UNIKS Rapid Pro Pocket Multifunction Tester User Manual

June 13, 2024
UNIKS

UNIKS Rapid Pro Pocket Multifunction Tester

Product Information

Video Tutorial: https://www.uniks.it/registrazione-prodotto/

Product Registration: Register your product on the provided link to stay updated on news.

Product Usage Instructions

Introduction

Follow the instructions given in the manual to avoid damage to the instrument or dangerous situations. There is a risk of electric shocks due to high voltage. The maximum voltage input is 265V, and connecting the instrument to higher voltage can cause permanent damage and electrical shock.

General Description

The Rapid Pro pocket multifunction tester can perform the following tests:

  1. VOLT and Socket Test (Correct wiring of Plug)
  2. Voltage measurement L-N, TRMS
  3. Residual Current (RCD) type A, AC, and F with CONTACT VOLTAGE measurement
  4. Z LOOP (Global earth resistance in TT system and impedance L-Pe in TN with short circuit current)
  5. Short circuit current
  6. Voltage harmonics up to 49th
  7. THD% (Total harmonics Distortion)
  8. Frequency of the fundamental Harmonics and up to 49th

VOLT and SOCKET TEST

This feature measures the voltage between phase and neutral and tests the socket wiring according to local requirements.

  1. Plug the instrument into the socket.
  2. Select the Voltage function with the button.
  3. The display will show the voltage between Phase and Neutral if the socket is correctly wired and the voltage contact is 50V.

Solution:

  • Adjust the socket wiring
  • Connect Neutral wire
  • Check Earth connection
  • Dangerous Voltage on mass

PRODUCTS REGISTRATION

INTRODUCTION

Congratulations for purchase Rapid Pro, the first multifunction tester in the shape of a socket tester.It allow the test of electrical system according the IEC standard as the common installation tester do.In addition to the TRMS Voltage measurement and the Socket Tester features allow Installation test to be performed from anyone ( RCD, LOOP L-PE ) in according to IEC61557-3 and IEC61557-6. Super bright color Display TFT 1,77” With internal memory for store results.Super- Cap technology let the instruments turn on even when disconnected from the socket.

SAFETY and WARNINGS

Attention: Follow the instructions given in the manual; improper use could cause damage to the instrument or create dangerous situations for the operator.
High Voltage Danger: risk of electric shocks

This products is manufactured following IEC/EN61010-1, guidelines for safety installation testers.Follow this user manual for avoid damage the instruments :

  • Do not measure in high humidity or wet enviroment.
  • Avoid measurement in highly flammable place.
  • Avoid contact with the circuit unders test if you are not measuring
  • Avoid contact with metallic part that can be under voltage
  • If the instruments look broken or damaged please avoid the use for measure.

Maximum Voltage input is 265 V .Do not connect the instrument to higher voltage. Permanent damage to the instruments and electrical shock can occur if you don’t respect this guidelines.

GENERAL DESCRIPTION

Rapid Pro execute the following test:

  1. VOLT and Socket Test (Correct wiring of Plug)
  2. Voltage measurement L-N , TRMS
  3. Residual Current (RCD) type A, AC and F also in AUTO mode with CONTACT VOLTAGE measurement
  4. Z LOOP (Global earth resistance in TT system and impedance L-Pe in TN with short circuit current )
  5. Short circuit current
  6. Voltage harmonics up to 49 th
  7. THD% (Total harmonics Distortion)
  8. Frequency of the fundamental Harmonics and up to 49 th

Function can be selected thorugh the dedicated button. Sub function features can be selected through the arrow button for example for selecting the RCD type or evaluate different harmonics. The instruments is powered from the line and due to the SUPERCAP technology can keep the power even when disconnected from the line. Fully charged supercap allow 45 second after switch off from the line. This allow the user to read the value after the RCD is tripped out(with tripping time) or when is difficult to read the display value Outcome are always GREEN when the measured value is correct in according the local regulations or RED when the test is not passed. In the SOCKET TEST uncorrect value the instruments generate also a sound alarm.

PRODUCT DESCRIPTION

Legend

  1. Antiscratch glass
  2. Display TFT 1,77”
  3. Function
  4. TEST
  5. subfeatures selection
  6. subfeatures selection
  7. SCHUKO plug

Function button allow to select the measure. Display shows the following features: Socket Test / VOLT – RCD – LOOP – Harmonics / Memory. Arrow button ,allow to select subparameters for test and read the memory or to analyze the harmonics value up to 49th. Red button can start the RCD test or LOOP Resistance ( no trip RCD).

VOLT e SOCKET TEST

This feature measure Voltage between phase and neutral and test the socket wiring in according to local requirement.

