Kidde K7CO Carbon Monoxide Alarms Installation Guide
- June 13, 2024
- Kidde
Table of Contents
- Kidde K7CO Carbon Monoxide Alarms Installation Guide
- Thank You for Purchasing this Kidde Alarm
- ENVIRONMENTAL PROTECTION
- . Carbon Monoxide Alarm: What To Do When the Alarm Sounds
- WARNING: CARBON MONOXIDE ALARM ACTIVATION INDICATES THE PRESENCE OF
- Never restart the source of the CO problem until it has been corrected.
- 2.Other Alarm Visual and Audible Indicators
- 3 Troubleshooting Guide
- 4. Introduction, Product Features and Specifications
- Product Features
- Limitations of CO Alarms
- LIMITATIONS OF CO ALARMS
- 3.Recommended Locations for CO Alarms
- Additional Instructions for Caravans and Boats
- Operation and Testing
- Operation
- Testing
- Recognizing Nuisance Alarms
- Carbon Monoxide (CO) Nuisance
- Battery
- Replace battery
- Chirping:
- General Carbon Monoxide (CO) Information
- What is Carbon Monoxide?
- Cleaning Your Alarm
- Service and Warranty
- Ten-Year Limited Warranty
- Quick Start Instructions
- Model: K7CO, K7DCO (Model K7CO shown)
- Read More About This Manual & Download PDF:
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Kidde K7CO Carbon Monoxide Alarms Installation Guide
Thank You for Purchasing this Kidde Alarm
Powered by two AA batteries, these models include a digital display (model
K7DCO only), and a Reset function to temporarily silence nuisance alarms.
Teach children how to respond to the alarm and that they should never play
with the unit. This alarm is designed to detect carbon monoxide from any
source of combustion in a residential environment. As well as being
recommended for use in homes, this alarm is approved for use in caravans,
motor homes and boats.
NOTE: Please thoroughly read this user guide and save the document for
future reference and to pass on to any subsequent owner.
IMPORTANT: Additional markings can be found on the back of the unit.
The manufacturer recommends replacing this alarm ten years from the install
date on the side of alar
ENVIRONMENTAL PROTECTION
Waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with Local Authority or Supplier for recycling advice.
. Carbon Monoxide Alarm: What To Do When the Alarm Sounds
The carbon monoxide (CO) alarm pattern is four quick beeps repeating every 5 seconds. The red LED blinks in sync with the beep pattern. The digital display on model K7DCO will show the PPM level of CO detected.
WARNING: CARBON MONOXIDE ALARM ACTIVATION INDICATES THE PRESENCE OF
CARBON MONOXI O AT HIGH CONCENTRATIONS WHICH CAN KILL YOU.
Based on recommendations from EN 50292, follow these steps if alarm sounds:
- Keep calm and open all doors and windows. Turn off all fuel-burning appliances if possibl Note: it is possible that outdoor conditions could influence domestic CO alarms (bad traffic pollution in cold weather, for example). In these circumstances, the level of indoor CO might actually increase when doors and windows are opened.
- If the alarm continues to sound, even after being reset (where appropriate), then evacuate the premises, alerting other occupants to the risk. Leave doors and windows open. Do not re-enter the premises.
- Get medical help for anyone suffering the effects of CO poisoning, and advise that CO inhalation is suspected.
- Call Gas Emergency Services: 0800 111 999, or your local Gas Safe Registered Engineer:
Never restart the source of the CO problem until it has been corrected.
Never ignore the sound of the alarm!
N O T E : **** See Section RECOGNIZING NUISANCE ALARMS, for nuisance alarm situations.
2.Other Alarm Visual and Audible Indicators
Operational Mode| Visual Indications| Audible Indications|
Action/Note:
---|---|---|---
Normal (standby)| Green LED blinks approx every 30 sec.| |
Test (button press when no alarm condition is present)| Green and
amber LEDs illuminate. Red LED blinks in sync with beep pattern.
Model K7DCO digital display will show 3 dashes and then “888”.
| 4 loud pulses, a pause, 4 loud pulses.
Single beep
| Perform test button press once a week to verify proper alarm operation.
CO Alarm Memory (unit has experienced a CO alarm event or 100 ppm or more
CO within the last 14 days)| Red LED blinks every 60 sec.| None.| Model
K7CO: Push button to clear Alarm Memory.
