OXBOX J4PG4xxxB Gas Electric Units Instruction Manual

June 13, 2024
Oxbox

OXBOX J4PG4xxxB Gas Electric Units

Product Information

Product Name Package Gas Electric Units featuring R-410A 14 SEER Series
Product Type Gas Electric Unit
SEER Rating 14
Certifications UL STD. 1995, CSA STD. C22.2 NO. 236, ANSI STD Z21.47-2016,

CSA
STD 2.3-2016

Product Usage Instructions

Safety

  • Read and follow all safety warnings and instructions carefully.
  • Do not store or use gasoline, flammable vapors and liquids, or other combustible materials near the appliance.
  • Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or death. Installation and service must be performed by a qualified installer, service agency, or gas supplier.
  • In the Commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter for appropriate fuel.
  • Do not use the furnace if any part has been under water. Contact a qualified service agency to inspect the furnace and  replace any wet gas controls, control system parts, electricalparts, or the furnace if necessary.

RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION

WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage.

WARNING

  • Do not store or use gasoline or other flammable vapors and liquids, or other combustible materials in the vicinity of this or any other appliance.
  • WHAT TO DO IF YOU SMELL GAS
    • Do not try to light any appliance; do not touch any electrical switch; do not use any phone in your building.
    • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
    • If you cannot reach your gas supplier, call the fire department.
    • Do not return to your home until authorized by the gas supplier or fire department.
  • Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or death.
  • Refer to this manual, installation and service must be performed by a qualified installer, service agency or the gas supplier. In the commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter for appropriate fuel.

NOTE: Do not use this furnace if any part has been under water. A flood- damaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and to replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary. DO NOT DESTROY THIS MANUAL Please read carefully and keep in a safe place for future reference by a serviceman This document is customer property and is to remain with this unit. These instructions do not cover all the different variations of systems  nor does it provide for every possible contingency to be met inconnection with installation. All phases of this installation must comply with NATION, STATE AND LOCAL CODES. If additional information is required please contact your local distributor.

SAFETY

When you see the symbols below on labels or in the manual, be alert to the potential or immediate hazards of personal injury, property and/or product damage. It is the owner’s or installer’s responsibility to comply with all safety instructions and information accompanying these symbols.

WARNING: This is a safety alert symbol indicating a potential hazardous situation, which could result in personal injury, property and/or product damage or death.
CAUTION: This is a safety alert symbol indicating a potential hazardous situation, which could result in moderate personal injury, and/or property and product damage.

WARNING
These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
WARNING
The manufacturer’s warranty does not cover any damage or defect to the gas/electric unit caused by the attachment or use of any components, accessories or devices (other than those authorized by the manufacturer) into, onto or in conjunction with the gas/electric unit. You should be aware that the use of unauthorized components, accessories or devices may adversely affect the operation of the gas/electric unit and may also endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized components, accessories or devices.
WARNING
Do not, under any circumstances, connect return ductwork to any other heat producing device such as a fireplace insert, stove, etc. Unauthorized use of such devices may result in fire, CarbonMonoxide poisoning, explosion, property damage, severe personal injury or death.
WARNING
This unit is designed certified for outdoor installation only. Installation inside any part of a structure can result in inadequate unit performance as well as property damage. Installation inside can also cause recirculation of flue products into the conditioned space resulting in personal injury or death.
WARNING
The spark ignitor and ignition lead from the ignition control are high voltage. Keep hands or tools away to prevent electrical shock. Shut off electrical power before servicing any of the controls. Failure to adhere to this warning can result in personal injury or death.
WARNING
Proposition 65: This appliance contains fiberglass insulation. Respirable particles of fiberglass are known to the state of California to cause cancer. Exhaust gas from this appliance contains chemicals, including carbon monoxide, known to the state of california to cause birth defects of other reproductive harm.
WARNING
Never allow products of combustion or the flue products to enter the return air ductwork, or the circulating air supply. All return ductwork must be adequately sealed and secured to the furnace with sheet metal screws, and joints taped. All other duct joints must be secured with approved connections and sealed airtight.  Failure to prevent products of combustion from being circulatedinto the living space can create potentially hazardous conditions, including Carbon Monoxide poisoning that could result in personal injury or death.
WARNING
Holes in the exhaust transition or heat exchanger can cause toxic fumes to enter the home. The exhaust transition or heat exchanger must be replaced if they have holes or cracks in them. Failure to do so can cause Carbon Monoxide poisoning resulting in personal injury or death.
WARNING
Do not attempt to manually light this furnace with a match or any open flame. Attempting to do so can cause fire or explosion resulting in property damage, personal injury or death.
WARNING
Should overheating occur or the gas supply fail to shut off. Shut off the Manual Gas valve to the appliance before shutting off the supply. Failure to do so can result in an explosion or fire causing property damage, severe personal injury or death.
WARNING
Disconnect all power to the unit before starting maintenance. Failure to do so can result in severe electrical shock or death. Regular maintenance will reduce the buildup of contaminants and help to protect the unit’s finish.
WARNING
Turn off the main electrical power at the branch circuit disconnect closest to the unit before attempting any wiring. Failure to do socan cause electrical shock resulting in personal injury or death.
WARNING
DO NOT JUMPER THIS DEVICE! Do not reset the overtemperature control without taking corrective action to assure that an adequate supply of combustion air is maintained under all conditions of operation. Failure to do so can result in Carbon Monoxide poisoning or death. Replace this control only with the identical replacement part.
WARNING
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation resulting in fire ,electrical shock, property damage, personal injury or death.
WARNING
This unit is equipped at the factory for use on Natural Gas only. Conversion to LP Gas requires a special kit enclosed instructions with. DO NOT BURN ANY LIQUID FUEL OR SOLID FUEL IN THIS UNIT. Burning any unapproved fuel will result in damage to this unit heat exchanger, which could result in fire, Carbon Monoxide poisoning, explosion, personal injury, property damage or death.
WARNING
Install this unit only in a location and position as specified in the location requirements and considerations section of these instructions. Provide adequate combustion and ventilation air to the unit space as specified in the venting section of these instructions.
WARNING
Do not use this unit during construction if air laden corrosive compounds are present such as chlorine and fluorine. Otherwise, provisions must be taken to provide clean, uncontaminated combustion and ventilation air to the unit, combustion and ventilation air contaminated with these compounds forms acids during combustion which corrodes the heat exchanger and component parts, some of these contaminates are found in, but not limited to, paneling, dry wall, adhesives, paints, stains, varnishes, sealers, and masonry cleaning materials.
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in dangerous operation, serious injury, death or property damage. Improper installation,adjustment,alteration,service, maintenance or use could cause carbon monoxide poisoning, explosion,fire,electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified service agency,local gas supplier or your distributor or branch for information or assistance. The qualified service agency must use only factory- authorized and listed kits or accessories when modifying this product.
WARNING
Always install unit to operate within the unit’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in ducting section of these instructions, see also unit rating plate.
CAUTION
FURNACE RELIABILITY HAZARD Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure. Application of this furnace should be outdoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
CAUTION
CUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
CAUTION
R410A systems operate at higher pressures than R22 systems. Do not use R22 service equipment or components on R410A equipment.
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death or property damage.

  • Before servicing, disconnect all electrical power to furnace.
  • When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
  • Verify proper operation after servicing.

Improper installation, adjustment, alteration, service, Maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions include in  literature and attached to the unit. Consult local building codes,the current editions of the National Fuel Gas Code (NFGC) NFPA54/ANSI Z223.1 and the National Electrical Code (NEC) NFPA 70. A manufactured (mobile) home installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or when this Standard is not applicable, the Standard for Manufactured Home Installations (Manufactured Home Sites, Communities and Set-Ups), ANSI/NCS A225.1, and/or MH SeriesMobile Homes, CAN/CSA Z240. In Canada, refer to the current editions of the National Standards of Canada CAN/CSA-BI49.1 and .2 Natural Gas and Propane Installation Codes, and Canadian Electrical Code CSA C22.1 Recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced Installation, reliability, or operation.

  • Use only with type of gas approved for this unit. Refer to the unit rating plate.
  • Install this unit only in a location and position as specified in the “Installation” section of these instructions.
  • Provide adequate combustion and ventilation air to the unit space as specified in “Safety” section.
  • Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas Supply, Condensate drain and Piping” section.
  • Always install unit to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in the “Safety” section. See also unit rating plate.
  • When unit is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See “Ductwork” and “Return Air” section.
  • The unit may be used for construction heat provided that the furnace installation and operation complies with the CAUTION and WARING instructions in this manual.
  • The unit is design-certified for use with natural and propane gases (see unit rating plate) and for installation in outside only. The unit is factory-shipped for use with natural gas. A listed accessory gas conversion kit is required to convert unit for use with propane gas. The LP conversion kit is included with the unit.
  • The unit must be kept free and clear of insulating materials. Inspect surrounding area to ensure insulation material is in safe distance when installing furnaces or adding insulation materials. Insulation materials may be combustible. See Table 3-1 for required clearances to combustible construction.
  • Before heating season begins, exam the unit to determine that:
    • a. All flue gas carrying areas external to the unit (i.e. chimney, vent connector) are clear and free of obstructions.
    • b. The vent connector is in place, slopes upward and is physically sound without holes or excessive corrosion.
    • c. The return-air duct connection(s) is physically sound, is sealed to the furnace casing, and terminates outside the space containing the furnace.
    • d. The physical support of the unit is sound without sagging,cracks, gaps, etc around the base so as to provide a seal between the support and the base.
    • e. There are no obvious sign of deterioration of the unit.
    • f. The burner flames are in good adjustment (by comparison with pictorial sketches of the main burner flame.
  • Furnace operation needs air for combustion and ventilation. Do not block or obstruct air openings on furnace or spacing around furnace required for supplying sufficient combustion air and ventilation.

INSPECTION
As soon as unit is received, it should be inspected and noted for possible shipping damage during transportation. It is shipper’s responsibility to cover the cost of shipping damage. Manufacturer or distributor will not accept the claims from dealer for any transportation damage.
LIMITATIONS
Refer to Fig. 2-2, 2-3 for unit physical data and to Table 7-1 for electrical data. If components are to be added to a unit they must meet local codes, they are to be installed at the dealer’s and /or the customer’s expense. Size of unit for proposed installation should be based on heat loss / heat gain calculations made in accordance with industry recognized procedures identified by the Air conditioning contractors of America.
Note: Rating plate must be left visible for future reference.

BEFORE OPERATING

FOR YOUR SAFETY READ BEFORE OPERATING

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

  • A. This appliance does not have a pilot. it is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.

  • B. BEFORE OPERATING smell all around the appliancearea for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
    FOR YOUR SAFETY WHAT TO DO IF YOU SMELL GAS

    • Do not try to light any appliance.
    • Do not touch any electrical switch; do not use any phone in your building.
    • Immediately call your gas supplier from a neighbors’ phone. Follow the gas suppliers Instructions.
    • If you cannot reach your gas supplier, call the fire department.
  • C. Use only your hand to turn the gas control switch. Never use tools. If the switch will not turn by hand, don’t try to repair it; call a qualified service technician. Force or attempted repair may result in a fire or explosion.

  • D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

OPERATING INSTRUCTIONS

  1. STOP! Read the safety information above on this label.
  2. Set the thermostat to lowest setting.
  3. Turn off all electric power to the appliance.
  4. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
  5. Remove control access panel.
  6. Wait five (5) minutes to clear out any gas. if you then smell gas, STOP! Follow “B” in the safety information above on this label. If you don’t smell gas, go to the next step.
  7. Push gas control switch to “ON”.
    • NOTE: Do not force.
  8. Replace control access panel.
  9. Turn on all electric power to the appliance.
  10. Set thermostat to desired setting
  11. If the appliance will not operate, follow instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier.

TO TURN OFF GAS TO APPLIANCE

  1. Set the thermostat to lowest setting.
  2. Turn off all electric power to the appliance if service is to be performed.
  3. Remove control access panel.
  4. Push gas control to “OFF”. Do not force.
  5. Replace control access panel.

See Fig: Instruction of lighting/ shutdown operation. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting of the electrical supply.

INTRODUCTION

A Package Gas Electric Unit is a fully self-contained, combination gas heating/electric cooling unit designed for outdoor installation. All unit sizes have return and discharge openings for both horizontal and downflow configurations, and are factory shipped with all downflow duct openings covered. Units may be installed either on a rooftop or on a cement slab. In gas heating mode, this unit is designed for a minimum continuous return-air temperature and a maximum continuous return-air temperature. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and other components. This booklet contains the installation and operating instructions for your Package Gas Electric Unit. There are some precautions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or dangerous conditions. Read this booklet and any instructions packaged with separate equipment required to make up the system prior to installation. Give this booklet to the owner and explain its provisions. The owner should retain this booklet for future reference. A Package Gas Electric Unit includes a hermetically-sealed refrigerating system consisting of a compressor, condenser coil,  evaporator coil with thermal expansion valve (TXV) or throttle valve, acirculation air blower, a condenser fan, a heat exchanger assembly, gas burner and control assembly, combustion air motor and fan, and all necessary internal electrical wiring. The cooling system of these units is factory- evacuated, charged and performance tested. All units are factory charged with Refrigerant R410A. The figure shown in this manual is for reference only and may be slightly different from the actual product.

J4PG4024B1060AA,J4PG4030B1060AA,J4PG4036B1090AA,J4PG4042B1090AA

INSTALLATION

Install the unit in accordance with The American National Standard Z223.1-latest edition booklet entitled “National Fuel Gas Code”, and the requirements or codes of the local utility or other authority having jurisdiction. Unit should be installed in accordance with national and local safetycodes, including but not limit to ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1, local plumbing and wastewater codes and any other applicable codes. Additional helpful publications available from the “National Fire Protection Association” are: NFPA-90A – installation of Air Conditioning and Ventilating Systems 1985 or latest edition. NFPA-90B – Warm Air Heating and Air Conditioning Systems 1984.

PRE-INSTALLATION CHECK-POINTS

Before installation, carefully check the following:

  1. For rooftop installation, be sure the structure has enough strength to support the weight of unit.
  2. Clearances and provision for servicing.
  3. Power supply and wiring.
  4. Gas supply and piping.
  5. Air duct connections and sizing.
  6. Drain facilities and connections.
  7. Location for minimum noise and vibration.

LOCATION CONSIDERATIONS
The metal parts of the unit may be subject to rust or deterioration in adverse environmental conditions. This oxidation could shorten the equipment’s useful life. Salt spray, fog or mist in seacoast areas,  sulphur or chlorine from lawn watering systems, and various chemicalcontaminants from industries such as paper mills and petroleum refineries are especially corrosive. If the unit is to be installed in an area where contaminants are likely to be a problem, give special attention to the equipment
location and exposure:

  1. Avoid having lawn sprinkler heads spray directly on the unit cabinet.
  2. In coastal areas locate the unit on the side of the building away from the waterfront.
    • WARNING: Disconnect all power to the unit before starting maintenance. Failure to do so can cause electrical shock resulting in personal injury or death.
  3. Shielding by a fence or shrubs may give some protection.
  4. Elevate the unit off its slab or base enough to allow air circulation and avoid holding water against the base pan.
  5. Frequent washing of the cabinet, fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit.
  6. Regular cleaning and waxing of the cabinet with a good automobile polish will provide some protection.
  7. Use a good liquid cleaner several times a year to remove matter that will not wash off with water.

Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer. The best protection is frequent cleaning, maintenance and minimal exposure to contaminants.

OUTSIDE INSTALLATION

WARNING: This unit is designed certified for outdoor installation only. Installation inside any part of a structure can result in inadequate  unit performance as well as property damage. Installation insidecan also cause recirculation of flue products into the conditioned space resulting in personal injury or death.

Typical outdoor installation in shown in Figure 3-2:

  1. Select a location where external water drainage cannot collect around unit.
  2. Locate unit where operating sounds will not disturb owner or neighbors.
  3. The location of the unit should allow proper access for inspection and servicing.
  4. Locate unit so roof runoff water does not pour directly on the unit. Provide gutter or other shielding at roof level. Do not locate unit in an area where excessive snow drifting may occur or accumulate.
  5. Provide a concrete slab extending 3″ beyond all four sides of the unit. The slab should be sufficiently high enough above grade to prevent surface water from entering the unit. The slab should be isolated from the foundation wall.
  6. Pitch the slab approximately 1/2″ so that the unit will be pitched toward the drain. See Figure 3-3.
  7. It is essential that the unit be elevated above the base pad to allow for defrost water runoff, condensate drainage, and possible refreezing or condensate. Route condensation off the base pad to an area that will not become slippery and result in personal injury.
    • Important: Do not interfere with opening in bottom of unit.
  8. Where snowfall is anticipated, the height of the unit above the ground level must be considered. Mount unit high enough to be above average area snowfall to prevent snow from blocking the outdoor coil, to allow condensate runoff, and to allow combustion air to enter the combustion air inlet.

ATTACHING EXHAUST AND COMBUSTION AIR INLET HOODS

IMPOPTANT: Do not operate this unit without the exhaust and combustion air inlet hood property installed. These hoods are shipped in a carton in the return air compartment inside the unit and must be attached the unit is installed. See Fig. 2-1.
To attach exhaust and combustion air inlet hood:

  1. Remove 3 screws securing filter access panel and remove filter access panel. For location of filter access panel, see Fig.3-4.
  2. Remove both exhaust and combustion air inlet hoods from their carton, located inside the return air compartment.
  3. Attach filter access panel.
  4. Attach the combustion air inlet hood and the exhaust hood with 4 and 6 screws as shown in Fig. 2-1. Screws are in parts bag shipped in the burner compartment.
  5. Vent the unit using the flue exhaust hood, as supplied from the factory, without alteration addition. The only exception is with factory approved additions. Consult your local unity or other authority having jurisdiction for accepted venting techniques.

COVER PANEL INSTALLATION / CONVERSION PROCEDURE
All unit sizes have return and discharge openings for both horizontal and downflow configurations, and are factory shipped with all downflow duct openings covered, HORIZONTAL is factory shipped.

HORIZONTAL TO DOWNFLOW

  1. Remove screws and covers from the supply and return bottom section.
  2. Install gasket (supplied with parts bag) around perimeter of cover on the insulate side.
  3. Secure covers to the side of the unit using existing screws and those supplied in the parts bag. See Fig. 3-4.
  4. Seal duct covers with silicone caulk.

DOWNFLOW TO HORIZONTAL

  1. Remove screws and covers from the supply and return bottom section.
  2. Install gasket (factory shipped) around perimeter of cover on the insulate side.
  3. Secure covers to the bottom of the unit using existing screws and those supplied in the parts bag. See Fig. 3-5.

WARNING
This unit must not be installed directly on wood flooring, Class A, Class B or Class C roof covering materials, or any other combustion structure except as specified in Fig.3-1. Failure to adhere to this warning can cause a fire or explosion resulting in property damage, personal injury or death.

CLEARANCE
All units require certain clearance for proper operation and service. Refer to Table 3-1 for the minimum clearances required for construction, servicing and proper unit operation.

Table 3-1: Unit Clearance

Duct clearance: 1 inch clearance for all sides of air supply duct.

  1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
  2. The minimum clearance without economizer/fresh air damper. For distance with Economizer/fresh air damper, please refer to the relevant Install requirement.
  3. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
  4. If Economizer/fresh air damper is used, a 24″ minimum clearance is required on left side of unit.

NOTE
For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch between combustible roof curb material and this supply air duct.

RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails. Spreader bars, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit.

CAUTION
Before lifting, make sure the unit weight is distributed equally on the rigging cables so it will lift evenly. Units may be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose.

CAUTION
All panels must be secured in place when the unit is lifted. The condenser coils should be protected from rigging cable damage with plywood or other suitable material. ****

NOTE
A unit with electric heaters with an inlet or outlet duct that penetrates the building structure supporting the unit shall be provided with a mounting base of noncombustible material so designed that, after the unit is installed, there will be no open passages through the supporting structure that would permit flame or hot gases from a fire originating in the space below the supporting structure to travel to the space above that structure. If the unit is intended to be installed on a supporting structure of combustible material, the base shall be so designed that the required clearance will be maintained between the supporting structure and the unit, plenum, and attached duct. Spacers necessary to provide required clearances shall be attached to the unit mounting base, and shall extend not less than 76 mm (3 in.) below the upper surface of the supporting structure, except that, in a unit designed for use only in a mobile home, the distance shall be not less than 19 mm (3/4 in.).

Roof Curb
In applications using roof curbs,the unit must be placed on the curb so that the front of the unit is tightly close to curb. (See Fig.2-10 ROOF CURB DIMENSION) For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch between combustible roof curb material and this supply air duct.

CURB Dimensions(Inches)
“B” in.[mm] “C” in.[mm]
LARGE 14-1/4 [362]
SMALL 14-1/4 [362]

DUCTWORK
Ductwork should be made and sized by installer and in accordance with Air Manual from Conditioning Contractors of America and local codes.
NOTE
On ductwork exposed to outside air conditioning space, use at least 2” of insulation and a vapor barrier. Flexible joint may be used to reduce noise. These units are adaptable to horizontal use as well as rear supply and return air duct openings. To convert to downflow, use the steps is shown in 3.5. A closed return duct system shall be used. This shall not preclude use of economizers or ventilation air intake. Flexible joints may be used in the supply and return duct work to minimize the transmission of noise.

CAUTION
When fastening duct work to the side duct flanges on the unit, insert the screws through the duct flanges only. DO NOT insert the screws through the casing. Outdoor duct work must be insulation and waterproofed.
NOTE
Be sure to note supply and return openings. Refer to Fig. 3 and 4 for information concerning rear and bottom supply and return air duct openings.

RETURN AIR

WARNING: Never allow products of combustion to the flue products to enter the return air ductwork, or the circulating air supply. All return ductwork must be adequately sealed and secured to the furnace with sheet metal screws, and joints taped. All other duct joints must be secured with approved connections and sealed airtight. Failure to prevent products of combustion from beingcirculated into the living space can create potentially hazardous conditions, including carbon monoxide poisoning that could result in personal injury or death.

FILTERS
The installer must install field supplied filters in the return air duct. A field installed filter grille is recommended for easy and convenient access to the filters for periodic inspection and cleaning. Filters must have adequate face area for the rated air quantity of the unit. See air delivery tables for recommended filter size.

GAS SUPPLY, CONDENSATE DRAIN AND PIPING

GAS CONNECTION

IMPORTANT: Connect this unit only to gas supplied by a commercial utility.

  1. Install gas piping in accordance with local codes and regulations of the local utility company. In the absence of local codes, theinstallation must conform to the specifications of the National Fuel Gas Code, ANSI Z223.1 – latest edition.
    • NOTE: The use of flexible gas connectors is not permitted. If localcodes allow the use of a corrugated stainless steel flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously serviced another gas appliance.
    • NOTE: The Commonwealth of Massachusetts requires the gas shut-off valve to be a T-handle gas cock.
  2. Connect the gas line to the gas pipe inlet opening provided into the 1/2″ inlet valve. See Fig. 4-1 for typical piping.
  3. Size the gas line to the furnace adequate enough to prevent undue pressure drop and never less than 1/2″ nominal pipe size.
  4. Install a drip leg or sediment trap in the gas supply line as close to the unit as possible.
  5. Install an outside ground joint union to connect the gas supply to the control assembly at the burner tray, Unions may not be installed inside the unit.
  6. Gas valves have been factory installed. Install a manual gas valve where local codes specify a shut-off valve outside the unit casting.
  7. Make sure piping is tight. A pipe compound resistant to the action of liquefied petroleum gases must be used at all threaded pipe connections.
    • IMPORTANT: Any additions, changes or conversions required for the furnace to satisfactorily meet the application should be made by a qualified installer, service agency or the gas supplier, using factory-specified or approved parts. In the commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter for appropriate fuel.
    • IMPORTANT: Disconnect the furnace and its individual shutoff valve the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig or isolate the system from the gas supply piping system by closing its individual manual shutoff valve during any pressures equal to or less than 1/2 psig.

WARNING
FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death of property damage.Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life. TO CHECK FOR GAS LEAKS, USE A SOAP AND WATER SOLUTION OR OTHER APPROVED METHOD. DO NOT USE AN OPEN FLAME. IMPORTANT: Check the rating plate to make certain the appliance is equipped to burn the type of gas supplied. Care should be taken after installation of this equipment that the gas control valve not be subjected to high gas supply the pressure. In making gas connections, avoid strains as they may cause noise and damage the controls. A backup wrench is required to be used on the valve to avoid damage. The capacity of gas pipe of different diameters and lengths in CFH with pressure drop of 0.5 in. and specific gravity of 0.60 (natural gas) are shown in Table 4-1.

Table 4-1: Natural gas pipe capacity table (CFH – Cubic Feet of Gas Per Hour)

Nominal iron pipe size (in.) Equivalent length of pipe (ft.)
10 20
1/2 132
3/4 278
1 520
1-1/4 1050
1-1/2 1600

After determining the pipe length, select the pipe size which will provide the minimum cubic feet per hour required for the gas input rating of the furnace. By formula:

The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/Cubic FT) may be determined by consulting the local natural gas utility or the L.P. gas supplier.

LP CONVERSION

WARNING: This unit is equipped at the factory for use on Natural Gas only. Conversion to LP Gas requires a special kit which is included with the unit. DO NOT BURN ANY LIQUID FUEL OR SOLID FUEL IN THIS UNIT. Burning any unapproved fuel will result in damage to this unit heat exchanger, which could result in fire, Carbon Monoxide poisoning, explosion, personal injury, property damage or death. Convert the valve to use liquefied petroleum (LP) gas by replacing the pressure regulator spring with the conversion kit spring. This LP kit spring allows the regulator to maintain the proper manifold pressure for LP gas. The correct burner LP orifices are included in the kit.
NOTE: The LP conversion kit is included with the unit. See Conversion Kit Index shipped with unit for proper LP kit number.Furnace conversion to LP gas must be performed by a qualified technician.

Table 4-2: LP gas pipe capacity table (CFH – Cubic Feet of Gas Per Hour)

Nominal iron pipe size (in.) Equivalent length of pipe (ft.)
10 20
1/2 275
3/4 567
1 1071
1-1/4 2205
1-1/2 3307
2 6221

Example (LP): Input BTU requirement of unit, 150000 Equivalent length of pipe, 60 ft. =3/4″ IPS r

ADJUSTING OR CHECKING FURNACE INPUT

Manifold Gas Pressure

MODLE| Range| Orifice
Nature Gas| Propane Gas| Nature Gas| Propane Gas
J4PG4024B1060AA| 3.3″W.C| 9.6″W.C| 51| 59
J4PG4030B1060AA| 3.3″W.C| 9.6″W.C| 51| 59
J4PG4036B1090AA| 3.8″W.C| 10.5″W.C| 51| 59
J4PG4042B1090AA| 3.8″W.C| 10.5″W.C| 51| 59
J4PG4048B1090AA| 3.8″W.C| 10.0″W.C| 49| 56
J4PG4060B1090AA| 3.8″W.C| 10.0″W.C| 49| 56
J4PG4060B1110AA| 3.6″W.C| 10.4″W.C| 49| 56

Supply and manifold pressure taps are located on the gas valve body 1/8″ N.P.T. Use a properly calibrated manometer gauge for accurate gas pressure readings. Only small variations in the gas flow should be made by means of the ressure regulator adjustment. Furnaces functioning on LP gas must be set by means of the tank or branch supply regulators. The furnace utlet pressure should be set at 10″ W.C. at the gas control valve. To adjust the pressure regulator, remove the regulator cap and turn   he adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure. Then replace the regulator cap securely. Any necessary major changes in the gas flow rate should be made by changing the size of the burner orifices. To change orifice spuds, shut off the manual main gas valve and remove the gas manifold. For elevations up to 2000 feet, rating plate input rating apply. For high altitudes (elevations over 2000 feet), see conversion kit index for derating and orifice spud sizes. Check of input is important to prevent over-firing of the furnace beyond its designated input, NEVER SET INPUT ABOVE THAT SHOWN ON THE RATING PLATE. Use the following formula to determine input rate.

Start the furnace and measure the time required to burn on cubic foot of gas. Prior to checking the furnace input, make certain that all other gas appliances are shut off, with the exception of pilot burners. Time the meter with only the furnace in operation.
IMPORTANT NOTE FOR ALL ALTITUDES ABOVE 2000 FEET: The main burner orifices in your furnace and in these kits are sized for the nameplate input and intended for installations at elevations up to 2000 feet in the USA or Canada, or for elevations of 2000-4500 feet in Canada if the unit has been derated at the factory. For elevations above 2000 feet IN THE USA ONLY (see ANSI-Z223.1), the burner orifices must be sized to reduce the input 4% for each 1000 feet above sea level.
NOTICE: Derating of the heating input for high altitude in the field is unlawful in Canada (refer to CAN/CGA 2.17). Units installed in altitudes greater than 2000 feet must be shipped from the factory or from a factory authorized conversion station with the heating input derated by 10% so as to operate properly in altitudes from 2000-4500 feet.

CONDENSATE DRAIN

  1. Use the provided female NPT threaded fitting for outside connection and make sure that drain holes are not blocked.
  2. Insulation may be needed for drain line to prevent sweating.
  3. Use a sealing compound on male pipe threads. Install the condensate drain line (NPT) to spill into an open drain.
  4. Ensure a trap is included in the condensate drain line.
  5. Make sure that the outlet of the trap is at least 1 in. (25mm) lower than the drain pan condensate connection to prevent the pan from overflowing.

WIRING

POWER SUPPLY

WARNING: Turn off the main electrical power at the branch circuit disconnect closest to the unit before attempting any wiring. Failure to do so can cause electrical shock resulting in personal injury or death.

  1. All wiring should be made in accordance with the National Electrical Code. Consult the local power company to determine the availability of sufficient power to operate the unit. Check the voltage at power supply to make sure it corresponds to the unit’s rated voltage requirement. Install a branch circuit disconnect near the rooftop, in accordance with the N.E.C., C.E.C. or local codes.
  2. It is important that proper electrical power is available at the unit. Voltage should not vary more than 10% from that stamped on the unit nameplate. On three phase units, phases must be balanced within 3%.
  3. For branch circuit wiring (main power supply to unit disconnect), the minimum wire size for the length of run can be determined from Table 5-1 using the circuit ampacity found on the unit rating plate. Use the smallest wire size allowable in Table 5-1 from the disconnect to unit. The disconnect must be in sight and readily accessible of the unit.

Table 5-1: Branch circuit copper wire size (in.)

| Branch circuit ampacity
---|---
15| 20| 25| 30| 35| 40| 45| 50
__

__

Supply wire length (Ft.)

| 200| 6| 4| 4| 4| 3| 3| 2| 2
150| 8| 6| 6| 4| 4| 4| 3| 3
100| 10| 8| 8| 6| 6| 6| 4| 4
50| 14| 12| 10| 10| 8| 8| 6| 6

NOTES:

  1. Wire size based on 60°C rated wire insulation and 30°C Ambient Temp.
  2. For more than 3 conductors in a raceway or cable, see the N.E.C. for derating the ampacity of each conductor. When installed, the unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, if an external electrical source is utilized.

IMPORTANT: This unit is approved for use with copper conductors only connected to unit contactor. Warranty may be jeopardized if aluminum wire is connected to unit contactor.Special instructions apply for power wiring aluminum conductors: Warranty is void if connections are not made per instructions. Attach a length (6″ or more) of recommended size copper wire to the unit contactor terminals L1 and L3 for single phase. Select the equivalent aluminum wire size from the tabulation below: Splice copper wire pigtails to aluminum wire with U.L. recognized connectors for copper-aluminum splices. Please exercise the follow ing instructions very carefully to obtain a positive and lasting connection:

  1. Strip insulation from aluminum conductor.
  2. Coat the stripped end of the aluminum wire with the recommended inhibitor, and wire brush the aluminum surface through inhibitor.
    • INHIBITORS: Brundy-Pentex ”A”; Alcoa-No. 2EJC; T & B-KPOR Shield.
  3. Clean and recoat aluminum conductor with inhibitor.
  4. Make the splice using the below listed wire nuts or split bolt connectors.
  5. Coat the entire connection with inhibitor and wrap with electrical insulating tape.

AWG Copper Wire Size| AWG Aluminum Wire Size| Connector Type and Size (or equivalent)
---|---|---

12| #10| T & B Wire Nut        PT2

10| #8| T & B Wire Nut        PT3

8| #6| Sherman Split Bolt TSP6

6| #4| Sherman Split Bolt TSP4

4| #2| Sherman Split Bolt TSP2

HOOK-UP
To wire unit, refer to the following Fig. 5-1. Wiring to be done in the field between the unit and devices not attached to the unit, or between separate devices which are field installed and located, shall conform with the temperature limitation for Type T wire [63°F rise] when installed in accordance with the manufacturer’s instructions.

INTERNAL WIRING

IMPORTANT: Some single phase units are equipped with a single pole contactor. Caution must be exercised when servicing as only one leg of the power supply is broken with the contactor. Some models are equipped with an electronically commutated blower motor which is constantly energized unless the main unit disconnect is in the off position. A diagram of the internal wiring of this unit is located under the electrical box cover and in this manual. If any of the original wire as supplied with the appliance must be replaced, the wire gauge and insulation must be the same as the original wiring. Transformer is factory wired for 230 volt on 208/230 volt models and must be changed to 208 volt applications. See unit wiring diagram for 208 volt wiring.

THERMOSTAT
The room thermostat must be specifically designed to control package gas electric units.

FURNACE SECTION CONTROLS AND IGNITION SYSTEM

NORMAL FURNACE OPERATING SEQUENCE

This unit is equipped with an integrated direct spark ignition control.

  1. The thermostat calls for gas heat.
  2. The control board will run a self check to verify that the limit control and manual reset overtemperature control are closed and that the pressure switch is open. If so, the induced draft blower (inducer) begin a prepurge cycle.
  3. The air proving negative pressure switch closes.
  4. 15 seconds after the pressure switch closes, the gas valve opens and the spark is initiated for a 7 second trial for ignition.
  5. Burners ignite and flame sensor proves all burners have lit.
  6. The circulating air blower is energized after 45 seconds.
  7. The control board enters a normal operation loop in which all safety controls are monitored continuously.
  8. Thermostat is satisfied and opens.
  9. The gas valve is de-energized and closes, shutting down the burner flame.
  10. The control board will de-energized the inducer after a five second post purge.
  11. The circulating air blower BLOWER-LOW is de-energized after max. 90 seconds.
    • The integrated control board has a three times ignition system.
    • After a total of 3 trials for ignition without sensing main burner flame, the system goes into lockout mode.
    • After 1 hour, the ignition control repeats the prepurge and ignition cycles for 3 tries and then goes into lockout mode again.
    • It continues this sequence of cycles and lockout each hour until ignition is successful or power is interupted.
    • During the lockout mode, neither the spark ignition control or gas valve will be energized until the system is reset by turning the thermostat to the “OFF” position or interrupting the electrical power to the unit for 3 seconds or longer.
    • The induced draft blower and main burner will shut off when the thermostat is satisfied.
    • The circulating air blower will start and run on the heating speed if the thermostat fan switch is in the ”ON” position. The integrated furnace control is equipped with diagnostic LED. The LED is lit continuously when there is power to the control without a call for heat. If the LED is not lit, there is either no power to the control or there is an internal component failure within the control, and the control should be replaced. If the control detects the following failures, the LED will flash for designated failure detections.
    • 2 Flash: Failed to detect or sustain flame,system locked out.
    • 3 Flash: Pressure switch or induced draft blower problem detected.
    • 4 Flash: High limit or auxiliary limit open.
    • 5 Flash: Flame sensed and gas valve not energized or flame sensed with no “W” signal.
    • 6 Flash: Overtemperature switch open.
    • 7 Flash: Thermostat miswired; W1 and W2 swapped. Slow flash rate:Normal,call for heat.

OPERATING INSTRUCTIONS
This appliance is equipped with a direct spark intermittent ignition device. This device lights the main burners each time the room thermostat (closes) calls for gas heat. See operating instructions on the back of the furnace/controls access panel

WARNING
Do not attempt to manually light this furnace with a match or any open flame. Attempting to do so can cause an explosion or fire resulting in property damage, personal injury or death.

TO START THE FURNACE

  1. Set the thermostat to its lowest setting.
  2. Turn off all electric power to the appliance.
  3. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
  4. Remove control door.
  5. Turn the gas valve to the “OFF” position.
  6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow B in the safety information on the Operating Instructions located on the back of the controls/access panel. If you don’t smell gas, go to the next step.
  7. Turn the gas valve to the “ON” position.
  8. Replace the control door.
  9. Turn on all electric power to the appliance.
  10. Set the thermostat to the desired setting.
  11. If the appliance will not operate, follow the instructions below to shut down the furnace.

WARNING
The spark ignitor and ignition lead from the ignition control are high voltage. Keep hands or tools away to prevent electrical shock. Shut off electrical power before servicing any of the controls. Failure to adhere to this warning can result in personal injury or death. The initial start-up on a new installation may require the control system to be energized in some time until any air has bled through the system and fuel gas is available at the burners.

TO SHUT DOWN FURNACE

  1. Set the thermostat to the lowest setting.
  2. Turn off all electric power to the appliance if service is to be performed.
  3. Remove control door.
  4. Move gas valve to the“OFF”position.
  5. Replace control door.

WARNING
Should overheating occur or the gas supply fail to shut off. Shut off the Manual Gas valve to the appliance before shutting off the electrical supply. Failure to do so can result in an explosion or fire causing property damage, severe personal injury or death.

BURNERS
Burners for these units have been designed so that field adjustment is not required. Burners are tray-mounted and accessible for easy cleaning when required.
MANUAL RESET OVERTEMPERATURE CONTROL
A manual reset overtemperature control is located on the burner shield. This device senses blockage in the heat exchanger or insufficient combustion air. This shuts off the main burners if excessive temperatures occur in the burner compartment. Operation of this control indicates an abnormal condition. Therefore,  the unit should be examined by a qualified installer, service agency, orthe gas supplier before being placed back into operation.
WARNING
DO NOT JUMPER THIS DEVICE! Do not reset the overtemperature control without taking corrective action to assure that an adequate supply of combustion air is maintained under all conditions of operation. Failure to do so can result in Carbon Monoxide poisoning or death. Replace this control only with the identical replacement part.

PRESSURE SWITCH
This furnace has a negative pressure switch for sensing a blocked exhaust or a failed induced draft blower. It is normally closed when the induced draft blower starts, indicating air flow through the combustion chamber.
LIMIT CONTROL
The supply air high temperature limit cut-off is set at the factory and cannot be adjusted. It is calibrated to prevent the air temperature leaving the furnace from exceeding the maximum outlet air temperature. WARNING: DO NOT JUMPER THIS DEVICE! Replace this control only with the identical replacement part.

SYSTEM OPERATING INFORMATION

ADVISE THE CUSTOMER

  1. Keep the air filters clean. The heating system operates better, more efficiently and more economically.
  2. Arrange the furniture and drapes so that the supply air registers and the return air grilles are unobstructed.
  3. Close doors and windows. This reduces the heating load on the system.
  4. Avoid excessive use of exhaust fans.
  5. Do not permit the heat generated by television, lamps or radios to influence the thermostat operation.
  6. Except for the mounting platform, keep all combustible articles three feet from the unit and exhaust system.
  7. IMPORTANT: Replace all blower doors and compartment after servicing the unit. Do not operate the unit without all panels and doors securely in place.
  8. Do not allow snow or other debris to accumulate in the vicinity of the appliance.

FURNACE SECTION MAINTENANCE
The unit’s furnace should operate for many years without excessive scale build-up in flue passageways; and it should have a qualified installer, service agency, or gas supplier annually inspect the flue passageways, the exhaust system and the burners for continued safe operation, paying particular attention to deterioration from corrosion or other sources. If during inspection the flue passageways and exhaust system are determined to require cleaning, the following procedures should be followed (by a qualified installer, service agency, or gas supplier):

  1. Turn off the electrical power to the unit and set the thermostat to the lowest temperature.
  2. Shut off the gas supply to the unit either at the meter or at manual valve in the supply piping.
    • WARNING: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation resulting in fire ,electrical shock, property damage, personal injury or death.
  3. Remove the furnace controls access panel and the control box cover.
  4. Disconnect the gas supply piping from the gas valve.
  5. Disconnect the wiring to the induced draft blower motor, gas valve, flame sensor, and flame roll-out control, and igniter cable. Mark all wires disconnected for proper reconnection.
  6. Remove the screws (4) connecting the burner tray to the heat exchanger mounting panel.
  7. Remove the burner tray and the manifold assembly from the unit.
  8. Remove the screws (4) connecting the induced draft blower to the collector box and screws (16) connecting the collector box to the heat exchanger mounting panel. Remove the induced draft blower and the collector box from the unit.
  9. Remove the turbulators from inside the heat exchangers by inserting the blade of a screwdriver under the locking tabs. Pop the tabs out of the expanded grooves of the heat exchanger. Slide the turbulators out of the heat exchangers.
  10. Direct a water hose into the outlet of the heat exchanger top. Flush the inside of each heat exchanger tube with water. Blow out each tube with air to remove excessive moisture.
  11. Reassemble (steps 1 through 10 in reverse order). Be careful not to strip out the screw holes used to mount the collector box and inducer blower. Replace inducer blower gasket and collector box gasket with factory replacements if damaged.
    • WARNING: Holes in the exhaust transition or heat exchanger can cause toxic fumes to enter the home. The exhaust transition or heat exchanger must be replaced if they have holes or cracks in them. Failure to do so can cause Carbon Monoxide poisoning resulting in personal injury or death. The manufacturer recommends that a qualified installer, service agency or the gas suppler visually inspect the burner flames for the desired flame appearance at the beginning of the heating season and approximately midway in heating season. The manufacturer also recommends that a qualified installer, service agency or the gas supplier clean the flame sensor with steel wool at the beginning of the heating season.

WARNING
Disconnect main electrical power to the unit before attempting maintenance. Failure to do so may result in electrical shock or severe personal injury or death.

LUBRICATION
IMPORTANT: DO NOT attempt to lubricate the bearings on the blower motor or the induced draft blower motor. Addition of lubricants can reduce the motor life and void the warranty. The blower motor and induced draft blower motor are prelubricated by the manufacturer and do not require further attention. A qualified installer, service agency or the gas supplier must periodically clean the motors to prevent the possibility of overheating due to an accumulation of dust and dirt on the windings or on the motor exterior. And, as suggested elsewhere in these instruct ions, the air filters should be kept clean because dirty filters can restrict air flow and the motor depends upon sufficient air flowing across and through it to prevent overheating.

COOLING SECTION MAINTENANCE
It is recommended that at the beginning of each cooling season a qualified installer or service agency inspect and clean the cooling section of this unit. The following areas should be addressed: evaporator coil, condenser coil, condenser fan motor and venturi area.

To inspect the evaporator coil:

  1. Remove the filter access panel and the blower/evaporator coil access panel.
    • WARNING: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation resulting in fire ,electrical shock, property damage, personal injury or death.
  2. Unplug the wires from the circulating air blower and the limit control. Remove the two screws and slide the blower out of the unit sideways.
  3. Shine a flashlight on the evaporator coil (both sides) and inspect for accumulation of lint, insulation, etc.
  4. If coil requires cleaning, follow the steps shown below.

Cleaning Condenser Coil

  1. Remove screws from condenser fan grille assembly and lay grille over on the unit top panel.
  2. Remove the controls access panel and the control box cover.
  3. Disconnect the outdoor fan motor wiring from the compressor contactor and capacitor. Remove the strain relief in the bulkhead and pull the fan motor wires through. Set grille assembly to the side.
  4. Remove the screws that secure the unit top to the unit. Remove the top and set the unit top to the side.
  5. The coil should be cleaned when it is dry. If the coil is coated with dirt or lint, vacuum it with a soft brush attachment. Be careful not to bend the coil fins.
  6. If the coil is coated with oil or grease, clean it with a mild detergent-and-water solution. Rinse the coil thoroughly with water.
    • IMPORTANT: Do not use excessive water pressure. Excessive water pressure can bend the fins and tubing of the coil and lead to inadequate unit performance. Be careful not to splash water excessively into unit.
  7. Go to next section for cleaning the evaporator coil.

Cleaning Evaporator Coil, Drain Pan, Condensate Drain, Condenser Fan, Circulation
Air Blower and Venturi

  1. Remove the screws from the filter access panel and the blower/evaporator coil access panel from the unit. Remove the filter access panel and the blower/evaporator coil access panel.
  2. The coil should be cleaned when it is dry. If the coil is coated with dirt or lint, vacuum it with a soft brush attachment. Be careful not to bend the Coil fins.
  3. If the coil is coated with oil or grease, clean it with a mild detergent-and-water solution. Rinse the coil thoroughly with water.
    • IMPORTANT: Do not use excessive water pressure. Excessive water pressure can bend the tins and tubing of the coil and lead to inadequate unit performance. Be careful not to splash water excessively into unit.
  4. Inspect the drain pan and condensate drain at the same time the evaporator coil is checked. Clean the drain pan by flushing with water and removing any matters of obstructions which may be present.
  5. Flush the drain tube with water. If the drain tube is blocked, it can usually be cleared with high pressure water.
  6. The venturi should also be inspected for items of obstruction such as collections of grass, dirt or spider webs. Remove any that are present.
  7. Inspect the circulating air blower wheel and motor for accumulation  of lint, dirt or other obstruction and clean if necessary. Inspect the blower motor mounts and the blower housing for loose mounts or other damage. Repair or replace it necessary.

Re-assembly

  1. Place the condenser coil protective grille back on unit and replace all screws.
  2. Place top panel back on unit and replace all screws.
  3. Set condenser fan grille assembly on top of the unit with the fan on top and the motor wires on the venturi side. Run the fan motor wires through the bulkhead and pull wires through the hole on the bottom of the control box on the left side and into the control box. Reconnect fan motor wires per the wiring diagram attached to the back of the control box cover.
  4. Replace wire strain relief in bulkhead after the slack is pulled out of the wires on the fan side. This will assure wires will not be damaged by the fan during unit operation.
  5. Turn the condenser fan grille assembly over and into the recess in the unit top. Secure the grille to the unit with the four long #8 screws removed earlier.
  6. Replace the circulating air blower, making sure that all wires are properly reconnected per the unit wiring diagram.
  7. Replace the filter and blower/evaporator coil access panels.
  8. Replace the control box cover and controls access panel.
  9. Restore electrical power to the unit and check for proper operation, especially the condenser fan motor.

REPLACEMENT PARTS
Contact your local distributor for a complete parts list.
TROUBLE SHOOTING
Refer to Troubleshooting Chart included in this manual.
WIRING DIAGRAMS
Refer to the appropriate wiring diagram included in this manual.
CHARGING
Refer to the appropriate charge chart included in this manual.
BLOWER MOTOR SPEED TAPS
After determining necessary CFM and speed tap data, follow the steps below to change speeds.

  1. Remove control door.
  2. Please refer to the Table 10-1 & Table 10-2 and wiring diagram for the proper location of the wire on the speed tap block of the indoor blower motor to obtain the speed you have chosen.
  3. After adjusting the wires accordingly,replace control door.

OPERATION
Most single phase units are equipped with Permanent Split Capacitor (PSC) motors (no start relay or start capacitor). It is important that such systems be off for a minimum of 5 minutes before restarting to allow equalization of pressures. Do not move the thermostat to cycle  unit without waiting five minutes. To do so may cause the compressorto stop on an automatic open overload device or blow a fuse. Poor electrical service can cause nuisance tripping in overloads or blow fuses.
IMPORTANT: The compressor has an internal overload protector.
Under some conditions, it can take up to 2 hours for this overload toreset. Make sure overload has had time to reset before condensing the compressor. The control allows the blower to operate for up to 90 seconds after the thermostat is satisfied.

CONTROL SYSTEM OPERATION

  1. Heating mode
    The wall thermostat “calls for heat,” closing the R–to–W circuit. The furnace control performs a “NORMAL FURNACE OPERATING SEQUENCE”.

  2. Cooling mode
    In the cooling mode, The thermostat closes the R–to–G–and–Y circuits. The thermostat will energize the compressor contactor and the indoor blower relay. the blower motor will operate on BLOWER-SINGLE/HI speed , After the thermostat is satisfied, the compressor is de-energized and the cool mode delay-to-fan- offperiod begins. After the delay-to-fan- off period ends, the circulator fan is de-energized. The indoor blower can be operated continuously by setting the thermostat fan switch at the “ON” position.

  3. Fan mode
    When the circuit R–to–G is closed by the thermostat, the blowermotor will operate on BLOWER-LOW speed , If the thermostat fan switch is moved to the ON position, the circulator fan will be energized. When the fan switch is returned to the AUTO position, the circulator fan will be de-energized.

FAN DELAY ADJUSTMENT
As shipped, the circulator blower fan will remain on for 90 seconds after the gas valve closes. When a call for cooling occurs,the circulator fan comes on and remains on for 80 seconds after the call for cooling ends. During normal heating operation, the circulator fan will come on approximately 45 seconds after the gas valve opens.

PHYSICAL DATA

Table 9-1: 14 SEER Physical Data

Component Models
J4PG4024B1060AA J4PG4030B1060AA
Nominal Tonnage 2.0
ARI COOLING PERFORMANCE
ARI net capacity (Btu) 22800
EER 11.5
SEER 14
Nominal CFM 750
System power (kW) 1.98
Refrigerant type R410a
Refrigerant charge (lb-oz) 4-14
GAS HEATING PERFORMANCE
Heating input (Btu) 60000
Heating output (Btu) 48000
Temperature rise range (0F) 45-75
AFUE (%) 81%
Steady state efficiency (%) 81%
No. burners 5
No. stages 1
Gas connection pipe size (in.) 1/2″ NPT
DIMENSIONS (Inches)
Length 50-11/16
Width 35-1/16
Height 46-13/16
OPERATING WT. (lbs) 434
COMPRESSORS
Type Rotate
Quantity 1
CONDENSER COIL DATA
Face area (Sq. Ft) 14.11
Rows 1+2
Fins per inch 17
Tube diameter 9/32
Circuitry type interlaced
EVAPORATOR COIL DATA
Face area (Sq. Ft) 3.96
Rows 2
Fins per inch 17
Tube diameter 9/32
Circuitry type interlaced
Refrigerant control Orifice
CONDENSER FAN DATA
Fan diameter (inch) 23-5/8
Type Prop
Drive type Direct
No. speeds 1
Number of motors 1
Motor HP each 1/6(110W)
RPM 840
Nominal total CFM 2970
DIRECT DRIVE EVAP FAN DATA
Quantity 1
Fan Size (Inch) 10×10
Type Centrifugal
No. speeds 1
Motor HP each 1/5(150W)
Component Models
--- ---
J4PG4048B1090AA J4PG4060B1090AA
Nominal Tonnage 4.0
ARI COOLING PERFORMANCE
ARI net capacity (Btu) 48000
EER 11.5
SEER 14
Nominal CFM 1550
System power (kW) 4.17
Refrigerant type R410a
Refrigerant charge (lb-oz) 7-15
GAS HEATING PERFORMANCE
Heating input (Btu) 90000
Heating output (Btu) 72000
Temperature rise range (0F) 25-55
AFUE (%) 81%
Steady state efficiency (%) 81%
No. burners 6
No. stages 1
Gas connection pipe size (in.) 1/2″ NPT
DIMENSIONS (Inches)
Length 51-9/16
Width 44-13/16
Height 51-7/16
OPERATING WT. (lbs) 592
COMPRESSORS
Type Scroll
Quantity 1
CONDENSER COIL DATA
Face area (Sq. Ft) 20.17
Rows 1+2
Fins per inch 17
Tube diameter 9/32
Circuitry type interlaced
EVAPORATOR COIL DATA
Face area (Sq. Ft) 6.1
Rows 4
Fins per inch 17
Tube diameter 9/32
Circuitry type interlaced
Refrigerant control Orifice
CONDENSER FAN DATA
Fan diameter (inch) 26-3/8
Type Prop
Drive type Direct
No. speeds 1
Number of motors 1
Motor HP each 1/3(290W)
RPM 1070
Nominal total CFM 5170
DIRECT DRIVE EVAP FAN DATA
Quantity 1
Fan Size (Inch) 11×10-5/8
Type Centrifugal
No. speeds 1
Motor HP each 3/4(560W)

AIRFLOW PERFORMANCE
Airflow performance data is based on cooling performance with a coil and no filter in place. Use this performance table for appropriate unit size, external static applied to unit and allow operation within the minimum and maximum limits shown in table below for both cooling and electric heat operation.
Table 10-1 Indoor Airflow Performance – 230 Volts

Model Number Motor Speed External Static Pressure-Inches W.C.[kPa]
0[0] 0.1[.02] 0.2[.05]

0.8[.20]
__

__

__

__

__

24

| __

Low

| CFM| 900| 840| 760| 680| 600| /| /| /| /
Current/A| 1.0| 1.0| 1.0| 1.0| 1.0| /| /| /| /
Power/W| 234| 230| 227| 223| 220| /| /| /| /
__

Middle

| CFM| /| /| /| 890| 798| 708| 618| /| /
Current/A| /| /| /| 1.4| 1.4| 1.35| 1.3| /| /
Power/W| /| /| /| 318| 312| 306| 300| /| /
__

High

| CFM| /| /| /| /| 920| 830| 745| 670| 600
Current/A| /| /| /| /| 1.8| 1.8| 1.7| 1.7| 1.7
Power/W| /| /| /| /| 396| 389| 383| 375| 370
__

__

__

__

__

30

| __

Low

| CFM| 1110| 1044| 977| 916| 813| /| /| /| /
Current/A| 1.5| 1.4| 1.4| 1.4| 1.3| /| /| /| /
Power/W| 336| 328| 321| 309| 289| /| /| /| /
__

Middle

| CFM| /| 1179| 1106| 1039| 966| 851| 758| /| /
Current/A| /| 1.5| 1.5| 1.4| 1.4| 1.3| 1.3| /| /
Power/W| /| 345| 337| 328| 319| 298| 289| /| /
__

High

| CFM| /| /| /| /| 1111| 1031| 864| 786| 750
Current/A| /| /| /| /| 1.8| 1.8| 1.7| 1.7| 1.62
Power/W| /| /| /| /| 401| 390| 364| 356| 347
__

__

__

__

__

__

__

__

__

36

| Low (Tap1)| CFM| 1050| 903| /| /| /| /| /| /| /
Current/A| 1.2| 1.2| /| /| /| /| /| /| /
Power/W| 129| 135| /| /| /| /| /| /| /
Middle-1 (Tap2)| CFM| 1200| 1059| 988| 927| /| /| /| /| /
Current/A| 1.6| 1.6| 1.7| 1.7| /| /| /| /| /
Power/W| 200| 206| 212| 220| /| /| /| /| /
Middle-2 (Tap3)| CFM| 1294| 1233| 1177| 1109| 1035| 967| 919| /| /
Current/A| 2.3| 2.4| 2.4| 2.4| 2.5| 2.6| 2.6| /| /
Power/W| 262| 268| 274| 281| 292| 299| 305| /| /
Middle-3 (Tap4)| CFM| /| 1350| 1313| 1240| 1197| 1106| 1027| 953| 900
Current/A| /| 2.8| 2.9| 3.0| 3.0| 3.1| 3.0| 3.0| 3.0
Power/W| /| 344| 353| 357| 365| 374| 366| 356| 347
High (Tap5)| CFM| /| /| /| 1350| 1338| 1288| 1217| 1100| 1050
Current/A| /| /| /| 3.7| 3.8| 3.8| 3.9| 3.5| 3.1
Power/W| /| /| /| 465| 468| 478| 481| 436| 400
Model Number| Motor Speed| External Static Pressure-Inches W.C.[kPa]
---|---|---
| 0[0]| 0.1[.02]| 0.2[.05]| 0.3[.07]| 0.4[.10]| 0.5[.12]| 0.6[.15]| 0.7[.17]| 0.8[.20]
__

__

__

__

__

__

__

42

| Low

(Tap1)

| CFM| 1050| /| /| /| /| /| /| /| /
Current/A| 1.2| /| /| /| /| /| /| /| /
Power/W| 129| /| /| /| /| /| /| /| /
Middle-1

(Tap2)

| CFM| 1200| /| /| /| /| /| /| /| /
Current/A| 1.6| /| /| /| /| /| /| /| /
Power/W| 200| /| /| /| /| /| /| /| /
Middle-2

(Tap3)

| CFM| 1294| 1233| /| /| /| /| /| /| /
Current/A| 2.3| 2.4| /| /| /| /| /| /| /
Power/W| 262| 268| /| /| /| /| /| /| /
Middle-3

(Tap4)

| CFM| 1427| 1350| 1313| 1240| 1200| /| /| /| /
Current/A| 2.8| 2.8| 2.9| 3.0| 3.0| /| /| /| /
Power/W| 340| 344| 353| 357| 365| /| /| /| /
__

High

(Tap5)

| CFM| 1530| 1490| 1439| 1350| 1338| 1288| 1217| 1100| 1050
Current/A| 3.6| 3.7| 3.7| 3.7| 3.8| 3.8| 3.9| 3.5| 3.1
Power/W| 451| 457| 463| 465| 468| 478| 481| 436| 400
__

__

__

48

| Middle-1

(Tap2)

| CFM| 1500| 1364| 1288| 1214| /| /| /| /| /
Current/A| 1.5| 1.6| 1.6| 1.7| /| /| /| /| /
Power/W| 169| 177| 185| 194| /| /| /| /| /
Middle-2

(Tap3)

| CFM| 1773| 1706| 1639| 1572| 1508| 1445| 1394| 1325| 1268
Current/A| 2.6| 2.7| 2.8| 2.9| 2.9| 3.0| 3.1| 3.2| 3.3
Power/W| 316| 326| 336| 346| 356| 367| 378| 390| 400
Middle-3

(Tap4)

| CFM| /| /| /| /| /| 1763| 1715| 1667| 1619
Current/A| /| /| /| /| /| 4.2| 4.3| 4.4| 4.5
Power/W| /| /| /| /| /| 531| 543| 556| 568
High

(Tap5)

| CFM| /| /| /| /| /| /| /| /| 1800
Current/A| /| /| /| /| /| /| /| /| 5.7
Power/W| /| /| /| /| /| /| /| /| 735
__

__

__

__

__

60

| Middle-1

(Tap2)

| CFM| 1500| /| /| /| /| /| /| /| /
Current/A| 1.5| /| /| /| /| /| /| /| /
Power/W| 169| /| /| /| /| /| /| /| /
Middle-2

(Tap3)

| CFM| 1784| 1732| 1675| 1610| 1548| /| /| /| /
Current/A| 2.6| 2.7| 2.7| 2.8| 2.9| /| /| /| /
Power/W| 312| 321| 329| 337| 347| /| /| /| /
Middle-3

(Tap4)

| CFM| 2046| 1996| 1953| 1900| 1844| 1790| 1738| 1676| 1520
Current/A| 3.7| 3.8| 3.9| 3.9| 4.0| 4.1| 4.2| 4.3| 4.6
Power/W| 459| 471| 481| 492| 503| 514| 527| 538| 577
High

(Tap5)

| CFM| /| 2227| 2185| 2142| 2094| 2042| 1991| 1938| 1800
Current/A| /| 5.1| 5.2| 5.2| 5.3| 5.4| 5.5| 5.6| 5.7
Power/W| /| 646| 658| 670| 683| 695| 709| 724| 735

Table 10-2 Motor Speed from factory

__

Model

| Cooling| Gas Heat| Blower

Size

| Motor HP| Temperature rise  range(℉)
---|---|---|---|---|---
Usable Motor Speed| Motor Speed from factory| Usable Motor Speed| Motor Speed from factory
__

J4PG4024B1060AA

| __

All

| __

Low

| Low| __

Low

| __

10×10

| __

1/6

| __

45-75

Middle
High
__

J4PG4030B1060AA

| __

All

| __

Low

| Low| __

Low

| __

10×10

| __

1/4

| __

30-60

Middle
High
__

__

J4PG4036B1090AA

| __

__

All

| __

__

Middle-2

| Low| __

__

Middle-3

| __

__

10×10

| __

__

1/2

| __

__

45-75

Middle-1
Middle-2
Middle-3
High
__

__

J4PG4042B1090AA

| __

__

All

| __

__

Middle-3

| Low| __

__

Middle-3

| __

__

10×10

| __

__

1/2

| __

__

35-65

Middle-1
Middle-2
Middle-3
High
__

J4PG4048B1090AA

| Middle-1| __

Middle-2

| Middle-1| __

Middle-2

| __

11×10-5/8

| __

3/4

| __

25-55

Middle-2| Middle-2
Middle-3| Middle-3
High| High
__

J4PG4060B1090AA

| Middle-1| __

Middle-3

| Middle-1| __

Middle-2

| __

11×10-5/8

| __

3/4

| __

25-55

Middle-2| Middle-2
Middle-3| Middle-3
High| High
__

J4PG4060B1110AA

| Middle-1| __

Middle-3

| Middle-1| __

Middle-2

| __

11×10-5/8

| __

3/4

| __

30-60

Middle-2| Middle-2
Middle-3| Middle-3
High| High

  • The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor should use only industry-recognized procedures.
  • Each ton of cooling requires between 350 and 450 cubic feet of air per minute (CFM), or 400 CFM nominally.
  • Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship.
  • Air supply diffusers must be selected and located carefully. They must be sized and positoined to deliver treated air along the perimerter of the space. If they are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Return air grilles must be properly sized to carry air back to the blower. If they are too small, they also cause noise.
  • The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a comfortable living space.
  • An air velocity meter or airflow hood can give a reading of system CFM.
  • When installation, installer should select the air speed according to the actual setting static pressure. Please refer to the Table 10-1 & Table 10-2.

