Clippard CORDIS SERIES CP1 Dynamic Electronic Pressure Controls
Product Information
The Cordis Series CP1 Dynamic Electronic Pressure Controls are known for their reliability, innovation, and focus on miniature pneumatics. These pressure controllers utilize the EVP and DVP proportional valve series to provide precise, linear pressure control within a closed-loop system. They offer ultra-high resolution and repeatability, ensuring steady, accurate, and repeatable downstream pressure control even as demand or process changes.
Key Features:
- Precise, linear pressure control within a closed-loop system
- Ultra-high resolution and repeatability
- Utilizes EVP and DVP proportional valve series
- Reliable and innovative
- Suitable for miniature pneumatics
Product Usage Instructions
Mounting:
The Cordis series can be mounted in any orientation without negatively affecting process control.
Pneumatic Plumbing:
Ensure that the regulated supply pressure is connected properly.
The process to be controlled should be connected to the appropriate port.
Refer to Fig:1 for a visual representation of the pneumatic plumbing.
Safety & Best Practices:
- Recommended filtration for supply media is 40 micron or better.
- Regulate the supply pressure to the maximum pressure allowed for the calibrated range (refer to Table:2 & 3).
- If the supply pressure is not connected, disconnect the power.
- The inlet pressure must be at least 10% above the maximum calibrated range of Cordis to achieve maximum output.
- Always handle exposed circuit boards with precautionary measures: hold the circuit board on the edges to avoid damage.
- Store the device in an antistatic bag to prevent possible electrostatic discharge (ESD) damage.
Calibration:
The Cordis series is calibrated at the time of manufacture to NIST traceable
standards. Each unit is calibrated and the PIDs (Proportional-Integral-
Derivative) are set to the Cordis standard tuning. If the customer’s specific
application details are known prior to manufacture, the PIDs will be tuned
according to those specifications to provide stable and repeatable control.
Available Calibration Ranges and Maximum Allowed Inlet Pressure:
CALIBRATED RANGE | MAX. INLET PRESSURE (psig) |
---|---|
0 to 1 psig | 10 psig |
0 to 5 psig | 10 psig |
0 to 15 psig | 30 psig |
0 to 30 psig | 60 psig |
0 to 100 psig | 115 psig |
Operating Instructions
Precise, linear pressure control within a closed-loop system with ultra high resolution and repeatability
- Known for reliability, innovation and focus on miniature pneumatics, Clippard’s Cordis Pressure controllers utilize the proven EVP and DVP proportional valve series allowing for steady, accurate and repeatable downstream pressure control as demand or process changes. The result, a very precise linear pressure control within a closed-loop system providing ultra-high resolution and repeatability.
- The Cordis uses a microcontroller, an internal or external pres-sure sensor, and a Clippard proportional valve. The inlet valve is connected to the moderately regulated supply pressure. Once a command is increased, the proportional valve opens up to allow supply pressure to pass over the sensor element which provides an active feedback for the microcontroller to satisfy the set point in the process. If at any point the sensor detects a value higher than the set point, the proportional valve closes and allows process to consume the remaining downstream pressure.
Technical Data
ELECTRICAL|
---|---
Voltage| 15 to 24 VDC
Current Draw| < 250 mA max.
Signal/Command| Ele c tri c al : 0 to 10 VDC or
0 to 5 VDC
PERFORMANCE|
Accuracy| ± 0.25% of full scale
Resolution| ≤ 5 mV
Linearity| ± 0.05% BFSL
Max. Hysteresis| ± 0.05% of full scale
Calibrated Range| 0 to 0.5 psig min.
0 to 150 psig max.
Typical Flow| See Page 6
Response Time| < 20 ms typical (application dependent)
OPERATING CONDITIONS|
Operating Temperature|
32 to 120°F (0 to 49°C)
Medium| Clean, dry, non-corrosive gases
Mounting Attitude| Any
Process Connections| #10-32, M5, Manifold Mount
WETTED MATERIALS|
---|---
Elastomers| FKM
Manifold| Anodized aluminum
Valves| Nickel plated brass and Stainless Steel
Pressure Sensor| Silicon, wire bonds, ceramic, Nylon and RTV/epoxy
MORE DETAILS|
Website| clippard.com/link/cordis
Operational Description
The Cordis is designed to accept a pressure on the inlet port, and control to
a user-specific set pressure on the work port. The CP1 contains a
microcontroller, integrated pressure sensor, and a Clippard EVP/DVP
proportional valve.
For Cordis to control pressure in your process, a regulated supply pressure
should be connected to the inlet valve (I). The outlet valve (O) should be
connected to the downstream process. As the command signal increases the inlet
valve opens to allow pressure downstream. This pressure passes over the
internal sensor element which is constantly providing active feedback to the
microcontroller. As soon as this feedback matches the user-specified command,
the inlet valve closes and holds the commanded pressure downstream. If dynamic
conditions exist or if any consumption occurs downstream, the inlet valve will
open and instantly compensate to maintain the desired downstream setpoint.
Mounting
The Cordis series can be mounted in any orientation without negatively affecting process control.
Pneumatic Plumbing
Safety & Best Practices
- Recommended filtration for supply media is 40 micron or better.
- Supply pressure must be regulated to ≤ max pressure allowed for calibrated range. See Table: 2 & 3
- Disconnect power if supply pressure is not connected.