Model K7DCO: Push Test/ Reset while the Peak Level button is depressed to clear Alarm Memory.
Peak Level CO K7DCO only| Digital display shows the highest CO
reading between 11 and 999 ppm since the peak level was reset.*| None.| Push
test/reset button while peak level button is depressed to clear peak level
memory.
CO alarm reset| Red LED continues to signal the alarm pattern.| After
button push: CO alarm pattern stops.|
present or if it experienced a nuisance situation. Re-alarm means danger. Move to fresh air and call 0800 111 999.
NOTE: CO levels up to 30ppm can occur under normal non-dangerous conditions. Such conditions could includ
3 Troubleshooting Guide
Low Battery| Amber LED blinks every 60 sec.
Model K7DCO digital display will show “Lb”.
| Chirp every 60 sec.| * Push test button once to silence for 24 hrs. Note: 30 days after Low Battery begins, the
* Replace batteries as soon as possible.
---|---|---|---
Fault Mode| Amber LED blinks every 30 sec.
Model K7DCO digital display will show “Err”.
| Chirp every 30 sec.| * See Cleaning Your Alarm section.
- Push test button once to attempt to reset the unit.
End of Unit Life| Amber LED blinks twice every 60 sec.
Model K7DCO digital display will show “End”.
| Two chirps every 60 sec.| * Push button once to silence for 24 hrs.
Note: 30 days after End of Unit Life begins, the
- Remove, dispose unit, and replace as soon as possible.
MCU Failure| None.| Constant tone.| Replace alarm.
Stuck Button| Amber LED blinks every 5 sec.| Chirp every 5 sec.| Push
button to dislodge it from being stuck. If button cannot be unstuck, remove,
dispose unit, and replace as soon as possible.
NOTE: If at any time your alarm fails to operate correctly (erratic or low sound, for example), or if you require further information, please contact customer support at 0800 917 0722
4. Introduction, Product Features and Specifications
Introduction
This alarm detects carbon monoxide using an electrochemical cell. Many times
throughout this User Guide, we will refer to Carbon Monoxide as “CO.”
Ten (10) years after the unit was installed, this unit will automatically
alert you that it is time to replace the unit. This is called “End of Unit
Life” mode. See Troubleshooting Guide. To help track the life of your alarm,
write the installation date in the space provided on the side of the alarm. A
label has been provided that has important information on what to do in case
of a CO alarm. Place the label at eye level on a wall near the alarm after it
is mounted.
Product Features and Specifications:
Temperature Operating Range: -10°C to 45°C
Humidity Operating Range: up to 90% RH non-condensing Audible Alarm: 85+ dB(A)
at 3 m, 3.0 to 3.5 kHz pulsing alarm Digital Display (K7DCO only)
N O T E : Depending on the ambient condition
(temperature, humidity) and the condition of the sensor,
the display readings may vary. The digital readings tolerances are 0-999 +/-
30% +15ppm during these con- ditions: Ambient: 27°C ± 12°C (80°F ± 10°F),
atmospheric pressure ±10%, 40% ± 3% relative humidityCO Sensor:
Electrochemical
Peak Level Memory (K7DCO only) CO Alarm Reset
Powered by AA batteries
Storage and Transport Conditions: -20° C to +60° C, 5-95%RH (non-condensing)
Approved for use in homes, caravans, motor homes and boats.
Product Features
Limitations of CO Alarms
WARNING: PLEASE READ CAREFULLY AND THOROUGHLY
This alarm is not intended to alert hearing impaired individuals.
LIMITATIONS OF CO ALARMS
IMPORTANT: This alarm is designed to detect carbon monoxide gas from ANY
source of combustion. It is NOT designed to detect any other gas.
CAUTION: This alarm will only indicate the presence of carbon monoxide
gas at the sensor. Carbon monoxide gas may be present in other areas. Never
restart the source of a CO problem until it has been fixed. NEVER IGNORE THE
ALARM!
WARNING: THIS PRODUCT IS INTENDED FOR USE IN ORDINARY INDOOR LOCATIONS OF
FAMILY LIVING UNITS. IT IS NOT DESIGNED TO MEASURE COMPLIANCE WITH COMMERCIAL
AND INDUSTRIAL STANDARDS. THIS ALARM IS NOT SUITABLE FOR INSTALLATION IN HAZARD OUS LOCATIONS.
IMPORTANT: THIS CARBON MONOXIDE ALARM IS DESIGNED TO DETECT CARBON MONOXIDE
FROM ANY SOURCE OF COMBUSTION INCLUDING IMPROPER OR MALFUNCTIONING APPLIANC
ES. THE INSTALLATION OF THIS DEVICE SHOULD NOT BE USED AS A SUBSTITUTE FOR
PROPER INSTALLATION, USE AND MAINTENANCE OF FUEL BURNING APPLIANCES INCLUDING
APPRO PRIATE VENTILATION AND EXHAUST SYSTEMS.
This alarm does not prevent CO from occurring, nor can it solve any existing
CO problem.
WARNING: THIS DEVICE IS DESIGNED TO PROTECT INDIVIDUALS FROM ACUTE EFFECTS OF
CARBON MONOXIDE EXPOSURE. IT WILL NOT FULLY SAFEGUARD INDIVIDUALS WITH
SPECIFIC MEDICAL CONDITIONS. IF IN DOUBT, CONSULT A MEDICAL PRACTITIONER.
INDIVIDUALS WITH MEDICAL PROBLEMS MAY CONSIDER USING WARNING DEVICES WHICH
PROVIDE AUDIBLE AND VISUAL SIGNALS FOR CARBON MONOXIDE CONCENTRATIONS UNDER 30
PPM.
This alarm has not been investigated for carbon monoxide detection below 50
PPM.
This alarm requires a continuous supply of electrical power – it will not work
without power.
WARNING: THIS CARBON MONOXIDE ALARM IS NOT A SUBSTITUTE FOR INSTALLING AND
MAINTAINING AN APPROPRIATE NUMBER OF SMOKE ALARMS IN YOUR HOME. THIS ALARM
WILL NOT SENSE SMOKE, FIRE, OR ANY POISONOUS GAS OTHER THAN CARBON MONOXIDE.
FOR THIS REASON YOU MUST INSTALL SMOKE ALARMS TO PROVIDE EARLY WARNING OF FIRE AND TO PROTECT YOU AND YOUR FAMILY FROM FIRE AND ITS RELATED HAZARDS.
3.Recommended Locations for CO Alarms
N O T E : Note: CO alarms should be installed following
the guidance of relevant local standards, such as EN 50292.
Whether the alarm is wall-mounted or ceiling mounted, place the alarm a
horizontal distance of between 1 metre and 3 metres from a fuel burning
appliance.
When mounting the alarm on the wall, use an inside wall with the top edge of
the alarm at a minimum of 150 mm below the ceiling. The bottom of the alarm
should also be at a level greater than the height of any door or window.
Locate within hearing distance of bedrooms* and place at sleeping height if a
heating appliance is in the bedroom.
CO alarms in rooms with sloped ceilings should be located on the high side of
the room.
Ceiling mounted alarms should be at least 300 mm from any wall.
If there is a partition in the room, locate the alarm on the same side of the
partition as the potential source.
- A CO alarm should be installed in all rooms containing a fuel burning appliance. Additional CO alarms should be installed in rooms where most awake time is spent, in every sleeping area, and on every level of the home.
Locations to Avoid
In the garage. Products of combustion are present when you start your motor
vehicle.
Do not install alarms adjacent to, or directly above, heaters or air-
conditioning vents.
In very humid areas (above 90% RH, non-condensing), such as bathrooms and
shower rooms. Do not install directly above a sink, or near dishwashers or
washing machines. Moisture or steam can cause nuisance alarms.
Do not install within 1 m of heating or cooking appliances, measured
horizontally.
In an area where the temperature may fall below -10 º C or rise above 45 º C
such as garages and unfinished attics
Do not install alarms in dusty areas. Dust particles may cause nuisance alarm
or failure to alarm.
In insect-infested areas
Within 300 mm of a light fitting, as electronic “noise” generated by the
electronics may cause nuisance alarms.
Do not install in an enclosed space (cupboard) or where the ventilation
openings in the unit could be impeded by items such as newspapers, table-
cloths, furniture, curtains, etc.
Do not install next to a door, window, extractor fan, flue, chimney, or any
other area where high air flow may occur or the unit may be directly exposed
to weather.
Do not install in locations that are difficult or dangerous to reach for
testing or maintenance.
Additional Instructions for Caravans and Boats
It is not always possible to find an optimum location for an apparatus, for
example, a small caravan or boat may not have suitable vertical surfaces
available. Nevertheless, when fitting an apparatus in such situations, the
most important considerations when selecting an appropriate location are:
Avoid mounting the apparatus directly above a source of heat or steam
Mount the apparatus at a distance of 1 m to 3 m from the nearest edge of the
potential source.
Avoid running the engine when moored alongside objects such as a wharf, a wall
or another boat
Avoid running your engine when docked in a crowded marina as vehicle and
exhaust fumes can damage the alarm sensor. For further information visit
www.boatsafetyscheme.com\
**WARNING: TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE
THIS PRODUCT TO RAIN OR MOISTURE.**
Installation / Activation
CAUTION: THIS UNIT IS SEALED. THE COVER IS NOT REMOVABLE!
NOTE: YOUR CO ALARM MUST BE INSTALLED BY A COMPETENT PERSON, AND IS TO BE INSTALLED ACCORDING TO THESE INSTRUCTIONS.
After selecting the proper alarm location as described in the “Recommended Locations for CO Alarms” section, you may choose either a wall mounting or free-standing installation.
Wall-mounting (recommended by the manufacturer, if possible)
- Drill two holes in a wall 78 mm apart (you may wish to use the back-plate for guidance)
- Insert the two wall plugs, that are supplied, into the holes
- Insert the two screws as supplied into the holes ensuring enough of the screw sticks out of the wall (approx. 3mm)
- Hook the alarm back-plate over the screws
Free-standing
ALWAYS BE CAREFUL TO LOCATE A FREE-STANDING ALARM WHERE IT IS UNLIKELY TO BE
KNOCKED TO THE FLOOR, AND IN ACCORDANCE WITH THE RECOMMENDED LOCATIONS
SECTION.
Ensure free-standing alarms are placed in the upright position, and not lying
flat on a surface.
Activation
- Remove the batteries from the pack and insert them into the battery compartment. Make sure that you fit the batteries in accordance with the polarity markings (+ or -) within the battery compartment. If correctly installed, the alarm will give a short beep.
- Slide the alarm onto the back-plate.
The alarm is now activated! After installation / activation, test your alarm as described in Operation and Testing section.
WARNING: FAILURE TO PROPERLY INSTALL AND ACTIVATE THIS ALARM WILL PREVENT PROPER OPERATION OF THIS ALARM AND WILL PREVENT ITS RESPONSE TO HAZARDS.
Operation and Testing
Operation
The alarm is operating once it is activated and testing is complete (see “TESTING” below). When CO is detected, the unit sounds a loud alarm. See Section 1 for alarm signal descriptions. In high levels of CO, the unit will go into alarm in a shorter period of time than at low levels of CO.
Parts per Million (PPM) of CO | Time until Alarm |
---|---|
50 | Minutes |
100 | Minutes |
300 | Must alarm in less than 3 minutes |
Testing
Test your alarm weekly, or after returning from a vacation or absence, by
pressing and releasing the button quickly. A quick beep will confirm the
button has been pushed followed by the test sequence. See Other Alarm Visual
and Audible Indicators table. The alarm will sound if the electronic
circuitry, horn, and batteries are work- ing. If the alarm does not sound, or
gives erratic or low volume sound, the unit must be replaced.
WARNING: DUE TO THE LOUDNESS OF THE ALARM, ALWAYS STAND ABOUT 1 METRE AWAY
FROM THE UNIT OR USE EAR PROTECTION WHEN TESTING.
BUMP TEST MODE
This alarm includes a “bump test” mode that will allow the alarm to be qualitatively tested during field service using commercially available aerosol CO.
- Hold the test button down for 10 seconds.
- The unit will chirp 3 times indicating the start of test mode.
- The Green LED flashes once per second during test mode.
- Apply the commercially available aerosol CO.
- CO alarm sounds if CO reading is above 40 ppm.
- The alarm will automatically exit from the bump test mode after 2 minutes followed by
NOTE: The test can be terminated manually by pressing the test button.
CAUTION: This unit should only be bump tested using clean, dry CO test gas by a trained service engineer.
Recognizing Nuisance Alarms
Carbon Monoxide (CO) Nuisance
RESET: Pushing the test / reset button during CO alarm allows the unit to
reset calculations and double check for the presence of CO. If the unit re-
alarms, it is sensing high levels of CO which can quickly become a dangerous
situation. Move to fresh air and call 0800 111 999.
WARNING: IT IS IMPOSSIBLE TO DETERMINE THE SOURCE OF A CO ALARM USING SIGHT
OR SMELL. ALWAYS CONSIDER A CO ALARM EVENT AS DANGEROUS.
Battery
This alarm is powered by two AA batteries. Under normal operating conditions,
the batteries will last a mini- mum of one year. NOTE: Constant exposures to
extreme temperatures and humidities may affect battery life.
WARNING: DO NOT ATTEMPT TO OPEN THE ALARM FOR ANY REASON! DO NOT TRY TO REPAIR
THE ALARM YOURSELF.
Low Battery
This alarm is equipped with a low battery monitor circuit. If the battery capacity is nearing the point where it can no longer provide adequate power for all alarm functions, the low battery condition will occur. See Trou- bleshooting Guide. The batteries must be replaced within 30 days of the first occurrence of the “Low Battery Warning” to provide continuous alarm detection.
Replace battery
Slide alarm from back-plate.
Insert 2 x replacement ‘AA’ batteries (noting polarity – see sketch)
Replace back-plate and test the alarm
These batteries can be purchased from your local retailer.
NOTE: Do not use Lithium batteries in this unit .
W A R N I N G ! Alarm will not attach to
back-plate unless batteries are installed. Depleted or removed batter- ies
will render this alarm inoperative.
Chirping:
When End of Unit Life or Low Battery chirping begins, you can temporarily
silence these chirps by pressing the test button. See Troubleshooting Guide.
WARNING: Replace unit immediately after End of Unit Life. It will not
detect CO in this condition.
General Carbon Monoxide (CO) Information
What is Carbon Monoxide?
Carbon monoxide (CO) is a highly poisonous gas with no taste, colour or smell.
Carbon monoxide is a cumulative poison. Long term exposure to low levels may
cause symptoms. This alarm is time-weighted – the higher the level of CO, the
sooner it will alarm.
N O T E : The apparatus may respond to brief exhaust gas
emissions, for example during the initial start-up of an
appliance. Also, hydrogen acts as an interferent and can arise from some
battery charging activities and the curing of concrete or cement under certain
circumstances. Volatile Organic Compounds (VOCs), e.g. alcohols, which may
eventually activate the alarm, can be generated from use of damp-proofing
materials or other coatings containing alkylalkoxysilanes
The table below shows the effects of different levels of CO poisoning on the body;
Parts per Million (PPM) | Effects on Adults |
---|---|
100 | Slight headache, nausea, fatigue (flu-like symptoms) |
200 | Dizziness and headache within 2 – 3 hours |
400
| Nausea, frontal headache, drowsiness, confusion and rapid heart rate. Risk
to life after over 3 hours of exposure
800| Severe headaches, convulsions, vital organ failures. Death possible
within 2 – 3 hours
Warning: The device cannot warn against the chronic effects of exposure to
carbon monoxide or protect individuals who are at specific risk.
N O T E : If you recognise any of the above symptoms
consult your Doctor immediately.
N O T E : Young children, elderly and pets are more
susceptible to the dangers of CO.
N O T E : Your Kidde alarm is designed to detect CO gas.
It is not designed to detect other gas such as natural gas.
N O T E : This product is intended for use in ordinary
family homes. It is not designed to measure compliance with occupational
safety and the HSE.
N O T E : Individuals with certain specific medical
conditions may need an alarm that operates below 30ppm. If this applies
consult your Doctor.
IMPORTANT: Ensure that all family members are familiar with the symptoms
of CO poisoning and how your alarm works.
To be safe, know the possible sources of CO in your home, caravan, motor home,
or boat. Keep fuel burning appliances and their chimneys and vents in good
working condition. Learn the early symptoms of exposure, and if you suspect CO
poisoning, move outside to fresh air and get emergency help. Your first line
of defence is an annual inspection and regular maintenance of your appliances.
Contact a licensed contractor or call your local utility company for
assistance.
In rented properties your Landlord (or Council/ Housing Association), will
have an Emergency Response phone number, and be liable for the regular
maintenance of their combustion appliances(Gas/LPG/Oil/ Solid Fuel).
Further Information for Caravan and Boat OwnersThe following can lead to
carbon monoxide being produced:Using LPG cooking appliances for space heating
Leaving LPG appliances on overnight Barbecues within the boat cabin or near a
caravan door (e.g. under an awning)
Cleaning Your Alarm
Your Alarm Should be Cleaned at Least Once a Year
You can clean the interior of your alarm by using compressed air or a vacuum
cleaner hose and blowing or vacuuming through the openings around the
perimeter of the alarm. The outside of the alarm can be wiped with a damp
cloth. Use only water to dampen the cloth, use of detergents or cleaners could
damage the alarm.
If the alarm is in Fault mode, the alarm may be in need of cleaning. After
cleaning, press the test button. If the fault does not clear, the alarm needs
to be replaced.
Never use detergent or other solvents to clean the unit.Avoid spraying air
freshener, hair spray, or other aerosols near the alarm.
Do not paint the unit. Paint will seal the vents and interfere with the
sensor’s ability to detect CO. Keep away from nappy buckets.
Never attempt to disassemble the unit to clean inside. Altering the alarm in
any way may lead to a risk of electric shock or prevent it from functioning
correctly. This action will void your warranty.
The following substances can affect the CO sensor and may cause false readings
and damage to the sen- sor: Methane, propane, isobutane, iso-propanol, ethyl
acetate, hydrogen sulfide, sulfide dioxides, alcohol based products, paints,
thinner, solvents, adhesives, hair spray, aftershave, perfume, and some
cleaning agents.
NOTE: there could be other compounds occurring within a particular
household which could cause similar effects.
Move the Alarm and place in another location prior to performing any of the
following: Staining or stripping wood floors or furniture
PaintingWall papering Using adhesives
Storing the unit in a plastic bag during any of the above projects will
protect the sensors from damage. When household cleaning supplies or similar
contaminates are used, the area must be well ventilated.
\
WARNING: REINSTALL THE ALARM AS SOON AS POSSIBLE TO ENSURE CONTINUOUS DETECTION.
Service and Warranty
Ten-Year Limited Warranty
KIDDE SAFETY EUROPE LTD warrants to the original purchaser that the enclosed
alarm (batteries excluded) will be free from defects in material and
workmanship or design under normal use and service for a period of ten years
from the date of purchase. The obligation of KIDDE SAFETY EUROPE LTD under
this warranty is limited to repairing or replacing the alarm or any part which
we find to be defective in material, workmanship or design (part replacement
only, no installation), free of charge to the customer, upon sending the alarm
with proof of date of purchase, postage and return postage prepaid, to
distributor: Warranty Service Department, Kidde Safety Europe Ltd, Ash House,
Littleton Road, Ashford, TW15 1TZ, UK. Before shipping, please remove the
batteries from the alarm.
This warranty shall not apply to the alarm if it has been damaged, modified,
abused or altered after the date of purchase or if it fails to operate due to
improper maintenance or inadequate A.C. or D.C. electrical power.
THE LIABILITY OF KIDDE SAFETY EUROPE LTD OR ANY OF ITS PARENT OR SUBSIDIARY
CORPORATIONS ARISING FROM THE SALE OF THIS ALARM OR UNDER THE TERMS OF THIS
LIMITED WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACEMENT OF THE
ALARM AND, IN NO CASE, SHALL KIDDE SAFETY EUROPE LTD
OR ANY OF ITS PARENT OR SUBSIDIARY CORPORATIONS BE LIABLE FOR CONSEQUENTIAL
LOSS OR DAMAGES RESULTING FROM THE FAILURE OF THE ALARM OR FOR BREACH OF THIS
OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, EVEN IF THE LOSS OR DAMAGE IS
CAUSED BY THE COMPANY’S NEGLIGENCE OR FAULT.This warranty does not affect your
statutory rights.
Quick Start Instructions
Model: K7CO, K7DCO (Model K7CO shown)
Kidde Helpline (UK) 0800 917 0722 / (Ireland) 1800 818 601 Emergency Numbers:
Gas Emergency Services 0800 111 999
HETAS (Solid Fuel Emergency) 0845 634 5626
Oftec (oil) 0845 658 5080
Read More About This Manual & Download PDF:
References
- BSS | Boat Safety Scheme | Go Boating - Stay Safe
- Home Fire Safety Products (smoke & carbon monoxide alarms, fire extinguishers, etc.) from Kidde - Kidde
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>