SAFETY MANUAL
SEARCHLINE EXCEL PLUS™
SEARCHLINE EXCEL EDGE™
Open Path Flammable Gas Detector
Disclaimer
In no event shall Honeywell be liable for any damages or injury of any nature
or kind, no matter how caused, that arise from the use of the equipment
referred to in this manual.
Strict compliance with the safety procedures set out and referred to in this
manual, and extreme care in the use of the equipment, are essential to avoid
or minimise the chance of personal injury or damage to the equipment.
The information, figures, illustrations, tables, specifications, and
schematics contained in this manual are believed to be correct and accurate as
at the date of publication or revision. However, no representation or warranty
with respect to such correctness or accuracy is given or implied and Honeywell
will not, under any circumstances, be liable to any person or corporation for
any loss or damages incurred in connection with the use of this manual.
The information, figures, illustrations, tables, specifications, and
schematics contained in this manual are subject to change without notice.
Unauthorised modifications to the gas detection system or its installation are
not permitted, as these may give rise to unacceptable health and safety
hazards.
Any software forming part of this equipment should be used only for the
purposes for which Honeywell supplied it. The user shall undertake no changes,
modifications, conversions, translations into another computer language, or
copies (except for a necessary backup copy).
In no event shall Honeywell be liable for any equipment malfunction or damages
whatsoever, including (without limitation) incidental, direct, indirect,
special, and consequential damages, damages for loss of business profits,
business interruption, loss of business information, or other pecuniary loss,
resulting from any violation of the above prohibitions.
Warranty
Honeywell Analytics warrants the Search line Excel Plus and Search line Excel
Edge Open Path Flammable Hydrocarbon Gas Detector transmitter and receiver
components, except software and software components, for 5 years against
defective materials and faulty workmanship. The software and software
components, including any documentation designated for use with such software
or software components, are provided “AS IS” and with potential defects.
This warranty does not cover consumable items, batteries, fuses, normal wear
and tear, or damage caused by accident, abuse, improper installation,
unauthorized use, modification or repair, ambient environment, poisons,
contaminants or abnormal operating conditions.
This warranty does not apply to sensors or components that are covered under
separate warranties, or to any third party cables and components.
In no event shall Honeywell Analytics be liable for any damages or injury of
any nature or kind, no matter how caused, that arise from incorrect
installation, handling, maintenance, cleaning or use of this equipment.
In no event shall Honeywell Analytics be liable for any equipment malfunction
or damages whatsoever, including (without limitation) incidental, direct,
indirect, special, and consequential damages, damages for loss of business
profits, business interruption, loss of business information, or other
pecuniary loss, resulting from the incorrect installation, handling,
maintenance, cleaning or use of this equipment.
Any claim under the Honeywell Analytics Product Warranty must be made within
the warranty period and as soon as reasonably practicable after a defect is
discovered. Please contact your local Honeywell Analytics Service
representative to register your claim.
This is a summary. For full warranty terms please refer to the Honeywell
General Statement of Limited Product Warranty, which is available on request.
Copyright Notice
Microsoft, MS and Windows are registered trademarks of Microsoft Corp.
Other brand and product names mentioned in this manual may be trademarks or
registered trademarks of their respective companies and are the sole property
of their respective holders.
Honeywell is the registered trademark of Honeywell Safety and Productivity
Solutions (SPS).
Search line Excel Plus & Edge is a registered trademark of Honeywell (HA).
Find out more at www.sps.honeywell.com
Revision History
Revision | Comment | Date |
---|---|---|
Issue 1 | A05530 | Oct-21 |
Introduction
This Search line Excel Plus & Edge Safety Manual contains information, tables,
examples and instructions that are crucial and relevant to all areas of system
design, development, architecture, approvals, installation and commissioning,
and to its ongoing safety, function and fitness for purpose once correctly
installed and commissioned.
This manual should be read in conjunction with the References listed below,
and in conjunction with any associated 3rd-party manufacturer’s technical
documents.
This manual should be used as a reference source when calculating maintenance
and proof-testing periodicity, deferments and concessions, and when writing
preventive maintenance and proof-testing procedures.
This manual may be used to calculate the probability of Search line Excel Plus
& Edge or component failure (PFD/PFH) for use in risk assessments and other
scenarios.
1.1 References
IEC 61508: Functional Safety of Electrical/Electronic/Programmable Electronic
Safety-related Systems (E/E/PE, or E/E/PES)
IEC 61508 has seven parts:
- Parts 1-3 contain the requirements of the standard (normative)
- Parts 4-7 are guidelines and examples for development and are thus informative.
Central to the standard are the concepts of risk and safety function. Risk is
a function of the likely frequency of the hazardous event and the likely
consequence and severity of an event. The risk can be reduced to a tolerable
level by applying safety functions that may consist of E/E/PES and/or other
technologies. While other technologies may be employed in reducing the risk,
only those safety functions relying on E/E/PES are covered by the detailed
requirements of IEC 61508.
2017M1220 Search line Excel Plus & Edge Technical Manual
This manual contains all of the Search line Excel Plus & Edge specifications,
approvals, certifications and core technical information. It is intended for
use by authorised technical personnel and OEMs, and is available in Technical
English only.
2017M1225 Search line Excel Plus Quick Start Guide
2017M1230 Search line Excel Edge Quick Start Guide
These manuals are abridged and translated versions of the Search line Excel
Plus & Edge Technical Manual. They are intended for use by end users and
operators.
2017M1270 Fixed Platform App User Manual
This manual contains instructions on use of the Fixed Platform App for
servicing and maintenance of the Search line Excel Plus & Edge. This manual is
available in Technical English only.
1.2 Abbreviations
The following abbreviations have been used in this manual:
AC | Alternating Current |
---|---|
AIM | Analog Input Module |
ß | Beta Factor – Common Cause Failure Factor for Undetected Dangerous |
Failures
ßD| Beta Factor – Common Cause Failure Factor for Detected Dangerous Failures
DC| Direct Current
DD| Detected Dangerous Failures
DIM| Digital Input Module
Du| Undetected Dangerous Failures
I/O| Input/Output
LED| Light Emitting Diode
mA| Milliamp
NC| Normally Closed (circuit)
NO| Normally Open (circuit)
PFD| Probability of failure to perform its design function on demand
PFD avg| Probability of failure to perform its design function on demand
(Averaged)
PFH| Probability of a dangerous failure per hour
POST| Power On Self-Test
PSU| Power Supply Unit
SFF| Safe Failure Fraction; a percentage of safe failures as compared to all
failures
SIL| Safety Integrity Level
SIS| Safety Instrumented Systems
SPCO| Single Pole Change Over (Switch or Relay)
TÜV| TÜV is a leading international body for the certification of safety and
quality for products, services and management systems
UI| User Interface
1.3 Definitions
Check| Noun: An examination to test or ascertain accuracy, quality, or
satisfactory condition when compared to a known or stated value
Verb: Examine something in order to determine its accuracy, quality, or
condition when compared to a known or stated value, or to detect the absence
or presence of something
---|---
Examine| Inspect something thoroughly in order to determine its nature or
condition
Inspect| 1: Look at something closely, typically to assess its condition or to
discover any shortcomings
2: Examine something to ensure that it reaches an official standard
Test| Noun: A procedure intended to establish the quality, performance,
or reliability of something, especially before it is taken into widespread use
Verb: Take measures to check the quality, performance, or reliability of
something, especially before putting it into widespread use or practice
Searching Excel Plus & Edge Safety Function
The intended use of the Searching Excel Plus & Edge is to alert users to the
presence of a potentially dangerous gaseous leaks in a defined zone.
To achieve this aim, Searching Excel Plus & Edge provides a safety function
with two outputs which may be used simultaneously if required, providing
compatibility with different safety integrity levels.
An mA output is provided which is compatible with SIL 2 needs. Any output 1.5
mA or below must be treated as a fault condition and is a defined safe state
for this safety function. A range below 4 mA can be configured to provide
warning indications. Values above 4 mA up to 22 mA can be configured to
provide either an analogue representation of the leak level or a fixed alarm
output.
A set of relay output are also provided which are compatible with SIL 1 needs.
Independent Fault, Suspected Alarm and Confirmed Alarm relay contacts are
provided. A de-energized fault relay must be treated as a fault condition and
is a defined safe state for this safety function. The Alarm relay contacts can
be configured as either normally energized or normally de-energized dependent
on the application needs.
Compliance to IEC 61508:2010 has been assessed by an independent third party
and reference to their certification and test report can be found in the
following sections.
Bluetooth, Modbus or HART communications are specifically not a part of the
Searching Excel Plus & Edge safety function. These interfaces are non-
interfering functions typically used for device setup, commissioning,
diagnostics and troubleshooting. They do not interrupt the safety critical
functions of the device.
Searching Excel Plus & Edge Safety Parameters
The following safety parameters are in alignment with the TÜV report HP97656C. They are valid for Hardware Modification State 0 and firmware version 3.21 of the Searching Excel Plus & Edge.
The PFD figures quoted above assume a nominal one-year proof test interval and
8-hours repair time (MTTR).
The Searching Excel Plus & Edge internally has an HFT of 0 and is defined as a
Type B device as per IEC 61508.
The diagnostic test interval for the Searching Excel Plus & Edge is less than
30 seconds in normal operation.
3.1 Proof Test Interval
The purpose of a proof test is to return the unit to ‘as new’ condition in
terms of its safety parameters.
The nominal proof test interval is 12 calendar months but, as stated in IEC
61508 and always dependent on local conditions, users may vary the proof test
interval to meet their system needs. Honeywell allows such variations provided
that the proper calculation method for calculating a proof test interval – as
defined in IEC 61508 – is used to attain the required SIL level.
Proof test variations will depend on the system, hardware architectures and
applications, and should be reviewed annually.
Given that relay outputs could be complex to isolate and test, the user may
determine that a longer proof test interval would be desirable. The table
below can be used to understand the different PFD & PFH values for these
differing intervals.
Note:
The nominal proof test interval should not preclude more frequent maintenance
of Searching Excel Plus & Edge in accordance with the Operating Instructions
if site conditions or other factors require it.
The effect of different proof test intervals on the PFD avg:
Proof Test Interval | MTTR = 8 hours | MTTR = 72 hours |
---|---|---|
Relay PFDavg | mA Output PFDavg | Relay PFDavg |
0.25 year | 5.04 -04 | 2.08 -04 |
0.5 year | 6.92 -04 | 3.72 -04 |
1 year | 1.88 -03 | 6.98 -04 |
2 years | 3.71 -03 | 1.35 -03 |
3 years | 5.54 -03 | 2.00 -03 |
4 years | 7.38 -03 | 2.66 -03 |
5 years | 9.21 -03 | 3.31 -03 |
6 years | 1.10 -02 | 3.96 -03 |
7 years | 1.29 -02 | 4.62 -03 |
8 years | 1.47 -02 | 5.27 -03 |
9 years | 1.65 -02 | 5.92 -03 |
10 years | 1.84 -02 | 6.58 -03 |
3.2 Special Notes
-
This safety manual does not address installation, configuration, service, maintenance or decommissioning tasks.
The Searching Excel Plus & Edge Technical Manual must be read and referred to in order to accomplish these tasks.
Read and understand the Searching Excel Plus & Edge Technical Manual in full as this document also contains important safety information regarding the installation and continued use of the product.
It is important to understand and mitigate security risks associated with the day-to-day use of the system in connected IT infrastructures. Refer to the Searching Excel Plus & Edge Security Guide for information on additional security controls that should be implemented by users. -
Searching Excel Plus & Edge proof tests shall be carried out strictly in accordance with this manual while referring to the Searching Excel Plus & Edge Technical Manual as required, and also by including any additional instructions or requirements that may be issued from time-to-time. Searching Excel Plus & Edge must not be stored or otherwise exposed to temperatures or conditions outside of the allowable maximums listed in the Technical Manual and/or datasheet.
-
It is incumbent on all 3rd-Party OEMs and Partners to enforce these rules on all Searching Excel Plus & Edge equipment and assemblies manufactured and supplied by Honeywell.
-
Modification of settings in the Searching Excel Plus & Edge shall strictly follow the procedure detailed in the Searching Excel Plus & Edge Technical Manual or in the Fixed Platform App User Manual. Following modification of any settings in the Searching Excel Plus & Edge, the entire list of settings must be reviewed to ensure that the product configuration is correct. A proof test should then be undertaken to ensure the functionality of the product is understood and is as expected.
-
Access to the product is possible remotely using either the HART or Bluetooth connection. Security is provided on these connections by the use of authentication passwords and tokens. The user must take care to ensure such passwords and tokens do not become known to unauthorised parties. In case of concern, such passwords should be immediately changed to prevent unauthorised access to the product.
-
It is possible to upgrade the firmware in the Searching Excel Plus & Edge using the Fixed Platform App mobile application. Before performing an upgrade, the user must check that the new firmware has already been certified to the relevant functional safety standard. When performing an upgrade, the procedure listed in the Fixed Platform App User Manual must be followed. Following the upgrade, the version string must be interrogated to ensure it is as expected. Refer to the Fixed Platform App User Manual. A proof test should then be undertaken to ensure the functionality of the product is understood and is as expected.
-
Power supplied to the Searching Excel Plus & Edge or to the 4-20 mA loop of the product shall be of an isolating type (galvanic isolation from mains, providing basic insulation) but does not need to be a Class II (SELV) power supply. At no time should voltages exceeding 60V DC be provided to the product (with the exception of the relay contact connections).