Operation

Plug the instruments in the socket and select Voltage function with button.Voltage between Phase and Neutral will be shown at display if socket is correctly wired and voltage contact is <50V (Fig 1) error due to the uncorrect wiring is shown(Fig 2 e 3). Green bar indicate every parameter is correct. Frequency can be shown through button .

Wiring Error ( bar is Red and sound alarm)

  • Phase – Neutral Reverse
  • Phase – Ground Reverse
  • Open Neutral
  • No Ground
  • Voltage contact >50V

Solution

  • Adjust the socket wiring
  • Adjust the socket wiring
  • Connect Neutral wire
  • Check Earth connection
  • Dangerous Voltage on mass

RCD (RESIDUAL CURRENT DEVICE)

This feature allow test of RCD according EC/EN 61557-6 with tripping time and Voltage contact. Test Current of 30 mA is injected through the ground for type A , AC and F.

Test Mode

  • x1 IΔn –Test with 30mA
  • x5 IΔn –Test with 150mA
  • AUTO –Test sequence x1/2 – x1/2 180° – x1 – x1 180° – x5 – x5 180°

RCD x1 , x5

  • Connect RapidPro to the socket and press FUNC in order to select RCD function.

  • Press the button for select the type of RCD and button for select the current (x1,x5) Press RED button for 3 second for start the measure.

  • Tripping Time is shown on the display and Green bar means the test is performed correctly Vc is the contact Voltage. If Contact Voltage >50V the RCD tripping test will be stopped and the bar became RED

  • Display shown tripping time is higher than the limit standard and Red Bar means outcome NOT OK (Fig 5). Vc is the Contact Voltage.

AUTO function

Plug the instrument in the socket and press FUNC for select RCD function. Press arrow button for select type of RCD and button for select function AUTO . Start measuring by pressing the Red button,The instruments will execute all test in sequence when you re-arm the RCD and voltage is on.

AUTO mode consist of 6 test in the folowing sequence:

STEP 1 I∆n x1 OK IF <300 ms
STEP 2 I∆n x1 180° OK IF <300 ms
STEP 3 I∆n x5 OK IF <40 ms
STEP 4 I∆n x5 180° OK IF <40 ms
STEP 5 I∆n x1/2 OK IF >1000 ms
STEP 6 I∆n x1/2 180° OK IF >1000 ms
  • Display Show RCD tripping time in ms. For every STEPtripping time in ms will be shown. GREEN (Fig 6) if the test and tripping time are conform to local tripping time regulamentation.
  • Value in RED (Fig 7) means the test is not conform to the local guideline and the test will be stopped.

LOOP

The measurament is performed according IC/EN61557-3 it measure impedance between Phase and Ground without RCD trip. Test Mode:

  • TT: Measure Earth Resistance (0) and Contact Voltage (V) Fig.8
  • TN: Measure Impedance Z L-Pe (S) and Ipsc prospective short circuit current (A) Fig.9
  • Std: Test with 15mA nominal current
  • Low: Test with 6mA. Use this setup if during the test the RCD trip due to the presence of leakage current in the electric system under test.

LOOP FUNCTION

  • Plug Rapid PRO in the socket and press FUNC button for select LOOP. Press button for select TT or TN and press button for select TEST STD or LOW.
  • Press the RED button for 2 second to start the measurement

WARNING: During the LOOP measurement, if the SUPER CAP is not fully charged, the Display may switch off or decrease the intensity, however the measurement will be performed and shown at the end.

LOOP TT e TN

  • Z line:  PE impedance measurement in TT system
  • Z: Global Earth Resistance
  • Vc: Contact Voltage
  • NOTE: Limit for earth ground resistance is defined as:
  • Vc: Contact Voltage Limit (50V o 25V)
  • IΔn: Nominal RCD current

Impedance measurement Zs L-pe in TN system

  • Z: Fault Ground Impedance L-Pe
  • Ipsc: Prospective short circuit current (for check correct sizing of MCB or FUSE protecting the system)

HAR VOLTAGE HARMONICS

This function allow to check Voltage quality and harmonics up to 49th .
TEST MODE

  • Fund Fundamental harmonic h1 (red), his frequency (~50Hz) and THD% Indicate total harmonic distorsion of voltage supply (Fig. 10).
  • h2….50 Show VOLTAGE value TRMS of selected harmonics (red), his frequency and percentage (%) compared to h1 Fundamental 50Hz (Fig. 11)

HARMONICS FUNCTION

  • Plug Rapid Pro in to the socket and choose Har function by pressing FUNC button.
  • Press for select harmonics higher or button for select back to h1.
  • Is it possible to disconnect RapidPro from the supply power for easilly read and analyze the measurements until the SUPERCAP discharge (60 second when fully charged).

MEM Memory / REPORT

The instruments automatically save RCD and LOOP measurement in MEM area. Press FUNC button for enter MEM page. Press button or for move through the saved data or press simultaneously to clear the memory. It will be possible to store 64 consecutive measures. By pressing the RED button you can generate a QR CODE for the generation of REPORTS (Fig. 12). The 64 positions can be organized in chronological order. The last measurement will always be saved in the first free CELL in ascending order (1… 64).. surement for day of use . Last measure will be saved in the first Memory Slot free (1…64) or in the last cell if memory is full scaling all the other.

REPORT CREATE

  • Press the RED button to generate the QR CODE.
  • Scan the QR CODE with your smartphone using the RAPID PRO REPORT APP.
  • All saved measurements will be included in a REPORT with the possibility of exporting in pdf or csv.
  • Download the RAPID PRO REPORT APP for iOS and Android systems.

MEMORY

  • Column N ° indicates the measurement number (Fig. 13).
  • The FUNC column indicates the saved measurement with its settings.
  • The Value column indicates the outcome of the measurement.
  • The result of the RCD measurement is indicated:
    • GREEN if the result is OK
    • RED if the result is NO OK.

TECHNICAL DATA

TECHNICAL SPECIFICATION

INPUT

  • Overvoltage Category: CAT III 300V verso terra
  • Max Voltage input: 265V AC
  • Maximum absorbed current: <25mA
  • Input voltage fluctuation: 10%

INPUT

  • Measures Guidelines: IEC/EN61557-3
    • IEC/EN61557-6
  • Safety Guidelines: IEC/EN61010-1
    • IEC/EN61010-2-030
  • EMC: IEC/EN61326-1

Display and Memory

  • Display: TFT 1,77” Display
  • Memory Slot: 64

Enviromental Specification

  • Altitude: 0 ÷ 2000 m
  • Reference Temperature: 23°C ÷ 5°C
  • Operational Temperature: 5°C ÷ 40°C
  • Maximum Humidity: <80%RH
  • Stock temperature: 20°C ÷ 60°C
  • Stock Humidity: <80%RH
  • Pollution degree: 2

Mechanical Characteristics

  • Size: 81,5 x 70 x 83) mm
  • Weight: 110gr

ADAPTERS

The Rapid Pro can be connected to various adapters on the market such as extension cords or adapters for sockets other than the Schuko (Fig. 14). The use of an extension cord can help the operator perform LOOP or RCD measurements in environments where it is difficult to reach the socket for testing.

UNIKS Srl is not responsible for malfunctions due to adapters.

WARRANTY

  • This tool is guaranteed against any defect in material and workmanship, in accordance with the general conditions of sale. During the warranty period, defective parts can be replaced, but the manufacturer reserves the right to repair or replace the product. If the instrument must be returned to the after-sales service or to a retailer, the transport is charged to the Customer. The shipment must, in any case, be previously agreed. Attached to the shipment must always be inserted an explanatory note about the reasons for sending the instrument. For shipping use only the original packaging. Any damage caused by the use of non-original packaging will be charged to the Customer. The manufacturer declines all responsibility for damage caused to persons or objects.
  • The warranty is not applied in the following cases:
    • Repair and or replacement of accessories and battery (not covered by warranty).
    • Repairs that are necessary due to incorrect use of the instrument or its use with incompatible equipment.
    • Repairs that are necessary due to inadequate packaging.
    • Repairs that are necessary due to interventions carried out by unauthorized personnel.
    • Changes made to the instrument without the explicit permission of the manufacturer.
    • Use not covered by the instrument specifications or user manual.
    • The contents of this manual may not be reproduced in any form without the manufacturer’s permission.
    • Our products are patented and trademarks registered. The manufacturer reserves the right to make changes to specifications and prices if this is due to technological improvements.

Maintenance

Use a damp cloth and a small amount of detergent to clean the instrument shell.

  • Do not use abrasive or chemical solvents.
  • The instrument should be recycled as electronic waste

ASSISTANCE

If the instrument does not work properly, before contacting the Service Department, check the status of the socket and the casing. If the instrument continues to malfunction, check if the procedure for using it complies with what is indicated in this manual. If the instrument is to be returned to the after-sales service or to a retailer, the transport is charged to the Customer. The shipment must, in any case, be previously agreed. Attached to the shipment must always be inserted an explanatory note about the reasons for sending the instrument. For shipping use only the original packaging; any damage caused by the use of non-original packaging will be charged to the Customer. The repair must be carried out only by UNIKS Srl.

Contact

Uniks Srl

  • Via Vittori 57, 48018 Faenza (RA) – Italia
  • Phone: +39 0546 623002
  • Fax: +39 0546 6236691
  • P.IVA 02627000397
  • REA: RA – 218481
  • mail: [email protected]

VIDEO TUTORIAL

www.uniks.it

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

UNIKS User Manuals

Related Manuals