Russelectric RTSCD Commercial Duty Service Entrance Rated Transfer Switches Instruction Manual

June 13, 2024
Russelectric

Instruction Manual RUSSELECTRIC
RTSCD Commercial Duty Service Entrance
Rated Transfer Switches
www.russelectric.com

Product description

Russelectric RTSCD Service Entrance Rated Transfer  Switches combine automatic power switching with the  necessary disconnecting, grounding, and bonding required for use as service entrance equipment. The power transfer switch meets all National Electrical Code requirements of the Normal\ Utility source for service entrance use.

Typical applications

  • Commercial  buildings
  • Educational  campuses
  • High-rise  complexes
  • Industrial  Plants
  • Manufacturing facilities

Standards and certifications

  • UL1008upto480VAC
  • NFPA110
  • NECArticles700,701,702
  • EnclosureULType1or3R
  • Seismic Standards: IBC 2018, CBC2019

Key features

  • Availablein2,3&4Polewithsolidorfullyratedswitchedneutral
  • User friendly, intuitive keypad and display with both icons    and word  markings
  • Silver plated copper ground and neutral bus with solderless   mechanical type  terminals
  • Historical event log standard
  • Front  connected
  • RS485MODBUSRTUProtocol
  • Rapid and reliable arc quenching
  • Manual Transfer with rapid arc interruption and permanently  affixed handle
  • Quick-Break, Quick-Make high speed preloaded, over-center transfer
  • Double throw, mechanically held contactor mechanism
  • Contacts easily accessible for fast contact inspection
  • Flame retardant switchboard type wiring

Optional accessories

  • PM – Power Monitoring Package (PM)
  • API-Auto/LoadTestKeySwitchandLoadShedRelays  (Source Inhibit Relays) both sources
  • AP2–SelectorSwitchforAuto/Manual
  • PushbuttonsforManualTransfer(XK12,XP12,XP13)
  • Space Heater / Thermostat

The RTSCD line of transfer switches deliver Russelectric’s legendary reputation for quality and reliability in a commercial duty switch.
The RTSCD has a user friendly operator interface panel (O.I.P.), which utilizes softkeys and intuitive operation. Like all Russelectric transfer switches, the RTSCD features preloaded springs and an electric operator-driven over-center mechanism for extremely quick switching operations. This unique ATS design instantaneously opens and closes the ATS contacts and provides for rapid full arc interruption, even under maximum voltage and amperage. This considerably reduces contact erosion and effectively increases the switch’s useful life.
A manual operator is permanently fixed to the ATS switching chassis.

Example: RTSCD – ASA2603 AMW 1XXXX- Service Entrance Transfer Switch Open Transition, 260A,3 Polewith Solid Neutral, 480/277V, No Accessories.

Overall Dimensions

Shipping Weights And Dimensions Type 1 & 3R Wall-Mounted **Enclosed**

Dimensions Single Operator – 100A – 400A, 3 & 4 pole: 48”H x 36”W x 14.62”D
Dimensions Dual Operator – 100A – 400A, 3 & 4 pole: 60”H x 36”W x 14.62”D

Weights

| Single Operator|

Dual Operator

100A, 3 pole| 215 lbs.| 300 lbs.
100A, 4 pole| 230 lbs.| 315 lbs.
200A, 3 pole| 225 lbs.| 310 lbs.
200A, 4 pole| 241 lbs.| 326 lbs.
260A, 3 pole| 235 lbs.| 320 lbs.
260A, 4 pole| 253 lbs.| 338 lbs.
400A, 3 pole| 256 lbs.| 341 lbs.
400A, 4 pole| 263 lbs.| 348 lbs.

Note: On NEMA 3R units the circuit breaker toggle will employ a NEMA 3R rated circular twist knob.

Source 1 Service Entrance Breaker (included)

Amperage range 100-200 Siemens Type 3VA62 3P 250A 65KA ETU3-LIG 100
Amperage range 260-400 Siemens Type 3VA64 3P 400A 65KA ETU3-LIG 100

Note:

  1. Russelectric is providing the Siemens 3VA Molded Case Circuit Breaker for source 1 within the assembly. (More info on breaker available at Siemens website, search 3VA).
  2. Source 2 breaker is not included but it should follow the subsequent charts to maintain withstand ratings.
  3. The over-current setting (Ir/A) of the service entrance source 1 feeder breaker is set at the factory to the same ATS ampere rating and should not be changed. All other settings should only be set by qualified personnel.

