  • Product Name: MS132-0.25K Manual Motor Starter 0.16 … 0.25 A
  • Extended Product Type: MS132-0.25K
  • Product ID: 1SAM350010R1002
  • EAN: 4013614400322

Product Information
The MS132-0.25K Manual Motor Starter is a device used to start and protect motors with a rated current of 0.16 to 0.25 A. It is designed to provide short-circuit protection and is suitable for use in various applications.

Dimensions

  • Product Net Width: 45 mm
  • Product Net Height: 112 mm
  • Product Net Depth / Length: 87 mm
  • Product Net Weight: 0.256 kg

Technical Specifications

  • Rated Service Short-Circuit Breaking Capacity (Ics): (230 V AC) 100 kA, (250 V DC) 3 Poles in Series 10 kA
  • Rated Ultimate Short-Circuit Breaking Capacity (Icu): (400 V AC) 100 kA, (440 V AC) 100 kA, (500 V AC) 100 kA, (690 V AC) 100 kA
  • Rated Instantaneous Short-Circuit Current Setting (Ii): 3.1 A
  • Setting Range: 0.16 … 0.25 A (400 V) Three Phase
  • Rated Operational Power AC-3 (Pe): 0.06 kW
  • Rated Operational Voltage: Main Circuit 690 V AC, Main Circuit 250 V DC
  • Rated Operational Current (Ie): 0.25 A
  • Rated Operational Current AC-3 (Ie): 0.25 A
  • Rated Operational Current AC-3e (Ie): 0.25 A
  • Rated Operational Current DC-5 (Ie): 0.25 A
  • Rated Frequency (f): Main Circuit 50 Hz, Main Circuit 60 Hz
  • Rated Impulse Withstand Voltage (Uimp): Main Circuit 6 kV
  • Rated Insulation Voltage (Ui): 690 V
  • Power Loss: at Rated Operating Conditions per Pole 0.7 … 1.6 W
  • Number of Poles: 3
  • Conventional Free-air Thermal Current (Ith): Main Circuit 0.25 A
  • Degree of Protection: Housing IP20, Main Circuit Terminals IP20
  • Pollution Degree: 2
  • Electrical Durability: 1SBC100212C0203, 2CDC131120M6801, 2CDC131060M0202, 2CDC131063M6801, 1SAM300505F0102, 1SAM300507F0001, 1SAM300507F0003, 1SAM300508F0001, 1SAM300508F0003, 2CDC001079B0201
  • Mechanical Durability: 9AKK108466A6074, 9AKK108466A6068, 9AKK107991A4712, 2CDC131153V0201
  • Terminal Type: Pozidriv 2
  • Connecting Capacity: 1 … 6 TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715, TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715, Electrical Conductive Board, Horizontal – Up to 400 V 0 mm, Electrical Conductive Board, Horizontal – Up to 690 V 1.5 mm, Electrical Conductive Board, Vertical 75 mm, Other Device Same Type, Horizontal 0 mm, Other Device Same Type, Vertical 150 mm

Usage Instructions

  1. Ensure that the power supply to the motor is disconnected before installing the MS132-0.25K Manual Motor Starter.
  2. Mount the MS132-0.25K on a DIN rail with the recommended mounting distance.
  3. Connect the motor to the MS132-0.25K using the appropriate connecting capacity.
  4. Use a screwdriver with the recommended size to tighten the connections.
  5. Verify that the wire stripping length is correct for the terminal type.
  6. Position the MS132-0.25K in the desired mounting position.
  7. Ensure that the actuator type is set to the desired contact position (ON/OFF/TRIP).
  8. Refer to the standards and regulations for proper installation and usage of the MS132-0.25K.

PRODUCT-DETAILS

MS132-0.25K

MS132-0.25K Manual Motor Starter 0.16 … 0.25

General Information

ABB-1SAM350010R1002-MS132-0.25K-Motor-Protection-
Circuit-1

Ordering

  • Minimum Order Quantity 1 piece
  • Customs Tariff Number 85362010

Popular Downloads

  • Data Sheet, Technical Information 1SBC100212C0203
  • Instructions and Manuals 2CDC131120M6801
  • Manuals Manuals (Part 2) 2CDC131060M0202
  • Ex Operating Instructions 2CDC131063M6801
  • Time-Current Characteristic Curve 1SAM300505F0102
  • I²t Characteristic 1SAM300507F0001 1SAM300507F0003
  • Cut-off Current Characteristic 1SAM300508F0001 1SAM300508F0003
  • CAD Dimensional Drawing 2CDC001079B0201
  • Installation Video 9AKK108466A6074 9AKK108466A6068
  • Marketing Video 9AKK107991A4712 2CDC131153V0201

Dimensions

  • Product Net Width 45 mm
  • Product Net Height 112 mm
  • Product Net Depth /Length 87 mm
  • Product Net Weight 0.256 kg

Technical

  • Rated Service Short- (230 V AC) 100 kA

  • Circuit Breaking (250 V DC) 3 Poles in Series 10 kA

  • Capacity (Ics) (400 V AC) 100 kA
    (440 V AC) 100 kA
    (500 V AC) 100 kA
    (690 V AC) 100 kA

  • Rated Ultimate Short- (230 V AC) 100 kA

  • Circuit Breaking (400 V AC) 100 kA

  • Capacity (Icu) (440 V AC) 100 kA
    (500 V AC) 100 kA
    (690 V AC) 100 kA

  • Rated Instantaneous Short-Circuit Current Setting (Ii) 3.1 A

  • Setting Range 0.16 … 0.25 A

  • Rated Operational Power AC-3 (Pe) (400 V) Three Phase 0.06 kW

  • Rated Operational Power AC-3e (Pe) (400 V) Three Phase 0.06 kW

  • Rated Operational Voltage Main Circuit 690 V AC Main Circuit 250 V DC

  • Rated Operational Current (Ie) 0.25 A

  • Rated Operational Current AC-3e (Ie) 0.25 A

  • Rated Operational Current DC-5 (Ie) 0.25 A

  • Rated Frequency (f) Main Circuit 50 Hz Main Circuit 60 Hz

  • Rated Impulse Withstand Voltage (Uimp ) Main Circuit 6 kV

  • Rated Insulation Voltage (Ui) 690 V

  • Power Loss at Rated Operating Conditions per Pole 0.7 … 1.6 W

  • Number of Poles 3

  • Conventional Free-air Thermal Current (Ith) Main Circuit 0.25 A

  • Degree of Protection Housing IP20

  • Main Circuit Terminals IP20

  • Pollution Degree 3

  • Electrical Durability 50000 cycle

  • Mechanical Durability 100000 cycle

  • Terminal Type Push-in Spring Terminals

  • Connecting Capacity Main Circuit Flexible with Ferrule 1/2x 0.5 … 4 mm² Flexible with Insulated Ferrule 1x 0.5 … 4 mm² Flexible with Insulated Ferrule 2x 0.5 … 2.5 mm² Flexible 1/2x 0.75 … 4 mm²

  • Solid 1/2x 1 … 2.5 mm²

  • Stranded 1/2x 1 … 6 mm²

  • Wire Stripping Length Main Circuit 12 mm

  • Recommended Screw Driver Pozidriv 2

  • Mounting Position 1 … 6

  • Mounting on DIN Rail TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715

  • Minimum Mounting Distance Electrical Conductive Board, Horizontal – Up to 400 V 0 mm Electrical Conductive Board, Horizontal – Up to 690 V 1.5 mm Electrical Conductive Board, Vertical 75 mm

  • Other Device Same Type, Horizontal 0 mm

  • Other Device Same Type, Vertical 150 mm

  • Actuator Type Rotary Handle

  • Contact Position Indication  ON / OFF / TRIP
    Standards IEC/EN 60947-1
    IEC/EN 60947-2
    IEC/EN 60947-4-1
    UL 60947-1
    UL 60947-4-1

  • Remarks UL508 Self-Protected Combination Motor Controller (Type E) in combination with terminal spacer TS1-M3-K

Technical UL/CSA

  • Short-Circuit Current Rating (SCCR) Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 65 kA
  • Manual Self-Protected Combination Controllers (Type E), (600Y / 347 V AC) 47 kA
  • Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kA
  • Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 47 kA
  • Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kA
  • Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 47 kA
  • Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
  • Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA
  • Maximum Operating Voltage UL/CSA Main Circuit 600 V AC
  • Full Load Amps Motor (200 V AC) Three Phase 0.25 A (208 V AC) Three Phase 0.25 A
  • (220 … 240 V AC) Three Phase 0.25 A (440 … 480 V AC) Three Phase 0.25 A (550 … 600 V AC) Three Phase 0.25 A
  • Locked Rotor Amps (200 V AC) Three Phase 1.5 A
  • (208 V AC) Three Phase 1.5 A
  • (220 … 240 V AC) Three Phase 1.5 A (440 … 480 V AC) Three Phase 1.5 A (550 … 600 V AC) Three Phase 1.5 A
  • General Use Rating UL/CSA (600 V AC) 0.25 A
  • Connecting Capacity Main Circuit UL/CSA Stranded 1/2x 18-10 AWG Stranded 1x 8 AWG

Environmental

  • Ambient Air Around the Enclosure 0 … +40 °C
  • Temperature Operation -25 … +70 °C
  • Operation Compensated -25 … +60 °C Storage -50 … +80 °C
  • Ambient Air Temperature Compensation Yes
  • Maximum Operating Altitude Permissible 2000 m
  • Resistance to Shock acc. to IEC 60068-2-27 11 ms Pulse 25g
  • Resistance to Vibrations acc. to IEC 60068-2-6 5g / 3 … 150 Hz
  • RoHS Status Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Certificates and Declarations

  • ABS Certificate 1SAA963001-0101

  • ATEX Certificate 1SAA963000-3902

  • CB Certificate 1SAA963002-2002

  • CQC Certificate CQC2017010307034621

  • Cut-off Current 1SAM300508F0001

  • Characteristic   1SAM300508F0003

  • Declaration of Conformity – CCC 2020980307004600

  • Declaration of Conformity – CE 1SAD101100-3402

  • Declaration of Conformity – UKCA 1SAD201100-3402

  • EAC Certificate 1SAA963004-2701

  • I²t Characteristic 1SAM300507F0001
    1SAM300507F0003

  • IECEx Certificate 1SAA963000-4001

  • KC Certificate 1SAA963002-1502

  • RINA Certificate 1SAA963002-0802

  • UL Certificate E137861-20090225

  • E345003-20090225

Container Information

  • Package Level 1 Units box 1 piece
  • Package Level 1 Width 50 mm
  • Package Level 1 Depth /Length 117 mm
  • Package Level 1 Height 82 mm
  • Package Level 1 Gross Weight 0.282 kg
  • Package Level 1 EAN 4013614400322
  • Package Level 2 Units carton 28 piece
  • Package Level 2 Width 280 mm
  • Package Level 2 Depth /Length 395 mm
  • Package Level 2 Height 210 mm
  • Package Level 2 Gross Weight 14.026 kg
  • Package Level 2 EAN 4013614522642

Classifications

  • Object Classification Code F
  • ETIM 5 EC000074 – Motor protective circuit-breaker
  • ETIM 6 EC000074 – Motor protection circuit-breaker
  • ETIM 7 EC000074 – Motor protection circuit-breaker
  • ETIM 8 EC000074 – Motor protection circuit-breaker
  • eClass V11.0 : 27370401
  • UNSPSC 39121521
  • IDEA Granular Category Code (IGCC) 4731 >> Manual Starters
  • E-Number (Finland) 3707832
  • E-Number (Sweden) 3110451

