ATIS KOUKAAM CHQ-PCM-SCI HFP Loop Powered Output Module Instruction Manual
- June 13, 2024
- ATIS KOUKAAM
Table of Contents
ATIS KOUKAAM CHQ-PCM-SCI HFP Loop Powered Output Module Instruction Manual
The CHQ-PCM(SCI) is a loop powered output module with four independent change- over relay outputs, with N/O and N/C volt free contacts. These outputs can be driven separately under the control of the fire alarm panel and can be used for the control of devices such as dampers or for plant and equipment shutdown. Four inputs are provided for local fire and fault monitoring and these are fully monitored for open and short circuit, which if required, can be enabled or disabled in pairs using a two-way DIL switch. Note:- The state of the relay contacts will be indeterminate until the unit is powered
Components
Standard “Smart-Fix” Modules are supplied as two individual components (see
Fig 1 & 2). DIN versions are supplied as one unit (see Fig 3)
“Smart-Fix” CHQ Module (Back Plate inc PCB Component)
( Note: configuration of Wiring Terminal blocks differs between models)
CHQ-LID Transparent Module Lid
(Supplied with four screws and acrylic retaining washers)
Setting the Loop Address
-
The analogue address of the Module is set using the first 7 switches of the 8-bit DIL switch, which in the case of the Standard CHQ is located through the cut-out section on the top of the PCB cover. On the DIN version, this switch is located on the edge of the PCB behind the clear door (see Fig 3).
-
The switches are numbered 1 to 8 (left to right):
DIN Rail Mountable CHQ Module
CHQ MODULE| SWITCH UP| ON|
---|---|---|---
SWITCH DOWN| OFF|
DIN MODULE| SWITCH UP| OFF|
SWITCH DOWN| ON| -
The switches should be set using a small-tipped screwdriver or similar.
-
Refer to the Address Chart (Fig 5) on page 3 for a quick reference on addresses.
-
Switch 8 is not used and must be switched to “OFF”.
Connection Details
The module has been designed for easy installation
and contains two connector blocks for termination of the field wiring; refer
to Fig. 4 (right) for correct connection details
A – EOL Monitoring Resistor, 10 KΩ
B – Operational Resistor, 470 Ω (volt-free contact)
Setting the Fault Monitoring
The general purpose inputs on the CHQ-PCM(SCI) are fully monitored for open and short circuit, however, if the monitoring facility is not required then they can be disabled by the two-way DIL switch, refer to the table below
CHQ MODULE| SWITCH 1 DOWN| INPUTS 1 & 2 MONITORED| In Non-Monitored mode
*** , the unit ignores open or short-circuit condition – but still requires
470 Ω to activate.
---|---|---|---
SWITCH 1 UP| INPUTS 1 & 2 NOT MONITORED
SWITCH 2 DOWN| INPUTS 3 & 4 MONITORED
SWITCH 2 UP| INPUTS 3 & 4 NOT MONITORED
DIN MODULE**| SWITCH 1 DOWN| INPUTS 1 & 2 NOT MONITORED
SWITCH 1 UP| INPUTS 1 & 2 MONITORED
SWITCH 2 DOWN| INPUTS 3 & 4 NOT MONITORED
SWITCH 2 UP| INPUTS 3 & 4 MONITORED
Specification
Order codes | CHQ-PCM(SCI) (module)CHQ-PCM/DIN(SCI) (DIN module) |
---|---|
Transmission method | Digital communication using ESP |
Loop | Operating voltage |
Quiescent current | 300 mA |
Current consumption whilst polling | 22 mA ± 20 % |
Relay contact rating | 30 Vdc max, 1 A (resistive load) |
Input E.O.L resistor | 10 kW, ±5%, 0.25 W |
Input threshold level | ON=470 W, Short cct <50 W, Open cct >100 KW |
Isolator | Switch current (switch closed) |
Leakage current (switch open) | 3 mA (max) |
Weight (g) Dimensions (mm) | CHQ Module |
with lid),
567| H79 (CHQ Module with lid and CHQ-BACKBOX)
DIN Module| 150| L119 x W108 x H24 (CHQ DIN Module)
Colour and enclosure material| CHQ Module & CHQ-BACKBOX white ABS, DIN Module
green ABS
Fire alarm control panel compatibility is required for both variants of this product. See AP0127 for short circuitisolator specifications.
Note:- All EOL and operational resistors are supplied with the unit – DO NOT DISCARD!
Installation – “Smart-Fix” Version
Set analogue address before installation .
The fixing surface should be dry and stable.
- Hold the back plate up against the fixing surface and mark the position of the four corner fixing holes.
- Determine which cut-out sections along the top and bottom edges of the module require removing to accommodate the cables being used.
- Remove cut-outs by scoring with a sharp knife before breaking off with pliers or snips.
- Mount the back plate using appropriate fixings (not supplied) for the fixing surface.
- Terminate and connect field wiring as per the wiring diagrams on pages 2 & 3 (and the terminal block indications on the product label).
The transparent lid (CHQ-LID) is supplied with four screws and eight retaining washers.
- Push the screws through one of the retaining washers and then through the holes in the lid from front to back, pushing another retaining washer onto the end inside the lid.
- Screw the lid onto the back plate; do not over tighten the screws as this could damage the unit.
NOTE: A white plastic version of the lid is available (sold separately – CHQ-LID(WHT))
Installation with Back Box
For installations requiring glanded cables, a module back box (CHQ-BACKBOX) is available (sold separately). This is mounted on the fixing surface; the CHQ Module is then fitted to the top of the back box and the CHQ LID is added creating a sealed enclosure. For further details refer to the CHQ-BACKBOX Instructions (2-3-0-800). For CHQ PCM installations utilising heavy-duty cabling (for example, 1.5mm2 solid conductor) the use of the SMB-1 Box with the SMB-ADAPTOR plate and CHQ-ADAPTOR is recommended. For further details refer to the SMB-ADAPTOR Instructions (2-3-0-1502). Ensure any glands used (not supplied) conform to IP67, if such ingress protection is required.
Installation – DIN Version
Set analogue address before installation (see above) and write loop address in space provided on door label.
- DIN modules should be mounted in an SMB-2 or SMB-3 enclosure in conjunction with an NS 35 mounting rail with the loop connections at the bottom of the unit. Use glands that conform to IP65 if such ingress protection is required.
- Terminate and connect field wiring as per the wiring diagram on page 2 (and the terminal block indications on the product label).
- Suitable anti-static precautions must be taken when handling these products.
Status LEDs
A green LED flashes each time the unit is polled by the fire alarm control panel.
An amber LED is continually illuminated when unit detects short-circuit fault.
Protocol specified in TI/006| CHQ-PCM(SCI)| 0832-CPD-1679| 11| EN54-17 Short Circuit Isolators
EN54-18 Input/Output Modules
---|---|---|---|---
CHQ-PCM/DIN(SCI)| 0832-CPD-1680| 11
Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been made to ensure the accuracy of the information contained within this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description. Please check our web site for the latest version of this document.
Hochiki Europe (UK) Ltd
Grosvenor Road, Gillingham Business Park,
Gillingham, Kent, ME8 0SA, England
Telephone: +44(0)1634 260133
Facsimile: +44(0)1634 260132
Email: sales@hochikieurope.com
Web: www.hochikieurope.com