Short Circuit Closing and Withstand Ratings Specific Circuit Breaker Manufacturers 100-200A (Feeder Breaker not included)

Short-circuit current (kA)| Max. Voltage (VAC)| Manufacturer| Type| Max.Current Rating (Amperes)
50| 480| Siemens| 3VA5| 100
50| 480| Siemens| 3VA5| 150
50| 480| Siemens| 3VA5| 250
50| 480| Siemens| 3VA6| 150
50| 480| Siemens| 3VA6| 250
50| 480| Schneider Electric| DC| 100
50| 480| Schneider Electric| FI| 100
50| 480| Schneider Electric| HD| 100
50| 480| Schneider Electric| HG| 100
50| 480| Schneider Electric| HJ| 100
50| 480| Schneider Electric| HL| 100
50| 480| Schneider Electric| JD| 250
50| 480| Schneider Electric| JG| 250
50| 480| Schneider Electric| JJ| 250
50| 480| Schneider Electric| JL| 250
35| 480| Eaton| FCL| 250
35| 480| Eaton| JGS| 250
35| 480| Eaton| JGH| 250
35| 480| Eaton| JGC| 250
Short Circuit Closing and Withstand Ratings When Protected by Current Limiting Fuses
Short-circuit current (kA)| Max. Voltage (VAC)| Fuse Class| Max Current Rating (Amperes)
100| 480| J| 400
Mechanical Lug Sizing
100A: (1) 1/0 – 14 AWG OR (2) 4 – 12 AWG
200A: (1) 250MCM – 6 AWG

NOTE: When protected by a circuit breaker of specific manufacturer, type, and ampere rating as marked above, this transfer switch is suitable for use in circuits capable of delivering the short-circuit current at the maximum voltage marked.

RTSCD Commercial Duty Service Entrance Rated Transfer Switches

Short Circuit Closing and Withstand Ratings Specific Circuit Breaker Manufacturers 260-400A (Feeder Breaker not included)

Short-circuit current (kA)| Max. Voltage (VAC)| Manufacturer| Type| Max.Current Rating (Amperes)
65| 480| Siemens| 3VA5| 250
65| 480| Siemens| 3VA6| 250
50| 480| Siemens| 3VA6| 400
50| 480| Siemens| 3VA6| 600
65| 480| Schneider Electric| NSX| 400
100| 480| Schneider Electric| JJ| 250
100| 480| Schneider Electric| JL| 250
100| 480| Schneider Electric| JR| 250
65| 480| ABB (GE)| SFL| 250
100| 240| ABB (GE)| SFL| 250
50| 480| Eaton| LGH| 400
Short Circuit Closing and Withstand Ratings When Protected by Current Limiting Fuses
Short-circuit current (kA)| Max. Voltage (VAC)| Fuse Class| Max Current Rating (Amperes)
100| 480| J| 600
Mechanical Lug Sizing
260 – 400A: (1) 4-600MCM or (2) 1/0 – 250MCM

NOTE: When protected by a circuit breaker of specific manufacturer, type, and ampere rating as marked above, this transfer switch is suitable for use in circuits capable of delivering the short-circuit current at the maximum voltage marked.

Notes:…………
This document contains a general description of available technical options only, and its effectiveness will be subject to specific variables including field conditions and project parameters.
Siemens does not make representations, warranties, or assurances as to the accuracy or completeness of the content contained herein. Siemens reserves the right to modify the technology and product specifications in its sole discretion without advance notice.

Legal Manufacturer Russelectric,

A SiemensBusiness

South Shore Park

Hingham, MA 02043

United States of America

[email protected]  

www.russelectric.com  

Phone:781-749-6000

800-225-5250

Order No. RSBR-RTSCDSE-0823
© 08.2023, Siemens Industry, Inc.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals