating/vitodens-tools-and- services.html

6171 178 UK 05/2023
Copyright Viessmann.Duplication and alternative use only with prior written consent. Subject to technical modifications.

Viessmann Limited
Hortonwood 30,
Telford, Shropshire TF1 7YP
Phone: 01952 675000
Email:info-uk@viessmann.com
www.viessmann.co.uk

Documents / Resources

| VIESSMANN Vitodens 100-W/111-W Wall Mounted Gas Condensing Boilers [pdf] User Guide
Vitodens 100-W 111-W Wall Mounted Gas Condensing Boilers, Vitodens 100-W 111-W, Wall Mounted Gas Condensing Boilers, Mounted Gas Condensing Boilers, Gas Condensing Boilers, Condensing Boilers
---|---
| VIESSMANN VITODENS 100-W/111-W Wall Mounted Gas Condensing Boilers [pdf] User Guide
VITODENS 100-W 111-W Wall Mounted Gas Condensing Boilers, VITODENS 100-W 111-W, Wall Mounted Gas Condensing Boilers, Gas Condensing Boilers, Condensing Boilers, Boilers

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

VIESSMANN User Manuals

Related Manuals