Table 10-3 Refrigerant charge for 24K A/C system

24K

Cooling Mode Mode

De Refroidissement

| Cooling Charge Chart/Tableau De Charge de Refroidissement
---|---
Outdoor Ambient Temperature(°F)/Temperature Amdiante Exterieure(en F)
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
High Pressure Detected Valve(psig)/Vanne Détecté de Pression Haute(en psig)
__

Low Pressure Detected Valve(psig)

| __

Vanne Détectée de Pression Basse(en psig)

| 165| | | 269| 288| 307| 326| 349| 371| 393| 414| 435| 456| 476
161| | | 269| 288| 307| 326| 349| 371| 393| 414| 434| 454| 474
157| | | 267| 286| 305| 324| 347| 369| 391| 412| 432| 452| 472
153| | 245| 265| 284| 303| 322| 345| 367| 389| 410| 430| 450| 470
149| | 243| 263| 282| 301| 320| 343| 365| 387| 408| 428| 448| 468
145| | 241| 261| 280| 299| 318| 341| 363| 385| 406| 426| 446| 466
141| 220| 239| 259| 278| 297| 316| 339| 361| 383| 404| 424| 444| 464
137| 218| 237| 257| 276| 295| 314| 337| 359| 381| 402| 422| 442| 462
133| 216| 235| 255| 274| 293| 312| 335| 357| 379| 400| 420| 440| 460
129| 214| 233| 253| 272| 291| 310| 333| 355| 377| 398| 418| 438| 458
125| 212| 231| 251| 270| 289| 308| 331| 353| 375| 396| 416| 436| 456
121| 210| 229| 249| 268| 287| 306| 329| 351| 373| 394| 414| 434| 454
117| 208| 227| 247| 266| 285| 304| 327| 349| 371| 392| 412| 432| 452
113| 206| 225| 245| 264| 283| 302| 325| 347| 369| 390| 410| 430| 450
109| 204| 223| 243| 262| 281| 300| 323| 345| 367| 388| 408| 428| 448
105| 202| 221| 241| 260| 279| 298| 321| 343| 365| 386| 406| 426| 446

Table 10-4 Refrigerant charge for 30K A/C system

30K

Cooling Mode Mode

De Refroidissement

| Cooling Charge Chart/Tableau De Charge de Refroidissement
---|---
Outdoor Ambient Temperature(°F)/Temperature Amdiante Exterieure(en F)
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
High Pressure Detected Valve(psig)/Vanne Détecté de Pression Haute(en psig)
__

Low Pressure Detected Valve(psig)

| __

Vanne Détectée de Pression Basse(en psig)

| 165| | | 269| 290| 310| 331| 350| 370| 390| 411| 432| 453| 474
161| | | 269| 290| 310| 331| 350| 370| 390| 411| 431| 452| 472
157| | | 267| 288| 308| 329| 348| 368| 388| 409| 429| 450| 470
153| | 245| 265| 286| 306| 327| 346| 366| 386| 407| 427| 448| 468
149| | 243| 263| 284| 304| 325| 344| 364| 384| 405| 425| 446| 466
145| | 241| 261| 282| 302| 323| 342| 362| 382| 403| 423| 444| 464
141| 219| 239| 259| 280| 300| 321| 340| 360| 380| 401| 421| 442| 462
137| 217| 237| 257| 278| 298| 319| 338| 358| 378| 399| 419| 440| 460
133| 215| 235| 255| 276| 296| 317| 336| 356| 376| 397| 417| 438| 458
129| 213| 233| 253| 274| 294| 315| 334| 354| 374| 395| 415| 436| 456
125| 211| 231| 251| 272| 292| 313| 332| 352| 372| 393| 413| 434| 454
121| 209| 229| 249| 270| 290| 311| 330| 350| 370| 391| 411| 432| 452
117| 207| 227| 247| 268| 288| 309| 328| 348| 368| 389| 409| 430| 450
113| 205| 225| 245| 266| 286| 307| 326| 346| 366| 387| 407| 428| 448
109| 203| 223| 243| 264| 284| 305| 324| 344| 364| 385| 405| 426| 446
105| 201| 221| 241| 262| 282| 303| 322| 342| 362| 383| 403| 424| 444

Table 10-5 Refrigerant charge for 36K A/C system

36K

Cooling Mode Mode

De Refroidissement

| Cooling Charge Chart/Tableau De Charge de Refroidissement
---|---
Outdoor Ambient Temperature(°F)/Temperature Amdiante Exterieure(en F)
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
High Pressure Detected Valve(psig)/Vanne Détecté de Pression Haute(en psig)
__

Low Pressure Detected Valve(psig)

| __

Vanne Détectée de Pression Basse(en psig)

| 165| | | 273| 294| 314| 335| 359| 383| 407| 430| 453| 475| 498
161| | | 273| 294| 314| 335| 359| 383| 407| 429| 452| 474| 496
157| | | 271| 292| 312| 333| 357| 381| 405| 427| 450| 472| 494
153| | 249| 269| 290| 310| 331| 355| 379| 403| 425| 448| 470| 492
149| | 247| 267| 288| 308| 329| 353| 377| 401| 423| 446| 468| 490
145| | 245| 265| 286| 306| 327| 351| 375| 399| 421| 444| 466| 488
141| 223| 243| 263| 284| 304| 325| 349| 373| 397| 419| 442| 464| 486
137| 221| 241| 261| 282| 302| 323| 347| 371| 395| 417| 440| 462| 484
133| 219| 239| 259| 280| 300| 321| 345| 369| 393| 415| 438| 460| 482
129| 217| 237| 257| 278| 298| 319| 343| 367| 391| 413| 436| 458| 480
125| 215| 235| 255| 276| 296| 317| 341| 365| 389| 411| 434| 456| 478
121| 213| 233| 253| 274| 294| 315| 339| 363| 387| 409| 432| 454| 476
117| 211| 231| 251| 272| 292| 313| 337| 361| 385| 407| 430| 452| 474
113| 209| 229| 249| 270| 290| 311| 335| 359| 383| 405| 428| 450| 472
109| 207| 227| 247| 268| 288| 309| 333| 357| 381| 403| 426| 448| 470
105| 205| 225| 245| 266| 286| 307| 331| 355| 379| 401| 424| 446| 468

Table 10-6 Refrigerant charge for 42K A/C system

42K

Cooling Mode Mode

De Refroidissement

| Cooling Charge Chart/Tableau De Charge de Refroidissement
---|---
Outdoor Ambient Temperature(°F)/Temperature Amdiante Exterieure(en F)
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
High Pressure Detected Valve(psig)/Vanne Détecté de Pression Haute(en psig)
__

Low Pressure Detected Valve(psig)

| __

Vanne Détectée de Pression Basse(en psig)

| 165| | | 265| 284| 303| 323| 347| 371| 395| 417| 440| 462| 484
161| | | 265| 284| 303| 323| 347| 371| 395| 417| 439| 460| 482
157| | | 263| 282| 301| 321| 345| 369| 393| 415| 437| 458| 480
153| | 241| 261| 280| 299| 319| 343| 367| 391| 413| 435| 456| 478
149| | 239| 259| 278| 297| 317| 341| 365| 389| 411| 433| 454| 476
145| | 237| 257| 276| 295| 315| 339| 363| 387| 409| 431| 452| 474
141| 216| 235| 255| 274| 293| 313| 337| 361| 385| 407| 429| 450| 472
137| 214| 233| 253| 272| 291| 311| 335| 359| 383| 405| 427| 448| 470
133| 212| 231| 251| 270| 289| 309| 333| 357| 381| 403| 425| 446| 468
129| 210| 229| 249| 268| 287| 307| 331| 355| 379| 401| 423| 444| 466
125| 208| 227| 247| 266| 285| 305| 329| 353| 377| 399| 421| 442| 464
121| 206| 225| 245| 264| 283| 303| 327| 351| 375| 397| 419| 440| 462
117| 204| 223| 243| 262| 281| 301| 325| 349| 373| 395| 417| 438| 460
113| 202| 221| 241| 260| 279| 299| 323| 347| 371| 393| 415| 436| 458
109| 200| 219| 239| 258| 277| 297| 321| 345| 369| 391| 413| 434| 456
105| 198| 217| 237| 256| 275| 295| 319| 343| 367| 389| 411| 432| 454

Table 10-7 Refrigerant charge for 48K A/C system

48K

Cooling Mode Mode

De Refroidissement

| Cooling Charge Chart/Tableau De Charge de Refroidissement
---|---
Outdoor Ambient Temperature(°F)/Temperature Amdiante Exterieure(en F)
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
High Pressure Detected Valve(psig)/Vanne Détecté de Pression Haute(en psig)
__

Low Pressure Detected Valve(psig)

| __

Vanne Détectée de Pression Basse(en psig)

| 165| | | 277| 299| 320| 342| 364| 387| 410| 434| 457| 481| 505
161| | | 277| 299| 320| 342| 364| 387| 410| 433| 456| 480| 503
157| | | 275| 297| 318| 340| 362| 385| 408| 431| 454| 478| 501
153| | 252| 273| 295| 316| 338| 360| 383| 406| 429| 452| 476| 499
149| | 250| 271| 293| 314| 336| 358| 381| 404| 427| 450| 474| 497
145| | 248| 269| 291| 312| 334| 356| 379| 402| 425| 448| 472| 495
141| 224| 246| 267| 289| 310| 332| 354| 377| 400| 423| 446| 470| 493
137| 222| 244| 265| 287| 308| 330| 352| 375| 398| 421| 444| 468| 491
133| 220| 242| 263| 285| 306| 328| 350| 373| 396| 419| 442| 466| 489
129| 218| 240| 261| 283| 304| 326| 348| 371| 394| 417| 440| 464| 487
125| 216| 238| 259| 281| 302| 324| 346| 369| 392| 415| 438| 462| 485
121| 214| 236| 257| 279| 300| 322| 344| 367| 390| 413| 436| 460| 483
117| 212| 234| 255| 277| 298| 320| 342| 365| 388| 411| 434| 458| 481
113| 210| 232| 253| 275| 296| 318| 340| 363| 386| 409| 432| 456| 479
109| 208| 230| 251| 273| 294| 316| 338| 361| 384| 407| 430| 454| 477
105| 206| 228| 249| 271| 292| 314| 336| 359| 382| 405| 428| 452| 475

Table 10-8 Refrigerant charge for 60K A/C system

60K

Cooling Mode Mode

De Refroidissement

| Cooling Charge Chart/Tableau De Charge de Refroidissement
---|---
Outdoor Ambient Temperature(°F)/Temperature Amdiante Exterieure(en F)
55| 60| 65| 70| 75| 80| 85| 90| 95| 100| 105| 110| 115
High Pressure Detected Valve(psig)/Vanne Détecté de Pression Haute(en psig)
__

Low Pressure Detected Valve(psig)

| __

Vanne Détectée de Pression Basse(en psig)

| 165| | | 289| 311| 334| 357| 379| 400| 431| 457| 482| 508| 533
161| | | 287| 309| 332| 355| 377| 398| 430| 455| 479| 505| 530
157| | | 285| 307| 330| 353| 375| 396| 428| 453| 478| 503| 528
153| | 260| 283| 305| 328| 351| 373| 394| 426| 451| 476| 501| 526
149| | 258| 281| 303| 326| 349| 371| 392| 424| 449| 474| 499| 524
145| | 256| 279| 301| 324| 347| 369| 390| 422| 447| 472| 497| 522
141| 232| 254| 277| 299| 322| 345| 367| 388| 420| 445| 470| 495| 520
137| 230| 252| 275| 297| 320| 343| 365| 386| 418| 443| 468| 493| 518
133| 228| 250| 273| 295| 318| 341| 363| 384| 416| 441| 466| 491| 516
129| 226| 248| 271| 293| 316| 339| 361| 382| 414| 439| 464| 489| 514
125| 224| 246| 269| 291| 314| 337| 359| 380| 412| 437| 462| 487| 512
121| 222| 244| 267| 289| 312| 335| 357| 378| 410| 435| 460| 485| 510
117| 220| 242| 265| 287| 310| 333| 355| 376| 408| 433| 458| 483| 508
113| 218| 240| 263| 285| 308| 331| 353| 374| 406| 431| 456| 481| 506
109| 216| 238| 261| 283| 306| 329| 351| 372| 404| 429| 454| 479| 504
105| 214| 236| 259| 281| 304| 327| 349| 370| 402| 427| 452| 477| 502

TROUBLESHOOTING

Table 11-1 Trouble shooting chart

SYMPTOM POSSIBLE CAUSE REMEDY

__

__

__

__

__

Unit will not run

| Power off or loose electrical connection| Check for correct voltage at compressor contactor in control box
Thermostat out of calibration-set too high| Reset
Failed contactor| Check for 24 volts at contactor coil – replace if contacts are open
Blown fuses| Replace fuses
Transformer defective| Check wiring – replace transformer
Interconnecting low voltage wiring damaged| Replace thermostat wiring
__

__

__

Condenser fan runs, compressor doesn’t

| Run or start capacitor failed (single phase only)| Replace
Loose connection| Check for correct voltage at compressor – check & tighten all connection
Compressor stuck, grounded or open motor winding open internal overload| Wait at least 2 hours for overload to reset. If still open, replace the compressor.
__

Low voltage condition

| Determine cause and correct. At compressor terminals, voltages must be within 10% of rating plate volts when unit is operating.
__

__

__

Insufficient cooling

| Improperly sized unit| Recalculate load
Improper airflow| Check – should be approximately 400 CFM per ton.
Incorrect refrigerant charge| Charge per procedure attached to unit service panel.
Air, non-condensible or moisture in system| Recover refrigerant, evacuate & recharge, add filter drier
__

Incorrect voltage

| Determine cause and correct. At compressor terminals, voltages must be within 10% of rating plate volts when unit is operating.
__

Compressor short cycles

| Incorrect voltage| At compressor terminals, voltage must be ±10% or nameplate marking when unit is operating.
Defective overload protector| Replace – check for correct voltage
Refrigerant undercharge| Add refrigerant
SYMPTOM| POSSIBLE CAUSE| REMEDY
---|---|---
__

__

Compressor operates continuously

| Dirty air filter| Replace filter
Unit undersized for load| Decrease load or increase unit size
Thermostat temperature set too low| Reset thermostat
Low refrigerant charge| Locate leak, repair, and recharge
Air in system| Recover refrigerant, evacuate system, and recharge
Outdoor coil dirty or restricted| Clean coil or remove restriction
Registers sweat| Low evaporator airflow| Increase speed of blower or reduce restriction – replace air filter
__

__

High head-low vapor pressure

| Restriction in liquid line, expansion device or filter drier| Remove or replace defective component
Flow check piston size too small| Change to correct size piston
Incorrect capillary tubes| Change coil assembly
TXV does not open| Replace TXV
High head-high or normal vapor pressure – Cooling mode| Dirty condenser coil| Clean coil
Refrigerant overcharge| Correct system charge
Condenser fan not running| Repair or replace
Air or non-condensible in system| Recover refrigerant, evacuate & recharge
Low head-high vapor pressures| Defective compressor valves| Replace compressor
Incorrect capillary tubes| Replace coil assembly
Low vapor – cool compressor – iced evaporator coil| Low evaporator airflow| Increase speed of blower or reduce restriction – replace air filter
Operating below 65°F outdoors| Add Low Ambient Kit
Moisture in system| Recover refrigerant – evacuate & recharge – add filter drier
High vapor pressure| Excessive load| Recheck load calculation
Defective compressor| Replace
Fluctuating head & vapor

pressure

| TXV hunting| Check TXV bulb clamp – check air distribution on coil – replace TXV
Air or non-condensible in system| Recover refrigerant – evacuate & recharge
Gurgle or pulsing noise at expansion device or liquid line| __

Air or non-condensible in system

| __

Recover refrigerant – evacuate & recharge

Circulating air blower & inducer run continuously, compressor will not start| Manual reset overtemperature control tripped| Reset or replace
Wire loose in limit circuit| Check wiring
__

__

__

__

__

Burners will not ignite

| Water in gas line| Drain. Install drip leg.
No power to furnace| Check power supply fuses, wiring or circuit breaker.
No 24 volts power supply to control circuit| Check transformer.
Miswired or loose connections| Check all wiring and wire nut connections
Misaligned spark electrodes| Check flame ignition and sense electrode positioning. Adjust as necessary.
__

No gas at main burners

| Check gas line for air. Purge as necessary. NOTE: After purging gas line of air, wait at least 5 minutes for any gas to dissipate before attempting to light unit.
Check gas valve.
__

__

__

Inadequate heating

| Dirty air filter| Clean or replace filter as necessary
Gas input to furnace too low| Check gas pressure at manifold with that on unit nameplate
Unit undersized for application| Replace with proper unit or add additional unit
Restricted airflow| Clean or replace filter, remove any restriction
Limit switch cycles main burners| Check rotation of blower, temperature rise of unit. Adjust as necessary
__

__

Poor flame characteristics

| __

__

Incomplete combustion results in: Aldehyde odors, carbon monoxide, sooting flame, floating flame

| Tighten all screws around burner compartment
Cracked heat exchanger. Replace as necessary.
Unit over-fired. Reduce input (change orifices or adjust gas line or manifold pressure).
Check burner alignment
Inspect heat exchanger for blockage. Clean as necessary.
Both condenser fan and compressor startup and shutdown frequently (about three minutes per cycle)| __

__

Abnormal high discharge pressure caused the high pressure switch act

| __

__

Reference to the remedy of ‘High head-high or normal

vapor pressure-cooling mode’.

High Altitude

__

__

MODLE

| __

NUMBER OF   BURNERS

| NATURAL GAS
---|---|---
HEATING VALVE 1075BTU/CU.FT.
SPECIFIC GRAVITY 0.65/MANIFOLD PRESSURE @3.5″W.C.
ELEVATION 0-2000′

(USA/CANADA)

| ELEVATION

4000′

(USA ONLY)

| ELEVATION 6000′

(USA ONLY)

| ELEVATION 8000′

(USA ONLY)

| ELEVATION

2000-4500′ (CANADA)

J4PG4024B1060AA| 5| 51| 53| 53| 54| 51
J4PG4030B1060AA| 5| 51| 53| 53| 54| 51
J4PG4036B1090AA| 7| 51| 52| 53| 53| 51
J4PG4042B1090AA| 7| 51| 52| 53| 53| 51
J4PG4048B1090AA| 6| 49| 50| 51| 52| 49
J4PG4060B1090AA| 6| 49| 50| 51| 52| 49
J4PG4060B1110AA| 7| 49| 50| 51| 51| 49
__

__

MODLE

| __

NUMBER OF  BURNERS

| PROPANE GAS
HEATING VALVE 2500BTU/CU.FT.
SPECIFIC GRAVITY 0.65/MANIFOLD PRESSURE @10.0″W.C.
ELEVATION 0-2000′

(USA/CANADA)

| ELEVATION 4000′

(USA ONLY)

| ELEVATION 6000′

(USA ONLY)

| ELEVATION 8000′

(USA ONLY)

| ELEVATION 2000-4500′ (CANADA)
J4PG4024B1060AA| 5| 59| 63| 64| 64| 59
J4PG4030B1060AA| 5| 59| 63| 64| 64| 59
J4PG4036B1090AA| 7| 59| 62| 63| 64| 59
J4PG4042B1090AA| 7| 59| 62| 63| 64| 59
J4PG4048B1090AA| 6| 56| 59| 60| 61| 56
J4PG4060B1090AA| 6| 56| 59| 60| 61| 56
J4PG4060B1110AA| 7| 56| 58| 59| 60| 56

For addressing derating at altitudes above 2000 ft (610 m), the instructions shall indicate one of the following:

  1. Installation of this furnace at altitudes above 2000 ft (610 m) shall be in accordance with local codes, or in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or National Standard of Canada, Natural Gas and Propane Installation Code, CSA B149.1.
  2. For furnaces requiring modifications other than only gas orifice and/or manifold pressure adjustment for installation at high altitude, “Installation of this furnace at altitudes above 2000 ft (610 m) shall be made in accordance with the Listed High Altitude Conversion Kit available with this furnace.”
  3. For furnaces requiring only gas orifice and/or manifold pressure adjustment for installation at high altitude, the furnace installation instructions shall provide adequate details on proper adjustments for various altitudes.

J4PG4024B1060AA

J4PG4030B1060AA

J4PG4036B1090AA

J4PG4042B1090AA

J4PG4048B1090AA

J4PG4060B1090AA

J4PG4060B1110AA

  • CONFORMS TO UL STD. 1995
  • CERTIFIED TO CSA STD. C22.2 NO. 236
  • CENTRAL FURNACE
  • CONFORMS TO ANSI STD Z21.47-2016,
  • CERTIFIED TO CSA STD 2.3-2016

PACKAGE GAS ELECTRIC UNITS
FEATURING R-410A 14 SEER SERIES – (2-5Tons)

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Oxbox User Manuals

Related Manuals