Product Details
Product Name: MO132-2.5 Manual Motor Starter Magnetic Only 2.5 A
Product ID: MO132-2.5
Extended Product Type: 1SAM360000R1007
EAN: 4013614400223
Catalog Description: MO132-2.5 Manual Motor Starter Magnetic Only 2.5 A
General Information
The MO132-2.5 manual motor starter magnetic only is a compact 45 mm width device with a rated operational current of 2.50 A. This device is used to manually switch on and off loads/motors and to protect them reliably and without the need for a fuse from short-circuits. The manual motor starter offers a rated service short-circuit breaking capacity of 100 kA at 400 V AC. It features a built-in disconnect function, trip-free mechanism, and a rotary handle with a clear switch position indication. The manual motor starter magnetic only is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, and power in-feed blocks are available as accessories.
Technical Specifications
- Rated Service Short-Circuit Breaking Capacity (Ics): 100 kA at 400 V AC
- Rated Ultimate Short-Circuit Breaking Capacity (Icu): 100 kA
- Rated Instantaneous Short-Circuit Current Setting (Ii): Not specified
- Setting Range: Not specified
- Rated Operational Power AC-3 (Pe): 0.75 kW at 400 V Three Phase
- Rated Operational Voltage: 690 V AC
- Rated Operational Current (Ie): 2.5 A
- Rated Frequency (f): 50 Hz
- Rated Impulse Withstand Voltage (Uimp): 6 kV
- Rated Insulation Voltage (Ui): 690 V
- Power Loss: 1.7 W
- Number of Poles: 3
- Conventional Free-air Thermal Current (Ith): 2.5 A
Product Usage Instructions
- Ensure that the power supply to the motor or load is switched off.
- Connect the main circuit wires to the appropriate terminals on the manual motor starter.
- If necessary, connect auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, or other accessories as required.
- Mount the manual motor starter on a DIN rail in a suitable position.
- Tighten the mounting screws securely using the recommended screwdriver and torque.
- Verify that the rotary handle is in the “OFF” position.
- Switch on the power supply to the motor or load.
- To start the motor or activate the load, turn the rotary handle to the “ON” position.
- To stop the motor or deactivate the load, turn the rotary handle back to the “OFF” position.
- If necessary, lock the handle to prevent unauthorized changes.
General Information
- Extended Product Type MO132-2.5
- Product ID 1SAM360000R1007
- EAN 4013614400223
- Catalog Description MO132-2.5 Manual Motor Starter Magnetic Only 2.5 A
- Long Description The MO132-2.5 manual motor starter magnetic only is a compact 45 mm width device with a rated operational current of Ie = 2.50 A. This device is used to manually switch on and off loads/motors and to protect them reliably and without the need for a fuse from short-circuits. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 100 kA at 400 V AC. A combination together with overload relays or motor controllers allows the protection of motors. Further features are the built-in disconnect function, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter magnetic only is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks are available as accessory.
Ordering
- Minimum Order Quantity 1 piece
- Customs Tariff Number 85362010
Popular Downloads
- Data Sheet, Technical Information 2CDC131035D0202
- Instructions and Manuals 2CDC131034M6801
- Instructions and Manuals (Part 2) 2CDC131060M0202
- Time-Current Characteristic Curve 1SAM300515F0005
- I²t Characteristic
- 1SAM300507F0001
- 1SAM300507F0003
- Cut-off Current Characteristic
- 1SAM300508F0001
- 1SAM300508F0003
- CAD Dimensional Drawing 2CDC001079B0201
- Dimension Diagram 1SAM300402F0001
Dimensions
- Product Net Width 45 mm
- Product Net Height 90 mm
- Product Net Depth /Length 86.75 mm
- Product Net Weight 0.265 kg
Technical
- Rated Service Short- Circuit Breaking Capacity (Ics)
- (230 V AC) 100 kA
- (400 V AC) 100 kA
- (440 V AC) 100 kA
- (500 V AC) 100 kA
- (690 V AC) 100 kA
- Rated Ultimate Short- Circuit Breaking Capacity (Icu)
- (230 V AC) 100 kA
- (400 V AC) 100 kA
- (440 V AC) 100 kA
- (500 V AC) 100 kA
- (690 V AC) 100 kA
- Rated Instantaneous Short-Circuit Current Setting (Ii) 31.3 A
- Setting Range None
- Rated Operational Power AC-3 (Pe) (400 V) Three Phase 0.75 kW
- Rated Operational Power AC-3e (Pe) (400 V) Three Phase 0.75 kW
- Rated Operational Main Circuit Voltage 690 V AC
- Rated Operational Current (Ie) 2.5 A
- Rated Operational Current AC-3 (Ie) 2.5 A
- Rated Operational Current AC-3e (Ie) 2.5 A
- Rated Frequency (f)
- Main Circuit 50 Hz
- Main Circuit 60 Hz
- Rated Impulse Main Circuit 6 kV Withstand Voltage (Uimp )
- Rated Insulation Voltage 690 V (Ui)
- Power Loss at Rated Operating Conditions per Pole 1.7 W
- Number of Poles 3
- Conventional Free-air Main Circuit 2.5 A Thermal Current (Ith)
- Degree of Protection Housing IP20 Main Circuit Terminals IP10
- Pollution Degree 3
- Electrical Durability 50000 cycle
- Mechanical Durability 100000 cycle
- Terminal Type Screw Terminals
- Flexible with Ferrule 1/2x 0.75 … 2.5 mm²
- Flexible with Insulated Ferrule 1/2x 0.75 … 2.5 mm²
- Flexible 1/2x 0.75 … 2.5 mm²
- Rigid 1/2x 1 … 4 mm²
- Connecting Capacity Main Circuit
- Tightening Torque Main Circuit 0.8 … 1.2 N·m
- Wire Stripping Length Main Circuit 9 mm
- Recommended Screw Driver Pozidriv 2
- Mounting Position 1 … 6
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
- TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- Mounting on DIN Rail
- Minimum Mounting DistanceElectrical Conductive Board, Horizontal – Up to 400 V 0 mm
- Electrical Conductive Board, Horizontal – Up to 690 V 1.5 mm
- Electrical Conductive Board, Vertical 75 mm
- Other Device Same Type, Horizontal 0 mm
- Other Device Same Type, Vertical 150 mm
- Actuator Type Rotary Handle
- Contact Position Indication ON / OFF / TRIP
- Standards
- IEC/EN 60947-1
- IEC/EN 60947-2
- IEC/EN 60947-4-1
- UL 60947-1
- UL 60947-4-1
- Remarks
- For overload protection of the motors, an appropriate thermal or electronic overload relays must be used
Technical UL/CSA
- Short-Circuit Current Rating (SCCR)
- Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kA
- Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 47 kA
- Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kA
- Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 47 kA
- Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
- Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA
- Maximum Operating Voltage UL/CSA Main Circuit 600 V AC
- Horsepower Rating UL/CSA
- (200 V AC) Three Phase 0.5 Hp
- (208 V AC) Three Phase 0.5 Hp
- (220 … 240 V AC) Three Phase 0.5 Hp
- (440 … 480 V AC) Three Phase 1 Hp
- (550 … 600 V AC) Three Phase 1.5 Hp
- Full Load Amps Motor Use
- (200 V AC) Three Phase 2.5 A
- (208 V AC) Three Phase 2.5 A
- (220 … 240 V AC) Three Phase 2.5 A
- (440 … 480 V AC) Three Phase 2.5 A
- (550 … 600 V AC) Three Phase 2.5 A
- Locked Rotor Amps
- (200 V AC) Three Phase 15 A
- (208 V AC) Three Phase 15 A
- (220 … 240 V AC) Three Phase 15 A
- (440 … 480 V AC) Three Phase 15 A
- (550 … 600 V AC) Three Phase 15 A
- General Use Rating (600 V AC) 2.5 A UL/CSA
- Connecting Capacity Flexible 1/2x 16-12 AWG
- Main Circuit UL/CSA Stranded 1/2x 16-12 AWG
- Tightening Torque Main Circuit 10 in·lb UL/CSA
Environmental
- Ambient Air Temperature
- Around the Enclosure 0 … +40 °C
- Operation -25 … +60 °C
- Storage -50 … +80 °C
- Ambient Temperature Compensation Air No
- Maximum Operating Altitude Permissible 2000 m
- Resistance to Shock acc. to IEC 60068-2-27 11 ms Pulse 25g
- Resistance to Vibrations 5g / acc. to IEC 60068-2-6 3 … 150 Hz
- RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Certificates and Declarations
- ABS Certificate 1SAA963001-0101
- BV Certificate 1SAA963001-0202
- CB Certificate 1SAA963002-2002
- CQC Certificate CQC2010010307387700
- Cut-off Current Characteristic
- 1SAM300508F0001
- 1SAM300508F0003
- Declaration of 2020980307003526 Conformity – CCC
- Declaration of 1SAD101100-3403 Conformity – CE
- Declaration of 1SAD201100-3403 Conformity – UKCA
- DNV GL Certificate 1SAA963001-0304
- EAC Certificate 1SAA963000-2701
- 1SAM300507F0001
- 1SAM300507F0003
- I²t Characteristic
- KC Certificate 1SAA963002-1502
- LR Certificate 1SAA963001-0502
- RINA Certificate 1SAA963002-0802
- RMRS Certificate 1SAA918000-0704
- UL Certificate
- E137861-20090225
- E345003-20090225
Container Information
- Package Level 1 Units box 1 piece
- Package Level 1 Width 92 mm
- Package Level 1 Depth / 95 mm Length
- Package Level 1 Height 50 mm
- Package Level 1 Gross 0.28 kg Weight
- Package Level 1 EAN 4013614400223
- Package Level 2 Units carton 40 piece
- Package Level 2 Width 280 mm
- Package Level 2 Depth / Length 395 mm
- Package Level 2 Height 210 mm
- Package Level 2 Gross Weight 11.586 kg
- Package Level 2 EAN 4013614443671
Classifications
- Object Classification F Code
- ETIM 4 EC000074 – Motor protective circuit-breaker
- ETIM 5 EC000074 – Motor protective circuit-breaker
- ETIM 6 EC000074 – Motor protection circuit-breaker
