Monitoring unit
Type PR-OCTO
PR-OCTO Monitoring Unit
IoT Enabler for remote control and tracking of refrigeration equipment
Introduction
The PR-OCTO device is an IoT Enabler specifically designed for cooling
applications like bottle coolers, ice cream cabinets, and other refrigeration
type of equipment. This Enabler allows connectivity and access to the Alsense™
Cloud solutions from Danfoss.
Electronic thermostats, in general, by monitoring the temperatures and states
related to the equipment, control the compressor and fan relays, and generate
warnings and alarms. By means of a wired connection, PR-OCTO can obtain from
the thermostats diagnostic and alarm data relating to the equipment, or create
new ones. Thanks to the presence of a modem and an M2M SIM on board, PR-OCTO
communicates with the Alsense™ monitoring platform through the mobile network,
transmitting the collected data. PR-OCTO also scans the mobile network and
nearby WiFi HotSpots to determine its position and transmit it to Alsense™.
If in Alsense™ the refrigeration system is located in a position other than
that transmitted by PR-OCTO, an alarm is notified on the monitoring platform.
Authorized personnel can access Alsense™ to view active alarms and decide if
PR-OCTO has to lock the operation of the refrigeration system.
Danfoss guarantees continuous after-sales maintenance of the PR-OCTO devices
as they can be updated remotely (FOTA) or on-site via the mobile app.
Layout
Figure 1 and Figure 2 illustrate the layout of the PR-OCTO device.
Table 1: LED operation details
RED LED OFF | The device is not correctly powered. |
---|---|
RED LED blinking | The device is powered and the communication with the |
electronic thermostat is not
established yet.
RED LED ON| The device is powered and the communication with the electronic
thermostat is correctly established.
RED LED fast blinking| The device is powered while the communication with the
electronic thermostat has been interrupted.
GREEN LED OFF| The modem is not running
GREEN LED fast blinking| The modem is not registered to the network
GREEN LED blinking| The modem is registered to the network
Compatibility
The PR-OCTO device gives the possibility to execute the lock command and to
collect the diagnostic information only in conjunction with an electronic
thermostat.
The current version of the PR-OCTO includes compatibility with the thermostats
listed in Table 2.
Table 2: Compatible electronic thermostats
Manufacturer | Models |
---|---|
Danfoss | ERC111, ERC112, EETa |
Eliwell | EWPLUS400, EWPLUS961, EWPLUS974, EWPLUS974 Smart, EWPLUS978 |
Carel | PJP4COHGOO (PYUG3R05R3, PYKM1Z051P), PZPU family (es. PZPUCOMBO3K, |
PZPUCOMBO6K), PYHB1 R0555 (PYFZ1Z056M), PZHBCOHOOV, PYHB1 R057F (PYHB1 R05E9), PJP7COHGOO
Connections and wires
The PR-OCTO requires two connections, one for the power supply, and the other
with the electronic thermostat.
The power supply must be shared with the electronic thermostat: the PR-OCTO
must be powered on only when the thermostat is also powered on. If the PR-OCTO
is powered on when the thermostat is off, a “Controller communication failure”
alarm is raised after 60 minutes.
Note: Neither the cables nor the connectors are included in the PR-OCTO
package.
For the POWER SUPPLY connector of the PR-OCTO, either two standard fast-on
connectors or one connector with a screw terminal can be used. Fig 4,
illustrates the Lumberg 3611 02 K1, an easy plug connector with a lift clamp
and protection against misplacing and fast assembling. Neither the easy plug
connector nor the standard fast-on connectors are included in the PR-OCTO
package.
Note: If the power supply cable is not double insulated, it must be
physically separated from the COMM cable.
Fig. 4: Two possible OCTO terminations for the power supply cable.
The one on the right is the Lumberg 3611 02 K1.
Concerning the COMM Cable (the communication cable between the PR-OCTO and the
electronic thermostat) a specified cable must be used depending on the
specified thermostat.
The COMM Cable could be either assembled by the cooler manufacturer or could
be purchased from Danfoss (see COMM table for details).
Table 3: COMM cables for Danfoss controllers
Controller | Length | Code no. |
---|---|---|
ERC11x | 0.6 m | 080G3396 |
ERC11x | 2 m | 080G3388 |
ERC11x | 4 m | 080G3389 |
EETa | 2 m | 080NO330 |
EETa | 4 m | 080NO331 |
For other options on cabling and connection to different controllers, please contact Danfoss.
Choosing the position in the cooler
The most important requirement for the OCTO installation is to find the location inside the cooler where the mobile network signal is stronger and the device protected. The diagram below suggests the recommended positions for coolers:
On standard visi coolers, the best area is inside the canopy, since the canopy
usually does not have metal plates that could decrease the mobile network
signal.
On the lean cooler, since the lack of the canopy and the presence of metallic
plates all around the cooler, the OCTO can only be installed outside the
cooler, in the back area, next to the top.
Note: In case of installation on the back side of the cooler, the OCTO
has to be protected with an additional box to protect people from electric
shock. Mobile application (recommended)
Danfoss has developed a mobile application for Android and IoS that can be
used also to check the best position where to install the OCTO in the cooler.
This is the suggested way to check the best position to install the PR-OCTO
into the cooler. You can find more details at: User Guide for ProsaLink mobile
app
PC application
Danfoss has developed specific PC software to help discover the right
position of the OCTO in the cooler. To exploit such software, follow these
steps:
Step 1: Download the VBCTKSignalTester application from this URL:
http://area.riservata.it/vbctksignaltester-1.0.0-setup-x86_32.exe
Step 2: Install the VBCTKSignalTester application in a Windows PC.
Step 3: Connect the ‘Test Cable’ (see Fig. 5) to the PC and to the OCTO.
Step 4: Power on the OCTO (see Section 4 for the power supply cable).
Step 5: Run VBCTKSignalTester and select the appropriate Serial COM port to
which the ‘Test Cable’ is connected, as shown in Fig. 6a.
Step 6: If the program shows “No Connection” as in Fig. 6b, try to change the
COM port listed in the combo or check the cable connection.
Step 7: When the system is finally connected to the device, it starts to
display the Antenna Signal Level of the OCTO’s internal antenna. Such level
could be low (like in Fig. 6e), medium intensity (like in Fig. 6f ), or almost
the best signal level (like in Fig. 6d).
Step 8: Try to change the position of the OCTO in the cooler in order to
discover the highest possible Antenna Signal Level.
Step 9: Power off the OCTO and disconnect the PC ‘test cable’.
Fig. 5: PC Test Cable for monitoring the OCTO GPRS transmission signal level.
Once discovered the best position with respect to the Antenna Signal Level, it
is possible to decide if it is the case to protect the Side B (the one with
the connectors) of the OCTO. To this aim, it can be adopted the same approach
that the cooler manufacturer uses to protect the connector side of the
electronic thermostat, hence a piece of plastic with an appropriate shape can
be used. If a piece of plastic is not available, a metallic plate can be used
but the covered area of the OCTO has to be as small as possible (the limit
should be 5 cm from the front of the OCTO, as illustrated in Fig. 7).
Fig 7: In case of metallic protection, do not cross the indicated line
otherwise the signal of the internal antenna results corrupted.
Installation in the coolers
During the industrial production of the coolers, there should be a phase in which the electronic thermostat is installed. In the same phase, also the OCTO device has to be installed. The following preconditions have to be satisfied:
Pre-condition 1: The installation position has to be determined during the
analysis performed as described in Section 5.
Pre-condition 2: One COMM CABLE for each cooler has been correctly assembled
for the corresponding thermostat model with the appropriate length with
respect to the position of both the OCTO and the electronic thermostat.
Pre-condition 3: A power supply cable has been prepared using one of the
connectors illustrated in Fig. 4.
Pre-condition 4: If metal protection is provided, this must not cover the
antenna of the device (see Fig. 7).
Pre-condition 5: the controller has to be programmed in order to properly
manage all the sensors. Thus, for example, if a door sensor is installed, even
if it is not needed for the cooler management (i.e. no need to switch off the
fan), the controller must be programmed in order to properly detect and manage
the door sensor itself. For any clarification,
ask to your local Danfoss agent.
For the installation, the following steps have to be performed:
Step 1: While the cooler is off, put the OCTO unplugged inside the cooler in
the appropriate position.
Step 2: Connect the COMM cable to the thermostat and to the OCTO.
Step 3: Connect the power supply cable to the OCTO while such cable is not
powered, as illustrated in Fig. 3.
Step 4: Install the protection, if any.
Step 5: Power on the cooler (and consequently the OCTO). The red led of the
OCTO starts blinking. Wait until the red led stops blinking. If it results
always on, then the device is powered and the communication with the
electronic thermostat is correctly established.
Step 6: Wait until the green led remains always on.
Step 7: In case of success in STEP 6, and only in such case, the cooler code
and the OCTO code have to be associated. This association is illustrated in
Fig. 8. Both the cooler serial number and the OCTO Device Code have to be read
using a bar code reader and be traced in a special document where the cooler
model, the cooler serial number, and the OCTO device code must be written.
Note: In case STEP 7 is not properly executed, the future owner of the
cooler will not recognize the cooler through the Prosa infrastructure.
Prosa mandatory settings
This section is to highlight the fundamental importance of STEP 7 listed in
Section 6.
The association between the equipment and the PR-OCTO can be done:
- Using the mobile app
- With the Alsense Portal
- or other modalities previously agreed with Danfoss (contact via e-mail: support.prosa@danfoss.com).
The association must be done before shipping the equipment to the final customer. Any shipment to the final customer must be notified with an e-mail containing the equipment codes and the customer’s warehouse address to support.prosa@danfoss.com.
Technical specification
The techincal specification can be found on the following datasheets:
- PR-OCTO
- PR-OCTO Lean
Dimensions
Warnings
- The installation of the PR-OCTO has to be performed only and exclusively by qualified and skilled technicians.
- The installation of the PR-OCTO should be performed while the cooler is switched off.
- Inside the device there is a GPRS antenna. For this reason, while the PR-OCTO is working it must be at a minimum distance of 9.5 cm (4”) from the people. The installation must be done to ensure this distance.
- The PR-OCTO has to be installed in a protected position. The PR-OCTO has to be embedded in the cooler and not accessible. In case of installation on the back side of the cooler, the PR-OCTO has to be protected with an additional box to protect people from electric shock.
- If the power supply cable of the PR-OCTO is not double insulated, it has to be physically separated from the COMM cable (the communication cable with the thermostat).
- The PR-OCTO input power supply is protected by over-currents by the F002 device, with this characteristic: delayed fuse 250 V 400 mA.
- Any document related to the conformity declaration of the PR-OCTO can be downloaded from www.danfoss.com.