PI-PF PureFlow Press Zero Lead Bronze Fittings
![Viega PI PF PureFlow Press Zero Lead Bronze Fittings
- Product Overview 3](https://manuals.plus/wp-content/uploads/2023/09/Viega- PI-PF-PureFlow-Press-Zero-Lead-Bronze-Fittings-Product-Overview-3.jpg)
Viega products are designed to be installed by licensed and trained plumbing
and mechanical professionals who are familiar with Viega products and their
installation.
Installation by non-professionals may void
Viega LLC’s warranty.
DANGER!
Read and understand all instructions for installing PureFow Press fittings.
Failure to follow all instructions may result in extensive property damage,
serious injury, or death.
Zero Lead identifies Viega® products meeting the lead free requirements of
NSF 61-G through testing under NSF/ANSI 372 (0.25% or less maximum weighted
average lead content).
-
Square off tubing to proper length. Uneven, jagged, or irregular cuts will produce unsatisfactory connections.
-
Insert PureFlow Press fitting with attached sleeve into tubing and engage fully.
-
Ensure full tubing insertion at view holes in attached press sleeve. Full insertion means tubing must be completely visible in at least two view holes and partially visible in the one.
If using hand tools continue with steps 4 to 7. If using power tools skip to steps 8 to 11.
Pressing with a Hand Tool -
Position the PureFlow press tool perpendicular over the press sleeve, resting it against the tool locator ring. Make sure the PureFlow press tool is properly aligned (see step 6 figure if it is not).
The tool locator ring must be in the factory installed position while making a press to ensure a consistent leak-proof connection.
It may be necessary to rotate the tool locator ring to avoid interference between the ring and tool. -
Close handles, using trigger to reduce grip span if desired.
-
If the PureFlow press tool is not properly aligned with the locator ring, use the emergency release (using a screw driver to turn the emergency release) to open the press tool. Once released, align the PureFlow press tool properly and go back to step 4.
WARNING!
The connection is not leak-proof when the tool has been opened by emergency release. The tool locator ring must be present to ensure a proper PureFlow Press connection. -
Extend the PureFlow press tool handle and continue ratcheting until automatic tool release occurs at the proper compression force.
CAUTION!
Do not press twice.
Pressing with a Power Tool -
Insert the appropriate PureFlow press jaw into the press tool and push in the holding pin until it locks.
-
Open jaw and position perpendicular over press sleeve resting it against the tool locator ring.
The tool locator ring must be in the factory installed position while making a press to ensure a consistent leak-proof connection.
It may be necessary to rotate the tool locator ring to avoid interference between the ring and tool. -
Start the pressing process; hold the trigger until the jaw has automatically released.
-
When press connection is complete, open and remove the jaw.
WARNING!
The tool locator ring must be present to ensure a proper PureFlow Press connection.
CAUTION!
Do not press twice.