- Inlet pressure must be a minimum of 10% above max calibrated range of Cordis to achieve max output. Always take precautionary measures while handling exposed circuit boards: Hold circuit board on edges whenever handling device. Store device in antistatic bag to prevent possible ESD from damaging
Calibration
The calibration of the Cordis series is done at the time of manufacture to NIST traceable standards. Each unit is calibrated and the PIDs are set to the Cordis standard tuning. If a customer’s specific application details are known prior to manufacture (recommended), the PIDs will be tuned in accordance with the known specifications to provide the most stable and repeatable control. Below are the available calibration ranges and maximum allowed inlet pressure for each range.
Rated Inlet Pressure for Calibrated Range (psig)
CALIBRATED RANGE | MAX. INLET PRESSURE |
---|---|
0 to 1 psig | 10 psig |
0 to 5 psig | 10 psig |
0 to 15 psig | 30 psig |
0 to 30 psig | 60 psig |
0 to 100 psig | 115 psig |
0 to 150 psig | 165 psig |
Rated Inlet Pressure for Calibrated Range (bar)
CALIBRATED RANGE | MAX. INLET PRESSURE |
---|---|
0 to 0,5 bar | 0,70 bar |
0 to 1 bar | 2 bar |
0 to 2 bar | 4 bar |
0 to 7 bar | 8 bar |
0 to 10 bar | 11 bar |
Recalibration
The Cordis series does not require recalibration during its lifetime. If the
calibration needs to be changed and/or modified, the unit must be returned to
Clippard or completed by a certified field technician. Any attempt to
recalibrate in the field without prior authorization will void the warranty.
Please contact Clippard for all Return Material Authorization (RMA) requests:
Clippard
7390 Colerain Avenue | Cincinnati, OH 45239 |
sales@clippard.com |
1-877-245-6247 Please have the serial
number(s) available for reference.
0 to 10 VDC Electrical Connection
Make sure AC power is disconnected before DC connections are made
The Cordis requires 15 to 24 VDC on Pin 1 of the electrical connector. It uses
0 to 10 VDC command signal on Pin 3 of the electrical connector. The power
supply ground, command source ground and Pin 2 must be tied together. If the
analog monitor signal is being used, utilize Pin 4 to send the 0 to 10 VDC
signal to a measuring device like a volt meter, panel meter or acquisition
device.
Model Electrical Pin-out
PIN NUMBER | FUNCTION | COLOR |
---|---|---|
1 | DC Common/Ground | Green |
2 | Power, 15-24 VDC | Red |
3 | +Command Input | White |
4 | Analog VDC Output | Black |
Flow & Orifice Selection
PN REF.| ORIFICE SIZE| FLOW @ MAX. PRESSURE| MAX.
PRESSURE (P2)
---|---|---|---
A| 0.009” EVP| 2.7 l/min (5.72 scfh)| 150 psig (10,34 bar)
B| 0.013” EVP| 6.7 l/min (14.2 scfh)| 100 psig (6,89 bar)
C| 0.026” DVP| 25.0 l/min (53.0 scfh)| 100 psig (6,89 bar)
D| 0.052” DVP| 65.01 l/min (137.7 scfh)| 100 psig (6,89 bar)
F| 0.035” DVP| 32.0 l/min (67.8 scfh)| 100 psig (6,89 bar)
Flow & Valve Selection Notes
Max flow assumes a P1 value of (at least) 10% above max pressure listed. Ex: a max pressure out of 50 psig assumes a min P1 value of 55 psig.
Accessories Cable
Ordering Information
Dimensions
In-Line Mount
Manifold Mount
Mounting Interface
7390 Colerain Avenue Cincinnati, OH 45239
1-513-521-4261
1-877-245-6247
Cordis, of the heart
Other Useful Materials
- Digital vs. Analog Control White Paper
- Pressure vs. Flow Control White Paper
- Resolution in Proportional Control White Paper
- View Frequently Asked Questions
- View Web Site
Limited Warranty
All information contained in this publication is for reference only. Proper
design engineering procedures should be used to assure any compliances.
Clippard Instrument Laboratory, Inc. reserves the right to make changes
without notice and does not warrant or guarantee the information contained
herein.
Clippard Instrument Laboratory, Inc. (Seller) warrants its products to be free
from defects in material and workmanship for a period of one (1) year from the
date of sale. Seller’s liability shall be limited at seller’s option to
repair, replace or refund purchase price of product found by seller’s
examination to be defective. All claims under this warranty must be made in
writing to seller’s factory sales department giving full details, prior to
return of product, postpaid, to factory. Seller shall not be responsible for
product failure due to normal wear, accident, buyer’s misapplication, abuse,
neglect or alteration of product. Seller will not be responsible for any
consequential damages. Clippard makes no other warranty of any kind, expressed
or implied. Circuits shown in this catalog are for instructional purposes
only. All circuits used on equipment and machinery should be thoroughly tested
by qualified personnel under actual working conditions to determine their
suitability for buyer’s intended use. All technical data and operations are
average values based on standard production models. Some deviations can be
expected and considerations should be given during initial design stages. All
operating characteristics are based on new equipment, under normal conditions
of use and environments and oil free air supply. Dimensions stated may be
nominal and are subject to change without notice. Contact Clippard for
specific dimensional tolerances when dimensions are critical.
Proudly made in the USA.