-
Searching Excel Plus & Edge contains relays that may be used to perform executive actions when an alarm is triggered. Ensure that such systems are identified and inhibited / disconnected before carrying out any proof testing, bump testing, or sensor calibrations.
-
For SIL 2 applications, users must use the mA output to determine both alarm and fault conditions. Configurations for SIL 2 alarm relay outputs are described in point 10d). Relay outputs can be used simultaneously for SIL 1 or non-safety applications.
-
If relay outputs are used for safety purposes, the following directions must be adhered to:
a) The relay contacts must be protected with a fuse rated at a maximum of 3 A.
b) Only resistive loads should be connected to the relay contacts.
c) The fault relay output must be energised under normal conditions.
d) It is possible to realize a SIL 2 relay output for alarm conditions. If such a configuration is required the suspected and confirmed alarm relay outputs must be wired as shown below. Configuration 1 should be used when an “open contact” represents the activation of the safety function whereas Configuration 2 should be used when a “closed contact” represents the activation of the safety function. Configuration 1 requires the addition of a protective fuse rated at a maximum of 3 A to protect the relay contacts from adverse events which may cause contact welding.
3.3 Environmental Conditions
The environmental conditions that the Searching Excel Plus & Edge is designed
to operate within are listed below:
Voltage: 18 to 32V DC
Temperature: -55°C to +75°C
Humidity: 0-100% RH Condensing
Altitude: 0-1500m
EMC: EN 50270, IEC/EN 61000-6-4; Radio Equipment Directive 2014/53/EU
IP-Protection: IP 66/67 (Type 4X in accordance with NEMA 250)
Proof Test
To give the user confidence and ensure that proof testing is always carried
out on an optimal system, it is recommended that users carry out routine
maintenance procedures before carrying out more specific proof tests.
Example inspection, testing and calibration procedures are given below, but
users should always refer to the relevant manufacturer’s technical
documentation for details appropriate to their installations.
4.1 Visual Inspection
- Visually inspect the Searching Excel Plus & Edge paying particular attention to signs of insecurity, loose connections, damage, corrosion, ingress of moisture, or contamination. Clean and repair as required before proceeding with any functional testing or calibrations.
- Switch off and isolate electrical power, then open the rear enclosure and carry out a visual inspection and clean as listed in item 1 above. Pay particular attention to the security and condition of electrical connections and terminals.
- Switch on the electrical power. Observe the LEDs for correct operation while the POST is being carried out.
- Record all adverse findings and their remedies to aid future proof testing analysis and fault finding.
4.2 Electrical Testing
- Electrically test all external cables, paying particular attention to insulation resistance, shielding and Earthing (Grounding) resistance, and cable continuity and resistance.
- Record all figures to aid future proof testing analysis and fault finding.
4.3 Output Testing
Follow the procedures described in the Searching Excel Plus & Edge Technical
Manual and the Fixed Platform App User Manual to accomplish output testing of
relays, mA Loop and status indicator. Ensure that all operate as expected.
All relays should be forced both de-energized and energized. The mA Loop
should be tested at the extents, at 4 mA and at mid-range points.
4.4 Bump Testing
- Carry out Bump Testing in accordance with the appropriate technical handbooks and manufacturer’s technical specifications.
- Record all figures to aid future proof testing analysis and fault finding.
Please Note:
While every effort has been made to ensure accuracy in this publication, no
responsibility can be accepted for errors or omissions. Data may change, as
well as legislation and you are strongly advised to obtain copies of the most
recently issued regulations, standards and guidelines.
This publication is not intended to form the basis of a contract.
Find out more
www.sps.honeywell.com
Contact Honeywell Analytics:
Europe, Middle East, Africa
Life Safety Distribution GmbH
Tel: 00800 333 222 44 (Freephone no.)
Tel: +41 (0)44 943 4380 (Alternative no.)
Middle East Tel: +971 4 450 5800 (Fixed Gas Detection)
Middle East Tel: +971 4 450 5852 (Portable Gas Detection)
gasdetection@honeywell.com
Americas
Honeywell Analytics Distribution Inc.
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
detectgas@honeywell.com
Asia Pacific
Honeywell Analytics Asia Pacific
Tel: +82 (0) 2 6909 0300
India Tel: +91 124 4752700
China Tel: +86 10 5885 8788-3000
analytics.ap@honeywell.com
Technical Services
EMEA: HAexpert@honeywell.com
US: ha.us.service@honeywell.com
AP: ha.ap.service@honeywell.com
www.sps.honeywell.com
10/2021
2017M1245 Issue 1 EN A05530
© 2021 Honeywell Analytics
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>