Danfoss AB Solenoid Coil Installation Guide

June 4, 2024
Danfoss

ENGINEERING TOMORROW
042R9019
Installation guide


Solenoid coil

Type AB, AM, AC, AK, AL, AP, BB, BA, BC, and BD

Type of control 1
Class of protection Class I
Ambient temperature See Tambient on coil
Voltage variation Voltage tolerances For voltage variation, see print on coil

For voltage tolerances see datasheet, when ordering the coil
Humidity| Only none-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation is to be expected.
Ball pressure test| 200 °C (392 °F) in accordance to IEC 60695-10-2
Impulse withstand voltage| Spade
Plug
Plug| 4.0 kV at altitude <4000 m (13123 ft)
4.0 kV at altitude <2000 m (6561 ft)
3.1 kV 2000 m<altitude<4000 m (6561<altitude<13123 ft)
Overvoltage category| III
Degree of protection IPxx Pollution degree PDX| Enclosure rating according to IEC standard 60529 (See illustration for details A-B) Pollution degree according to EN60664-1 (See illustration for details A-B)
Installation| Integrated control
Incorporated control
Independently mounted control (IP65/1P67)
Suitable cable, Conductor size for plug| Ø6.6 — 011 mm (Ø0.26 — Ø0.43 in)
0.75 — 1.5 mm2(21 — 15 AWG flexible cord)
Suitable cable for cable plug| See datasheet when ordering the coil
Cable conductor size| 3 x 0.75 mm2 (3 x 0.001 in2)
Plugs can be removed/mounted| 10 times
Surface temperature| Independently mounted controls must be inaccessible in normal use if the surface temperature on the control > 85°C

  • Only qualified personnel is allowed to install or maintain this product
  • Disconnect the power when dismounting the coil
  • Avoid direct exposure to alkaline conditions, use in neutral conditions is recommended
  • Ensure that the O-ring is in place on the valve
  • If the coil is used as independently mounted control, the end-user shall use a plastic cable gland with strain relief

Visit www.products.danfoss.com for further technical data

© Danfoss | Climate Solutions | 2021.12
AN353730866505en-000301
Info for UK customers only: Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB