PROSELECT SKU00000000 Condensate Removal Tank Pump Instruction Manual
- June 13, 2024
- PROSELECT
Table of Contents
PROSELECT SKU00000000 Condensate Removal Tank Pump
Product Information:
The Condensate Removal Tank Pump is designed for the removal of pH 7 – 2.2 air conditioner/furnace/boiler/dehumidifier condensate water. It is available in different models with varying specifications:
- SKU: SKU00000000
- Wall-mounting clips (removable)
- Overflow pipe adaptor
- Clear PVC hose: 10mm x 6m (PSCPV315WS20T & PSCPV320WS20T only)
- Cable ties: 200mm x 4.8mm
- Voltage Options:
- 115V: 15ft, 20ft
- 230V: 17ft
- Flow Rate Options:
- 65 US gph (250 l/h) – 115 vac 15ft (4.5m) – 115 vac
- 135 US gph (511 l/h) – 115 vac 20ft (6m) – 115 vac
- 100 US gph (379 l/h) – 230 vac 17ft (5m) – 230 vac
- Power Consumption:
- 115VAC, 1.6 A, 95W, 60Hz
- 230VAC, 0.7 A, 80W, 60Hz
- Noise Level: 44 dB(A) – 115 VAC, 1.6 A, 95W, 60Hz
- Refrigeration Tonnage:
- 94ton / 1.1m Btu/h – 115 vac
- 192ton / 2.3m Btu/h – 115 vac
- 142ton / 1.7m Btu/h – 230 vac
- Pipe Size: 3/4 (21mm) to 1 (27mm)
Product Usage Instructions
-
This appliance should ONLY be fitted and serviced by a competent and qualified HVAC/R installer.
-
This appliance must be provided with means for disconnection that is incorporated into the fixed wiring in accordance with the relevant local wiring regulations.
-
If the supply cord is damaged, the pump should be replaced.
-
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety. -
This appliance must be earthed.
-
This pump is not intended for use inside air plenums.
-
This pump has been designed for the removal of pH 7 – 2.2 air conditioner/furnace/boiler/dehumidifier condensate water ONLY.
-
Confirm that the condensate production of the indoor evaporating coil is within the capacity of the condensate pump.
In The Box – Pump
Robust and intuitive, installer-friendly outlet adapter for easy servicing and maintenance
Specifications
Specifications| 115V 15ft| 115V 20ft| 230V
17ft
---|---|---|---
Max flow (@ 0 m/ft)
| 65 US gph (250 l/h) – 115 vac| 135 US gph (511 l/h) – 115 vac| 100 US gph
(379 l/h) – 230 vac
Max rec. head| 15ft (4.5m) – 115 vac| 20ft (6m) – 115 vac| 17ft (5m) – 230 vac
Sound level @ 1m| 44 dB(A)
Pump power supply| 115 VAC, 1.6 A, 95W, 60Hz| 115 VAC, 1.6 A, 95W, 60Hz| 230
VAC, 0.7 A, 80W, 60Hz
Non Continuous| 5 mins on, 5 mins off • Marche 5 minutes
Class| I Appliance
Max unit output| 94ton / 1.1m Btu/h – 115 vac| 192ton / 2.3m Btu/h – 115 vac|
142ton / 1.7m Btu/h – 230 vac
Max water temp| 140º F / 60º C
Inlets| 3/4″ (21mm) to 1″ (27mm)
Outlets| 1/4″ (6mm) / 3/8″ (9.5mm)| 3/8″ (9.5mm)| 3/8″ (9.5mm)
IP protection| IP24 – Splash proof • IP24 Protection
Safety switch| 3A Normally closed •
Thermal protection| ✓
Performance Graphs
AC max unit sizing chart
Head / ft| US gph| BTU/Hr| Refrigeration Tonnage
0| 66| 1,136,000| 94
3.3| 48| 822,000| 68
6.6| 37| 638,000| 53
9.8| 24| 409,000| 34
12| 12| 205,000| 17
15| 5| 85,000| 7
16| 0| 0| 0
AC max unit sizing chart
Head / ft| US gph| BTU/Hr| Refrigeration Tonnage
0| 135| 2.3m| 193
3| 122| 2.1m| 175
6| 100| 1.7m| 143
9| 82| 1.4m| 117
12| 62| 1.0m| 88
15| 46| 0.8m| 66
17| 25| 0.4m| 35
20| 0| 0| 0
AC max unit sizing chart
Head / ft| US gph| BTU/Hr| Refrigeration Tonnage
0| 100| 1.7m| 143
3| 91| 1.5m| 130
6| 83| 1.4m| 119
9| 74| 1.2m| 106
12| 55| 0.9m| 79
15| 29| 0.5m| 41
17| 12| 0.2m| 17
20| 0| 0| 0
IMPORTANT
HEALTH & SAFETY
- This appliance should ONLY be fitted and serviced by a competent and qualified HVAC/R installer.
- This appliance must be provided with means for disconnection that is incorporated into the fixed wiring in accordance with the relevant local wiring regulations.
- If the supply cord is damaged, the pump should be replaced.
- This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
- THIS APPLIANCE MUST BE EARTHED.
- This pump is not intended for use inside air plenums.
IMPORTANT
PRODUCT SAFETY
-
This pump has been designed for the removal of pH 7 – 2.2 air conditioner/furnace/boiler/dehumidifier condensate water ONLY.
-
Confirm condensate production of indoor evaporating coil is within capacity of condensate pump.
-
Ensure correct amp fuse is installed.
-
Following installation of the pump, the tank should be filled with water until the motor runs. Pipes and connections should be checked for leaks and discharge of water. The operation of the safety switch should also be checked.
-
Do not use these pumps in oily or very dusty environments.
-
Install hose and wiring in accordance with manufacturer’s instructions. Do not use discharge hose larger than 3/8″/10mm I.D.
-
Inspect pump, clean floats and tank, regularly checking for correct operation.
-
Do not operate this pump when any unapproved cleaning chemicals are present in the condensate drainage system. Operating the pump when unapproved or poorly mixed cleaning chemicals are present will result in permanent damage
to pump and void warranty. Ensure all cleaning chemicals are thoroughly flushed out of the pump with clean water. -
After initial installation and/or maintenance, do not leave site until pump has been tested for correct operation.
-
Check for any construction debris that has entered the evaporator coil and/or drain pan prior to initial activation of pump – this will damage the pump permanently.
-
NOISE: All PROSELECT pumps operate quietly; however, under certain conditions where an extremely low ambient noise level is present, the sound of their intermittent operation may still be perceived as noisy. Always confirm acceptable noise level before installing any condensate pump in a bedroom or other noise sensitive area.
Correct sequence of operation
- AC/Furnace unit drain pan fills with water which flows into pumps tank.
- When the water lifts the float to the correct level,the pump will activate.
Fault Conditions: In the unlikely event of a pump failure, check the following:
- Power supply: Ensure power is supplied to pump.
- High level safety switch: Ensure high level safety switch has not been operated. If it has, check pump performance is suited to incoming flow rate.
- Pump is loud: Pump fixing may be loose or the connected cables and hoses may be vibrating against a hard surface.
- Outlet pipe: Check pipe and outlet barb are not blocked with debris or kinked.
If these checks do not resolve the problem, please contact PROSELECT for
further assistance:
Tel US: 1-800-221-3379
Email: owat@ferguson.com
Installation
This pump is designed to collect condensate water from a high-efficiency condensing boiler, furnace, AC unit, or dehumdifier and discharge it up to the recommended maximum head of 15 to 20 feet (varies by model; see Specifications). The internal safety float is a low-current switch to stop the condensing equipment in the event of pump failure. The pump is operated by an internal float switch.
CHECK
- Suitable AC/furnace capacity
- Water tight connections
- 115V – 3 Amp fuse installed
- High water level safety switch
Power | Alarm/Volt Free |
---|---|
US 230V: |
EN
| (L) LINE 1: Black
(N) LINE 2: Red(N) LINE
| (L) LINE 1: Black
(N) LINE 2: White
| (N.C.) NORMALLY CLOSED: Yellow (COM) COMMON: Yellow
FR
| (L) LIGNE 1: Noir
(N) LIGNE 2: Rouge
| (L) LIGNE 1: Noir
(N) LIGNE 2: Blanc
| (N.C.) NORMALEMENT FERMÉ: Jaune (COM) COMMUN: Jaune
ES
| (L) LINE 1: Negro
(N) LINE 2: Rojo
| (L) LINE 1: Negro
(N) LINE 2: Blanco
| (N.C.) NORMALMENTE CERRADO: Amarillo
(COM) COMÚN: Amarillo
High Level Safety Switch (Excludes PSCPV315)
Furnace
Shut off the electrical power supply at the fuse box before making any
connections. All wiring must comply with local codes. Make sure that line
voltage corresponds to voltage specified on the motor’s name plate. For
correct operation, ensure that the pump is connected to a constant power
source (not an intermittent switching power source).
The pump’s safety switch should be used on 24V Class II control circuits only. The Normally Closed (N.C.) safety switch has dry contacts and should be connected in series with the 24V thermostat circuit to shut off the system. Do not exceed 42V peak.
115V – where appropriate a 3 amp fuse MUST be installed in the live supply to the pump
Service
Tank removal method
- Unscrew
- Press ends of tank under clips
- Release clips and detach tank
WARNING
WEEE DIRECTIVE WARNING
Meaning of crossed out wheeled dustbin:
Do not dispose of electrical appliances as unsorted municipal waste; use
separate collection facilities. Contact your local government for information
regarding the collection systems available. If electrical appliances are
disposed of in landfills or dumps, hazardous substances can leak into the
groundwater and get into the food chain, damaging your health and well-being.
When replacing old appliances with new ones, the retailer is legally obligated
to take back your old appliance for disposals at least free of charge.
Warranty
-
What Is Covered.
Ferguson Enterprises, LLC. “Ferguson” or the
“Company” warrants its products to be free from defects in material and workmanship under normal use and service FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF INSTALLATION. -
What Is Not Covered.
The warranty set forth in paragraph 1 does not cover installation or any other labor charges and does not apply to products which have been damaged as a result of any accident, abuse, improper installation or maintenance,
or modification of original plumbing product. The warranty of such products is limited to the warranty extended to Ferguson by the product manufacturer. Finally, FERGUSON SHALL NOT BE RESPONSIBLE OR LIABLE FOR ANY FAILURE OR DAMAGE TO THIS PRODUCT OR ANY COMPONENT THEREOF CAUSED BY THE USE OF ABRASIVE CLEANERS. -
How To Obtain Warranty Service
The purchaser should contact their local Ferguson location, installing contractor or builder from whom the product was purchased. To find your nearest Ferguson location, please visit www.ferguson.com and enter in your address into the Find a Location field. -
Limitations of Implied Warranty and Disclaimer of Consequential or Incidental Damages
FERGUSON DISCLAIMS ANY LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES AND DISCLAIMS ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, AS SET FORTH ABOVE. IMPLIED WARRANTIES OF THE PRODUCTS AND PRODUCT COMPONENTS SET FORTH IN PARAGRAPH 1 ABOVE ARE LIMITED TO THE DURATIONS OF THE RESPECTIVE WARRANTY. Some states do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied warranty lasts, so the above limitations may not apply to you. This warranty gives you specific legal rights and you may also have other rights, which vary from state to state.
PROSELECT is a registered trademark of Ferguson Enterprises, LLC.
©2023 Ferguson Enterprises, LLC 0323 4983590