Danfoss BB Solenoid Coil Installation Guide

June 4, 2024
Danfoss

Danfoss BB Solenoid Coil Installation Guide

Instructions

Instructions

Type of control 1
Class of protection Class I
Ambient temperature See Tambient on coil
Voltage variation Voltage tolerances For voltage variation, see print on coil

For voltage tolerances see datasheet, when ordering the coil
Humidity| Only none-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation is to be expected.
Ball pressure test| 200 °C (392 °F)
Impulse withstand voltage| Terminal box Cable Spade| 4.0 kV at altitude <4000 m (13123 ft)

4.0 kV at altitude <4000 m (13123 ft)

4.0 kV at altitude <4000 m (13123 ft)

Plug| 4.0 kV at altitude <2000 m (6561 ft)
3.1 kV 2000 m<altitude<4000 m (6561<altitude<13123 ft)
Overvoltage category| III
Degree of protection IPXX Pollution degree PDX| Enclosure rating according to IEC standard 60529 Pollution degree according to EN60664-1| IP67 plug| PD4
IP65 plug IP20 protection cap IP00 spade| PD3
Installation| Integrated control (picture A – D) Incorporated control (picture A – D)
Independently mounted control (IP65 and IP67) (picture B – D)
Suitable cable and conductor size for terminal box| ø6.6 – ø11 mm (ø0.26 – ø0.43 in)
0.75 – 1.5 mm² (21 – 15 AWG flexible cord)
Suitable cable for cable plug| See datasheet when ordering the coil
Moulded cable size Cable conductor size| Ø6.6 mm (ø0.26 in )

3 x 0.75 mm² (3 x 0.001 in2)

Moulded cable| The supply cord of this control cannot be replaced, if the cord is damaged. The control should be discard-

ed

Plugs can be removed/mounted| 10 times
Surface temperature| Indenpendantly mounted controls should be sealed of if the coil temperature exceed higher than 85⁰C

  • Only qualified personnel is allowed to install or maintain this product
  • Disconnect the power when dismounting the coil
  • Avoid direct exposure to alkaline conditions, use in neutral conditions is recommended
  • If the coil is used as independently mounted control, the end-user shall use a plastic cable gland with strain relief
  • Technical specifications are according to EN60730-1

Instructions

Visit www.products.danfoss.com for further technical data

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Danfoss User Manuals

Related Manuals