Honeywell KTF00-65-2M CableType Bulb Temperature Sensors Owner’s Manual

June 13, 2024
Honeywell

Honeywell KTF00-65-2M CableType Bulb Temperature Sensors

Product Information

The KTFxx cable-type bulb temperature sensors are versatile sensors that can be used as strap-on sensors or immersion sensors. They are suitable for hot and cold water installations in systems that use Pt1000, NTC 10k, or NTC 20k temperature sensing elements. The sensors feature stainless steel probes and have an IP65 rating for high accuracy.
The KTFxx sensors are available in various models:

  • KTF00-65-2M: Pt1000 sensor with a 2-meter cable
  • KTF10-65-2M: NTC 10k sensor with a 2-meter cable
  • KTF20-65-2M: NTC 20k sensor with a 2-meter cable
  • KTF10-65-2M-B: NTC 10k sensor with a 2-meter cable, pack of 50
  • KTF20-65-2M-B: NTC 20k sensor with a 2-meter cable, pack of 50
  • KTF20-65-5M-B: NTC 20k sensor with a 5-meter cable, pack of 50
  • KTF00-65-2M-300: Pt1000 sensor with a 2-meter cable and a temperature range of up to 300°C

The sensors have a high accuracy and are made of stainless steel (1.4571) for durability. The cable sheath material is PVC, except for the KTF00-65-2M-300 model, which has PTFE. The electrical connection is a 2-m or 5-m cable with 2×0.22 mm2 wires. The sensors have an IP65 rating for safety.

GENERAL

The KTFxx cable-type bulb temperature sensors can be used as strap-on sensors or immersion sensors. The sensors can be employed for hot and cold water installations in systems using Pt1000, NTC 10k, or NTC 20k temperature sensing elements.

NOTE: Immersion well not included. For information on immersion well options, see VF Immersion

  • Temperature Sensors – Product Data (Product
  • Literature No.: EN0B-0724GE51).

FEATURES

  • Pt1000, NTC 10k, or NTC 20k temperature sensing element
  • Stainless steel probes, IP65 rating
  • High accuracy

Models

OS no.| sensor type| description| temperature range
---|---|---|---
KTF00-65-2M| Pt1000| 2-meter cable| -30…+105 °C (-22…+221 °F)
KTF10-65-2M| NTC 10k| 2-meter cable
KTF20-65-2M| NTC 20k| 2-meter cable
KTF10-65-2M-B| NTC 10k| 2-meter cable, pack of 50
KTF20-65-2M-B| NTC 20k| pack of 50 KTF20-65-2M
KTF20-65-5M-B| NTC 20k| 5-meter cable, pack of 50
KTF00-65-2M-300| Pt1000| 2-meter cable| -20…+260 °C (-4…+500 °F)

Accessory
When securing new sensors into old-style VFxx immersion wells, order the accessory VF-SPRING.

SPECIFICATION

  • Nominal value
    • Pt1000 1000 Ω at 0 ΩC (32 °F)
    • NTC 10k 10 kΩ at 25 ΩC (77 °F)
    • NTC 20k 20 kΩ at 25 ΩC (77 °F)
  • Accuracy
    • Pt1000 (IEC751 Class B) ±0.3 C at 0 °C (32 °F)
    • NTC 10k ±0.2 C at 25 °C (77 °F)
    • NTC 20k ±0.2 C at 25 °C (77 °F)
  • Sensitivity
    • Pt1000 Ω 3.85 Ω / K
    • NTC 10k -440 Ω / K at 25 °C (non-linear)
    • NTC 20k Ω-934.5 Ω / K at 25 °C (non-lin.)
  • Time constant
    • Immersion well appl. < 30 sec
  • Sensor sleeve material stainless steel (1.4571)
  • Cable sheath material PVC (excepting the KTF00-65- 2M-300, which has PTFE)
  • Electrical connection 2-m or 5-m cable, 2×0.22 mm2
  • Ambient Limits (wiring box)
    • Storage temperature -30…+70 °C (-22…+158 °F)
    • Humidity 5…95% rh, non-condensing
  • Safety IP65 as per EN 60529
  • Dimensions see Fig. 1 on page 2

DIMENSIONS

Honeywell-KTF00-65-2M-CableType-Bulb-Temperature-
Sensors-1

WIRING

wiring run max. length
sensor to controller 200 m (660 ft)

Offset due to wire resistance per 10 m of distance from sensor to controller, when using the KTF00-65-2M (Pt1000):

type of wire temperature offset Pt1000
0.5 mm2 (AWG20) 0.18 °C (0.324 °F)
1.0 mm2 (AWG17) 0.09 °C (0.162 °F)
1.5 mm2 (AWG15) 0.06 °C (0.108 °F)

INSTALLATION

NOTE: Use shielded wiring in areas with high EMI. Keep 15 cm (5.9’’) minimum distance between sensor lines and 230 Vac power lines.

Manufactured for and on behalf of the Connected Building Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:

Home and Building Technologies
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich, Germany
Phone +49 (0) 7031 637 01
Fax +49 (0) 7031 637 740
http://ecc.emea.honeywell.com