MTN648704 SpaceLogic KNX Blind Actuator
User Manual Art. no. MTN648704
For your safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The safe electrical installation must be carried out only by skilled
professionals. Skilled professionals must prove profound knowledge in the
following areas:
- Connecting to installation networks
- Connecting several electrical devices
- Laying electric cables
- Connecting and establishing KNX networks
- Safety standards, local wiring rules, and regulations
Failure to follow these instructions will result in death or serious injury.
DANGER
RISK OF FATAL INJURY FROM ELECTRIC SHOCK
The output may carry an electrical current even when the load is switched off.
- When working on the device: Always disconnect the device from the supply by means of the fuse in the incoming circuit.
- Even if the manual switch is in the „OFF“ position, a KNX telegram can switch the connections to being live at any time. Before working on the device, always disconnect the fuse in the incoming circuit from the supply.
Failure to follow these instructions will result in death or serious injury.
CAUTION
The device may be damaged!
- Always operate the product in compliance with the specified technical data.
- Only connect one motor per channel.
- Only install devices with at least basic insulation next to the device.
Failure to follow these instructions can result in equipment damage.
Blind actuator introduction
The blind actuator REG-K/4×24/6 with manual mode (referred to below as the
actuator) can control up to four blind drives with limit switches
independently of one another.
You can switch the actuator to manual operation and check that it works even
without ETS programming, and you can control the connected loads directly at
the actuator in the event of a bus failure.
The actuator has a bus coupler. It is installed on a DIN rail, with the bus
connection made via a bus connecting terminal. It is supplied with power from
the bus voltage.
A data rail is not required.
Connections, displays and operating elements
A Programming button and programming LED (red)
B Under the cable cover: Bus connecting terminal
C Operating LED “RUN” (green)
D Manual operation LED “Manual” (red)
E Manual operation key “Manual”
F Channel terminals for loads
G Supply voltage for loads
H Channel keys for manual control of the corresponding channel, only respond
when the manual operation is switched on
I Channel status LEDs (yellow) for the corresponding channel
When and how the LEDs light up
RUN (green) | lights up during normal operation |
---|---|
Manual (red) | lights up during manual operation |
Channel (yellow) | lights up during movement |
Mounting the actuator
- Set the actuator onto the DIN rail.
CAUTION
The device may be damaged!
- Connect the bus connection and the supply voltage with the correct polarity.
- Connect the bus voltage first and only then the load voltage.
- Protect the switch contacts with a series-connected 6 A circuit breaker.
- Only install devices with at least basic insulation next to the device.
Failure to follow these instructions can result in equipment damage.
-
Connect KNX.
-
Connect the bus voltage.
-
Wait at least 30 seconds.
After the bus voltage has been switched on, all the actuator relays are moved to a predefined position (factory setting: “Off”).
-
Connect the load.
-
Connect the load voltage.
CAUTION
If the toggle times are too short, the blind motor could be damaged.!
- The toggle time at the factory setting is 500 ms. A longer toggle time may be necessary for other motors. Refer to the manufacturer’s specifications in the datasheet for the motor.
Failure to follow these instructions can result in equipment damage.
Now you can check the functionality of the actuator and the connected loads
without having to load the application from the ETS. (See the “Manual
operation” section.)
Putting the actuator into operation
-
Press the programming button.
The programming LED lights up. -
Load the physical address and application into the device from the ETS.
The programming LED goes out.
The operating LED lights up The application was loaded successfully, the
device is ready for operation.
Manual operation
Normally, you control the blinds using push buttons or by remote control.
However, you can also switch the actuator to manual operation and then raise
or lower each blind manually using its channel keys. In order to be able to do
this, the ETS parameter “Manual operation enabled” must be set to “enabled”
and bus voltage must be present.
Manual operation before downloading the application for the first time
Immediately after the initial installation, you can switch the actuator to
manual operation, e.g. in order to test the drives.
Manual operation with the ETS setting “Bus and manual operation”
In manual operation, the actuator also responds to KNX telegrams. The command
last received is given priority.
Exception: Safety alarms (e.g. weather) always have priority with this
setting.
Manual operation with the ETS setting “Manual operation only”
In manual operation, the actuator does not respond to KNX telegrams, nor to
safety alarms. This setting can be useful when carrying out maintenance, for
example.
CAUTION
Loads could be damaged. When operating loads in “Manual operation only” using
the channel keys, prioritized safety functions (e.g. weather alarm position,
disable position) no longer work. To prevent damage, you should therefore be
very careful when operating manually.
Make sure that the ETS parameter “Manual the operating mode” is set to “Bus
and manual operation” (not “Manual operation only”), when you hand over the
system to the operator.
Time-limited manual operation is another function that can be set in the ETS. With this function, you can set a time period after which manual operation (including “Manual operation only”) is canceled automatically. The actuator then responds to KNX telegrams again.
Change the actuator over to manual operation
- Press the manual operation key E.
The red manual operation LED D lights up. The actuator is in manual operation.
– The green operating LED C goes out when “Manual operation only” is set in the ETS.
– The green operating LED C remains on when “Bus and manual operation” is set in the ETS.
Controlling the blinds in manual operation
WARNING
Blinds can cause injury when they are moving. If you are operating
blinds/roller shutters using channel keys, make sure that no people are in the
range of movement.
- To raise (arrow up) or lower (arrow down) the blind: press the corresponding channel key H.
- To halt the movement of travel: press the channel key H again.
The corresponding channel status LED I lights up during movement.
Exit manual operation
- Press the manual operation key E again.
The red manual operation LED D goes out. The green operating LED C lights up. The actuator now only responds to KNX telegrams.
**What should I do if there is a problem?
**
The red manual operation LED and the green operating LED are not lit. Manual operation cannot be activated.
-
The bus voltage has failed.
– Check the bus voltage. -
The application was not loaded properly.
– Load it again.
The green operating LED is not lit.
-
The bus voltage has failed.
– Check the bus voltage. -
The application was not loaded properly.
– Load it again -
Red manual operation LED is lit: Manual operation is active and “Manual operation only” is set in the ETS.
Only manual operation is possible. There is no fault.
– Switch off manual operation.
The actuator does not react to the manual operation key, the red manual
operation LED does not light up, and manual operation is not possible.
-
ETS parameter “Manual operation enabled” is set to “blocked”. There is no fault.
– Set the “Manual operation enabled” parameter to “Enabled/enable”. -
“Manual operation enabled” is blocked by an object (value=0), there is no fault.
– Enable manual operation via object.
In manual operation, the actuator does not react to the activation of the channel keys, the red manual operation LED lights up, and manual mode is not possible. -
The green operating LED is still lit: ETS parameter
“Manual operation mode” is set to “Bus and manual operation”, a prioritized function (e.g. weather alarm or lock) is activated, and there is no malfunction.
– Wait until the higher-level function has been completed, or switch the ETS parameter “Manual operation type” to “Manual operation only”.
In manual operation, the actuator controls connected loads without a channel key being pressed.
- The ETS parameter “Manual operating mode” is set to “Bus and manual operation”. The control command for the actuator came via a KNX telegram. There is no fault.
– Switch the ETS parameter “Manual operating mode” to “Manual operation only”.
Technical data
Power supply from the bus: | DC 24 V, max. 17.5 mA |
---|---|
Insulation voltage: | AC 4 kV between bus and switch outputs |
Nominal voltage: | DC 24 V |
Nominal current: | 6:00 AM |
Load type: | 24 V direct current drives max. 15 times per minute at nominal |
load
Switching frequency: Fuse:| one 6 A circuit breaker connected upstream per
channel
Ambient temperature
Operation:| -5 °C to +45 °C
Storage:| -25 °C to +55 °C
Transport:| -25°C to +70°C
Environment:| can be used at up to 2000 above sea level (MSL)
Max. humidity:| 93 %, no moisture condensation
Operating elements: Display elements:| 1 programming button,
1 “Manual” manual operation key,
2 channel keys per channel
Display elements:| 1 red LED: programming check,
1 green LED: ready for the operation, “RUN”,
1 red LED: manual operation status,
2 yellow status LEDs per channel
KNX connection:| two 1 mm pins for bus connecting terminal
24 V connection:| per channel pair one plug-in 4-gang screw terminal for max.
2.5 mm 2
Device width:| 4 depth units = approx. 72 mm
Permitted current depending on the connection voltage:
Schneider Electric -Contact
Schneider Electric Industries SAS
35 rue Joseph Monier
Rueil Malmaison 92500
France
If you have technical questions, please contact the Customer Care Centre in
your country.
se.com/contact
UK Representative
Schneider Electric Limited
Telford, TF3 3 BL, UK
Stafford Park 5
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>