Accessories

1SAM201901R1001 HKF1-11 Auxiliary Contact HKF1-11 1 piece
1SAM201901R1201 HKF1-11K Auxiliary Contact HKF1-11K 1 piece
1SAM201901R1002 HKF1-20 Auxiliary Contact HKF1-20 1 piece
1SAM201901R1202 HKF1-20K Auxiliary Contact HKF1-20K 1 piece
1SAM201901R1004 HKF1-01 Auxiliary Contact HKF1-01 1 piece
1SAM201901R1003 HKF1-10 Auxiliary Contact HKF1-10 1 piece
1SAM201902R1002 HK1-20 Auxiliary Contact HK1-20 1 piece
1SAM201902R1202 HK1-20K Auxiliary Contact HK1-20K 1 piece
1SAM201902R1001 HK1-11 Auxiliary Contact HK1-11 1 piece
1SAM201902R1201 HK1-11K Auxiliary Contact HK1-11K 1 piece
1SAM201902R1003 HK1-02 Auxiliary Contact HK1-02 1 piece
1SAM201902R1203 HK1-02K Auxiliary Contact HK1-02K 1 piece
1SAM201902R1004 HK1-20L Auxiliary Contact HK1-20L 1 piece
1SAM201902R1204 HK1-20LK Auxiliary Contact HK1-20LK 1 piece
1SAM201903R1002 SK1-20 Signaling Contact SK1-20 1 piece
1SAM201903R1202 SK1-20K Signaling Contact SK1-20K 1 piece
1SAM201903R1005 SK1-20AR Signaling Contact SK1-20AR 1 piece
1SAM201903R1205 SK1-20ARK Signaling Contact SK1-20ARK 1 piece
1SAM201903R1001 SK1-11 Signaling Contact SK1-11 1 piece
1SAM201903R1201 SK1-11K Signaling Contact SK1-11K 1 piece
1SAM201903R1004 SK1-11AR Signaling Contact SK1-11AR 1 piece
1SAM201903R1204 SK1-11ARK Signaling Contact SK1-11ARK 1 piece
1SAM201903R1003 SK1-02 Signaling Contact SK1-02 1 piece
1SAM201903R1203 SK1-02K Signaling Contact SK1-02K 1 piece
1SAM201903R1006 SK1-02AR Signaling Contact SK1-02AR 1 piece
1SAM201903R1206 SK1-02ARK Signaling Contact SK1-02ARK 1 piece
--- --- --- --- ---
1SAM301901R1002 CK1-20 Short Circuit Signaling Contact CK1-20 1 piece
1SAM301901R1001 CK1-11 Short Circuit Signaling Contact CK1-11 1 piece
1SAM301901R1003 CK1-02 Short Circuit Signaling Contact CK1-02 1 piece
1SAM201910R1001 AA1-24 Shunt Trip AA1-24 1 piece
1SAM201910R1002 AA1-110 Shunt Trip AA1-110 1 piece
1SAM201910R1003 AA1-230 Shunt Trip AA1-230 1 piece
1SAM201910R1004 AA1-400 Shunt Trip AA1-400 1 piece
1SAM201904R1010 UA1-20 Undervoltage Release UA1-20 1 piece
1SAM201904R1001 UA1-24 Undervoltage Release UA1-24 1 piece
1SAM201904R1002 UA1-48 Undervoltage Release UA1-48 1 piece
1SAM201904R1003 UA1-60 Undervoltage Release UA1-60 1 piece
1SAM201904R1004 UA1-110 Undervoltage Release UA1-110 1 piece
1SAM201904R1008 UA1-208 Undervoltage Release UA1-208 1 piece
1SAM201904R1005 UA1-230 Undervoltage Release UA1-230 1 piece
1SAM201904R1006 UA1-400 Undervoltage Release UA1-400 1 piece
1SAM201904R1007 UA1-415 Undervoltage Release UA1-415 1 piece
1SAM201904R1009 UA1-575 Undervoltage Release UA1-575 1 piece
1SAM301903R1002 PS1-2-0-65K Busbar PS1-2-0-65K 1 piece
1SAM301903R1003 PS1-3-0-65K Busbar PS1-3-0-65K 1 piece
1SAM301903R1004 PS1-4-0-65K Busbar PS1-4-0-65K 1 piece
1SAM301903R1005 PS1-5-0-65K Busbar PS1-5-0-65K 1 piece
1SAM301903R1012 PS1-2-1-65K Busbar PS1-2-1-65K 1 piece
1SAM301903R1013 PS1-3-1-65K Busbar PS1-3-1-65K 1 piece
1SAM301903R1014 PS1-4-1-65K Busbar PS1-4-1-65K 1 piece
1SAM301903R1015 PS1-5-1-65K Busbar PS1-5-1-65K 1 piece
1SAM201909R1001 FS116 Screw Fixing Kit FS116 1 piece
1SAM301913R1001 TS1-M3-K Terminal Spacer TS1-M3-K 1 piece
GJF1101903R0002 SA2 Terminals and Installation Material SA2 1 piece
1SAM201911R1012 IB132-F Enclosure IB132-F 1 piece
1SAM201911R1010 IB132-G Enclosure IB132-G 1 piece
1SAM201911R1011 IB132-Y Enclosure IB132-Y 1 piece
1SAM201912R1010 DMS132-G Door Mounting Kit DMS132-G 1 piece
1SAM201912R1011 DMS132-Y Door Mounting Kit DMS132-Y 1 piece
1SAM201909R1021 MSAH1 Shaft Supporter MSAH1 1 piece
1SAM201920R1011 MSHD-LTB Handles MSHD-LTB 1 piece
1SAM201920R1012 MSHD-LTY Handles MSHD-LTY 1 piece
1SAM201920R1000 MSH-AR Shaft Alignment Ring MSH-AR 1 piece
1SAM101923R0002 MSMN Driver MSMN 1 piece
1SAM101923R0012 MSMNO Driver MSMNO 1 piece
1SCA101647R1001 OXS6X85 SHAFT OXS6X85 1 piece
1SCA108043R1001 OXS6X105 SHAFT OXS6X105 1 piece
1SCA101655R1001 OXS6X130 SHAFT OXS6X130 1 piece
1SCA101659R1001 OXS6X180 SHAFT OXS6X180 1 piece

Categories

  • Low Voltage Products and Systems → Circuit Breakers → Manual Motor Starters
  • Low Voltage Products and Systems → Control Products → Manual Motor Starters → Manual Motor Starters

MS132-0.25K

© 2023 ABB. All rights reserved. 2023/08/10 Subject to change without notice

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals