HOTSPOT FULHAM FHS2-UNV-56S Emergency LED Driver
Product Information
- Product Model: FHS2-UNV-56S
- Installation Instructions: Included
- Mechanical Data: NiCd/LiFePO4
- UL Certification: E313578
- LED Module Compatibility: Any LED module designed to accept an input voltage range of 12-56VDC and can operate up to a current of 700mA
- General Specifications:
- Input Voltage: 100-277VAC, 50/60Hz
- Input Current: 0.1A Max.
- Input Power: 6W Max.
- Max Output Rating (Red Lead): 3A, 60V Max.
- Input Power Pass-Through Rating (White/Black Lead): 2A Max.
- Standby Input Power: Not specified
- Driver Type: Not specified
- Output Current: Not specified
- Output Voltage Range: Not specified
- Output Power: Not specified
- Number of Output Channels: Not specified
- RFI/EMI Output Type: Not specified
- Battery Type: Not specified
- Battery Capacity: Not specified
- Available Battery Recharge Time: Not specified
- Battery Discharge Time: Not specified
- Test Switch: Not specified
- Remote Mounting Distance: Not specified
- Wire Length: Not specified
- Ambient Operating Temperature Range: Not specified
- Input Surge Protection: Included
- Protections: Not specified
- Service Life: Not specified
- Approvals/Class: Not specified
Product Usage Instructions
- Ensure that the input voltage is within the range of 100-277VAC and the frequency is 50/60Hz.
- Connect the power supply to the driver using the appropriate wires.
- Make sure the LED module is designed to accept an input voltage range of 12-56VDC and can operate up to a current of 700mA.
- Connect the LED module to the driver using the provided connectors or wiring.
- Verify that the connections are secure and properly insulated.
- Switch on the power supply and test the LED module to ensure proper operation.
Note: For detailed information on specific specifications, protections, battery-related details, and operating temperature range, please refer to the product manual
INSTALLATION INSTRUCTIONS
- Emergency LED Driver
- Output Wattage range of 1.2-20W
- Universal Voltage: 100-277VAC, 50/60Hz
- Output Current range of 100mA – 700mA
- Output voltage range of 12-56VDC
This Driver Will Operate The Following LED Modules: Any LED module designed to accept an input voltage range of 12-56VDC and can operate up to a current of 700mA.
General Specifications
- Input Voltage 100-277VAC, 50/60Hz
- Input Current 0.1A Max.
- Input Power 6W Max.
- Max Output Rating (Red Lead) 3A,60V Max.
- Input Power Pass-Through Rating (White/Black Lead) 2A Max.
- Standby Input Power <0.8W
- Driver Type Constant Current
- Output Current 100mA -700mA Initial (Refer to accesory chart)
- Output Voltage Range 12-56VDC
- Output Power 20W Max.
- Number of Output Channels 1 Channel
- RFI/EMI FCC Part 15 Class B , EN55015
- Output Type LED Class 2
- Battery Type NiCd 9.6VDC or LiFePO4 9.6VDC
- Battery Capacity Available 900mAh, 1000mAh, 1200mAh, 1500mAh, 1800mAh, 3000mAh, 4000mAh, 6000mAh
- Battery Recharge Time 24-32 Hours (Refer To Battery chart)
- Battery Discharge Time 90 Minutes Min.
- Test Switch Remote Mounting Distance 20′ (6m) Max.
- Wire Length Input: 18AWG, Output: 22AWG, Red Lead: 18WG, Test Switch: 22AWG, Battery: 22AWG
- Ambient Operating Temperature Range
- NiCd: 0°C to 50°C (32°F to 122°F), LiFePO4: 10°C to 50°C (50°F to 122°F)
- FHSBATCC3-3: -20°C to 50°C (-4°F to 122°F)
- FHS2-UNV-56S: -20°C to 50°C (-4°F to 122°F)
- Input Surge Protection 2.5KV Ring Wave
- Protections
- Battery Over Discharge Protection
- Output Short Circuit Protection
- Service Life 50,000 hours
Approvals / Class RoHS , cURus 1310 , cURus 924 , CEC Title 20 , CE , Dry and Damp Locations
Mechanical Data
Important and Safety Instructions
When using electrical equipment and this lighting device basic safety precaution should be followed at all times including but not limited to the following:
PLEASE READ CAREFULLY AND FOLLOW ALL INSTRUCTIONS FOR YOUR OWN SAFETY
- IMPORTANT: Do not connect battery until fixture is installed.
- IMPORTANT: An un-switched AC power source of 100VAC to 277VAC is required.
- This device is designed for use in fixtures listed for dry and damp locations.
- CAUTION: Make sure all electrical connections conform to the National Electrical Code and all applicable local regulations.
- CAUTION: Do not let power supply cords touch hot surfaces.
- CAUTION: Do not mount near gas or electric heaters.
- CAUTION : Battery is rechargeable Ni-Cd or LiFePO4 type and must be recycled or disposed of properly.
- Do not use this emergency driver with accessory equipment other than recommended by manufacturer; failure to follow this may cause an unsafe condition. Servicing should only be performed by qualified service personnel. Do not use this emergency driver for other than intended use. Not suitable for high-risk task area lighting. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
- IMPORTANT: The output EM power will not exceed the max power rating of the battery.
- IMPORTANT: Indicator (LED light) illuminated indicates battery in charge mode when AC power is applied. It is recommended and required by applicable code to test emergency ballast to ensure proper function of the system; push the test switch for thirty (30) seconds every thirty (30) days to ensure the emergency driver is functioning by illuminating the light source. Conduct a ninety (90) minutes discharge test one (1) time per year; LED light source should be illuminated for a minimum of ninety (90) minutes .
ASSEMBLY and FIELD INSTALLATION WIRING:
WARNING: AC power must be off before proceeding with assembly or
installation of emergency driver.
TESTING SYSTEM: The emergency battery requires a charge minimum of one
(1) hour before testing the circuit. A full charge requires twenty four (24)
or thirty two (32) hours, depending upon battery pack. Please refer to battery
chart for charging time.
IMPORTANT: In order to maintain proper operation and warranty coverage,
the battery must be recharged once per year prior to installation.
- Fulham Head Quarters:
- Fulham Co., Inc
- 12705 South Van Ness Ave.
- Manufacturer:
- North China
- Fulham Electronic Co. Ltd.
- No. 9 Xingchang Road, Nanshao Zhen Changping Science Park, Beijing, P.R. China
Wiring Diagrams
Wiring Diagrams 1
NOTE:
- Drill ½” Dia. hole in mounting.
- Plate to insert test switch.
- Double insulation between the input wire and battery wire.
Wiring Diagram (TYP)
WIRING DIAGRAM (EMERGENCY ONLY)
INPUT
Wire Color| Length
(Inches)
---|---
Black| 12.99” ±0.5”
White| 12.99” ±0.5”
Black / White| 14.96” ±0.5”
OUTPUT
Wire Color| Length
(Inches)
---|---
Red| 20.87” ±0.5”
Test Switch| 5.51” ±0.19”
Output Harness| 2.99” ±0.19”
Battery Chart
Fulham Model No.| Chemistry| Compliant| Pack Capacity| Max Load for 90 min.|
Battery Voltage| Battery Count| Recharge Time| Dimensions (L x W x H)| 12″
Harness (Optional)| Mounting Accessory (Included / Optional)
---|---|---|---|---|---|---|---|---|---|---
FHSBATT8-AA.9| NiCd| | 900mAh| 4W| ****
9.6V
| 8 Cells| 24Hrs| 5.23″ x 2.5″ x 0.7″| ****
FHS-EXTM
| ****
Bracket Included
FHSBATL3-1| LiFePO4| RoHS| 1000mAh| 4W| 3 Cells| 24Hrs| 3.48″ x 2.35″ x 0.99″
FHSBATL6-.6| LiFePO4| RoHS| 1200mAh| 6W| 6 Cells| 24Hrs| 5.23″ x 1.87″ x 0.85″
FHSBATL3-1.5| LiFePO4| RoHS| 1500mAh| 8W| 3 Cells| 24Hrs| 3.48 “x 2.76″ x
0.99”
FHSBATL3-1.5S| LiFePO4| RoHS| 1500mAh| 8W| 3 Cells| 24Hrs| 8.87″ x 1.11″ x
0.955″
FHSBATL9-.6| LiFePO4| RoHS| 1800mAh| 10W| 9 Cells| 24Hrs| 7.52″ x 1.87″ x
0.85″
FHSBATL6-1.5S| LiFePO4| RoHS| 3000mAh| 14W| 6 Cells| 24Hrs| 16.67″ x 1.11″ x
0.955″
FHSBATCC3-3
(-20°C Cold Pack)
| LiFePO4| RoHS| 3000mAh| 14W/10W*| 3 Cells| 24Hrs| 6″ x 3.6″ x 1.55″
FHSBATT8-C3| NiCd| | 3000mAh| 16W| 8 Cells| 24Hrs| 4.15″ x 3.29″ x 2.11″
FHSBATT8-C3L| NiCd| | 3000mAh| 16W| 8 Cells| 24Hrs| 7.89″ x 2.17″ x 1.04″|
FHSBATSC8-C3L
FHSBATL3-3| LiFePO4| RoHS| 3000mAh| 16W| 3 Cells| 24Hrs| 4.39″ x 2.82″ x 1.3″|
Bracket Included
FHSBATL6-1.5| LiFePO4| RoHS| 3000mAh| 16W| 6 Cells| 24Hrs| 5.7″ x 2.76″ x
0.99″
FHSBATL6-1.5L*| LiFePO4| RoHS| 3000mAh| 16W| 6 Cells| 24Hrs| 7.89″ x 1.56″ x
0.92″| FHSBATSC6-1.5L
FHSBATT8-D4| NiCd| | 4000mAh| 20W| 8 Cells| 24Hrs| 4.89″ x 3.84″ x 2.72″|
Bracket Included
FHSBATL6-3| LiFePO4| RoHS| 6000mAh| 20W/16W*| 6 Cells| 32Hrs| 7.52″ x 2.82″ x
1.3″
FHSBATL6-3L| LiFePO4| RoHS| 6000mAh| 20W/16W**| 6 Cells| 32Hrs| 7.94″ x 2.17″
x 1.21″| FHSBATSC6-3L
- CAUTION: Replace battery only with corresponding part number.
- Note: These batteries do not include mounting means, separate mounting brackets are available.
- Note: This battery rating applies for Canada use only.
Accessory Harness (Wire length 24″)
Part Number| Description| Part Number| Description
FHS-HARNESS-100| 100 m A LED Harness| FHS-HARNESS-125| 125 m A LED Harness
FHS-HARNESS-150| 150 m A LED Harness| FHS-HARNESS-175| 175 m A LED Harness
FHS-HARNESS-200| 200 m A LED Harness| FHS-HARNESS-225| 225 m A LED Harness
FHS-HARNESS-250| 250 m A LED Harness| FHS-HARNESS-300| 300 m A LED Harness
FHS-HARNESS-350| 350 m A LED Harness| FHS-HARNESS-400| 400 m A LED Harness
FHS-HARNESS-450| 450 m A LED Harness| FHS-HARNESS-500| 500 m A LED Harness
FHS-HARNESS-550| 550 m A LED Harness| FHS-HARNESS-600| 600 m A LED Harness
FHS-HARNESS-650| 650 m A LED Harness| FHS-HARNESS-700| 700 m A LED Harness
Dimensions
Battery Dimensions
Mounting Bracket Dimensions (Optional)
Mounting Bracket Dimensions (Optional)
Mounting Bracket Dimensions (Optional)
TEST SWITCH INDICATOR STATUS:
Indicators Type | LED Indicators Status | EM Driver Status/Mode |
---|---|---|
Bi-Color Indicator | ● Solid Green | System OK/AC OK (Self-diagnostic Enabled or |
Disabled).
Single Color Indicator| ● Solid RED ON
Bi-Color Indicator| ● Flashing Green, 0.1s on/3s off| System OK / EM Mode
Single Color Indicator| ● Flashing RED, 0.1s on/3s off
Bi-Color Indicator| ● Slow Flashing Red, 4s on/1s off| Battery not detected,
check battery switch or connection.
Single Color Indicator| ● Slow Flashing Red, 4s on/1s off
Bi-Color Indicator| ● Flashing Red, 1s on/1s off| Replace battery.
Single Color Indicator| ● Flashing Red, 1s on/1s off
Bi-Color Indicator| ● Flashing Green, 2s on/2s off| Self-Diagnostic test
underway.
Single Color Indicator| ● Flashing Red, 2s on/2s off
Bi-Color Indicator| ● Fast Flashing Red, 0.1s on/0.1s off| Abnormal driver
performance, replace driver.
Single Color Indicator| ● Fast Flashing Red, 0.1s on/0.1s off
Bi-Color Indicator| ● Very Slow Flashing Red, 1s on/7s off| Over temperature.
Single Color Indicator| ● Very Slow Flashing Red, 1s on/7s off
Bi-Color Indicator| ● Very Slow Flashing Red, 4s on/4s off| LED output load is
Short/Over Current/Over Voltage/Open Circuit in EM Mode.
Single Color Indicator| ● Very Slow Flashing Red, 4s on/4s off
TEST SWITCH OPERATIONS
- EM Test: Press and hold test button (>1s)to enter EM mode for testing in normal AC powered .
- Manual Self-Diagnostic: After charging twelve (12) hours or battery fully charged, quickly press the test button three times within two seconds to force the controller to enter a Self-Diagnostic cycle. To quit the self-diagnostic cycle after engaged press and hold the test button for ten seconds.
- Enable/Disable Auto Self-Diagnostic: Press and hold the test button for one second, then release and quickly press the test button two times, then release and press and hold the test button for two seconds. When properly executed the indicator on the test button will display the appropriate color for the Enable/Disable status. A flashing of 2.5s ON/0.5s OFF means “Enabled”, while a flashing of 0.5s ON/2.5s off means “Disabled”. Once Enable/Disable is set the status color on the test button will remain the same throughout normal operation (refer to Indicator Status Table).
- Enable/Disable Self-Diagnostic Status: Fast click 2 times within 2s to query the Self-Diagnostic Enabled/Disabled status. The indicator would blink for current status for 3 cycles. 2.5s ON/0.5s OFF stands for Enabled. 0.5s ON/2.5s OFF stands for Disabled.
- Exit Output Short Circuit/No Load/Over Voltage Protection: When the test button flashes red for 4s on/4s off, press and hold the test switch for 10 seconds.
- Turn off EM output: Press and hold the test switch for 10 seconds during EM output condition to turn off EM output. This is useful for production environment to turn off the EM output once a luminaire has completed functionality testing. This applies to products with Serial Number starting with Date code: S12017 or higher.
Programming:
Unless otherwise programmed the output will self-program to the rated output
of the harness. This driver can be programmed usin gFulham SmartSet TPSB-100
or TPSM-100E. Programming features include the following:
- Enable/Disable Self-Diagnostic
- Output EM Current : 0mA,100-700mA
- When programmed to 0mA; output current defaults to rating of output harness(Refer to accessory harness chart).
Fulham extends a limited warranty to the original purchaser or first user for a period of 5 years from the date of manufacture when properly installed and operated under normal conditions of use. For complete terms and conditions, please refer to the Warranty Center at www.fulham.com. Specifications subject to change without notice.