- ETIM 7 EC000074 – Motor protection circuit-breaker
- ETIM 8 EC000074 – Motor protection circuit-breaker
- eClass V11.0 : 27370401 UNSPSC 39121521
- IDEA Granular Category 4731 >> Manual Starters Code (IGCC)
- E-Number (Finland) 3705885
- E-Number (Sweden) 3110035
Accessories
1SAM201901R1001 | HKF1-11 Auxiliary Contact | HKF1-11 | 1 | piece |
---|---|---|---|---|
1SAM201901R1201 | HKF1-11K Auxiliary Contact | HKF1-11K | 1 | piece |
1SAM201901R1002 | HKF1-20 Auxiliary Contact | HKF1-20 | 1 | piece |
1SAM201901R1202 | HKF1-20K Auxiliary Contact | HKF1-20K | 1 | piece |
1SAM201901R1004 | HKF1-01 Auxiliary Contact | HKF1-01 | 1 | piece |
1SAM201901R1003 | HKF1-10 Auxiliary Contact | HKF1-10 | 1 | piece |
1SAM201902R1002 | HK1-20 Auxiliary Contact | HK1-20 | 1 | piece |
1SAM201902R1202 | HK1-20K Auxiliary Contact | HK1-20K | 1 | piece |
1SAM201902R1001 | HK1-11 Auxiliary Contact | HK1-11 | 1 | piece |
1SAM201902R1201 | HK1-11K Auxiliary Contact | HK1-11K | 1 | piece |
1SAM201902R1003 | HK1-02 Auxiliary Contact | HK1-02 | 1 | piece |
1SAM201902R1203 | HK1-02K Auxiliary Contact | HK1-02K | 1 | piece |
1SAM201902R1004 | HK1-20L Auxiliary Contact | HK1-20L | 1 | piece |
1SAM201902R1204 | HK1-20LK Auxiliary Contact | HK1-20LK | 1 | piece |
1SAM201903R1002 | SK1-20 Signaling Contact | SK1-20 | 1 | piece |
1SAM201903R1202 | SK1-20K Signaling Contact | SK1-20K | 1 | piece |
1SAM201903R1001 | SK1-11 Signaling Contact | SK1-11 | 1 | piece |
1SAM201903R1201 | SK1-11K Signaling Contact | SK1-11K | 1 | piece |
1SAM201903R1003 | SK1-02 Signaling Contact | SK1-02 | 1 | piece |
1SAM201903R1203 | SK1-02K Signaling Contact | SK1-02K | 1 | piece |
1SAM201910R1001 | AA1-24 Shunt Trip | AA1-24 | 1 | piece |
1SAM201910R1002 | AA1-110 Shunt Trip | AA1-110 | 1 | piece |
1SAM201910R1003 | AA1-230 Shunt Trip | AA1-230 | 1 | piece |
1SAM201910R1004 | AA1-400 Shunt Trip | AA1-400 | 1 | piece |
1SAM201904R1010 | UA1-20 Undervoltage Release | UA1-20 | 1 | piece |
1SAM201904R1001 | UA1-24 Undervoltage Release | UA1-24 | 1 | piece |
1SAM201904R1002 | UA1-48 Undervoltage Release | UA1-48 | 1 | piece |
1SAM201904R1003 | UA1-60 Undervoltage Release | UA1-60 | 1 | piece |
1SAM201904R1004 | UA1-110 Undervoltage Release | UA1-110 | 1 | piece |
--- | --- | --- | --- | --- |
1SAM201904R1008 | UA1-208 Undervoltage Release | UA1-208 | 1 | piece |
1SAM201904R1005 | UA1-230 Undervoltage Release | UA1-230 | 1 | piece |
1SAM201904R1006 | UA1-400 Undervoltage Release | UA1-400 | 1 | piece |
1SAM201904R1007 | UA1-415 Undervoltage Release | UA1-415 | 1 | piece |
1SAM201904R1009 | UA1-575 Undervoltage Release | UA1-575 | 1 | piece |
1SAM201906R1102 | PS1-2-0-65 Busbar | PS1-2-0-65 | 1 | piece |
1SAM201906R1112 | PS1-2-1-65 Busbar | PS1-2-1-65 | 1 | piece |
1SAM201906R1122 | PS1-2-2-65 Busbar | PS1-2-2-65 | 1 | piece |
1SAM201916R1103 | PS1-3-0-100 Busbar | PS1-3-0-100 | 1 | piece |
1SAM201906R1103 | PS1-3-0-65 Busbar | PS1-3-0-65 | 1 | piece |
1SAM201916R1113 | PS1-3-1-100 Busbar | PS1-3-1-100 | 1 | piece |
1SAM201906R1113 | PS1-3-1-65 Busbar | PS1-3-1-65 | 1 | piece |
1SAM201916R1123 | PS1-3-2-100 Busbar | PS1-3-2-100 | 1 | piece |
1SAM201906R1123 | PS1-3-2-65 Busbar | PS1-3-2-65 | 1 | piece |
1SAM201916R1104 | PS1-4-0-100 Busbar | PS1-4-0-100 | 1 | piece |
1SAM201906R1104 | PS1-4-0-65 Busbar | PS1-4-0-65 | 1 | piece |
1SAM201916R1114 | PS1-4-1-100 Busbar | PS1-4-1-100 | 1 | piece |
1SAM201906R1114 | PS1-4-1-65 Busbar | PS1-4-1-65 | 1 | piece |
1SAM201906R1124 | PS1-4-2-65 Busbar | PS1-4-2-65 | 1 | piece |
1SAM201916R1105 | PS1-5-0-100 Busbar | PS1-5-0-100 | 1 | piece |
1SAM201906R1105 | PS1-5-0-65 Busbar | PS1-5-0-65 | 1 | piece |
1SAM201916R1115 | PS1-5-1-100 Busbar | PS1-5-1-100 | 1 | piece |
1SAM201906R1115 | PS1-5-1-65 Busbar | PS1-5-1-65 | 1 | piece |
1SAM201906R1125 | PS1-5-2-65 Busbar | PS1-5-2-65 | 1 | piece |
1SAM201907R1101 | S1-M1-25 Power Infeed Block | S1-M1-25 | 1 | piece |
1SAM201907R1102 | S1-M2-25 Power Infeed Block | S1-M2-25 | 1 | piece |
1SAM201907R1103 | S1-M3-25 Power Infeed Block | S1-M3-25 | 1 | piece |
1SAM201913R1103 | S1-M3-35 Power Infeed Block | S1-M3-35 | 1 | piece |
1SAM201914R1002 | S1-PB1-25 Power Infeed Block | S1-PB1-25 | 1 | piece |
1SAM301911R1001 | TS1-M3-S1 Terminal Spacer | TS1-M3-S1 | 1 | piece |
1SAM301912R1001 | TS1-M3-S2 Terminal Spacer | TS1-M3-S2 | 1 | piece |
1SAM201914R1001 | PB1-1-32 Connecting Link | PB1-1-32 | 1 | piece |
1SAM201908R1001 | BS1-3 Protection Cover | BS1-3 | 1 | piece |
1SAM201909R1001 | FS116 Screw Fixing Kit | FS116 | 1 | piece |
GJF1101903R0002 | SA2 Terminals and Installation Material | SA2 | 1 | piece |
1SAM201911R1012 | IB132-F Enclosure | IB132-F | 1 | piece |
1SAM201911R1010 | IB132-G Enclosure | IB132-G | 1 | piece |
1SAM201911R1011 | IB132-Y Enclosure | IB132-Y | 1 | piece |
1SAM201912R1010 | DMS132-G Door Mounting Kit | DMS132-G | 1 | piece |
1SAM201912R1011 | DMS132-Y Door Mounting Kit | DMS132-Y | 1 | piece |
1SAM201909R1021 | MSAH1 Shaft Supporter | MSAH1 | 1 | piece |
1SAM201920R1011 | MSHD-LTB Handles | MSHD-LTB | 1 | piece |
1SAM201920R1012 | MSHD-LTY Handles | MSHD-LTY | 1 | piece |
1SAM201920R1000 | MSH-AR Shaft Alignment Ring | MSH-AR | 1 | piece |
1SAM101923R0002 | MSMN Driver | MSMN | 1 | piece |
1SAM101923R0012 | MSMNO Driver | MSMNO | 1 | piece |
1SCA101647R1001 | OXS6X85 SHAFT | OXS6X85 | 1 | piece |
1SCA108043R1001 | OXS6X105 SHAFT | OXS6X105 | 1 | piece |
1SCA101655R1001 | OXS6X130 SHAFT | OXS6X130 | 1 | piece |
1SCA101659R1001 | OXS6X180 SHAFT | OXS6X180 | 1 | piece |
Categories
- Low Voltage Products and Systems → Circuit Breakers → Manual Motor Starters
- Low Voltage Products and Systems → Control Products → Manual Motor Starters → Manual Motor Starters
© 2023 ABB. All rights reserved.
Subject to change without notice
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>